sourcefile~~plantheatexchanger.f90~~EfferentGraph sourcefile~plantheatexchanger.f90 PlantHeatExchanger.f90 sourcefile~outputreportpredefined.f90 OutputReportPredefined.f90 sourcefile~outputreportpredefined.f90->sourcefile~plantheatexchanger.f90 sourcefile~reportsizingmanager.f90 ReportSizingManager.f90 sourcefile~outputreportpredefined.f90->sourcefile~reportsizingmanager.f90 sourcefile~outputprocessor.f90 OutputProcessor.f90 sourcefile~outputreportpredefined.f90->sourcefile~outputprocessor.f90 sourcefile~schedulemanager.f90 ScheduleManager.f90 sourcefile~schedulemanager.f90->sourcefile~plantheatexchanger.f90 sourcefile~nodeinputmanager.f90 NodeInputManager.f90 sourcefile~schedulemanager.f90->sourcefile~nodeinputmanager.f90 sourcefile~emsmanager.f90 EMSManager.f90 sourcefile~schedulemanager.f90->sourcefile~emsmanager.f90 sourcefile~sqlitefortranroutines.f90 SQLiteFortranRoutines.f90 sourcefile~schedulemanager.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~schedulemanager.f90->sourcefile~outputprocessor.f90 sourcefile~dataloopnode.f90 DataLoopNode.f90 sourcefile~dataloopnode.f90->sourcefile~plantheatexchanger.f90 sourcefile~dataplant.f90 DataPlant.f90 sourcefile~dataloopnode.f90->sourcefile~dataplant.f90 sourcefile~dataloopnode.f90->sourcefile~nodeinputmanager.f90 sourcefile~plantutilities.f90 PlantUtilities.f90 sourcefile~dataloopnode.f90->sourcefile~plantutilities.f90 sourcefile~dataloopnode.f90->sourcefile~emsmanager.f90 sourcefile~branchnodeconnections.f90 BranchNodeConnections.f90 sourcefile~dataloopnode.f90->sourcefile~branchnodeconnections.f90 sourcefile~branchinputmanager.f90 BranchInputManager.f90 sourcefile~dataloopnode.f90->sourcefile~branchinputmanager.f90 sourcefile~curvemanager.f90 CurveManager.f90 sourcefile~dataloopnode.f90->sourcefile~curvemanager.f90 sourcefile~outairnodemanager.f90 OutAirNodeManager.f90 sourcefile~dataloopnode.f90->sourcefile~outairnodemanager.f90 sourcefile~fluidproperties.f90 FluidProperties.f90 sourcefile~fluidproperties.f90->sourcefile~plantheatexchanger.f90 sourcefile~fluidproperties.f90->sourcefile~nodeinputmanager.f90 sourcefile~fluidproperties.f90->sourcefile~plantutilities.f90 sourcefile~general.f90 General.f90 sourcefile~general.f90->sourcefile~plantheatexchanger.f90 sourcefile~general.f90->sourcefile~schedulemanager.f90 sourcefile~general.f90->sourcefile~fluidproperties.f90 sourcefile~general.f90->sourcefile~reportsizingmanager.f90 sourcefile~general.f90->sourcefile~dataplant.f90 sourcefile~general.f90->sourcefile~nodeinputmanager.f90 sourcefile~general.f90->sourcefile~plantutilities.f90 sourcefile~general.f90->sourcefile~emsmanager.f90 sourcefile~general.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataenvironment.f90 DataEnvironment.f90 sourcefile~general.f90->sourcefile~dataenvironment.f90 sourcefile~general.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataheatbalance.f90 DataHeatBalance.f90 sourcefile~general.f90->sourcefile~dataheatbalance.f90 sourcefile~general.f90->sourcefile~branchinputmanager.f90 sourcefile~general.f90->sourcefile~curvemanager.f90 sourcefile~general.f90->sourcefile~outputprocessor.f90 sourcefile~psychroutines.f90 PsychRoutines.f90 sourcefile~general.f90->sourcefile~psychroutines.f90 sourcefile~runtimelanguageprocessor.f90 RuntimeLanguageProcessor.f90 sourcefile~general.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datahvacglobals.f90 DataHVACGlobals.f90 sourcefile~datahvacglobals.f90->sourcefile~plantheatexchanger.f90 sourcefile~datahvacglobals.f90->sourcefile~general.f90 sourcefile~datahvacglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~datahvacglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~reportsizingmanager.f90->sourcefile~plantheatexchanger.f90 sourcefile~dataplant.f90->sourcefile~plantheatexchanger.f90 sourcefile~dataplant.f90->sourcefile~plantutilities.f90 sourcefile~dataairsystems.f90 DataAirSystems.f90 sourcefile~dataplant.f90->sourcefile~dataairsystems.f90 sourcefile~dataprecisionglobals.f90 DataPrecisionGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantheatexchanger.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataprecisionglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataprecisionglobals.f90->sourcefile~general.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataplant.f90 sourcefile~databranchairloopplant.f90 DataBranchAirLoopPlant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataglobals.f90 DataGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataprecisionglobals.f90->sourcefile~emsmanager.f90 sourcefile~datasizing.f90 DataSizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasizing.f90 sourcefile~datainterfaces.f90 DataInterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datainterfaces.f90 sourcefile~inputprocessor.f90 InputProcessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataipshortcuts.f90 DataIPShortCuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~datasystemvariables.f90 DataSystemVariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datasurfaces.f90 DataSurfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataruntimelanguage.f90 DataRuntimeLanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datavectortypes.f90 DataVectorTypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datavectortypes.f90 sourcefile~databsdfwindow.f90 DataBSDFWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataroomair.f90 DataRoomAir.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~datacomplexfenestration.f90 DataComplexFenestration.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataequivalentlayerwindow.f90 DataEquivalentLayerWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataerrortracking.f90 DataErrorTracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataerrortracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputprocessor.f90 sourcefile~datacontaminantbalance.f90 DataContaminantBalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataprecisionglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~datazonecontrols.f90 DataZoneControls.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~dataairloop.f90 DataAirLoop.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairloop.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantheatexchanger.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantutilities.f90 sourcefile~databranchairloopplant.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~curvemanager.f90 sourcefile~dataglobals.f90->sourcefile~plantheatexchanger.f90 sourcefile~dataglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataglobals.f90->sourcefile~general.f90 sourcefile~dataglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataglobals.f90->sourcefile~dataplant.f90 sourcefile~dataglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataglobals.f90->sourcefile~emsmanager.f90 sourcefile~dataglobals.f90->sourcefile~datasizing.f90 sourcefile~dataglobals.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataglobals.f90->sourcefile~psychroutines.f90 sourcefile~sortandstringutilities.f90 SortAndStringUtilities.f90 sourcefile~dataglobals.f90->sourcefile~sortandstringutilities.f90 sourcefile~dataoutputs.f90 DataOutputs.f90 sourcefile~dataglobals.f90->sourcefile~dataoutputs.f90 sourcefile~dataglobalconstants.f90 DataGlobalConstants.f90 sourcefile~dataglobals.f90->sourcefile~dataglobalconstants.f90 sourcefile~dataglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~dataglobals.f90->sourcefile~dataairloop.f90 sourcefile~databranchnodeconnections.f90 DataBranchNodeConnections.f90 sourcefile~dataglobals.f90->sourcefile~databranchnodeconnections.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantheatexchanger.f90 sourcefile~nodeinputmanager.f90->sourcefile~branchinputmanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~outairnodemanager.f90 sourcefile~plantutilities.f90->sourcefile~plantheatexchanger.f90 sourcefile~emsmanager.f90->sourcefile~plantheatexchanger.f90 sourcefile~datasizing.f90->sourcefile~plantheatexchanger.f90 sourcefile~datasizing.f90->sourcefile~dataplant.f90 sourcefile~datasizing.f90->sourcefile~plantutilities.f90 sourcefile~datasizing.f90->sourcefile~inputprocessor.f90 sourcefile~datasizing.f90->sourcefile~branchinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~plantheatexchanger.f90 sourcefile~datainterfaces.f90->sourcefile~schedulemanager.f90 sourcefile~datainterfaces.f90->sourcefile~fluidproperties.f90 sourcefile~datainterfaces.f90->sourcefile~general.f90 sourcefile~datainterfaces.f90->sourcefile~reportsizingmanager.f90 sourcefile~datainterfaces.f90->sourcefile~dataplant.f90 sourcefile~datainterfaces.f90->sourcefile~nodeinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~plantutilities.f90 sourcefile~datainterfaces.f90->sourcefile~emsmanager.f90 sourcefile~datainterfaces.f90->sourcefile~branchnodeconnections.f90 sourcefile~datainterfaces.f90->sourcefile~inputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~dataenvironment.f90 sourcefile~datainterfaces.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datainterfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datainterfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datainterfaces.f90->sourcefile~branchinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~curvemanager.f90 sourcefile~datainterfaces.f90->sourcefile~outputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~psychroutines.f90 sourcefile~datainterfaces.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~outairnodemanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantheatexchanger.f90 sourcefile~branchnodeconnections.f90->sourcefile~nodeinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~plantheatexchanger.f90 sourcefile~inputprocessor.f90->sourcefile~schedulemanager.f90 sourcefile~inputprocessor.f90->sourcefile~fluidproperties.f90 sourcefile~inputprocessor.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90->sourcefile~dataplant.f90 sourcefile~inputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~inputprocessor.f90->sourcefile~branchnodeconnections.f90 sourcefile~inputprocessor.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~inputprocessor.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~curvemanager.f90 sourcefile~inputprocessor.f90->sourcefile~outputprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~dataglobalconstants.f90 sourcefile~inputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~outairnodemanager.f90 sourcefile~dataenvironment.f90->sourcefile~plantheatexchanger.f90 sourcefile~dataenvironment.f90->sourcefile~schedulemanager.f90 sourcefile~dataenvironment.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataenvironment.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataenvironment.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90->sourcefile~outputprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~psychroutines.f90 sourcefile~dataenvironment.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~outairnodemanager.f90 sourcefile~datastringglobals.f90 DataStringGlobals.f90 sourcefile~datastringglobals.f90->sourcefile~schedulemanager.f90 sourcefile~datastringglobals.f90->sourcefile~general.f90 sourcefile~datastringglobals.f90->sourcefile~inputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datastringglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datastringglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~schedulemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~general.f90 sourcefile~dataipshortcuts.f90->sourcefile~inputprocessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~curvemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~schedulemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~inputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasystemvariables.f90->sourcefile~curvemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datasurfaces.f90->sourcefile~general.f90 sourcefile~datasurfaces.f90->sourcefile~emsmanager.f90 sourcefile~datasurfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasurfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datasurfaces.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataruntimelanguage.f90->sourcefile~general.f90 sourcefile~dataruntimelanguage.f90->sourcefile~emsmanager.f90 sourcefile~dataruntimelanguage.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datavectortypes.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90->sourcefile~databsdfwindow.f90 sourcefile~datavectortypes.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90->sourcefile~datasurfaces.f90 sourcefile~databsdfwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~reportsizingmanager.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~outputprocessor.f90 sourcefile~dataroomair.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataheatbalance.f90->sourcefile~emsmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataheatbalance.f90->sourcefile~outputprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datacomplexfenestration.f90->sourcefile~dataheatbalance.f90 sourcefile~dataequivalentlayerwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~branchinputmanager.f90->sourcefile~dataplant.f90 sourcefile~curvemanager.f90->sourcefile~branchinputmanager.f90 sourcefile~curvemanager.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataerrortracking.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~branchinputmanager.f90 sourcefile~outputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~outputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~outputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datacontaminantbalance.f90->sourcefile~nodeinputmanager.f90 sourcefile~datacontaminantbalance.f90->sourcefile~outairnodemanager.f90 sourcefile~psychroutines.f90->sourcefile~nodeinputmanager.f90 sourcefile~psychroutines.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~psychroutines.f90->sourcefile~outairnodemanager.f90 sourcefile~sortandstringutilities.f90->sourcefile~inputprocessor.f90 sourcefile~sortandstringutilities.f90->sourcefile~outputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~inputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobalconstants.f90->sourcefile~outputprocessor.f90 sourcefile~runtimelanguageprocessor.f90->sourcefile~emsmanager.f90 sourcefile~dataairsystems.f90->sourcefile~emsmanager.f90 sourcefile~outairnodemanager.f90->sourcefile~emsmanager.f90 sourcefile~datazonecontrols.f90->sourcefile~emsmanager.f90 sourcefile~dataairloop.f90->sourcefile~emsmanager.f90 sourcefile~databranchnodeconnections.f90->sourcefile~branchnodeconnections.f90
Help

Files Dependent On This One

sourcefile~~plantheatexchanger.f90~~AfferentGraph sourcefile~plantheatexchanger.f90 PlantHeatExchanger.f90 sourcefile~plantloopequipment.f90 PlantLoopEquipment.f90 sourcefile~plantheatexchanger.f90->sourcefile~plantloopequipment.f90 sourcefile~plantmanager.f90 PlantManager.f90 sourcefile~plantloopequipment.f90->sourcefile~plantmanager.f90 sourcefile~plantloopsolver.f90 PlantLoopSolver.f90 sourcefile~plantloopequipment.f90->sourcefile~plantloopsolver.f90 sourcefile~simulationmanager.f90 SimulationManager.f90 sourcefile~plantmanager.f90->sourcefile~simulationmanager.f90 sourcefile~utilityroutines.f90 UtilityRoutines.f90 sourcefile~plantmanager.f90->sourcefile~utilityroutines.f90 sourcefile~hvacmanager.f90 HVACManager.f90 sourcefile~plantmanager.f90->sourcefile~hvacmanager.f90 sourcefile~plantloopsolver.f90->sourcefile~plantmanager.f90 sourcefile~simulationmanager.f90->sourcefile~utilityroutines.f90 sourcefile~energyplus.f90 EnergyPlus.f90 sourcefile~simulationmanager.f90->sourcefile~energyplus.f90 sourcefile~hvacmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90 HeatBalanceAirManager.f90 sourcefile~hvacmanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancesurfacemanager.f90 HeatBalanceSurfaceManager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancemanager.f90 HeatBalanceManager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~simulationmanager.f90 sourcefile~sizingmanager.f90 SizingManager.f90 sourcefile~heatbalancemanager.f90->sourcefile~sizingmanager.f90 sourcefile~sizingmanager.f90->sourcefile~simulationmanager.f90
Help


