sourcefile~~cooltower.f90~~EfferentGraph sourcefile~cooltower.f90 CoolTower.f90 sourcefile~schedulemanager.f90 ScheduleManager.f90 sourcefile~schedulemanager.f90->sourcefile~cooltower.f90 sourcefile~watermanager.f90 WaterManager.f90 sourcefile~schedulemanager.f90->sourcefile~watermanager.f90 sourcefile~watermanager.f90->sourcefile~cooltower.f90 sourcefile~general.f90 General.f90 sourcefile~general.f90->sourcefile~cooltower.f90 sourcefile~general.f90->sourcefile~schedulemanager.f90 sourcefile~general.f90->sourcefile~watermanager.f90 sourcefile~psychroutines.f90 PsychRoutines.f90 sourcefile~general.f90->sourcefile~psychroutines.f90 sourcefile~dataheatbalance.f90 DataHeatBalance.f90 sourcefile~general.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90 DataEnvironment.f90 sourcefile~general.f90->sourcefile~dataenvironment.f90 sourcefile~datahvacglobals.f90 DataHVACGlobals.f90 sourcefile~datahvacglobals.f90->sourcefile~cooltower.f90 sourcefile~datahvacglobals.f90->sourcefile~watermanager.f90 sourcefile~datahvacglobals.f90->sourcefile~general.f90 sourcefile~psychroutines.f90->sourcefile~cooltower.f90 sourcefile~dataprecisionglobals.f90 DataPrecisionGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~cooltower.f90 sourcefile~dataprecisionglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~watermanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~general.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90 DataGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataglobals.f90 sourcefile~dataheatbalfansys.f90 DataHeatBalFanSys.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalfansys.f90 sourcefile~datawater.f90 DataWater.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datawater.f90 sourcefile~datainterfaces.f90 DataInterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datainterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90 InputProcessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataipshortcuts.f90 DataIPShortCuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~datasystemvariables.f90 DataSystemVariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datasurfaces.f90 DataSurfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90 DataVectorTypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datavectortypes.f90 sourcefile~databsdfwindow.f90 DataBSDFWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataruntimelanguage.f90 DataRuntimeLanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datacomplexfenestration.f90 DataComplexFenestration.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataequivalentlayerwindow.f90 DataEquivalentLayerWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~datasizing.f90 DataSizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasizing.f90 sourcefile~dataglobals.f90->sourcefile~cooltower.f90 sourcefile~dataglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataglobals.f90->sourcefile~watermanager.f90 sourcefile~dataglobals.f90->sourcefile~general.f90 sourcefile~dataglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90->sourcefile~datawater.f90 sourcefile~dataglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~sortandstringutilities.f90 SortAndStringUtilities.f90 sourcefile~dataglobals.f90->sourcefile~sortandstringutilities.f90 sourcefile~dataoutputs.f90 DataOutputs.f90 sourcefile~dataglobals.f90->sourcefile~dataoutputs.f90 sourcefile~dataglobals.f90->sourcefile~datasizing.f90 sourcefile~dataheatbalfansys.f90->sourcefile~cooltower.f90 sourcefile~datawater.f90->sourcefile~cooltower.f90 sourcefile~datawater.f90->sourcefile~watermanager.f90 sourcefile~datainterfaces.f90->sourcefile~cooltower.f90 sourcefile~datainterfaces.f90->sourcefile~schedulemanager.f90 sourcefile~datainterfaces.f90->sourcefile~watermanager.f90 sourcefile~datainterfaces.f90->sourcefile~general.f90 sourcefile~datainterfaces.f90->sourcefile~psychroutines.f90 sourcefile~datainterfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datainterfaces.f90->sourcefile~inputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~dataenvironment.f90 sourcefile~datainterfaces.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataheatbalance.f90->sourcefile~cooltower.f90 sourcefile~dataheatbalance.f90->sourcefile~watermanager.f90 sourcefile~inputprocessor.f90->sourcefile~cooltower.f90 sourcefile~inputprocessor.f90->sourcefile~schedulemanager.f90 sourcefile~inputprocessor.f90->sourcefile~watermanager.f90 sourcefile~inputprocessor.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90->sourcefile~cooltower.f90 sourcefile~dataenvironment.f90->sourcefile~schedulemanager.f90 sourcefile~dataenvironment.f90->sourcefile~watermanager.f90 sourcefile~dataenvironment.f90->sourcefile~psychroutines.f90 sourcefile~dataenvironment.f90->sourcefile~dataheatbalance.f90 sourcefile~datastringglobals.f90 DataStringGlobals.f90 sourcefile~datastringglobals.f90->sourcefile~schedulemanager.f90 sourcefile~datastringglobals.f90->sourcefile~general.f90 sourcefile~datastringglobals.f90->sourcefile~inputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~dataipshortcuts.f90->sourcefile~schedulemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~general.f90 sourcefile~dataipshortcuts.f90->sourcefile~inputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~schedulemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~inputprocessor.f90 sourcefile~datasurfaces.f90->sourcefile~watermanager.f90 sourcefile~datasurfaces.f90->sourcefile~general.f90 sourcefile~datasurfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datavectortypes.f90->sourcefile~dataheatbalance.f90 sourcefile~datavectortypes.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90->sourcefile~databsdfwindow.f90 sourcefile~databsdfwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90->sourcefile~datasurfaces.f90 sourcefile~dataruntimelanguage.f90->sourcefile~general.f90 sourcefile~datacomplexfenestration.f90->sourcefile~dataheatbalance.f90 sourcefile~dataequivalentlayerwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~sortandstringutilities.f90->sourcefile~inputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~inputprocessor.f90 sourcefile~datasizing.f90->sourcefile~inputprocessor.f90
Help

Files Dependent On This One

sourcefile~~cooltower.f90~~AfferentGraph sourcefile~cooltower.f90 CoolTower.f90 sourcefile~hvacmanager.f90 HVACManager.f90 sourcefile~cooltower.f90->sourcefile~hvacmanager.f90 sourcefile~heatbalanceairmanager.f90 HeatBalanceAirManager.f90 sourcefile~hvacmanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~simulationmanager.f90 SimulationManager.f90 sourcefile~hvacmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancesurfacemanager.f90 HeatBalanceSurfaceManager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~energyplus.f90 EnergyPlus.f90 sourcefile~simulationmanager.f90->sourcefile~energyplus.f90 sourcefile~utilityroutines.f90 UtilityRoutines.f90 sourcefile~simulationmanager.f90->sourcefile~utilityroutines.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancemanager.f90 HeatBalanceManager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~simulationmanager.f90 sourcefile~sizingmanager.f90 SizingManager.f90 sourcefile~heatbalancemanager.f90->sourcefile~sizingmanager.f90 sourcefile~sizingmanager.f90->sourcefile~simulationmanager.f90
Help

Source Code


Source Code

! (ref: Object: COOLTOWER:SHOWER)
MODULE CoolTower
  ! Module containing the data for cooltower system

  ! MODULE INFORMATION:
  !       AUTHOR         Daeho Kang
  !       DATE WRITTEN   Aug 2008
  !       MODIFIED       na
  !       RE-ENGINEERED  na

  ! PURPOSE OF THIS MODULE:
  ! To encapsulate the data and algorithyms required to manage the cooltower component.

  ! METHODOLOGY EMPLOYED:
  ! na

  ! REFERENCES:
  ! Baruch Givoni. 1994. Passive and Low Energy Cooling of Buildings. Chapter 5: Evaporative Cooling Systems.
  !     John Wiley & Sons, Inc.
  !
  ! OTHER NOTES: none

  ! USE STATEMENTS:
USE DataPrecisionGlobals
USE DataGlobals
USE DataHeatBalance
USE DataInterfaces

          ! Use statements for access to subroutines in other modules

IMPLICIT NONE

  ! MODULE PARAMETER DEFINITIONS
INTEGER, PARAMETER :: WaterSupplyFromMains = 101
INTEGER, PARAMETER :: WaterSupplyFromTank  = 102
INTEGER, PARAMETER :: WaterFlowSchedule = 0
INTEGER, PARAMETER :: WindDrivenFlow    = 1

! DERIVED TYPE DEFINITIONS
TYPE CoolTowerParams
    CHARACTER(len=MaxNameLength) :: Name       =' '    ! The component name
    CHARACTER(len=MaxNameLength) :: CompType   =' '    ! Type of component
    CHARACTER(len=MaxNameLength) :: Schedule   =' '    ! Available schedule
    CHARACTER(len=MaxNameLength) :: ZoneName   =' '    ! Name of zone the component is serving
    CHARACTER(len=MaxNameLength) :: PumpSchedName =' ' ! Available schedule of the water pump
    INTEGER :: SchedPtr                  = 0 ! Index to schedule
    INTEGER :: ZonePtr                   = 0 ! Point to this zone
    INTEGER :: PumpSchedPtr              = 0 ! Index to schedule for water pump
    INTEGER :: FlowCtrlType              = 0 ! Type of cooltower operation
    INTEGER :: CoolTWaterSupplyMode      = WaterSupplyFromMains ! Type of water source
    CHARACTER(len=MaxNameLength) :: CoolTWaterSupplyName = ' '  ! Name of water source
    INTEGER :: CoolTWaterSupTankID       = 0 ! Index to water storage tank
    INTEGER :: CoolTWaterTankDemandARRID = 0 ! Index to water storage demand
    REAL(r64) :: TowerHeight             = 0.0d0 ! Effective cooltower height in m
    REAL(r64) :: OutletArea              = 0.0d0 ! Outlet area where conditioned air comes in m2
    REAL(r64) :: OutletVelocity          = 0.0d0 ! Outlet velocity of the cooltower in m/s
    REAL(r64) :: MaxAirVolFlowRate       = 0.0d0 ! Maximum allowable airflow in m3/s
    REAL(r64) :: AirMassFlowRate         = 0.0d0 ! Air mass flow rate in kg/s
    REAL(r64) :: CoolTAirMass            = 0.0d0 ! Air mass in kg
    REAL(r64) :: MinZoneTemp             = 0.0d0 ! Lower temperature limit to prevent over cooling in C
    REAL(r64) :: FracWaterLoss           = 0.0d0 ! Fraction of estimated blowdown and drift water
    REAL(r64) :: FracFlowSched           = 0.0d0 ! Fraction of airflow loss
    REAL(r64) :: MaxWaterFlowRate        = 0.0d0 ! Maximum limit of water flow rate in m3/s
    REAL(r64) :: ActualWaterFlowRate     = 0.0d0 ! Actual water mass flow rate in m3/s
    REAL(r64) :: RatedPumpPower          = 0.0d0 ! Rated power consumption for water pump serving the cooltower in watts
    REAL(r64) :: SenHeatLoss             = 0.0d0 ! Sensible heat loss in Joules
    REAL(r64) :: SenHeatPower            = 0.0d0 ! Sensible heat loss rate in watts
    REAL(r64) :: LatHeatLoss             = 0.0d0 ! Latent heat loss in Joules
    REAL(r64) :: LatHeatPower            = 0.0d0 ! Latent heat loss rate in watts
    REAL(r64) :: AirVolFlowRate          = 0.0d0 ! Air flow rate in m3/s
    REAL(r64) :: CoolTAirVol             = 0.0d0 ! Air volume in m3
    REAL(r64) :: ActualAirVolFlowRate    = 0.0d0 ! Actual air flow rate in m3/s
    REAL(r64) :: InletDBTemp             = 0.0d0 ! Outdoor dry bulb temperature in C
    REAL(r64) :: InletWBTemp             = 0.0d0 ! Outdoor wet bulb temperature in C
    REAL(r64) :: InletHumRat             = 0.0d0 ! Outdoor humidity ratio
    REAL(r64) :: OutletTemp              = 0.0d0 ! Dry bulb temperature at cooltower exit in C
    REAL(r64) :: OutletHumRat            = 0.0d0 ! Humidity ratio at cooltower exit
    REAL(r64) :: CoolTWaterConsumpRate   = 0.0d0 ! Total water consumption during the processes in m3/s
    REAL(r64) :: CoolTWaterStarvMakeupRate = 0.0d0 ! Water provided from the mains (m3/s)
    REAL(r64) :: CoolTWaterStarvMakeup   = 0.0d0 ! Water provided from the mains
    REAL(r64) :: CoolTWaterConsump       = 0.0d0 ! Total water consumption in m3
    REAL(r64) :: PumpElecPower           = 0.0d0 ! Pump power in watts
    REAL(r64) :: PumpElecConsump         = 0.0d0 ! Pump energy consumption in Joules

END TYPE CoolTowerParams

! MODULE VARIABLES DECLARATIONS:
TYPE (CoolTowerParams), ALLOCATABLE, DIMENSION(:) :: CoolTowerSys
INTEGER :: NumCoolTowers = 0                    ! Total cooltower statements in inputs

! Subroutine Specifications for the Heat Balance Module
PUBLIC  ManageCoolTower
PRIVATE GetCoolTower
PRIVATE CalcCoolTower
PRIVATE UpdateCoolTower
PRIVATE ReportCoolTower