Source Code

MODULE PlantHeatExchangerFluidToFluid

          ! Module containing the routines dealing with the HeatExchanger:FluidToFluid

          ! MODULE INFORMATION:
          !       AUTHOR         B. Griffith, derived from legacy code by  Sankaranarayanan K P, and S. Rees
          !       DATE WRITTEN   November 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS MODULE:
          ! Simulate a generic plant heat exchanger with a variety of control options

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! OTHER NOTES:
          ! na

          ! USE STATEMENTS:
USE DataPrecisionGlobals
USE DataInterfaces
USE DataPlant
USE DataLoopNode
USE DataGlobals, ONLY: MaxNameLength
IMPLICIT NONE ! Enforce explicit typing of all variables

PRIVATE ! Everything private unless explicitly made public

          ! MODULE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER :: CrossFlowBothUnMixed    = 1
  INTEGER, PARAMETER :: CrossFlowBothMixed      = 2
  INTEGER, PARAMETER :: CrossFlowSupplyLoopMixedDemandLoopUnMixed = 3
  INTEGER, PARAMETER :: CrossFlowSupplyLoopUnMixedDemandLoopMixed = 4
  INTEGER, PARAMETER :: CounterFlow   = 5
  INTEGER, PARAMETER :: ParallelFlow  = 6
  INTEGER, PARAMETER :: Ideal         = 7

  INTEGER, PARAMETER :: UncontrolledOn                            = 1001
  INTEGER, PARAMETER :: OperationSchemeModulated                  = 1002
  INTEGER, PARAMETER :: OperationSchemeOnOff                      = 1003
  INTEGER, PARAMETER :: HeatingSetpointModulated                  = 1004
  INTEGER, PARAMETER :: HeatingSetpointOnOff                      = 1005
  INTEGER, PARAMETER :: CoolingSetpointModulated                  = 1006
  INTEGER, PARAMETER :: CoolingSetpointOnOff                      = 1007
  INTEGER, PARAMETER :: DualDeadbandSetpointModulated             = 1008
  INTEGER, PARAMETER :: DualDeadbandSetpointOnOff                 = 1009
  INTEGER, PARAMETER :: CoolingDifferentialOnOff                  = 1010
  INTEGER, PARAMETER :: CoolingSetpointOnOffWithComponentOverride = 1011
  INTEGER, PARAMETER :: TrackComponentOnOff                       = 1012

  INTEGER, PARAMETER :: WetBulbTemperature                        = 10
  INTEGER, PARAMETER :: DryBulbTemperature                        = 11
  INTEGER, PARAMETER :: LoopTemperature                           = 12

  INTEGER, PARAMETER :: HeatingSupplySideLoop   = 501
  INTEGER, PARAMETER :: CoolingSupplySideLoop   = 502

          ! DERIVED TYPE DEFINITIONS:
  TYPE PlantConnectionStruct
    INTEGER        :: LoopNum              = 0  ! plant loop connection index
    INTEGER        :: LoopSideNum          = 0  ! plant loop side connection index
    INTEGER        :: BranchNum            = 0  ! plant loop branch connection index
    INTEGER        :: CompNum              = 0  ! plant loop component connection index
    INTEGER        :: InletNodeNum         = 0  ! plant loop inlet node index
    INTEGER        :: OutletNodeNum        = 0  ! plant loop outlet node index
    REAL(r64)      :: MassFlowRateMin      = 0.d0 ! minimum (hardware) flow rate for component [kg/s]
    REAL(r64)      :: MassFlowRateMax      = 0.d0 ! maximum (hardware) flow rate for component [kg/s]
    REAL(r64)      :: DesignVolumeFlowRate = 0.d0 ! design flow rate [m3/s]
    REAL(r64)      :: MyLoad  =0.d0   ! current load request of supply equip for op scheme control[W]
    REAL(r64)      :: MinLoad = 0.d0  ! reports back size for load dispatch routines [W]
    REAL(r64)      :: MaxLoad = 0.d0  ! reports back size for load dispatch [W]
    REAL(r64)      :: OptLoad = 0.d0  ! reports back size for load dispatch [W]
    REAL(r64)      :: InletTemp = 0.d0 ! current inlet fluid temperature [C]
    REAL(r64)      :: InletMassFlowRate = 0.d0 ! current inlet mass flow rate [kg/s]
    REAL(r64)      :: OutletTemp = 0.d0 ! componenent outlet temperature [C]
  END TYPE PlantConnectionStruct

  TYPE PlantLocatorStruct
    INTEGER        :: LoopNum              = 0  ! plant loop connection index
    INTEGER        :: LoopSideNum          = 0  ! plant loop side connection index
    INTEGER        :: BranchNum            = 0  ! plant loop branch connection index
    INTEGER        :: CompNum              = 0  ! plant loop component connection index
    INTEGER        :: InletNodeNum         = 0  ! plant loop inlet node index
  END TYPE PlantLocatorStruct

  TYPE HeatExchangerStruct
    CHARACTER(len=MaxNameLength) :: Name                  = ' '
    INTEGER                      :: AvailSchedNum         = 0
    INTEGER                      :: HeatExchangeModelType = 0
    REAL(r64)                    :: UA                    = 0.d0
    INTEGER                      :: ControlMode           = 0
    INTEGER                      :: SetpointNodeNum       = 0
    REAL(r64)                    :: TempControlTol        = 0.d0
    INTEGER                      :: ControlSignalTemp     = 0
    REAL(r64)                    :: MinOperationTemp      = -99999.d0
    REAL(r64)                    :: MaxOperationTemp      =  99999.d0
    TYPE(PlantConnectionStruct)  :: DemandSideLoop        ! plant connections and data for the side of HX connected to demand side
    TYPE(PlantConnectionStruct)  :: SupplySideLoop
    CHARACTER(len=MaxNameLength) :: HeatTransferMeteringEndUse = ' '
    CHARACTER(len=MaxNameLength) :: ComponentUserName     = ' ' ! user name for control-associated  component
    CHARACTER(len=MaxNameLength) :: ComponentClassName    = ' ' ! object class name for control-associated component
    INTEGER                      :: ComponentTypeOfNum    = 0
    TYPE(PlantLocatorStruct)     :: OtherCompSupplySideLoop
    TYPE(PlantLocatorStruct)     :: OtherCompDemandSideLoop
    REAL(r64)                    :: SizingFactor          = 1.d0
    REAL(r64)                    :: HeatTransferRate      = 0.d0
    REAL(r64)                    :: HeatTransferEnergy    = 0.d0
    REAL(r64)                    :: Effectiveness         = 0.d0
    REAL(r64)                    :: OperationStatus       = 0.d0
    INTEGER                      :: DmdSideModulatSolvNoConvergeErrorCount = 0
    INTEGER                      :: DmdSideModulatSolvNoConvergeErrorIndex = 0
    INTEGER                      :: DmdSideModulatSolvFailErrorCount = 0
    INTEGER                      :: DmdSideModulatSolvFailErrorIndex = 0
  END TYPE HeatExchangerStruct

          ! MODULE VARIABLE DECLARATIONS:
  CHARACTER(Len=26) :: ComponentClassName = 'HeatExchanger:FluidToFluid'
  INTEGER  :: NumberOfPlantFluidHXs = 0
  TYPE(HeatExchangerStruct), DIMENSION(:), ALLOCATABLE :: FluidHX
  LOGICAL  :: GetInput = .TRUE.
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckFluidHXs

          ! SUBROUTINE SPECIFICATIONS FOR MODULE
  PUBLIC SimFluidHeatExchanger
  PRIVATE GetFluidHeatExchangerInput

  PRIVATE InitFluidHeatExchanger
  PRIVATE SizeFluidHeatExchanger
  PRIVATE ControlFluidHeatExchanger
  PRIVATE FindHXDemandSideLoopFlow
  PRIVATE HXDemandSideLoopFlowResidual
  PRIVATE CalcFluidHeatExchanger
  PRIVATE UpdateFluidHeatExchanger
  PRIVATE ReportFluidHeatExchanger

CONTAINS

SUBROUTINE SimFluidHeatExchanger(LoopNum, LoopSideNum, EquipType,EquipName, &
                                 CompIndex,InitLoopEquip,MyLoad,MaxCap,MinCap,OptCap)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   November 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Main entry point and simulation manager for heat exchanger

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor, ONLY: FindItemInList
  USE General,        ONLY: TrimSigDigits

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN)          :: LoopNum  ! plant loop sim call originated from
  INTEGER, INTENT(IN)          :: LoopSideNum  ! plant loop side sim call originated from
  CHARACTER(len=*), INTENT(IN) :: EquipType  ! type of equipment, 'PlantComponent:UserDefined'
  CHARACTER(len=*), INTENT(IN) :: EquipName  ! user name for component
  INTEGER, INTENT(INOUT)       :: CompIndex
  LOGICAL, INTENT(INOUT)       :: InitLoopEquip
  REAL(r64), INTENT(IN)        :: MyLoad
  REAL(r64), INTENT(OUT)       :: MinCap
  REAL(r64), INTENT(OUT)       :: MaxCap
  REAL(r64), INTENT(OUT)       :: OptCap

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER       :: CompNum

  IF (GetInput) THEN
    CALL GetFluidHeatExchangerInput
    GetInput=.FALSE.
  END IF

  ! Find the correct Equipment
  IF (CompIndex == 0) THEN
    CompNum = FindItemInList(EquipName, FluidHX%Name, NumberOfPlantFluidHXs)
    IF (CompNum == 0) THEN
      CALL ShowFatalError('SimFluidHeatExchanger: HeatExchanger:FluidToFluid not found')
    ENDIF
    CompIndex = CompNum
  ELSE
    CompNum = CompIndex
    IF (CompNum < 1 .OR. CompNum > NumberOfPlantFluidHXs) THEN
      CALL ShowFatalError('SimFluidHeatExchanger: Invalid CompIndex passed='//  &
                           TRIM(TrimSigDigits(CompNum))// &
                           ', Number of heat exchangers ='//TRIM(TrimSigDigits(NumberOfPlantFluidHXs))// &
                           ', Entered heat exchanger name = '//TRIM(EquipName) )
    ENDIF
    IF(CheckFluidHXs(CompNum)) THEN
      IF (EquipName /= FluidHX(CompNum)%Name) THEN
        CALL ShowFatalError('SimFluidHeatExchanger: Invalid CompIndex passed='//  &
                           TRIM(TrimSigDigits(CompNum))// &
                           ', heat exchanger name='//TRIM(EquipName)//', stored name for that index='// &
                           TRIM(FluidHX(CompNum)%Name) )
      ENDIF
      CheckFluidHXs(CompNum) = .FALSE.
    ENDIF
  ENDIF

  IF (InitLoopEquip) THEN
    CALL InitFluidHeatExchanger(CompNum, LoopNum)
    CALL SizeFluidHeatExchanger(CompNum)
    IF (LoopNum == FluidHX(CompNum)%DemandSideLoop%LoopNum) THEN
      MinCap = 0.d0
      MaxCap = FluidHX(CompNum)%DemandSideLoop%MaxLoad
      OptCap = FluidHX(CompNum)%DemandSideLoop%MaxLoad * 0.9d0
    ELSEIF(LoopNum == FluidHX(CompNum)%SupplySideLoop%LoopNum) THEN
      MinCap = 0.d0
      MaxCap = FluidHX(CompNum)%SupplySideLoop%MaxLoad
      OptCap = FluidHX(CompNum)%SupplySideLoop%MaxLoad * 0.9d0
    ENDIF
  ENDIF

  CALL InitFluidHeatExchanger(CompNum, LoopNum)

  ! for op scheme led HXs, only call controls if called from Loop Supply Side
  IF ((FluidHX(CompNum)%ControlMode == OperationSchemeModulated) .OR. &
      (FluidHX(CompNum)%ControlMode == OperationSchemeOnOff ) ) THEN
    IF (LoopNum == FluidHX(CompNum)%SupplySideLoop%LoopNum) THEN
      CALL ControlFluidHeatExchanger(CompNum, LoopNum, MyLoad)
    ENDIF
  ELSE
    CALL ControlFluidHeatExchanger(CompNum, LoopNum, MyLoad)
  ENDIF

  CALL CalcFluidHeatExchanger(CompNum, &
                              Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%MassFlowRate, &
                              Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%MassFlowRate)

  CALL UpdateFluidHeatExchanger(CompNum)

  CALL ReportFluidHeatExchanger(CompNum)

  RETURN

END SUBROUTINE SimFluidHeatExchanger

SUBROUTINE GetFluidHeatExchangerInput

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   November 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! get input for heat exchanger model