CONTAINS


SUBROUTINE ManageCoolTower

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Daeho Kang
          !       DATE WRITTEN   Aug 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine manages the simulation of Cooltower component.
          ! This driver manages the calls to all of the other drivers and simulation algorithms.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  LOGICAL, SAVE :: GetInputFlag=.true.
!unused1208  LOGICAL :: ErrorsFound=.false.
!unused1208  INTEGER :: CoolTowerNum

        ! Obtains and allocates heat balance related parameters from input
  IF (GetInputFlag) THEN
    CALL GetCoolTower
    GetInputFlag=.false.
  ENDIF

  IF (NumCoolTowers == 0) RETURN

  CALL CalcCoolTower

  CALL UpdateCoolTower

  CALL ReportCoolTower

  RETURN

END SUBROUTINE ManageCoolTower


SUBROUTINE GetCooltower

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Daeho Kang
          !       DATE WRITTEN   Aug 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine gets input data for cooltower components
          ! and stores it in the Cooltower data structure.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor,   ONLY: GetNumObjectsFound,GetObjectItem,FindItemInList,SameString,VerifyName,GetObjectDefMaxArgs
  USE ScheduleManager,  ONLY: GetScheduleIndex
  USE WaterManager,     ONLY: SetupTankDemandComponent
  USE General,          ONLY: RoundSigDigits

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:

          ! SUBROUTINE PARAMETER DEFINITIONS:
  CHARACTER(len=*), PARAMETER :: Blank = ' '
  CHARACTER(len=*), PARAMETER :: CurrentModuleObject='ZoneCoolTower:Shower'
  REAL(r64), PARAMETER :: MaximumWaterFlowRate = 0.016667d0  ! Maximum limit of water flow rate in m3/s (1000 l/min)
  REAL(r64), PARAMETER :: MinimumWaterFlowRate = 0.0d0       ! Minimum limit of water flow rate
  REAL(r64), PARAMETER :: MaxHeight = 30.0d0      ! Maximum effective tower height in m
  REAL(r64), PARAMETER :: MinHeight = 1.0d0       ! Minimum effective tower height in m
  REAL(r64), PARAMETER :: MaxValue = 100.0d0      ! Maximum limit of outlet area, airflow, and temperature
  REAL(r64), PARAMETER :: MinValue = 0.0d0        ! Minimum limit of outlet area, airflow, and temperature
  REAL(r64), PARAMETER :: MaxFrac = 1.0d0         ! Maximum fraction
  REAL(r64), PARAMETER :: MinFrac = 0.0d0         ! Minimum fraction

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
    LOGICAL :: ErrorsFound = .false.    ! If errors detected in input
    LOGICAL :: IsNotOK                  ! Flag to verify name
    LOGICAL :: IsBlank                  ! Flag for blank name
    INTEGER :: CoolTowerNum             ! Cooltower number
    INTEGER :: NumAlphas                ! Number of Alphas for each GetobjectItem call
    INTEGER :: NumNumbers               ! Number of Numbers for each GetobjectItem call
    INTEGER :: NumArgs
    INTEGER :: IOStat
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cAlphaArgs      ! Alpha input items for object
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cAlphaFields   ! Alpha field names
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cNumericFields ! Numeric field names
    REAL(r64), ALLOCATABLE, DIMENSION(:) :: rNumericArgs          ! Numeric input items for object
    LOGICAL, ALLOCATABLE, DIMENSION(:)   :: lAlphaBlanks      ! Logical array, alpha field input BLANK = .true.
    LOGICAL, ALLOCATABLE, DIMENSION(:)   :: lNumericBlanks    ! Logical array, numeric field input BLANK = .true.

            ! Initializations and allocations
   CALL GetObjectDefMaxArgs(CurrentModuleObject,NumArgs,NumAlphas,NumNumbers)
   ALLOCATE(cAlphaArgs(NumAlphas))
   cAlphaArgs=' '
   ALLOCATE(cAlphaFields(NumAlphas))
   cAlphaFields=' '
   ALLOCATE(cNumericFields(NumNumbers))
   cNumericFields=' '
   ALLOCATE(rNumericArgs(NumNumbers))
   rNumericArgs=0.0d0
   ALLOCATE(lAlphaBlanks(NumAlphas))
   lAlphaBlanks=.true.
   ALLOCATE(lNumericBlanks(NumNumbers))
   lNumericBlanks=.true.

NumCoolTowers = GetNumObjectsFound(CurrentModuleObject)

ALLOCATE (CoolTowerSys(NumCoolTowers))

            ! Obtain inputs
DO CoolTowerNum = 1, NumCoolTowers

    CALL GetObjectItem(CurrentModuleObject,CoolTowerNum,cAlphaArgs,NumAlphas,rNumericArgs,NumNumbers,IOStat,  &
                   AlphaBlank=lAlphaBlanks,NumBlank=lNumericBlanks,  &
                   AlphaFieldnames=cAlphaFields,NumericFieldNames=cNumericFields)
        IsNotOK=.false.
        IsBlank=.false.
        CALL VerifyName(cAlphaArgs(1),CoolTowerSys%Name,CoolTowerNum,IsNotOK,IsBlank,CurrentModuleObject//' Name')

        IF (IsNotOK) THEN
           ErrorsFound = .true.
        ENDIF

    CoolTowerSys(CoolTowerNum)%Name = cAlphaArgs(1)       ! Name of cooltower

    CoolTowerSys(CoolTowerNum)%Schedule = cAlphaArgs(2)   ! Get schedule
    IF (lAlphaBlanks(2)) THEN
      CoolTowerSys(CoolTowerNum)%SchedPtr  = ScheduleAlwaysOn
    ELSE
      CoolTowerSys(CoolTowerNum)%SchedPtr  = GetScheduleIndex(cAlphaArgs(2))
      IF (CoolTowerSys(CoolTowerNum)%SchedPtr == 0) THEN
        CALL ShowSevereError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid data')
        CALL ShowContinueError('Invalid-Schedule not found '//trim(cAlphaFields(2))//'="'//trim(cAlphaArgs(2))//'".')
        ErrorsFound = .TRUE.
      ENDIF
    ENDIF

    CoolTowerSys(CoolTowerNum)%ZoneName = cAlphaArgs(3)   ! Name of zone where cooltower is serving
    CoolTowerSys(CoolTowerNum)%ZonePtr = FindIteminList(cAlphaArgs(3),Zone%Name,NumOfZones)
    IF (CoolTowerSys(CoolTowerNum)%ZonePtr == 0) THEN
      IF (lAlphaBlanks(3)) THEN
        CALL ShowSevereError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cAlphaFields(3))//' is required but input is blank.')
      ELSE
        CALL ShowSevereError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cAlphaFields(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
      END IF
      ErrorsFound = .TRUE.
    ENDIF

    CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyName = cAlphaArgs(4) ! Name of water storage tank
    IF (lAlphaBlanks(4)) THEN
       CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyMode = WaterSupplyFromMains
    ELSE IF (CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyMode == WaterSupplyFromTank) THEN
       CALL SetupTankDemandComponent(CoolTowerSys(CoolTowerNum)%Name, CurrentModuleObject, &
                    CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyName, ErrorsFound, &
                    CoolTowersys(CoolTowerNum)%CoolTWaterSupTankID, &
                    CoolTowerSys(CoolTowerNum)%CoolTWaterTankDemandARRID)
    ENDIF

    SELECT CASE (cAlphaArgs(5))    ! Type of flow control
      CASE ('WATERFLOWSCHEDULE')
        CoolTowerSys(CoolTowerNum)%FlowCtrlType = WaterFlowSchedule
      CASE ('WINDDRIVENFLOW','NONE',' ')
        CoolTowerSys(CoolTowerNum)%FlowCtrlType = WindDrivenFlow
      CASE DEFAULT
        CALL ShowSevereError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
          trim(cAlphaFields(5))//'="'//trim(cAlphaArgs(5))//'".')
        ErrorsFound = .TRUE.
    END SELECT

    CoolTowerSys(CoolTowerNum)%PumpSchedName = cAlphaArgs(6)  !Get schedule for water pump
    CoolTowerSys(CoolTowerNum)%PumpSchedPtr  = GetScheduleIndex(cAlphaArgs(6))
    IF (CoolTowerSys(CoolTowerNum)%PumpSchedPtr == 0) THEN
      IF (lAlphaBlanks(6)) THEN
        CALL ShowSevereError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cAlphaFields(6))//' is required but input is blank.')
      ELSE
        CALL ShowSevereError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cAlphaFields(6))//'="'//trim(cAlphaArgs(6))//'" not found.')
      ENDIF
      ErrorsFound = .TRUE.
    ENDIF

    CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate = rNumericArgs(1)   ! Maximum limit of water supply
    IF (CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate > MaximumWaterFlowRate) THEN
        CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate = MaximumWaterFlowRate
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(1))//'=['//trim(RoundSigDigits(rNumericArgs(1),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaximumWaterFlowRate,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate < MinimumWaterFlowRate) THEN
        CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate = MinimumWaterFlowRate
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(1))//'=['//trim(RoundSigDigits(rNumericArgs(1),2))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinimumWaterFlowRate,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%TowerHeight = rNumericArgs(2)     ! Get effctive tower height
    IF (CoolTowerSys(CoolTowerNum)%TowerHeight > MaxHeight) THEN
        CoolTowerSys(CoolTowerNum)%TowerHeight = MaxHeight
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(2))//'=['//trim(RoundSigDigits(rNumericArgs(2),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaxHeight,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%TowerHeight < MinHeight)  THEN
        CoolTowerSys(CoolTowerNum)%TowerHeight = MinHeight
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(2))//'=['//trim(RoundSigDigits(rNumericArgs(2),2))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinHeight,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%OutletArea = rNumericArgs(3)      ! Get outlet area
    IF (CoolTowerSys(CoolTowerNum)%OutletArea > MaxValue) THEN
        CoolTowerSys(CoolTowerNum)%OutletArea = MaxValue
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(3))//'=['//trim(RoundSigDigits(rNumericArgs(3),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaxValue,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%OutletArea < MinValue) THEN
        CoolTowerSys(CoolTowerNum)%OutletArea = MinValue
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(3))//'=['//trim(RoundSigDigits(rNumericArgs(3),2))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinValue,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate = rNumericArgs(4)   ! Maximum limit of air flow to the space
    IF (CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate > MaxValue) THEN
        CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate = MaxValue
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(4))//'=['//trim(RoundSigDigits(rNumericArgs(4),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaxValue,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate < MinValue) THEN
        CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate = MinValue
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(4))//'=['//trim(RoundSigDigits(rNumericArgs(4),2))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinValue,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%MinZoneTemp = rNumericArgs(5)     ! Get minimum temp limit which gets this cooltower off
    IF (CoolTowerSys(CoolTowerNum)%MinZoneTemp > MaxValue) THEN
        CoolTowerSys(CoolTowerNum)%MinZoneTemp = MaxValue
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(5))//'=['//trim(RoundSigDigits(rNumericArgs(5),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaxValue,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%MinZoneTemp < MinValue) THEN
        CoolTowerSys(CoolTowerNum)%MinZoneTemp = MinValue
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(5))//'=['//trim(RoundSigDigits(rNumericArgs(5),2))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinValue,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%FracWaterLoss = rNumericArgs(6)   ! Fraction of water loss
    IF (CoolTowerSys(CoolTowerNum)%FracWaterLoss > MaxFrac) THEN
        CoolTowerSys(CoolTowerNum)%FracWaterLoss = MaxFrac
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(6))//'=['//trim(RoundSigDigits(rNumericArgs(6),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaxFrac,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%FracWaterLoss < MinFrac) THEN
        CoolTowerSys(CoolTowerNum)%FracWaterLoss = MinFrac
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(6))//'=['//trim(RoundSigDigits(rNumericArgs(6),2))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinFrac,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%FracFlowSched = rNumericArgs(7)   ! Fraction of loss of air flow
    IF (CoolTowerSys(CoolTowerNum)%FracFlowSched > MaxFrac) THEN
        CoolTowerSys(CoolTowerNum)%FracFlowSched = MaxFrac
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(7))//'=['//trim(RoundSigDigits(rNumericArgs(7),2))//'].')
        CALL ShowContinueError('...Maximum Allowable=['//trim(RoundSigDigits(MaxFrac,2))//'].')
    END IF
    IF (CoolTowerSys(CoolTowerNum)%FracFlowSched < MinFrac) THEN
        CoolTowerSys(CoolTowerNum)%FracFlowSched = MinFrac
        CALL ShowWarningError(trim(CurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//   &
           trim(cNumericFields(7))//'=['//trim(RoundSigDigits(rNumericArgs(7),5))//'].')
        CALL ShowContinueError('...Minimum Allowable=['//trim(RoundSigDigits(MinFrac,2))//'].')
    END IF

    CoolTowerSys(CoolTowerNum)%RatedPumpPower = rNumericArgs(8)  ! Get rated pump power

END DO

  DEALLOCATE(cAlphaArgs)
  DEALLOCATE(cAlphaFields)
  DEALLOCATE(cNumericFields)
  DEALLOCATE(rNumericArgs)
  DEALLOCATE(lAlphaBlanks)
  DEALLOCATE(lNumericBlanks)

  IF (ErrorsFound) Call ShowFatalError(CurrentModuleObject//' errors occurred in input.  Program terminates.')