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor,        ONLY: GetNumObjectsFound, GetObjectDefMaxArgs, GetObjectItem, &
                                   FindItemInList, VerifyName, SameString, FindItem
  USE General,               ONLY: RoundSigDigits
  USE NodeInputManager,      ONLY: GetOnlySingleNode
  USE BranchNodeConnections, ONLY: TestCompSet
  USE DataGlobals,           ONLY: ScheduleAlwaysOn, AnyEnergyManagementSystemInModel
  USE ScheduleManager,       ONLY: GetScheduleIndex
  USE EMSManager ,           ONLY: CheckIfNodeSetpointManagedByEMS, iTemperatureSetpoint, &
                                   iTemperatureMinSetpoint, iTemperatureMaxSetpoint

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
  CHARACTER(len=*), PARAMETER :: RoutineName='GetFluidHeatExchangerInput: '

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  LOGICAL    :: ErrorsFound = .FALSE.
  INTEGER    :: NumAlphas ! Number of elements in the alpha array
  INTEGER    :: NumNums   ! Number of elements in the numeric array
  INTEGER    :: IOStat    ! IO Status when calling get input subroutine
  LOGICAL    :: IsNotOK   ! Flag to verify name
  LOGICAL    :: IsBlank   ! Flag for blank name
  INTEGER    :: MaxNumAlphas = 0 !argument for call to GetObjectDefMaxArgs
  INTEGER    :: MaxNumNumbers = 0 !argument for call to GetObjectDefMaxArgs
  INTEGER    :: TotalArgs = 0 !argument for call to GetObjectDefMaxArgs
  CHARACTER(len=MaxNameLength+40),ALLOCATABLE, DIMENSION(:) :: cAlphaFieldNames
  CHARACTER(len=MaxNameLength+40),ALLOCATABLE, DIMENSION(:) :: cNumericFieldNames
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: lNumericFieldBlanks
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: lAlphaFieldBlanks
  CHARACTER(len=MaxNameLength),ALLOCATABLE, DIMENSION(:) :: cAlphaArgs
  REAL(r64),ALLOCATABLE, DIMENSION(:) :: rNumericArgs
  CHARACTER(len=MaxNameLength) :: cCurrentModuleObject
  INTEGER  :: CompLoop
  LOGICAL :: NodeEMSSetpointMissing

  cCurrentModuleObject = 'HeatExchanger:FluidToFluid'

  NumberOfPlantFluidHXs = GetNumObjectsFound(cCurrentModuleObject)
  IF (NumberOfPlantFluidHXs == 0) RETURN

  CALL GetObjectDefMaxArgs(cCurrentModuleObject,TotalArgs,NumAlphas,NumNums)
  MaxNumNumbers=NumNums
  MaxNumAlphas=NumAlphas

  ALLOCATE(cAlphaFieldNames(MaxNumAlphas))
  cAlphaFieldNames=' '
  ALLOCATE(cAlphaArgs(MaxNumAlphas))
  cAlphaArgs=' '
  ALLOCATE(lAlphaFieldBlanks(MaxNumAlphas))
  lAlphaFieldBlanks=.false.
  ALLOCATE(cNumericFieldNames(MaxNumNumbers))
  cNumericFieldNames=' '
  ALLOCATE(rNumericArgs(MaxNumNumbers))
  rNumericArgs=0.0d0
  ALLOCATE(lNumericFieldBlanks(MaxNumNumbers))
  lNumericFieldBlanks=.false.



  IF (NumberOfPlantFluidHXs > 0) THEN
    ALLOCATE(FluidHX(NumberOfPlantFluidHXs))
    ALLOCATE(CheckFluidHXs(NumberOfPlantFluidHXs))
    CheckFluidHXs = .TRUE.
    DO CompLoop =1, NumberOfPlantFluidHXs
      CALL GetObjectItem(cCurrentModuleObject, CompLoop, cAlphaArgs, NumAlphas, rNumericArgs, &
             NumNums, IOSTAT, AlphaBlank=lAlphaFieldBlanks, NumBlank=lNumericFieldBlanks, &
             AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      IsNotOK = .FALSE.
      IsBlank = .FALSE.
      CALL VerifyName(cAlphaArgs(1), FluidHX%Name, CompLoop - 1, IsNotOK, IsBlank, TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound = .TRUE.
        IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
      END IF
      FluidHX(CompLoop)%Name =  cAlphaArgs(1)

      IF (lAlphaFieldBlanks(2)) THEN
        FluidHX(CompLoop)%AvailSchedNum = ScheduleAlwaysOn
      ELSE
        FluidHX(CompLoop)%AvailSchedNum = GetScheduleIndex(cAlphaArgs(2))
        IF (FluidHX(CompLoop)%AvailSchedNum <= 0) THEN
          CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
          CALL ShowContinueError('Invalid '//TRIM(cAlphaFieldNames(2))//' = '//TRIM(cAlphaArgs(2)) )
          CALL ShowContinueError('Schedule was not found ')
          ErrorsFound = .TRUE.
        ENDIF
      ENDIF

      FluidHX(CompLoop)%DemandSideLoop%InletNodeNum = &
        GetOnlySingleNode(cAlphaArgs(3),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Inlet, 1, ObjectIsNotParent)
      FluidHX(CompLoop)%DemandSideLoop%OutletNodeNum = &
               GetOnlySingleNode(cAlphaArgs(4),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Outlet, 1, ObjectIsNotParent)
      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(3),cAlphaArgs(4),  &
             'Loop Demand Side Plant Nodes')
      FluidHX(CompLoop)%DemandSideLoop%DesignVolumeFlowRate = rNumericArgs(1)

      FluidHX(CompLoop)%SupplySideLoop%InletNodeNum = &
        GetOnlySingleNode(cAlphaArgs(5),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Inlet, 2, ObjectIsNotParent)
      FluidHX(CompLoop)%SupplySideLoop%OutletNodeNum = &
               GetOnlySingleNode(cAlphaArgs(6),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Outlet, 2, ObjectIsNotParent)
      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(5),cAlphaArgs(6),  &
             'Loop Supply Side Plant Nodes')
      FluidHX(CompLoop)%SupplySideLoop%DesignVolumeFlowRate = rNumericArgs(2)

      IF (SameString(cAlphaArgs(7), 'CrossFlowBothUnMixed')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = CrossFlowBothUnMixed
      ELSEIF (SameString(cAlphaArgs(7), 'CrossFlowBothMixed')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = CrossFlowBothMixed
      ELSEIF (SameString(cAlphaArgs(7), 'CrossFlowSupplyMixedDemandUnMixed')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = CrossFlowSupplyLoopMixedDemandLoopUnMixed
      ELSEIF (SameString(cAlphaArgs(7), 'CrossFlowSupplyUnMixedDemandMixed')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = CrossFlowSupplyLoopUnMixedDemandLoopMixed
      ELSEIF (SameString(cAlphaArgs(7), 'CounterFlow')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = CounterFlow
      ELSEIF (SameString(cAlphaArgs(7), 'ParallelFlow')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = ParallelFlow
      ELSEIF (SameString(cAlphaArgs(7),'Ideal')) THEN
        FluidHX(CompLoop)%HeatExchangeModelType = Ideal
      ELSE
        CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
        CALL ShowContinueError('Invalid '//TRIM(cAlphaFieldNames(7))//' = '//TRIM(cAlphaArgs(7)) )
        ErrorsFound = .TRUE.
      ENDIF

      IF (.NOT. lNumericFieldBlanks(3)) THEN
        FluidHX(CompLoop)%UA = rNumericArgs(3)
      ELSE
        IF (FluidHX(CompLoop)%HeatExchangeModelType /= Ideal) THEN
          CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
          CALL ShowContinueError('Missing entry for '//TRIM(cNumericFieldNames(3)) )
          ErrorsFound = .TRUE.
        ENDIF
      ENDIF

      IF (    SameString(cAlphaArgs(8) , 'UncontrolledOn')) THEN
        FluidHX(CompLoop)%ControlMode = UncontrolledOn
      ELSEIF (SameString(cAlphaArgs(8) , 'OperationSchemeModulated')) THEN
        FluidHX(CompLoop)%ControlMode = OperationSchemeModulated
      ELSEIF (SameString(cAlphaArgs(8) , 'OperationSchemeOnOff')) THEN
        FluidHX(CompLoop)%ControlMode = OperationSchemeOnOff
      ELSEIF (SameString(cAlphaArgs(8) , 'HeatingSetpointModulated')) THEN
        FluidHX(CompLoop)%ControlMode = HeatingSetpointModulated
      ELSEIF (SameString(cAlphaArgs(8) , 'HeatingSetpointOnOff')) THEN
        FluidHX(CompLoop)%ControlMode = HeatingSetpointOnOff
      ELSEIF (SameString(cAlphaArgs(8) , 'CoolingSetpointModulated')) THEN
        FluidHX(CompLoop)%ControlMode = CoolingSetpointModulated
      ELSEIF (SameString(cAlphaArgs(8) , 'CoolingSetpointOnOff')) THEN
        FluidHX(CompLoop)%ControlMode = CoolingSetpointOnOff
      ELSEIF (SameString(cAlphaArgs(8) , 'DualDeadbandSetpointModulated')) THEN
        FluidHX(CompLoop)%ControlMode = DualDeadbandSetpointModulated
      ELSEIF (SameString(cAlphaArgs(8) , 'DualDeadbandSetpointOnOff')) THEN
        FluidHX(CompLoop)%ControlMode = DualDeadbandSetpointOnOff
      ELSEIF (SameString(cAlphaArgs(8) , 'CoolingDifferentialOnOff')) THEN
        FluidHX(CompLoop)%ControlMode = CoolingDifferentialOnOff
      ELSEIF (SameString(cAlphaArgs(8) , 'CoolingSetpointOnOffWithComponentOverride')) THEN
        FluidHX(CompLoop)%ControlMode = CoolingSetpointOnOffWithComponentOverride
      ELSEIF (SameString(cAlphaArgs(8) , 'TrackComponentOnOff')) THEN
        FluidHX(CompLoop)%ControlMode = TrackComponentOnOff
      ELSE
        CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
        CALL ShowContinueError('Invalid '//TRIM(cAlphaFieldNames(8))//' = '//TRIM(cAlphaArgs(8)) )
        ErrorsFound = .TRUE.
      ENDIF

      IF (.NOT. lAlphaFieldBlanks(9)) THEN
        FluidHX(CompLoop)%SetpointNodeNum = &
               GetOnlySingleNode(cAlphaArgs(9),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Sensor, 1, ObjectIsNotParent)
        ! check that node actually has setpoints on it
        IF (    (FluidHX(CompLoop)%ControlMode == HeatingSetpointModulated) &
           .OR. (FluidHX(CompLoop)%ControlMode == HeatingSetpointOnOff)     &
           .OR. (FluidHX(CompLoop)%ControlMode == CoolingSetpointModulated) &
           .OR. (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOff)     &
           .OR. (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOffWithComponentOverride) ) THEN
          IF (Node(FluidHX(CompLoop)%SetpointNodeNum)%TempSetPoint == SensedNodeFlagValue) THEN
            IF (.NOT. AnyEnergyManagementSystemInModel) THEN
              CALL ShowSevereError(RoutineName//' Missing temperature setpoint for node = '//TRIM(cAlphaArgs(9)) )
              CALL ShowContinueError('Occurs for '//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1)) )
              CALL ShowContinueError(' Use a setpoint manager to place a single temperature setpoint on the node')
              ErrorsFound=.true.
            ELSE
                ! need call to EMS to check node
              NodeEMSSetpointMissing = .FALSE.
              CALL CheckIfNodeSetpointManagedByEMS(FluidHX(CompLoop)%SetpointNodeNum,  &
                                   iTemperatureSetpoint, NodeEMSSetpointMissing)
              IF (NodeEMSSetpointMissing) THEN
                CALL ShowSevereError(RoutineName//' Missing temperature setpoint for node = '//TRIM(cAlphaArgs(9)) )
                CALL ShowContinueError('Occurs for '//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1)) )
                CALL ShowContinueError( &
                     'Use a setpoint manager or EMS actuator to place a single temperature setpoint on the node')
                ErrorsFound=.true.
              ENDIF
            ENDIF
          ENDIF
        ELSEIF ((FluidHX(CompLoop)%ControlMode == DualDeadbandSetpointModulated) &
             .OR. (FluidHX(CompLoop)%ControlMode == DualDeadbandSetpointOnOff)) THEN
          IF ((Node(FluidHX(CompLoop)%SetpointNodeNum)%TempSetPointHi == SensedNodeFlagValue) &
              .OR. (Node(FluidHX(CompLoop)%SetpointNodeNum)%TempSetPointLo == SensedNodeFlagValue) ) THEN
            IF (.NOT. AnyEnergyManagementSystemInModel) THEN
              CALL ShowSevereError(RoutineName//' Missing dual temperature setpoints for node = '//TRIM(cAlphaArgs(9)) )
              CALL ShowContinueError('Occurs for '//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1)) )
              CALL ShowContinueError(' Use a setpoint manager to place a dual temperature setpoint on the node')
              ErrorsFound=.true.
            ELSE
                ! need call to EMS to check node
              NodeEMSSetpointMissing = .FALSE.
              CALL CheckIfNodeSetpointManagedByEMS(FluidHX(CompLoop)%SetpointNodeNum,  &
                                   iTemperatureMinSetpoint, NodeEMSSetpointMissing)
              CALL CheckIfNodeSetpointManagedByEMS(FluidHX(CompLoop)%SetpointNodeNum,  &
                                   iTemperatureMaxSetpoint, NodeEMSSetpointMissing)
              IF (NodeEMSSetpointMissing) THEN
                CALL ShowSevereError(RoutineName//' Missing temperature setpoint for node = '//TRIM(cAlphaArgs(9)) )
                CALL ShowContinueError('Occurs for '//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1)) )
                CALL ShowContinueError( &
                     'Use a setpoint manager or EMS actuators to place a dual temperature setpoints on the node')
                ErrorsFound=.true.
              ENDIF
            ENDIF
          ENDIF
        ENDIF


      ELSE
        ! need to name a setpoint node if using a setpoint type control mode
        IF (    (FluidHX(CompLoop)%ControlMode == HeatingSetpointModulated) &
           .OR. (FluidHX(CompLoop)%ControlMode == HeatingSetpointOnOff)     &
           .OR. (FluidHX(CompLoop)%ControlMode == CoolingSetpointModulated) &
           .OR. (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOff)     &
           .OR. (FluidHX(CompLoop)%ControlMode == DualDeadbandSetpointModulated) &
           .OR. (FluidHX(CompLoop)%ControlMode == DualDeadbandSetpointOnOff) &
           .OR. (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOffWithComponentOverride) ) THEN
          CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
          CALL ShowContinueError('Missing entry for '//TRIM(cAlphaFieldNames(9)) )
          ErrorsFound = .TRUE.
        ENDIF
      ENDIF

      IF (.NOT. lNumericFieldBlanks(4)) THEN
        FluidHX(CompLoop)%TempControlTol = rNumericArgs(4)
      ELSE
        FluidHX(CompLoop)%TempControlTol = 0.01d0
      ENDIF

      FluidHX(CompLoop)%HeatTransferMeteringEndUse = cAlphaArgs(10)

      IF (.NOT. lAlphaFieldBlanks(11)) THEN
        FluidHX(CompLoop)%OtherCompSupplySideLoop%InletNodeNum = &
             GetOnlySingleNode(cAlphaArgs(11),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Actuator, 1, ObjectIsNotParent)
      ELSE
        IF (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOffWithComponentOverride) THEN
          CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
          CALL ShowContinueError('Missing entry for '//TRIM(cAlphaFieldNames(11)) )
          ErrorsFound = .TRUE.
        ENDIF
      ENDIF

      IF (.NOT. lAlphaFieldBlanks(12)) THEN
        FluidHX(CompLoop)%OtherCompDemandSideLoop%InletNodeNum = &
             GetOnlySingleNode(cAlphaArgs(12),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),NodeType_Water, &
               NodeConnectionType_Actuator, 1, ObjectIsNotParent)
      ELSE
        IF (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOffWithComponentOverride) THEN
          CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
          CALL ShowContinueError('Missing entry for '//TRIM(cAlphaFieldNames(12)) )
          ErrorsFound = .TRUE.
        ENDIF
      ENDIF

      IF (.NOT. lAlphaFieldBlanks(13)) THEN
        IF (     SameString(cAlphaArgs(13) , 'WetBulbTemperature')) THEN
          FluidHX(CompLoop)%ControlSignalTemp = WetBulbTemperature
        ELSEIF ( SameString(cAlphaArgs(13) , 'DryBulbTemperature')) THEN
          FluidHX(CompLoop)%ControlSignalTemp = DryBulbTemperature
        ELSEIF ( SameString(cAlphaArgs(13) , 'Loop')) THEN
          FluidHX(CompLoop)%ControlSignalTemp = LoopTemperature
        ENDIF
      ELSE
        IF (FluidHX(CompLoop)%ControlMode == CoolingSetpointOnOffWithComponentOverride) THEN
          CALL ShowSevereError(RoutineName//TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//'", invalid entry.')
          CALL ShowContinueError('Missing entry for '//TRIM(cAlphaFieldNames(13)) )
          ErrorsFound = .TRUE.
        ENDIF

      ENDIF

      IF (.NOT. lNumericFieldBlanks(5)) THEN
        FluidHX(CompLoop)%SizingFactor = rNumericArgs(5)
      ELSE
        FluidHX(CompLoop)%SizingFactor = 1.d0
      ENDIF

      IF (.NOT. lNumericFieldBlanks(6)) THEN
        FluidHX(CompLoop)%MinOperationTemp = rNumericArgs(6)
      ELSE
        FluidHX(CompLoop)%MinOperationTemp = -9999.d0
      ENDIF

      IF (.NOT. lNumericFieldBlanks(7)) THEN
        FluidHX(CompLoop)%MaxOperationTemp = rNumericArgs(7)
      ELSE
        FluidHX(CompLoop)%MaxOperationTemp =  9999.d0
      ENDIF

    ENDDO
  ENDIF



  IF (ErrorsFound) THEN
    CALL ShowFatalError(RoutineName//'Errors found in processing '//TRIM(cCurrentModuleObject)//' input.')
  ENDIF

  DO CompLoop =1, NumberOfPlantFluidHXs

    CALL SetupOutputVariable('Fluid Heat Exchanger Heat Transfer Rate [W]', &
                            FluidHX(CompLoop)%HeatTransferRate, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )

    CALL SetupOutputVariable('Fluid Heat Exchanger Heat Transfer Energy [J]', &
                            FluidHX(CompLoop)%HeatTransferEnergy, 'System', 'Sum', &
                            FluidHX(CompLoop)%Name, &
                            ResourceTypeKey='ENERGYTRANSFER',EndUseKey=TRIM(FluidHX(CompLoop)%HeatTransferMeteringEndUse) &
                            ,GroupKey='Plant')

    CALL SetupOutputVariable('Fluid Heat Exchanger Loop Supply Side Mass Flow Rate [kg/s]', &
                            FluidHX(CompLoop)%SupplySideLoop%InletMassFlowRate, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Loop Supply Side Inlet Temperature [C]', &
                            FluidHX(CompLoop)%SupplySideLoop%InletTemp, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Loop Supply Side Outlet Temperature [C]', &
                            FluidHX(CompLoop)%SupplySideLoop%OutletTemp, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Loop Demand Side Mass Flow Rate [kg/s]', &
                            FluidHX(CompLoop)%DemandSideLoop%InletMassFlowRate, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Loop Demand Side Inlet Temperature [C]', &
                            FluidHX(CompLoop)%DemandSideLoop%InletTemp, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Loop Demand Side Outlet Temperature [C]', &
                            FluidHX(CompLoop)%DemandSideLoop%OutletTemp, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Operation Status [ ]', &
                            FluidHX(CompLoop)%OperationStatus, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
    CALL SetupOutputVariable('Fluid Heat Exchanger Effectiveness [ ]', &
                            FluidHX(CompLoop)%Effectiveness, 'System', 'Average', &
                            FluidHX(CompLoop)%Name )
  ENDDO

  RETURN

END SUBROUTINE GetFluidHeatExchangerInput

SUBROUTINE InitFluidHeatExchanger(CompNum, LoopNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   november, 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Initialize heat exchanger model

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE PlantUtilities,     ONLY: InitComponentNodes, InterConnectTwoPlantLoopSides
  USE FluidProperties,    ONLY: GetDensityGlycol, GetSpecificHeatGlycol
  USE DataGlobals,        ONLY: BeginEnvrnFlag, InitConvTemp

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: CompNum
  INTEGER, INTENT(IN) :: LoopNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  LOGICAL, SAVE                            :: MyOneTimeFlag = .TRUE. ! one time flag
  LOGICAL, ALLOCATABLE, SAVE, DIMENSION(:) :: MyEnvrnFlag            ! environment flag
  LOGICAL, ALLOCATABLE, SAVE, DIMENSION(:) :: MyFlag
  LOGICAL  :: errFlag
  CHARACTER(len=MaxNameLength):: RoutineName = 'InitFluidHeatExchanger: '
  REAL(r64)  :: rho
  INTEGER    :: LoopNum2
  INTEGER    :: LoopSideNum
  INTEGER    :: BranchNum
  INTEGER    :: LoopCompNum

  IF (MyOneTimeFlag) THEN
    ALLOCATE(MyFlag(NumberOfPlantFluidHXs))
    ALLOCATE(MyEnvrnFlag(NumberOfPlantFluidHXs))
    MyFlag = .TRUE.
    MyEnvrnFlag = .TRUE.
    MyOneTimeFlag = .FALSE.
  END IF

  IF (MyFlag(CompNum)) THEN
    ! locate the main two connections to the plant loops
    errFlag = .FALSE.
    CALL ScanPlantLoopsForObject(FluidHX(CompNum)%Name,           &
                                 TypeOf_FluidToFluidPlantHtExchg, &
                                 FluidHX(CompNum)%DemandSideLoop%LoopNum, &
                                 FluidHX(CompNum)%DemandSideLoop%LoopSideNum, &
                                 FluidHX(CompNum)%DemandSideLoop%BranchNum, &
                                 FluidHX(CompNum)%DemandSideLoop%CompNum, &
                                 InletNodeNumber = FluidHX(CompNum)%DemandSideLoop%InletNodeNum, &
                                 errFlag=errFlag )

    IF (FluidHX(CompNum)%DemandSideLoop%LoopSideNum /= DemandSide) THEN ! throw error
      CALL ShowSevereError(TRIM(RoutineName)//' Invalid connections for '//  &
                            TRIM(ccSimPlantEquipTypes(TypeOf_FluidToFluidPlantHtExchg)) &
                            //' name = "'//TRIM(FluidHX(CompNum)%Name)//'"')
      CALL ShowContinueError('The "Loop Demand Side" connections are not on the Demand Side of a plant loop')
      errFlag = .TRUE.
    ENDIF

    CALL ScanPlantLoopsForObject(FluidHX(CompNum)%Name,           &
                                 TypeOf_FluidToFluidPlantHtExchg, &
                                 FluidHX(CompNum)%SupplySideLoop%LoopNum, &
                                 FluidHX(CompNum)%SupplySideLoop%LoopSideNum, &
                                 FluidHX(CompNum)%SupplySideLoop%BranchNum, &
                                 FluidHX(CompNum)%SupplySideLoop%CompNum, &
                                 InletNodeNumber = FluidHX(CompNum)%SupplySideLoop%InletNodeNum, &
                                 errFlag=errFlag )

    IF (FluidHX(CompNum)%SupplySideLoop%LoopSideNum /= SupplySide) THEN ! throw error
      CALL ShowSevereError(TRIM(RoutineName)//' Invalid connections for '//  &
         TRIM(ccSimPlantEquipTypes(TypeOf_FluidToFluidPlantHtExchg)) &
                            //' name = "'//TRIM(FluidHX(CompNum)%Name)//'"')
      CALL ShowContinueError('The "Loop Supply Side" connections are not on the Supply Side of a plant loop')
      errFlag = .TRUE.
    ENDIF

    ! make sure it is not the same loop on both sides.
    IF (FluidHX(CompNum)%SupplySideLoop%LoopNum == FluidHX(CompNum)%DemandSideLoop%LoopNum) THEN ! user is being too tricky, don't allow
      CALL ShowSevereError(TRIM(RoutineName)//' Invalid connections for '//  &
         TRIM(ccSimPlantEquipTypes(TypeOf_FluidToFluidPlantHtExchg)) &
                            //' name = "'//TRIM(FluidHX(CompNum)%Name)//'"')
      CALL ShowContinueError('The "Loop Supply Side" and "Loop Demand Side" need to be on different loops.')
      errFlag = .TRUE.
    ELSE

      CALL InterConnectTwoPlantLoopSides(FluidHX(CompNum)%SupplySideLoop%LoopNum, &
                                       FluidHX(CompNum)%SupplySideLoop%LoopSideNum, &
                                       FluidHX(CompNum)%DemandSideLoop%LoopNum, &
                                       FluidHX(CompNum)%DemandSideLoop%LoopSideNum, &
                                       TypeOf_FluidToFluidPlantHtExchg, &
                                       .TRUE. )
    ENDIF

    !find remote component if control mode is of that type.
    IF  (FluidHX(CompNum)%ControlMode == CoolingSetpointOnOffWithComponentOverride)  THEN

      CALL ScanPlantLoopsForNodeNum( RoutineName, &
                                     FluidHX(CompNum)%OtherCompSupplySideLoop%InletNodeNum, &
                                     FluidHX(CompNum)%OtherCompSupplySideLoop%LoopNum, &
                                     FluidHX(CompNum)%OtherCompSupplySideLoop%LoopSideNum, &
                                     FluidHX(CompNum)%OtherCompSupplySideLoop%BranchNum, &
                                     CompNum = FluidHX(CompNum)%OtherCompSupplySideLoop%CompNum)

      CALL ScanPlantLoopsForNodeNum( RoutineName, &
                                     FluidHX(CompNum)%OtherCompDemandSideLoop%InletNodeNum, &
                                     FluidHX(CompNum)%OtherCompDemandSideLoop%LoopNum, &
                                     FluidHX(CompNum)%OtherCompDemandSideLoop%LoopSideNum, &
                                     FluidHX(CompNum)%OtherCompDemandSideLoop%BranchNum, &
                                     CompNum = FluidHX(CompNum)%OtherCompDemandSideLoop%CompNum)

      ! revise how loads served category for other controlled equipment
      LoopNum2     = FluidHX(CompNum)%OtherCompSupplySideLoop%LoopNum
      LoopSideNum = FluidHX(CompNum)%OtherCompSupplySideLoop%LoopSideNum
      BranchNum   = FluidHX(CompNum)%OtherCompSupplySideLoop%BranchNum
      LoopCompNum = FluidHX(CompNum)%OtherCompSupplySideLoop%CompNum

      SELECT CASE (PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%HowLoadServed)