DO CoolTowerNum = 1, NumCoolTowers
    CALL SetupOutputVariable('Zone Cooltower Sensible Heat Loss Energy [J]',CoolTowerSys(CoolTowerNum)%SenHeatLoss, &
                             'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Sensible Heat Loss Rate [W]',CoolTowerSys(CoolTowerNum)%SenHeatPower, &
                              'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Latent Heat Loss Energy [J]',CoolTowerSys(CoolTowerNum)%LatHeatLoss, &
                             'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Latent Heat Loss Rate [W]',CoolTowerSys(CoolTowerNum)%LatHeatPower, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Volume [m3]',CoolTowerSys(CoolTowerNum)%CoolTAirVol, &
                             'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Volume Flow Rate [m3/s]',CoolTowerSys(CoolTowerNum)%AirVolFlowRate, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Mass [kg]',CoolTowerSys(CoolTowerNum)%CoolTAirMass, &
                             'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Mass Flow Rate [kg/s]',CoolTowerSys(CoolTowerNum)%AirMassFlowRate, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Inlet Temperature [C]',CoolTowerSys(CoolTowerNum)%InletDBTemp, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Inlet Humidity Ratio [kgWater/kgDryAir]',CoolTowerSys(CoolTowerNum)%InletHumRat, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Outlet Temperature [C]',CoolTowerSys(CoolTowerNum)%OutletTemp, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Air Outlet Humidity Ratio [kgWater/kgDryAir]',  &
                             CoolTowerSys(CoolTowerNum)%OutletHumRat, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Pump Electric Power [W]',CoolTowerSys(CoolTowerNum)%PumpElecPower, &
                             'System','Average',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
    CALL SetupOutputVariable('Zone Cooltower Pump Electric Energy [J]',CoolTowerSys(CoolTowerNum)%PumpElecConsump, &
                             'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name, &
                             ResourceTypeKey='Electric',EndUseKey='Cooling',GroupKey='System')
    IF (CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyMode == WaterSupplyFromMains) THEN
        CALL SetupOutputVariable('Zone Cooltower Water Volume [m3]',CoolTowerSys(CoolTowerNum)%CoolTWaterConsump, &
                                  'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
        CALL SetupOutputVariable('Zone Cooltower Mains Water Volume [m3]',CoolTowerSys(CoolTowerNum)%CoolTWaterConsump, &
                                 'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name, &
                                  ResourceTypeKey='MainsWater',EndUseKey='Cooling',GroupKey='System')
    ELSE IF  (CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyMode == WaterSupplyFromTank) THEN
        CALL SetupOutputVariable('Zone Cooltower Water Volume [m3]',CoolTowerSys(CoolTowerNum)%CoolTWaterConsump, &
                                  'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
        CALL SetupOutputVariable('Zone Cooltower Storage Tank Water Volume [m3]',CoolTowerSys(CoolTowerNum)%CoolTWaterConsump, &
                                 'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name)
        CALL SetupOutputVariable('Zone Cooltower Starved Mains Water Volume [m3]',  &
                                  CoolTowerSys(CoolTowerNum)%CoolTWaterStarvMakeup, &
                                 'System','Sum',Zone(CoolTowerSys(CoolTowerNum)%ZonePtr)%Name, &
                                  ResourceTypeKey='MainsWater',EndUseKey='Cooling',GroupKey='System')
    END IF
END DO

RETURN

END SUBROUTINE GetCoolTower


SUBROUTINE CalcCoolTower

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Daeho Kang
          !       DATE WRITTEN   Aug 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          !

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! Baruch Givoni. 1994. Passive and Low Energy Cooling of Buildings. Chapter 5: Evaporative Cooling Systems.
          !     John Wiley & Sons, Inc.

          ! USE STATEMENTS:
USE DataHeatBalFanSys, ONLY: MAT, ZT, ZoneAirHumRat, MCPC, MCPTC, CTMFL
USE ScheduleManager,   ONLY: GetCurrentScheduleValue
USE Psychrometrics,    ONLY: PsyCpAirFnWTdb, PsyWFnTdbTwbPb, PsyWFnTdbH, PsyRhoAirFnPbTdbW, RhoH2O
USE DataEnvironment,   ONLY: OutBaroPress, OutDryBulbTemp, OutWetBulbTemp, OutHumRat, WindSpeed, OutEnthalpy

IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:

          ! SUBROUTINE PARAMETER DEFINITIONS:
REAL(r64), PARAMETER :: MinWindSpeed = 0.1d0    ! Minimum limit of outdoor air wind speed in m/s
REAL(r64), PARAMETER :: MaxWindSpeed = 30.0d0   ! Maximum limit of outdoor air wind speed in m/s
REAL(r64), PARAMETER :: UCFactor = 60000.0d0    ! Unit conversion factor m3/s to l/min

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
INTEGER :: ZoneNum              ! Number of zone being served
INTEGER :: CoolTowerNum         ! Number of coolter being served
REAL(r64), ALLOCATABLE, DIMENSION(:), SAVE :: CVF  ! Design flow rate in m3/s
REAL(r64) :: AirMassFlowRate    ! Actual air mass flow rate in kg/s
REAL(r64) :: AirSpecHeat        ! Specific heat of air
REAL(r64) :: AirDensity         ! Density of air
REAL(r64) :: RhoWater           ! Density of water
REAL(r64) :: PumpPartLoadRat    ! Pump part load ratio (based on user schedule, or 1.0 for no schedule)
REAL(r64) :: WaterFlowRate      ! Calculated water flow rate in m3/s
REAL(r64) :: AirVolFlowRate     ! Calculated air volume flow rate in m3/s
REAL(r64) :: InletHumRat        ! Humidity ratio of outdoor air
!unused1208REAL(r64) :: InletEnthalpy      ! Enthalpy of outdoor air
REAL(r64) :: OutletHumRat       ! Humidity ratio of air at the cooltower outlet
REAL(r64) :: OutletTemp         ! Dry bulb temperature of air at the cooltower outlet
REAL(r64) :: IntHumRat          ! Humidity ratio of initialized air

            ! Allocate the CVF array
IF (.NOT. ALLOCATED(CVF)) ALLOCATE(CVF(NumOfZones))
    CVF  = 0.0d0
    MCPTC = 0.0d0
    MCPC  = 0.0d0
    CTMFL = 0.0d0