      CASE (HowMet_ByNominalCap)
        PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%HowLoadServed &
                = HowMet_ByNominalCapFreeCoolCntrl
      CASE (HowMet_ByNominalCapLowOutLimit)
        PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%HowLoadServed &
                = HowMet_ByNominalCapLowOutLimitFreeCoolCntrl
      END SELECT

      SELECT CASE(FluidHX(CompNum)%ControlSignalTemp)
      CASE(WetBulbTemperature)
        PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%FreeCoolCntrlMode &
                = FreeCoolControlMode_WetBulb
      CASE(DryBulbTemperature)
        PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%FreeCoolCntrlMode &
                = FreeCoolControlMode_DryBulb
      CASE(LoopTemperature)
        PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%FreeCoolCntrlMode &
                = FreeCoolControlMode_Loop
        PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%FreeCoolCntrlNodeNum &
                = FluidHX(CompNum)%OtherCompDemandSideLoop%InletNodeNum
      END SELECT

    ENDIF
    IF  (FluidHX(CompNum)%ControlMode == TrackComponentOnOff) THEN
      IF (FluidHX(CompNum)%OtherCompSupplySideLoop%InletNodeNum > 0) THEN
        CALL ScanPlantLoopsForObject( FluidHX(CompNum)%ComponentUserName,                   &
                                      FluidHX(CompNum)%ComponentTypeOfNum,                  &
                                      FluidHX(CompNum)%OtherCompSupplySideLoop%LoopNum,     &
                                      FluidHX(CompNum)%OtherCompSupplySideLoop%LoopSideNum, &
                                      FluidHX(CompNum)%OtherCompSupplySideLoop%BranchNum,   &
                                      FluidHX(CompNum)%OtherCompSupplySideLoop%CompNum,     &
                                      InletNodeNumber = FluidHX(CompNum)%OtherCompSupplySideLoop%InletNodeNum, &
                                      errFlag=errFlag )
      ENDIF
      IF (FluidHX(CompNum)%OtherCompDemandSideLoop%InletNodeNum > 0) THEN
        CALL ScanPlantLoopsForObject( FluidHX(CompNum)%ComponentUserName,                   &
                                      FluidHX(CompNum)%ComponentTypeOfNum,                  &
                                      FluidHX(CompNum)%OtherCompDemandSideLoop%LoopNum,     &
                                      FluidHX(CompNum)%OtherCompDemandSideLoop%LoopSideNum, &
                                      FluidHX(CompNum)%OtherCompDemandSideLoop%BranchNum,   &
                                      FluidHX(CompNum)%OtherCompDemandSideLoop%CompNum,     &
                                      InletNodeNumber = FluidHX(CompNum)%OtherCompDemandSideLoop%InletNodeNum, &
                                      errFlag=errFlag )
      ENDIF
    ENDIF

    IF (errFlag) THEN
      CALL ShowFatalError(TRIM(RoutineName)//'Program terminated due to previous condition(s).')
    ENDIF
    MyFlag(CompNum) = .FALSE.
  ENDIF ! plant setup

  IF (BeginEnvrnFlag .AND. MyEnvrnFlag(CompNum) .AND. (PlantSizesOkayToFinalize)) THEN
    IF (PlantSizeNotComplete)  CALL SizeFluidHeatExchanger(CompNum)
    rho = GetDensityGlycol(PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%FluidName, &
                           InitConvTemp, &
                           PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%FluidIndex, &
                           'InitFluidHeatExchanger')
    FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax = rho *  &
                        FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate
    CALL InitComponentNodes(FluidHX(CompNum)%DemandSideLoop%MassFlowRateMin,  &
                            FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax,  &
                            FluidHX(CompNum)%DemandSideLoop%InletNodeNum,     &
                            FluidHX(CompNum)%DemandSideLoop%OutletNodeNum,    &
                            FluidHX(CompNum)%DemandSideLoop%LoopNum,          &
                            FluidHX(CompNum)%DemandSideLoop%LoopSideNum,      &
                            FluidHX(CompNum)%DemandSideLoop%BranchNum,        &
                            FluidHX(CompNum)%DemandSideLoop%CompNum)

    rho = GetDensityGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                           InitConvTemp, &
                           PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex, &
                           'InitFluidHeatExchanger')
    FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax = rho *  &
                        FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate
    CALL InitComponentNodes(FluidHX(CompNum)%SupplySideLoop%MassFlowRateMin,  &
                            FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax,  &
                            FluidHX(CompNum)%SupplySideLoop%InletNodeNum,     &
                            FluidHX(CompNum)%SupplySideLoop%OutletNodeNum,    &
                            FluidHX(CompNum)%SupplySideLoop%LoopNum,          &
                            FluidHX(CompNum)%SupplySideLoop%LoopSideNum,      &
                            FluidHX(CompNum)%SupplySideLoop%BranchNum,        &
                            FluidHX(CompNum)%SupplySideLoop%CompNum)
    MyEnvrnFlag(CompNum) = .FALSE.
  ENDIF
  IF (.not. BeginEnvrnFlag) THEN
    MyEnvrnFlag(CompNum) = .TRUE.
  ENDIF

  FluidHX(CompNum)%DemandSideLoop%InletTemp = Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp
  FluidHX(CompNum)%SupplySideLoop%InletTemp = Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp

  IF  (FluidHX(CompNum)%ControlMode == CoolingSetpointOnOffWithComponentOverride)  THEN
    ! store current value for setpoint in central plant loop data structure
    LoopNum2     = FluidHX(CompNum)%OtherCompSupplySideLoop%LoopNum
    LoopSideNum = FluidHX(CompNum)%OtherCompSupplySideLoop%LoopSideNum
    BranchNum   = FluidHX(CompNum)%OtherCompSupplySideLoop%BranchNum
    LoopCompNum = FluidHX(CompNum)%OtherCompSupplySideLoop%CompNum

    PlantLoop(LoopNum2)%LoopSide(LoopSideNum)%Branch(BranchNum)%Comp(LoopCompNum)%FreeCoolCntrlMinCntrlTemp &
                = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPoint
  ENDIF

  RETURN

END SUBROUTINE InitFluidHeatExchanger

SUBROUTINE SizeFluidHeatExchanger(CompNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   December 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Size plant heat exchanger flow rates, UA, and max capacity

          ! METHODOLOGY EMPLOYED:
          ! the supply side flow rate is obtained from the plant sizing structure
          ! the demand side is sized to match the supply side
          ! the UA is sized for an effectiveness of 1.0 using sizing temps
          ! the capacity uses the full HX model

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataSizing
  USE DataHVACGlobals,        ONLY: SmallWaterVolFlow
  USE DataGlobals,            ONLY: InitConvTemp
  USE FluidProperties,        ONLY: GetDensityGlycol, GetSpecificHeatGlycol
  USE OutputReportPredefined, ONLY: pdchMechType, pdchMechNomCap, PreDefTableEntry
  USE PlantUtilities,         ONLY: RegisterPlantCompDesignFlow
  USE ReportSizingManager,    ONLY: ReportSizingOutput

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: CompNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER    :: PltSizNumSupSide     ! Plant Sizing index for Loop Supply Side
  INTEGER    :: PltSizNumDmdSide     ! plant sizing index for Loop Demand Side
  REAL(r64)  :: tmpSupSideDesignVolFlowRate
  REAL(r64)  :: tmpDmdSideDesignVolFlowRate
  REAL(r64)  :: tmpUA
  REAL(r64)  :: tmpDeltaTSupLoop
  REAL(r64)  :: tmpDeltaTloopToLoop
  LOGICAL    :: ErrorsFound
  REAL(r64)  :: Cp
  REAL(r64)  :: rho
  REAL(r64)  :: tmpDesCap
  REAL(r64)  :: SupSideMdot
  REAL(r64)  :: DmdSideMdot

  ! first deal with Loop Supply Side
  ErrorsFound = .FALSE.
  PltSizNumSupSide = PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%PlantSizNum
  PltSizNumDmdSide = PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%PlantSizNum
  tmpSupSideDesignVolFlowRate = FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate
  IF (FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate == AutoSize) THEN
    IF (PltSizNumSupSide > 0) THEN
      IF (PlantSizData(PltSizNumSupSide)%DesVolFlowRate >= SmallWaterVolFlow) THEN
        tmpSupSideDesignVolFlowRate  = PlantSizData(PltSizNumSupSide)%DesVolFlowRate * FluidHX(CompNum)%SizingFactor
        IF (PlantSizesOkayToFinalize) FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate = tmpSupSideDesignVolFlowRate
      ELSE
        tmpSupSideDesignVolFlowRate = 0.d0
        IF (PlantSizesOkayToFinalize) FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate = tmpSupSideDesignVolFlowRate
      ENDIF
      IF (PlantSizesOkayToFinalize) CALL ReportSizingOutput('HeatExchanger:FluidToFluid', FluidHX(CompNum)%Name, &
                                           'Loop Supply Side Design Fluid Flow Rate [m3/s]', &
                                           FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate )
    ELSE
      CALL ShowSevereError('SizeFluidHeatExchanger: Autosizing of requires a loop Sizing:Plant object')
      CALL ShowContinueError('Occurs in heat exchanger object='//TRIM(FluidHX(CompNum)%Name))
      ErrorsFound = .TRUE.
    END IF
  ENDIF
  CALL RegisterPlantCompDesignFlow(FluidHX(CompNum)%SupplySideLoop%InletNodeNum, tmpSupSideDesignVolFlowRate)

  ! second deal with Loop Demand Side
  tmpDmdSideDesignVolFlowRate = FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate
  IF (FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate == AutoSize) THEN
    IF (tmpSupSideDesignVolFlowRate > SmallWaterVolFlow) THEN
      tmpDmdSideDesignVolFlowRate = tmpSupSideDesignVolFlowRate
      IF (PlantSizesOkayToFinalize) FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate = tmpDmdSideDesignVolFlowRate
    ELSE
      tmpDmdSideDesignVolFlowRate = 0.d0
      IF (PlantSizesOkayToFinalize) FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate = tmpDmdSideDesignVolFlowRate
    ENDIF
    IF (PlantSizesOkayToFinalize) CALL ReportSizingOutput('HeatExchanger:FluidToFluid', FluidHX(CompNum)%Name, &
                                           'Loop Demand Side Design Fluid Flow Rate [m3/s]', &
                                           FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate )
  ENDIF
  CALL RegisterPlantCompDesignFlow(FluidHX(CompNum)%DemandSideLoop%InletNodeNum, tmpDmdSideDesignVolFlowRate)

  ! size UA if needed
  tmpUA = FluidHX(CompNum)%UA
  IF (FluidHX(CompNum)%UA == AutoSize) THEN
    ! get nominal delta T between two loops
    IF (PltSizNumSupSide > 0 .AND. PltSizNumDmdSide > 0) THEN

      SELECT CASE (PlantSizData(PltSizNumSupSide)%LoopType)

      CASE (HeatingLoop)
        tmpDeltaTloopToLoop = ABS( (PlantSizData(PltSizNumSupSide)%ExitTemp - PlantSizData(PltSizNumSupSide)%DeltaT ) &
                                          - PlantSizData(PltSizNumDmdSide)%ExitTemp )
      CASE (CoolingLoop)
        tmpDeltaTloopToLoop = ABS( (PlantSizData(PltSizNumSupSide)%ExitTemp + PlantSizData(PltSizNumSupSide)%DeltaT ) &
                                          - PlantSizData(PltSizNumDmdSide)%ExitTemp )
      CASE (CondenserLoop)
        tmpDeltaTloopToLoop = ABS( (PlantSizData(PltSizNumSupSide)%ExitTemp + PlantSizData(PltSizNumSupSide)%DeltaT ) &
                                          - PlantSizData(PltSizNumDmdSide)%ExitTemp )
      CASE (SteamLoop)
        tmpDeltaTloopToLoop = ABS( (PlantSizData(PltSizNumSupSide)%ExitTemp - PlantSizData(PltSizNumSupSide)%DeltaT ) &
                                          - PlantSizData(PltSizNumDmdSide)%ExitTemp )
      END SELECT

      tmpDeltaTloopToLoop = MAX(2.d0, tmpDeltaTloopToLoop)
      tmpDeltaTSupLoop    = PlantSizData(PltSizNumSupSide)%DeltaT
      IF (tmpSupSideDesignVolFlowRate >= SmallWaterVolFlow) THEN

        Cp = GetSpecificHeatGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                                   InitConvTemp, &
                                   PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex, &
                                   'SizeFluidHeatExchanger' )

        rho = GetDensityGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                                   InitConvTemp, &
                                   PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex, &
                                   'SizeFluidHeatExchanger' )

        tmpDesCap = Cp * rho * tmpDeltaTSupLoop * tmpSupSideDesignVolFlowRate
        tmpUA = tmpDesCap/tmpDeltaTloopToLoop
        IF (PlantSizesOkayToFinalize) FluidHX(CompNum)%UA = tmpUA
      ELSE
        tmpUA = 0.d0
        IF (PlantSizesOkayToFinalize) FluidHX(CompNum)%UA = tmpUA
      END IF
      IF (PlantSizesOkayToFinalize) THEN
        CALL ReportSizingOutput('HeatExchanger:FluidToFluid', FluidHX(CompNum)%Name, &
                              'Heat Exchanger U-Factor Times Area Value [W/C]', FluidHX(CompNum)%UA)
        CALL ReportSizingOutput('HeatExchanger:FluidToFluid', FluidHX(CompNum)%Name, &
                              'Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]' &
                              ,tmpDeltaTloopToLoop)
      ENDIF
    ELSE
      CALL ShowSevereError('SizeFluidHeatExchanger: Autosizing of heat '//  &
         'Exchanger UA requires a loop Sizing:Plant objects for both loops')
      CALL ShowContinueError('Occurs in heat exchanger object='//TRIM(FluidHX(CompNum)%Name))
      ErrorsFound = .TRUE.
    END IF