DO CoolTowerNum = 1, NumCoolTowers
    ZoneNum = CoolTowerSys(CoolTowerNum)%ZonePtr

    IF (GetCurrentScheduleValue(CoolTowerSys(CoolTowerNum)%SchedPtr) > 0.0d0) THEN
            ! check component operation
        IF (WindSpeed < MinWindSpeed .OR. WindSpeed > MaxWindSpeed)  CYCLE
        IF (MAT(ZoneNum) < CoolTowerSys(CoolTowerNum)%MinZoneTemp)   CYCLE

            ! Unit is on and simulate this component
            ! Determine the temperature and air flow rate at the cooltower outlet
        IF (CoolTowerSys(CoolTowerNum)%FlowCtrlType == WindDrivenFlow) THEN
            CoolTowerSys(CoolTowerNum)%OutletVelocity = 0.7d0 * (CoolTowerSys(CoolTowerNum)%TowerHeight)**0.5d0 + &
                                                        0.47d0 * (WindSpeed - 1.d0)
            AirVolFlowRate = CoolTowerSys(CoolTowerNum)%OutletArea * CoolTowerSys(CoolTowerNum)%OutletVelocity
            AirVolFlowRate = Min(AirVolFlowRate,CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate)
            WaterFlowRate  = (AirVolFlowRate / (0.0125d0 * (CoolTowerSys(CoolTowerNum)%TowerHeight)**0.5d0))
            IF (WaterFlowRate > CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate * UCFactor) THEN
                WaterFlowRate = CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate * UCFactor
                AirVolFlowRate = 0.0125d0 * WaterFlowRate * (CoolTowerSys(CoolTowerNum)%TowerHeight)**0.5d0
                AirVolFlowRate = Min(AirVolFlowRate,CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate)
            END IF
            WaterFlowRate = MIN(WaterFlowRate,(CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate * UCFactor))
            OutletTemp    = OutDryBulbTemp - (OutDryBulbTemp - OutWetBulbTemp) * &
                            (1.d0-exp(-0.8d0 * CoolTowerSys(CoolTowerNum)%TowerHeight)) * &
                            (1.d0-exp(-0.15d0 * WaterFlowRate))
        ELSE IF (CoolTowerSys(CoolTowerNum)%FlowCtrlType == WaterFlowSchedule) THEN
            WaterFlowRate  = CoolTowerSys(CoolTowerNum)%MaxWaterFlowRate * UCFactor
            AirVolFlowRate = 0.0125d0 * WaterFlowRate * (CoolTowerSys(CoolTowerNum)%TowerHeight)**0.5d0
            AirVolFlowRate = Min(AirVolFlowRate,CoolTowerSys(CoolTowerNum)%MaxAirVolFlowRate)
            OutletTemp     = OutDryBulbTemp - (OutDryBulbTemp - OutWetBulbTemp) * &
                            (1.d0-exp(-0.8d0 * CoolTowerSys(CoolTowerNum)%TowerHeight)) * &
                            (1.d0-exp(-0.15d0 * WaterFlowRate))
        END IF

        IF (OutletTemp < OutWetBulbTemp) THEN
            CALL ShowSevereError('Cooltower outlet temperature exceed the outdoor wet bulb temperature '//&
                            'reset to input values')
            CALL ShowContinueError('Occurs in Cooltower ='//TRIM(CoolTowerSys(CoolTowerNum)%Name))
        END IF

            WaterFlowRate = WaterFlowRate / UCFactor
            ! Determine actual water flow rate
        IF (CoolTowerSys(CoolTowerNum)%FracWaterLoss > 0.0d0) THEN
            CoolTowerSys(CoolTowerNum)%ActualWaterFlowRate = WaterFlowRate * &
                                                            (1.0d0 + CoolTowerSys(CoolTowerNum)%FracWaterLoss)
        ELSE
            CoolTowerSys(CoolTowerNum)%ActualWaterFlowRate = WaterFlowRate
        END IF

            ! Determine actual air flow rate
        IF (CoolTowerSys(CoolTowerNum)%FracFlowSched > 0.0d0) THEN
            CoolTowerSys(CoolTowerNum)%ActualAirVolFlowRate = AirVolFlowRate * &
                                                            (1.0d0 - CoolTowerSys(CoolTowerNum)%FracFlowSched)
        ELSE
            CoolTowerSys(CoolTowerNum)%ActualAirVolFlowRate = AirVolFlowRate
        END IF

                     ! Determine pump power
        IF (GetCurrentScheduleValue(CoolTowerSys(CoolTowerNum)%PumpSchedPtr) > 0) THEN
            PumpPartLoadRat = GetCurrentScheduleValue(CoolTowerSys(CoolTowerNum)%PumpSchedPtr)
        ELSE
            PumpPartLoadRat = 1.0d0
        END IF

            ! Determine air mass flow rate and volume flow rate
        InletHumRat   = PsyWFnTdbTwbPb(OutDryBulbTemp,OutWetBulbTemp,OutBaroPress)
            ! Assume no pressure drops and no changes in enthalpy between inlet and outlet air
        IntHumRat  = PsyWFnTdbH(OutletTemp,OutEnthalpy)     ! Initialized humidity ratio
        AirDensity = PsyRhoAirFnPbTdbW(OutBaroPress,OutletTemp,IntHumRat)
        AirMassFlowRate = AirDensity * CoolTowerSys(CoolTowerNum)%ActualAirVolFlowRate
            ! From the mass balance W_in*(m_air + m_water) = W_out*m_air
        RhoWater = RhoH2O(OutletTemp)   ! Assume T_water = T_outlet
        OutletHumRat = (InletHumRat*(AirMassFlowRate + (CoolTowerSys(CoolTowerNum)%ActualWaterFlowRate * RhoWater))) &
                        / AirMassFlowRate
        AirSpecHeat  = PsyCpAirFnWTdb(OutletHumRat,OutletTemp)
        AirDensity   = PsyRhoAirFnPbTdbW(OutBaroPress,OutletTemp,OutletHumRat)  ! Outlet air density
        CVF(ZoneNum) = CoolTowerSys(CoolTowerNum)%ActualAirVolFlowRate * &
                        GetCurrentScheduleValue(CoolTowerSys(CoolTowerNum)%SchedPtr)
        MCPC(ZoneNum)  = CVF(ZoneNum) * AirDensity * AirSpecHeat
        MCPTC(ZoneNum) = MCPC(ZoneNum) * OutletTemp
        CTMFL(ZoneNum) = MCPC(ZoneNum) / AirSpecHeat

        CoolTowerSys(CoolTowerNum)%SenHeatPower = MCPC(ZoneNum) * ABS(ZT(ZoneNum) - OutletTemp)
        CoolTowerSys(CoolTowerNum)%LatHeatPower = CVF(ZoneNum) * ABS(ZoneAirHumRat(ZoneNum) - OutletHumRat)
        CoolTowerSys(CoolTowerNum)%OutletTemp   = OutletTemp
        CoolTowerSys(CoolTowerNum)%OutletHumRat = OutletHumRat
        CoolTowerSys(CoolTowerNum)%AirVolFlowRate = CVF(ZoneNum)
        CoolTowerSys(CoolTowerNum)%AirMassFlowRate = CTMFL(ZoneNum)
        CoolTowerSys(CoolTowerNum)%InletDBTemp = Zone(ZoneNum)%OutDryBulbTemp
        CoolTowerSys(CoolTowerNum)%InletWBTemp = Zone(ZoneNum)%OutWetBulbTemp
        CoolTowerSys(CoolTowerNum)%InletHumRat = OutHumRat
        CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate = (ABS(InletHumRat - OutletHumRat)*CTMFL(ZoneNum)) / RhoWater
        CoolTowerSys(CoolTowerNum)%CoolTWaterStarvMakeupRate = 0.0d0  ! initialize -- calc in update
        CoolTowerSys(CoolTowerNum)%PumpElecPower = CoolTowerSys(CoolTowerNum)%RatedPumpPower * PumpPartLoadRat
    ELSE    ! Unit is off
        CoolTowerSys(CoolTowerNum)%SenHeatPower = 0.0d0
        CoolTowerSys(CoolTowerNum)%LatHeatPower = 0.0d0
        CoolTowerSys(CoolTowerNum)%OutletTemp   = 0.0d0
        CoolTowerSys(CoolTowerNum)%OutletHumRat = 0.0d0
        CoolTowerSys(CoolTowerNum)%AirVolFlowRate = 0.0d0
        CoolTowerSys(CoolTowerNum)%AirMassFlowRate = 0.0d0
        CoolTowerSys(CoolTowerNum)%InletDBTemp = 0.0d0
        CoolTowerSys(CoolTowerNum)%InletHumRat = 0.0d0
        CoolTowerSys(CoolTowerNum)%PumpElecPower = 0.0d0
        CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate = 0.0d0
        CoolTowerSys(CoolTowerNum)%CoolTWaterStarvMakeupRate = 0.0d0
    END IF

END DO

RETURN

END SUBROUTINE CalcCoolTower


SUBROUTINE UpdateCoolTower

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       Aug 2008 Daeho Kang
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
USE DataWater

IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
INTEGER   :: CoolTowerNum
REAL(r64) :: AvailWaterRate

DO CoolTowerNum = 1, NumCoolTowers

       ! Set the demand request for supply water from water storage tank (if needed)
    IF (CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyMode == WaterSupplyFromTank) THEN
      WaterStorage(CoolTowerSys(CoolTowerNum)%CoolTWaterSupTankID)% &
      VdotRequestDemand(CoolTowerSys(CoolTowerNum)%CoolTWaterTankDemandARRID) &
      = CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate
    END IF

       !check if should be starved by restricted flow from tank
    IF (CoolTowerSys(CoolTowerNum)%CoolTWaterSupplyMode == WaterSupplyFromTank) THEN
      AvailWaterRate = WaterStorage(CoolTowerSys(CoolTowerNum)%CoolTWaterSupTankID)%VdotAvailDemand &
                    (CoolTowerSys(CoolTowerNum)%CoolTWaterTankDemandARRID)
      IF (AvailWaterRate < CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate) THEN
        CoolTowerSys(CoolTowerNum)%CoolTWaterStarvMakeupRate = &
                      CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate - AvailWaterRate
        CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate = AvailWaterRate
      END IF
    END IF

END DO

RETURN

END Subroutine UpdateCoolTower


SUBROUTINE ReportCoolTower

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Daeho Kang
          !       DATE WRITTEN   Aut 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
USE DataHVACGlobals, ONLY: TimeStepSys


IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
INTEGER :: CoolTowerNum
REAL(r64) :: TSMult

TSMult=TimeStepSys*SecInHour


DO CoolTowerNum = 1, NumCoolTowers

    CoolTowerSys(CoolTowerNum)%CoolTAirVol  = CoolTowerSys(CoolTowerNum)%AirVolFlowRate * TSMult
    CoolTowerSys(CoolTowerNum)%CoolTAirMass = CoolTowerSys(CoolTowerNum)%AirMassFlowRate * TSMult
    CoolTowerSys(CoolTowerNum)%SenHeatLoss      = CoolTowerSys(CoolTowerNum)%SenHeatPower * TSMult
    CoolTowerSys(CoolTowerNum)%LatHeatLoss      = CoolTowerSys(CoolTowerNum)%LatHeatPower * TSMult
    CoolTowerSys(CoolTowerNum)%PumpElecConsump   = CoolTowerSys(CoolTowerNum)%PumpElecPower * TSMult
    CoolTowerSys(CoolTowerNum)%CoolTWaterConsump = CoolTowerSys(CoolTowerNum)%CoolTWaterConsumpRate * TSMult
    CoolTowerSys(CoolTowerNum)%CoolTWaterStarvMakeup = CoolTowerSys(CoolTowerNum)%CoolTWaterStarvMakeupRate * TSMult
END DO

RETURN

END SUBROUTINE ReportCoolTower

!*****************************************************************************************
!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!