  ENDIF

  ! size capacities for load range based op schemes
  IF (PlantSizesOkayToFinalize  ) THEN

    IF (PltSizNumSupSide > 0 ) THEN
      SELECT CASE (PlantSizData(PltSizNumSupSide)%LoopType)
      CASE (HeatingLoop)
        Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp = &
                          (PlantSizData(PltSizNumSupSide)%ExitTemp - PlantSizData(PltSizNumSupSide)%DeltaT )
      CASE (CoolingLoop)
        Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp = &
                         (PlantSizData(PltSizNumSupSide)%ExitTemp + PlantSizData(PltSizNumSupSide)%DeltaT )
      CASE (CondenserLoop)
        Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp = &
                         (PlantSizData(PltSizNumSupSide)%ExitTemp + PlantSizData(PltSizNumSupSide)%DeltaT )
      CASE (SteamLoop)
        Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp = &
                         (PlantSizData(PltSizNumSupSide)%ExitTemp - PlantSizData(PltSizNumSupSide)%DeltaT )
      END SELECT

    ELSE ! don't rely on sizing, use loop setpoints
      ! loop supply side
      IF (PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%LoopDemandCalcScheme == SingleSetPoint ) THEN
        Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp = &
                      Node(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%TempSetPointNodeNum)%TempSetPoint
      ELSEIF (PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%LoopDemandCalcScheme == DualSetPointDeadBand) THEN
        Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp = &
              (Node(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%TempSetPointNodeNum)%TempSetPointHi + &
               Node(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%TempSetPointNodeNum)%TempSetPointLo) / 2.d0
      ENDIF

    ENDIF

    IF (PltSizNumDmdSide > 0) THEN
      Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp = PlantSizData(PltSizNumDmdSide)%ExitTemp
    ELSE ! don't rely on sizing, use loop setpoints
      ! loop demand side
      IF (PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%LoopDemandCalcScheme == SingleSetPoint ) THEN
        Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp = &
                      Node(PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%TempSetPointNodeNum)%TempSetPoint
      ELSEIF (PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%LoopDemandCalcScheme == DualSetPointDeadBand) THEN
        Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp = &
              (Node(PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%TempSetPointNodeNum)%TempSetPointHi + &
               Node(PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%TempSetPointNodeNum)%TempSetPointLo) / 2.d0
      ENDIF
    ENDIF

    rho = GetDensityGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                           InitConvTemp, &
                           PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex, &
                           'SizeFluidHeatExchanger')
    SupSideMdot = FluidHX(CompNum)%SupplySideLoop%DesignVolumeFlowRate * rho
    rho = GetDensityGlycol(PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%FluidName, &
                           InitConvTemp, &
                           PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%FluidIndex, &
                           'SizeFluidHeatExchanger')
    DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%DesignVolumeFlowRate * rho

    CALL CalcFluidHeatExchanger(CompNum, SupSideMdot, DmdSideMdot)
    FluidHX(CompNum)%SupplySideLoop%MaxLoad = ABS( FluidHX(CompNum)%HeatTransferRate )

  ENDIF
  IF (PlantSizesOkayToFinalize) THEN
    CALL PreDefTableEntry(pdchMechType,FluidHX(CompNum)%Name,'HeatExchanger:FluidToFluid')
    CALL PreDefTableEntry(pdchMechNomCap,FluidHX(CompNum)%Name,FluidHX(CompNum)%SupplySideLoop%MaxLoad)
  ENDIF

  RETURN

END SUBROUTINE SizeFluidHeatExchanger

SUBROUTINE ControlFluidHeatExchanger(CompNum, LoopNum, MyLoad)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   November 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! determine control state for fluid to fluid heat exchanger
          ! make fluid flow requests accordingly

          ! METHODOLOGY EMPLOYED:
          ! long CASE statement for different control options

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataBranchAirLoopPlant, ONLY: MassFlowTolerance
  USE ScheduleManager,        ONLY: GetCurrentScheduleValue
  USE DataHVACGlobals,        ONLY: SmallLoad
  USE FluidProperties,        ONLY: GetSpecificHeatGlycol
  USE PlantUtilities,         ONLY: SetComponentFlowRate
  USE DataEnvironment,        ONLY: OutDryBulbTemp, OutWetBulbTemp
  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,   INTENT(IN) :: CompNum
  INTEGER,   INTENT(IN) :: LoopNum
  REAL(r64), INTENT(IN) :: MyLoad

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)  :: AvailSchedValue
  LOGICAL    :: ScheduledOff
  LOGICAL    :: LimitTrippedOff
  REAL(r64)  :: mdotSupSide
  REAL(r64)  :: mdotDmdSide
  REAL(r64)  :: DeltaTCooling
  REAL(r64)  :: DeltaTHeating
  REAL(r64)  :: DeltaTCoolSetpointDemand
  REAL(r64)  :: DeltaTCoolSetpointSupply
  REAL(r64)  :: DeltaTHeatSetpointDemand
  REAL(r64)  :: DeltaTHeatSetpointSupply
  REAL(r64)  :: cp ! specific heat of fluid
  REAL(r64)  :: TargetLeavingTemp ! target temperature deg. C
  REAL(r64)  :: SetpointTemp  ! temperature setpoint for single setpoint
  REAL(r64)  :: SetpointTempLo ! low setpoint for dual deadband temperature setpoints
  REAL(r64)  :: SetpointTempHi ! High setpoint for dual deadband temperature setpoints
  REAL(r64)  :: ControlSignalValue
  LOGICAL    :: ChillerShutDown

  ! check if available by schedule
  AvailSchedValue = GetCurrentScheduleValue(FluidHX(CompNum)%AvailSchedNum)
  IF (AvailSchedValue <= 0) THEN
    ScheduledOff = .TRUE.
  ELSE
    ScheduledOff = .FALSE.
  ENDIF

  ! check if operational limits trip off unit
  LimitTrippedOff = .FALSE.
  IF ((Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp < FluidHX(CompNum)%MinOperationTemp) &
       .OR.  ( Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp <  FluidHX(CompNum)%MinOperationTemp)) THEN
    LimitTrippedOff = .TRUE.
  ENDIF
  IF ((Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp > FluidHX(CompNum)%MaxOperationTemp) &
       .OR.  ( Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp >  FluidHX(CompNum)%MaxOperationTemp)) THEN
    LimitTrippedOff = .TRUE.
  ENDIF

  IF (.NOT. ScheduledOff .AND. .NOT. LimitTrippedOff) THEN

    SELECT CASE (FluidHX(CompNum)%ControlMode)

    CASE (UncontrolledOn)

    ! make passive request for supply side loop flow
      mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
      CALL SetComponentFlowRate(mdotSupSide,                           &
                        FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                        FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                        FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                        FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                        FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                        FluidHX(CompNum)%SupplySideLoop%CompNum)
      IF (mdotSupSide > MassFlowTolerance) THEN
          ! if supply side loop has massflow, request demand side flow
        mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
      ELSE
        mdotDmdSide = 0.d0
      ENDIF
      CALL SetComponentFlowRate(mdotDmdSide,                           &
                        FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                        FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                        FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                        FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                        FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                        FluidHX(CompNum)%DemandSideLoop%CompNum)

    CASE (OperationSchemeModulated)

      IF (ABS(MyLoad) > SmallLoad) THEN
        IF (MyLoad < -1.d0*SmallLoad) THEN ! requesting cooling
          DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
          IF ( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) THEN ! can do cooling so turn on
            mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
            CALL SetComponentFlowRate(mdotSupSide,                      &
                         FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                         FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                         FluidHX(CompNum)%SupplySideLoop%CompNum)
            IF (mdotSupSide > MassFlowTolerance) THEN
              ! if supply side loop has massflow, request demand side flow
              cp = GetSpecificHeatGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                                     FluidHX(CompNum)%SupplySideLoop%InletTemp,                        &
                                     PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex,    &
                                     'ControlFluidHeatExchanger' )
              TargetLeavingTemp = FluidHX(CompNum)%SupplySideLoop%InletTemp - ABS(MyLoad)/(cp * mdotSupSide)

              CALL FindHXDemandSideLoopFlow(CompNum, TargetLeavingTemp, CoolingSupplySideLoop)
            ELSE ! no flow on supply side so do not request flow on demand side
              mdotDmdSide = 0.d0
              CALL SetComponentFlowRate(mdotDmdSide,                          &
                               FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                               FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                               FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                               FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                               FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                               FluidHX(CompNum)%SupplySideLoop%CompNum)
            ENDIF
          ELSE ! not able to cool so turn off
            mdotSupSide = 0.d0
            CALL SetComponentFlowRate(mdotSupSide,                          &
                             FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                             FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                             FluidHX(CompNum)%SupplySideLoop%CompNum)
            mdotDmdSide = 0.d0
            CALL SetComponentFlowRate(mdotDmdSide,                          &
                             FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                             FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                             FluidHX(CompNum)%SupplySideLoop%CompNum)
          ENDIF

        ELSE ! requesting heating
          DeltaTHeating = FluidHX(CompNum)%DemandSideLoop%InletTemp - FluidHX(CompNum)%SupplySideLoop%InletTemp
          IF ( DeltaTHeating > FluidHX(CompNum)%TempControlTol ) THEN ! can do heating so turn on
            mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
            CALL SetComponentFlowRate(mdotSupSide,                      &
                         FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                         FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                         FluidHX(CompNum)%SupplySideLoop%CompNum)
            IF (mdotSupSide > MassFlowTolerance) THEN
              cp = GetSpecificHeatGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                                     FluidHX(CompNum)%SupplySideLoop%InletTemp, &
                                     PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex, &
                                     'ControlFluidHeatExchanger' )
              TargetLeavingTemp = FluidHX(CompNum)%SupplySideLoop%InletTemp + ABS(MyLoad)/(cp * mdotSupSide)

              CALL FindHXDemandSideLoopFlow(CompNum, TargetLeavingTemp, HeatingSupplySideLoop)
            ELSE ! no flow on supply side so do not request flow on demand side
              mdotDmdSide = 0.d0
              CALL SetComponentFlowRate(mdotDmdSide,                          &
                               FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                               FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                               FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                               FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                               FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                               FluidHX(CompNum)%DemandSideLoop%CompNum)
            ENDIF
          ELSE ! not able to heat so turn off
            mdotSupSide = 0.d0
            CALL SetComponentFlowRate(mdotSupSide,                          &
                             FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                             FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                             FluidHX(CompNum)%SupplySideLoop%CompNum)
            mdotDmdSide = 0.d0
            CALL SetComponentFlowRate(mdotDmdSide,                          &
                             FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                             FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                             FluidHX(CompNum)%DemandSideLoop%CompNum)
          ENDIF
        ENDIF

      ELSE !  no load
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                          &
                         FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                         FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                         FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                          &
                         FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                         FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                         FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (OperationSchemeOnOff)
      IF (ABS(MyLoad) > SmallLoad)  THEN
        IF (MyLoad < SmallLoad) THEN ! requesting cooling
          DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
          IF ( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) THEN ! can do cooling so turn on
            mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
            CALL SetComponentFlowRate(mdotSupSide,                      &
                         FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                         FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                         FluidHX(CompNum)%SupplySideLoop%CompNum)
            IF (mdotSupSide > MassFlowTolerance) THEN
              mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
            ELSE
              mdotDmdSide = 0.d0
            ENDIF

            CALL SetComponentFlowRate(mdotDmdSide,                      &
                         FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                         FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                         FluidHX(CompNum)%DemandSideLoop%CompNum)
          ELSE ! not able to cool so turn off
            mdotSupSide = 0.d0
            CALL SetComponentFlowRate(mdotSupSide,                          &
                             FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                             FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                             FluidHX(CompNum)%SupplySideLoop%CompNum)
            mdotDmdSide = 0.d0
            CALL SetComponentFlowRate(mdotDmdSide,                          &
                             FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                             FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                             FluidHX(CompNum)%DemandSideLoop%CompNum)
          ENDIF

        ELSE ! requesting heating
          DeltaTHeating = FluidHX(CompNum)%DemandSideLoop%InletTemp - FluidHX(CompNum)%SupplySideLoop%InletTemp
          IF ( DeltaTHeating > FluidHX(CompNum)%TempControlTol ) THEN ! can do heating so turn on
            mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
            CALL SetComponentFlowRate(mdotSupSide,                      &
                         FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                         FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                         FluidHX(CompNum)%SupplySideLoop%CompNum)
            IF (mdotSupSide > MassFlowTolerance) THEN
              mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
            ELSE
              mdotDmdSide = 0.d0
            ENDIF
            CALL SetComponentFlowRate(mdotDmdSide,                      &
                         FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                         FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                         FluidHX(CompNum)%DemandSideLoop%CompNum)
          ELSE ! not able to heat so turn off
            mdotSupSide = 0.d0
            CALL SetComponentFlowRate(mdotSupSide,                          &
                             FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                             FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                             FluidHX(CompNum)%SupplySideLoop%CompNum)
            mdotDmdSide = 0.d0
            CALL SetComponentFlowRate(mdotDmdSide,                          &
                             FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                             FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                             FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                             FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                             FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                             FluidHX(CompNum)%DemandSideLoop%CompNum)
          ENDIF
        ENDIF

      ELSE ! no load
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                          &
                         FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                         FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                         FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                          &
                         FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                         FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                         FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                         FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                         FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                         FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (HeatingSetpointModulated)

      SetpointTemp = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPoint
      DeltaTHeating = FluidHX(CompNum)%DemandSideLoop%InletTemp - FluidHX(CompNum)%SupplySideLoop%InletTemp
      IF (( DeltaTHeating > FluidHX(CompNum)%TempControlTol ) .AND. &
          (SetpointTemp > FluidHX(CompNum)%SupplySideLoop%InletTemp)) THEN
        ! can and want to heat
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN

          TargetLeavingTemp = SetpointTemp
          CALL FindHXDemandSideLoopFlow(CompNum, TargetLeavingTemp, HeatingSupplySideLoop)
        ELSE
          mdotDmdSide = 0.d0
          CALL SetComponentFlowRate(mdotDmdSide,                           &
                            FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                            FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                            FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                            FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                            FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                            FluidHX(CompNum)%DemandSideLoop%CompNum)
        ENDIF
      ELSE ! not able are wanting to heat so turn off
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (HeatingSetpointOnOff)

      SetpointTemp = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPoint
      DeltaTHeating = FluidHX(CompNum)%DemandSideLoop%InletTemp - FluidHX(CompNum)%SupplySideLoop%InletTemp
      IF (( DeltaTHeating > FluidHX(CompNum)%TempControlTol ) .AND. &
          (SetpointTemp > FluidHX(CompNum)%SupplySideLoop%InletTemp)) THEN
        ! can and want to heat
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
        ELSE
          mdotDmdSide = 0.d0
        ENDIF
        CALL SetComponentFlowRate(mdotDmdSide,                       &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)
      ELSE ! not able are wanting to heat so turn off
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (CoolingSetpointModulated)

      SetpointTemp = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPoint
      DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
      IF (( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) .AND. &
          (SetpointTemp < FluidHX(CompNum)%SupplySideLoop%InletTemp)) THEN
        ! can and want to cool
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          TargetLeavingTemp = SetpointTemp
          CALL FindHXDemandSideLoopFlow(CompNum, TargetLeavingTemp, CoolingSupplySideLoop)
        ELSE
          mdotDmdSide = 0.d0
          CALL SetComponentFlowRate(mdotDmdSide,                           &
                            FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                            FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                            FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                            FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                            FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                            FluidHX(CompNum)%DemandSideLoop%CompNum)
        ENDIF
      ELSE ! not able are wanting to cool so turn off
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (CoolingSetpointOnOff)

      SetpointTemp = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPoint
      DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
      IF (( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) .AND. &
          (SetpointTemp < FluidHX(CompNum)%SupplySideLoop%InletTemp)) THEN
        ! can and want to cool
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
        ELSE
          mdotDmdSide = 0.d0
        ENDIF
        CALL SetComponentFlowRate(mdotDmdSide,                       &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)
      ELSE ! not able or are wanting to cool so turn off
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (DualDeadbandSetpointModulated)

      SetpointTempLo = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPointLo
      SetpointTempHi = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPointHi
      DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
      DeltaTCoolSetpointDemand = SetpointTempHi - FluidHX(CompNum)%DemandSideLoop%InletTemp
      DeltaTCoolSetpointSupply = SetpointTempHi - FluidHX(CompNum)%SupplySideLoop%InletTemp
      DeltaTHeating = FluidHX(CompNum)%DemandSideLoop%InletTemp - FluidHX(CompNum)%SupplySideLoop%InletTemp
      DeltaTHeatSetpointDemand = SetpointTempLo - FluidHX(CompNum)%DemandSideLoop%InletTemp
      DeltaTHeatSetpointSupply = SetpointTempLo - FluidHX(CompNum)%SupplySideLoop%InletTemp
      IF (( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) .AND. &
          (DeltaTCoolSetpointSupply < (-1.d0 * FluidHX(CompNum)%TempControlTol)) .AND. &
          (DeltaTCoolSetpointDemand > FluidHX(CompNum)%TempControlTol)  ) THEN
        ! can and want to cool
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          TargetLeavingTemp = SetpointTempHi
          CALL FindHXDemandSideLoopFlow(CompNum, TargetLeavingTemp, CoolingSupplySideLoop)
        ELSE
          mdotDmdSide = 0.d0
          CALL SetComponentFlowRate(mdotDmdSide,                           &
                            FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                            FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                            FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                            FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                            FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                            FluidHX(CompNum)%DemandSideLoop%CompNum)
        ENDIF
      ELSEIF (( DeltaTHeating > FluidHX(CompNum)%TempControlTol ) .AND. &
              (DeltaTHeatSetpointDemand < (-1.d0 * FluidHX(CompNum)%TempControlTol)) .AND. &
              (DeltaTHeatSetpointSupply > FluidHX(CompNum)%TempControlTol) ) THEN
        ! can and want to heat
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          TargetLeavingTemp = SetpointTempLo
          CALL FindHXDemandSideLoopFlow(CompNum, TargetLeavingTemp, HeatingSupplySideLoop)
        ELSE
          mdotDmdSide = 0.d0
          CALL SetComponentFlowRate(mdotDmdSide,                           &
                            FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                            FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                            FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                            FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                            FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                            FluidHX(CompNum)%DemandSideLoop%CompNum)
        ENDIF
      ELSE ! not able or don't want conditioning
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (DualDeadbandSetpointOnOff)

      SetpointTempLo = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPointLo
      SetpointTempHi = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPointHi
      DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
      DeltaTHeating = FluidHX(CompNum)%DemandSideLoop%InletTemp - FluidHX(CompNum)%SupplySideLoop%InletTemp
      IF (( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) .AND. &
          (SetpointTempHi < FluidHX(CompNum)%SupplySideLoop%InletTemp)) THEN
        ! can and want to cool
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
        ELSE
          mdotDmdSide = 0.d0
        ENDIF
        CALL SetComponentFlowRate(mdotDmdSide,                       &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)
      ELSEIF (( DeltaTHeating > FluidHX(CompNum)%TempControlTol ) .AND. &
              (SetpointTempLo > FluidHX(CompNum)%SupplySideLoop%InletTemp)) THEN
        ! can and want to heat
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
        ELSE
          mdotDmdSide = 0.d0
        ENDIF
        CALL SetComponentFlowRate(mdotDmdSide,                       &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)
      ELSE ! not able or don't want conditioning
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (CoolingDifferentialOnOff)

      DeltaTCooling = FluidHX(CompNum)%SupplySideLoop%InletTemp - FluidHX(CompNum)%DemandSideLoop%InletTemp
      IF ( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) THEN
        !  want to cool
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
        ELSE
          mdotDmdSide = 0.d0
        ENDIF
        CALL SetComponentFlowRate(mdotDmdSide,                       &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)
      ELSE ! not wanting to cool so turn off
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    CASE (CoolingSetpointOnOffWithComponentOverride)

      SELECT CASE (FluidHX(CompNum)%ControlSignalTemp)
      CASE (WetBulbTemperature)
        ControlSignalValue = OutWetBulbTemp
      CASE (DryBulbTemperature)
        ControlSignalValue = OutDryBulbTemp
      CASE (LoopTemperature )
        ! ControlSignalValue = FluidHX(CompNum)%DemandSideLoop%InletTemp
        ControlSignalValue = Node(FluidHX(CompNum)%OtherCompDemandSideLoop%InletNodeNum)%TempLastTimestep
      END SELECT

      SetpointTemp = Node(FluidHX(CompNum)%SetpointNodeNum)%TempSetPoint
      DeltaTCooling = SetpointTemp - ControlSignalValue
      !obtain shut down state
      ChillerShutDown = PlantLoop(FluidHX(CompNum)%OtherCompSupplySideLoop%LoopNum)     &
                        %LoopSide(FluidHX(CompNum)%OtherCompSupplySideLoop%LoopSideNum) &
                          %Branch(FluidHX(CompNum)%OtherCompSupplySideLoop%BranchNum)   &
                            %Comp(FluidHX(CompNum)%OtherCompSupplySideLoop%CompNum)%FreeCoolCntrlShutDown
      IF (ChillerShutDown .AND. ( DeltaTCooling > FluidHX(CompNum)%TempControlTol ) ) THEN
        ! can and want to cool
        mdotSupSide = FluidHX(CompNum)%SupplySideLoop%MassFlowRateMax
        CALL SetComponentFlowRate(mdotSupSide,                       &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
        IF (mdotSupSide > MassFlowTolerance) THEN
          mdotDmdSide = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
        ELSE
          mdotDmdSide = 0.d0
        ENDIF
        CALL SetComponentFlowRate(mdotDmdSide,                       &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)

      ELSE
        mdotSupSide = 0.d0
        CALL SetComponentFlowRate(mdotSupSide,                           &
                          FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                          FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                          FluidHX(CompNum)%SupplySideLoop%CompNum)
        mdotDmdSide = 0.d0
        CALL SetComponentFlowRate(mdotDmdSide,                           &
                          FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                          FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                          FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                          FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                          FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                          FluidHX(CompNum)%DemandSideLoop%CompNum)
      ENDIF

    END SELECT

  ELSE ! scheduled off
    mdotSupSide = 0.d0
    CALL SetComponentFlowRate(mdotSupSide,                           &
                      FluidHX(CompNum)%SupplySideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%SupplySideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%SupplySideLoop%LoopNum,       &
                      FluidHX(CompNum)%SupplySideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%SupplySideLoop%BranchNum,     &
                      FluidHX(CompNum)%SupplySideLoop%CompNum)
    mdotDmdSide = 0.d0
    CALL SetComponentFlowRate(mdotDmdSide,                           &
                      FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                      FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                      FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                      FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                      FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                      FluidHX(CompNum)%DemandSideLoop%CompNum)
  ENDIF

  RETURN

END SUBROUTINE ControlFluidHeatExchanger

SUBROUTINE CalcFluidHeatExchanger(CompNum, SupSideMdot, DmdSideMdot)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B.Griffith, derived from CalcEconHeatExchanger by  Sankaranarayanan K P aug. 2007
          !       DATE WRITTEN   November 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Evalutate heat exchanger model and calculate leaving temperatures

          ! METHODOLOGY EMPLOYED:
          ! apply heat transfer model depending on type of HX used

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE FluidProperties, ONLY: GetSpecificHeatGlycol
  USE DataLoopNode,    ONLY: Node

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,   INTENT(IN)  :: CompNum
  REAL(r64), INTENT(IN)  :: SupSideMdot ! mass flow rate of fluid entering from supply side loop
  REAL(r64), INTENT(IN)  :: DmdSideMdot ! mass flow rate of fluid entering from demand side loop
          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER     :: CmaxMixedCminUnmixed = 40
  INTEGER, PARAMETER     :: CmaxUnMixedCminMixed = 41

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)  :: SupSideLoopInletTemp
  REAL(r64)  :: DmdSideLoopInletTemp
  REAL(r64)  :: SupSideLoopInletCp  ! specific heat of fluid entering from supply side loop at inlet temp
  REAL(r64)  :: DmdSideLoopInletCp  ! specific heat of fluid entering from demand side loop at inlet temp
  REAL(r64)  :: SupSideCapRate ! product of specific heat and mass flow for supply side loop at inlet temp
  REAL(r64)  :: DmdSideCapRate ! product of specific heat and mass flow for demand side loop at inlet temp
  REAL(r64)  :: MinCapRate ! minimum capacity flow rate
  REAL(r64)  :: MaxCapRate ! maximum capacity flow rate
  REAL(r64)  :: NTU ! number of transfer units for heat exchanger performance model
  REAL(r64)  :: CapRatio
  REAL(r64)  :: ExpCheckValue1
  REAL(r64)  :: ExpCheckValue2
  REAL(r64)  :: Effectiveness
  REAL(r64)  :: HeatTransferRate
  REAL(r64)  :: MdotDmdSide
  REAL(r64)  :: LeavingTempMinFlow
  REAL(r64)  :: LeavingTempFullFlow
  INTEGER    :: CrossFlowEquation

  SupSideLoopInletTemp = Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%Temp
  DmdSideLoopInletTemp = Node(FluidHX(CompNum)%DemandSideLoop%InletNodeNum)%Temp

  SupSideLoopInletCp = GetSpecificHeatGlycol(PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidName, &
                                SupSideLoopInletTemp ,  &
                                PlantLoop(FluidHX(CompNum)%SupplySideLoop%LoopNum)%FluidIndex, &
                                'CalcFluidHeatExchanger')
  DmdSideLoopInletCp = GetSpecificHeatGlycol(PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%FluidName, &
                                DmdSideLoopInletTemp ,  &
                                PlantLoop(FluidHX(CompNum)%DemandSideLoop%LoopNum)%FluidIndex, &
                                'CalcFluidHeatExchanger')

  SupSideCapRate = SupSideMdot * SupSideLoopInletCp
  DmdSideCapRate = DmdSideMdot * DmdSideLoopInletCp
  MinCapRate = MIN(SupSideCapRate, DmdSideCapRate)
  MaxCapRate = MAX(SupSideCapRate, DmdSideCapRate)

  IF (MinCapRate > 0.d0) THEN

    SELECT CASE (FluidHX(CompNum)%HeatExchangeModelType)

    CASE (CrossFlowBothUnMixed)
      NTU = FluidHX(CompNum)%UA/MinCapRate
      CapRatio = MinCapRate/MaxCapRate
      EXPCheckValue1 = NTU**0.22d0/CapRatio
      EXPCheckValue2 = -CapRatio*NTU**0.78d0
      IF ((EXPCheckValue1 > EXP_UpperLimit) .OR. (EXPCheckValue2 > EXP_UpperLimit)) THEN
        IF (-NTU >= EXP_LowerLimit) THEN
          Effectiveness = 1.d0-EXP(-NTU)
          Effectiveness = MIN(1.d0,Effectiveness)
        ELSE
          Effectiveness = 1.d0
        ENDIF
      ELSE
        Effectiveness = 1.d0 - EXP((NTU**0.22d0/CapRatio) * &
                    (EXP(-CapRatio*NTU**0.78d0) - 1.0d0))
        Effectiveness = MIN(1.d0,Effectiveness)
      ENDIF