END MODULE CoolTower

AirflowNetworkBalanceManager.f90 AirflowNetworkSolver.f90 BaseboardRadiator.f90 BaseboardRadiatorElectric.f90 BaseboardRadiatorSteam.f90 BaseboardRadiatorWater.f90 BranchInputManager.f90 BranchNodeConnections.f90 ConductionTransferFunctionCalc.f90 CoolTower.f90 CostEstimateManager.f90 CurveManager.f90 CVFOnlyRoutines.f90 DataAirflowNetwork.f90 DataAirLoop.f90 DataAirSystems.f90 DataBranchAirLoopPlant.f90 DataBranchNodeConnections.f90 DataBSDFWindow.f90 DataComplexFenestration.f90 DataContaminantBalance.f90 DataConvergParams.f90 DataConversions.f90 DataCostEstimate.f90 DataDaylighting.f90 DataDaylightingDevices.f90 Datadefineequip.f90 DataDElight.f90 DataEnvironment.f90 DataEquivalentLayerWindow.f90 DataErrorTracking.f90 DataGenerators.f90 DataGlobalConstants.f90 DataGlobals.f90 DataHeatBalance.f90 DataHeatBalFanSys.f90 DataHeatBalSurface.f90 DataHVACControllers.f90 DataHVACGlobals.f90 DataInterfaces.f90 DataIPShortCuts.f90 DataLoopNode.f90 DataMoistureBalance.f90 DataMoistureBalanceEMPD.f90 DataOutputs.f90 DataPhotovoltaics.f90 DataPlant.f90 DataPlantPipingSystems.f90 DataPrecisionGlobals.f90 DataReportingFlags.f90 DataRoomAir.f90 DataRootFinder.f90 DataRuntimeLanguage.f90 DataShadowingCombinations.f90 DataSizing.f90 DataStringGlobals.f90 DataSurfaceColors.f90 DataSurfaceLists.f90 DataSurfaces.f90 DataSystemVariables.f90 DataTimings.f90 DataUCSDSharedData.f90 DataVectorTypes.f90 DataViewFactorInformation.f90 DataWater.f90 DataZoneControls.f90 DataZoneEnergyDemands.f90 DataZoneEquipment.f90 DaylightingDevices.f90 DaylightingManager.f90 DElightManagerF.f90 DElightManagerF_NO.f90 DemandManager.f90 DesiccantDehumidifiers.f90 DirectAir.f90 DisplayRoutines.f90 DXCoil.f90 EarthTube.f90 EconomicLifeCycleCost.f90 EconomicTariff.f90 EcoRoof.f90 ElectricPowerGenerators.f90 ElectricPowerManager.f90 EMSManager.f90 EnergyPlus.f90 ExteriorEnergyUseManager.f90 ExternalInterface_NO.f90 FanCoilUnits.f90 FaultsManager.f90 FluidProperties.f90 General.f90 GeneralRoutines.f90 GlobalNames.f90 HeatBalanceAirManager.f90 HeatBalanceConvectionCoeffs.f90 HeatBalanceHAMTManager.f90 HeatBalanceInternalHeatGains.f90 HeatBalanceIntRadExchange.f90 HeatBalanceManager.f90 HeatBalanceMovableInsulation.f90 HeatBalanceSurfaceManager.f90 HeatBalFiniteDifferenceManager.f90 HeatRecovery.f90 Humidifiers.f90 HVACControllers.f90 HVACCooledBeam.f90 HVACDualDuctSystem.f90 HVACDuct.f90 HVACDXSystem.f90 HVACEvapComponent.f90 HVACFanComponent.f90 HVACFurnace.f90 HVACHeatingCoils.f90 HVACHXAssistedCoolingCoil.f90 HVACInterfaceManager.f90 HVACManager.f90 HVACMixerComponent.f90 HVACMultiSpeedHeatPump.f90 HVACSingleDuctInduc.f90 HVACSingleDuctSystem.f90 HVACSplitterComponent.f90 HVACStandAloneERV.f90 HVACSteamCoilComponent.f90 HVACTranspiredCollector.f90 HVACUnitaryBypassVAV.f90 HVACUnitarySystem.f90 HVACVariableRefrigerantFlow.f90 HVACWaterCoilComponent.f90 HVACWatertoAir.f90 HVACWatertoAirMultiSpeedHP.f90 InputProcessor.f90 MatrixDataManager.f90 MixedAir.f90 MoistureBalanceEMPDManager.f90 NodeInputManager.f90 NonZoneEquipmentManager.f90 OutAirNodeManager.f90 OutdoorAirUnit.f90 OutputProcessor.f90 OutputReportPredefined.f90 OutputReports.f90 OutputReportTabular.f90 PackagedTerminalHeatPump.f90 PackagedThermalStorageCoil.f90 Photovoltaics.f90 PhotovoltaicThermalCollectors.f90 PlantAbsorptionChillers.f90 PlantBoilers.f90 PlantBoilersSteam.f90 PlantCentralGSHP.f90 PlantChillers.f90 PlantCondLoopOperation.f90 PlantCondLoopTowers.f90 PlantEIRChillers.f90 PlantEvapFluidCoolers.f90 PlantExhaustAbsorptionChiller.f90 PlantFluidCoolers.f90 PlantGasAbsorptionChiller.f90 PlantGroundHeatExchangers.f90 PlantHeatExchanger.f90 PlantIceThermalStorage.f90 PlantLoadProfile.f90 PlantLoopEquipment.f90 PlantLoopSolver.f90 PlantManager.f90 PlantOutsideEnergySources.f90 PlantPipeHeatTransfer.f90 PlantPipes.f90 PlantPipingSystemManager.f90 PlantPondGroundHeatExchanger.f90 PlantPressureSystem.f90 PlantPumps.f90 PlantSolarCollectors.f90 PlantSurfaceGroundHeatExchanger.f90 PlantUtilities.f90 PlantValves.f90 PlantWaterSources.f90 PlantWaterThermalTank.f90 PlantWatertoWaterGSHP.f90 PlantWaterUse.f90 PollutionAnalysisModule.f90 PoweredInductionUnits.f90 PsychRoutines.f90 Purchasedairmanager.f90 RadiantSystemHighTemp.f90 RadiantSystemLowTemp.f90 RefrigeratedCase.f90 ReportSizingManager.f90 ReturnAirPath.f90 RoomAirManager.f90 RoomAirModelCrossVent.f90 RoomAirModelDisplacementVent.f90 RoomAirModelMundt.f90 RoomAirModelUFAD.f90 RoomAirModelUserTempPattern.f90 RootFinder.f90 RuntimeLanguageProcessor.f90 ScheduleManager.f90 SetPointManager.f90 SimAirServingZones.f90 SimulationManager.f90 SizingManager.f90 SolarReflectionManager.f90 SolarShading.f90 SortAndStringUtilities.f90 sqlite3.c SQLiteCRoutines.c SQLiteFortranRoutines.f90 SQLiteFortranRoutines_NO.f90 StandardRatings.f90 SurfaceGeometry.f90 SystemAvailabilityManager.f90 SystemReports.f90 TarcogComplexFenestration.f90 ThermalChimney.f90 ThermalComfort.f90 UnitHeater.f90 UnitVentilator.f90 UserDefinedComponents.f90 UtilityRoutines.f90 VectorUtilities.f90 VentilatedSlab.f90 WaterManager.f90 WeatherManager.f90 WindowAC.f90 WindowComplexManager.f90 WindowEquivalentLayer.f90 WindowManager.f90 WindTurbine.f90 Zoneairloopequipmentmanager.f90 ZoneContaminantPredictorCorrector.f90 ZoneDehumidifier.f90 Zoneequipmentmanager.f90 ZonePlenumComponent.f90 ZoneTempPredictorCorrector.f90