    CASE (CrossFlowBothMixed)
      NTU = FluidHX(CompNum)%UA/MinCapRate
      CapRatio = MinCapRate/MaxCapRate
      EXPCheckValue1 =  -CapRatio*NTU
      EXPCheckValue2 =  -NTU
      IF (EXPCheckValue1 <  EXP_LowerLimit) THEN
        IF (EXPCheckValue2 >= EXP_LowerLimit) THEN
          Effectiveness = 1.d0-EXP(-NTU)
          Effectiveness = MIN(1.d0,Effectiveness)
        ELSE
          Effectiveness = 1.d0
        ENDIF

      ELSEIF ( (EXP(-NTU) == 1.d0) .or. (NTU == 0.d0) .OR. (EXP(-CapRatio*NTU) == 1.d0) ) THEN ! don't div by zero

        Effectiveness = 0.d0
      ELSE
        Effectiveness = 1.d0/( (1.d0/(1.d0-EXP(-NTU))) + (CapRatio/(1.d0 - EXP(-CapRatio*NTU) ) ) - ( 1.d0/ NTU) )
        Effectiveness = MIN(1.0d0,Effectiveness)
      ENDIF

    CASE (CrossFlowSupplyLoopMixedDemandLoopUnMixed, CrossFlowSupplyLoopUnMixedDemandLoopMixed)

      IF (SupSideCapRate == MaxCapRate .AND. FluidHX(CompNum)%HeatExchangeModelType &
                         == CrossFlowSupplyLoopMixedDemandLoopUnMixed) THEN
        CrossFlowEquation = CmaxMixedCminUnmixed
      ELSEIF (SupSideCapRate == MinCapRate .AND. FluidHX(CompNum)%HeatExchangeModelType &
                         == CrossFlowSupplyLoopMixedDemandLoopUnMixed) THEN
        CrossFlowEquation = CmaxUnMixedCminMixed
      ELSEIF (DmdSideCapRate == MaxCapRate .AND. FluidHX(CompNum)%HeatExchangeModelType &
                         == CrossFlowSupplyLoopUnMixedDemandLoopMixed) THEN
        CrossFlowEquation = CmaxMixedCminUnmixed
      ELSEIF (DmdSideCapRate == MinCapRate .AND. FluidHX(CompNum)%HeatExchangeModelType &
                         == CrossFlowSupplyLoopUnMixedDemandLoopMixed) THEN
        CrossFlowEquation = CmaxUnMixedCminMixed
      ELSE
        CrossFlowEquation = CmaxMixedCminUnmixed
      ENDIF

      NTU = FluidHX(CompNum)%UA/MinCapRate
      CapRatio = MinCapRate/MaxCapRate
      IF (CrossFlowEquation == CmaxMixedCminUnmixed) THEN
        ExpCheckValue1 = -NTU
        IF (CapRatio == 0.d0) THEN ! protect div by zero
          IF (ExpCheckValue1 >= EXP_LowerLimit) THEN
            Effectiveness = 1.d0-EXP(-NTU)
            Effectiveness = MIN(1.d0,Effectiveness)
          ELSE
            Effectiveness = 1.d0
          ENDIF
        ElSEIF (ExpCheckValue1 < EXP_LowerLimit ) THEN
          Effectiveness = 0.632d0/CapRatio
          Effectiveness = MIN(1.d0,Effectiveness)
        ELSE
          Effectiveness = (1.d0/CapRatio) * (1.d0 - EXP(CapRatio*EXP(-NTU)- 1.d0 ) )
          Effectiveness = MIN(1.d0,Effectiveness)
        ENDIF
      ELSEIF (CrossFlowEquation == CmaxUnMixedCminMixed) THEN
        ExpCheckValue1 = -CapRatio*NTU
        IF (CapRatio == 0.d0) THEN
          IF (-NTU >= EXP_LowerLimit) THEN
            Effectiveness = 1.d0-EXP(-NTU)
            Effectiveness = MIN(1.d0,Effectiveness)
          ELSE
            Effectiveness = 1.d0
          ENDIF
        ELSE
          EXPCheckValue2 = -(1.0d0/CapRatio)*(1.0d0 - EXP(-CapRatio*NTU) )
          IF (EXPCheckValue2 < EXP_LowerLimit) THEN
            Effectiveness = 1.d0
          ELSE
            Effectiveness = 1.0d0 - EXP(-(1.0d0/CapRatio)*(1.0d0 - EXP(-CapRatio*NTU) ) )
            Effectiveness = MIN(1.d0,Effectiveness)
          ENDIF
        ENDIF
      ENDIF

    CASE (CounterFlow)
      NTU = FluidHX(CompNum)%UA/MinCapRate
      CapRatio = MinCapRate/MaxCapRate
      EXPCheckValue1 = -NTU*(1.d0-CapRatio)
      IF (EXPCheckValue1 > EXP_UpperLimit) THEN
        IF (-NTU >= EXP_LowerLimit) THEN
          Effectiveness = 1.d0-EXP(-NTU)
          Effectiveness = MIN(1.d0,Effectiveness)
        ELSE
          Effectiveness = 1.d0
        ENDIF
      ELSEIF (CapRatio*EXP(-NTU*(1.d0-CapRatio)) == 1.0d0) THEN
        IF (-NTU >= EXP_LowerLimit) THEN
          Effectiveness = 1.d0-EXP(-NTU)
          Effectiveness = MIN(1.d0,Effectiveness)
        ELSE
          Effectiveness = 1.d0
        ENDIF
      ELSE
        Effectiveness = (1.d0-EXP(-NTU*(1.d0-CapRatio)))/(1.d0-CapRatio*EXP(-NTU*(1.d0-CapRatio)))
        Effectiveness = MIN(1.0d0,Effectiveness)
      ENDIF

    CASE (ParallelFlow)
      NTU = FluidHX(CompNum)%UA/MinCapRate
      CapRatio = MinCapRate/MaxCapRate
      EXPCheckValue1 = -NTU*(1.d0+CapRatio)
      IF (EXPCheckValue1 > EXP_UpperLimit) THEN
        IF (-NTU >= EXP_LowerLimit) THEN
          Effectiveness = 1.d0-EXP(-NTU)
          Effectiveness = MIN(1.d0,Effectiveness)
        ELSE
          Effectiveness = 1.d0
        ENDIF
      ELSE
        Effectiveness = (1.d0-EXP(-NTU*(1.d0+CapRatio)))/(1.d0+CapRatio)
        Effectiveness = MIN(1.d0,Effectiveness)
      ENDIF

    CASE (Ideal)
      Effectiveness = 1.d0
    END SELECT

  ELSE ! no capacity
    Effectiveness = 0.d0

  ENDIF

  HeatTransferRate = Effectiveness * MinCapRate * ( SupSideLoopInletTemp - DmdSideLoopInletTemp) ! + means supply side is cooled

  IF (SupSideMdot > 0.d0 ) THEN
    FluidHX(CompNum)%SupplySideLoop%OutletTemp = SupSideLoopInletTemp - HeatTransferRate/ (SupSideLoopInletCp * SupSideMdot)
  ELSE
    FluidHX(CompNum)%SupplySideLoop%OutletTemp = SupSideLoopInletTemp
  ENDIF

  IF (DmdSideMdot > 0.d0) THEN
    FluidHX(CompNum)%DemandSideLoop%OutletTemp = DmdSideLoopInletTemp + HeatTransferRate/ (DmdSideLoopInletCp * DmdSideMdot)
  ELSE
    FluidHX(CompNum)%DemandSideLoop%OutletTemp = DmdSideLoopInletTemp
  ENDIF
  FluidHX(CompNum)%Effectiveness                    = Effectiveness
  FluidHX(CompNum)%HeatTransferRate                 = HeatTransferRate
  FluidHX(CompNum)%SupplySideLoop%InletTemp         = SupSideLoopInletTemp
  FluidHX(CompNum)%SupplySideLoop%InletMassFlowRate = SupSideMdot
  FluidHX(CompNum)%DemandSideLoop%InletTemp         = DmdSideLoopInletTemp
  FluidHX(CompNum)%DemandSideLoop%InletMassFlowRate = DmdSideMdot

  RETURN

END SUBROUTINE CalcFluidHeatExchanger

SUBROUTINE FindHXDemandSideLoopFlow(CompNum, TargetSupplySideLoopLeavingTemp, HXActionMode)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   November 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! modulate demand side flow rate to hit a target leaving temperature (within tolerance)

          ! METHODOLOGY EMPLOYED:
          ! uses E+'s Regula Falsi numercial method

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataGlobals,    ONLY: WarmUpFlag
  USE General,        ONLY: RoundSigDigits, SolveRegulaFalsi
  USE PlantUtilities, ONLY: SetComponentFlowRate

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,   INTENT(IN) :: CompNum
  REAL(r64), INTENT(IN) :: TargetSupplySideLoopLeavingTemp
  INTEGER,   INTENT(IN) :: HXActionMode

          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER,   PARAMETER  :: MaxIte    = 500     ! Maximum number of iterations for solver
  REAL(r64), PARAMETER  :: Acc       = 1.d-3   ! Accuracy of solver result

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER                 :: SolFla              ! Flag of solver
  REAL(r64), DIMENSION(2) :: Par                 ! Parameter array passed to solver

  REAL(r64)               :: LeavingTempMinFlow
  REAL(r64)               :: LeavingTempFullFlow
  REAL(r64)  :: SupSideMdot ! mass flow rate of fluid entering from supply side loop
  REAL(r64)  :: DmdSideMdot ! mass flow rate of fluid entering from demand side loop

  SupSideMdot = Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%MassFlowRate
  ! first see if root is bracketed
  ! min demand flow
  DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMin
  CALL CalcFluidHeatExchanger(CompNum,SupSideMdot, DmdSideMdot)
  LeavingTempMinFlow = FluidHX(CompNum)%SupplySideLoop%OutletTemp

  ! full demand flow
  DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
  CALL CalcFluidHeatExchanger(CompNum,SupSideMdot, DmdSideMdot)
  LeavingTempFullFlow = FluidHX(CompNum)%SupplySideLoop%OutletTemp

  SELECT CASE (HXActionMode)

  CASE (HeatingSupplySideLoop)
    IF ((LeavingTempFullFlow > TargetSupplySideLoopLeavingTemp) &
        .AND. (TargetSupplySideLoopLeavingTemp > LeavingTempMinFlow )) THEN
      ! need to solve
      Par(1) = REAL( CompNum , r64) ! HX index
      Par(2) = TargetSupplySideLoopLeavingTemp

      CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, DmdSideMdot, HXDemandSideLoopFlowResidual,&
                            FluidHX(CompNum)%DemandSideLoop%MassFlowRateMin , &
                            FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax, Par)

      IF (SolFla == -1) THEN ! no convergence
        IF (.NOT. WarmupFlag) THEN
          IF (FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorCount < 1) THEN
            FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorCount = FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorCount + 1
            CALL ShowWarningError(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Iteration Limit exceeded calculating demand side loop flow rate' )
            CALL ShowContinueError('Simulation continues with calculated demand side mass flow rate = ' &
                                    //RoundSigDigits(DmdSideMdot, 7) )
          ENDIF
          CALL ShowRecurringWarningErrorAtEnd(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Iteration Limit exceeded calculating demand side loop flow rate continues.', &
                                  FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorIndex, DmdSideMdot, DmdSideMdot)
        ENDIF
      ELSEIF (SolFla == -2) THEN !f(x0) and f(x1) have the same sign
        DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax * &
                       (LeavingTempFullFlow - TargetSupplySideLoopLeavingTemp) &
                       /(LeavingTempFullFlow - LeavingTempMinFlow)
        IF (.NOT. WarmupFlag) THEN
          IF (FluidHX(CompNum)%DmdSideModulatSolvFailErrorCount < 1) THEN
            FluidHX(CompNum)%DmdSideModulatSolvFailErrorCount = FluidHX(CompNum)%DmdSideModulatSolvFailErrorCount + 1
            CALL ShowWarningError(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Solver failed to calculate demand side loop flow rate' )
            CALL ShowContinueError('Simulation continues with estimated demand side mass flow rate = ' &
                                    //RoundSigDigits(DmdSideMdot, 7) )
          ENDIF
          CALL ShowRecurringWarningErrorAtEnd(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Solver failed to calculate demand side loop flow rate continues.', &
                                  FluidHX(CompNum)%DmdSideModulatSolvFailErrorIndex, DmdSideMdot, DmdSideMdot)
        ENDIF
      ENDIF
      CALL SetComponentFlowRate(DmdSideMdot,                      &
                 FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                 FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                 FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                 FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                 FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                 FluidHX(CompNum)%DemandSideLoop%CompNum)

    ELSEIF ( ( TargetSupplySideLoopLeavingTemp >= LeavingTempFullFlow ) &
         .AND. (LeavingTempFullFlow > LeavingTempMinFlow) ) THEN
      ! run at full flow
      DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
      CALL SetComponentFlowRate(DmdSideMdot,                      &
                   FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                   FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                   FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                   FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                   FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                   FluidHX(CompNum)%DemandSideLoop%CompNum)

    ELSEIF ( LeavingTempMinFlow >=  TargetSupplySideLoopLeavingTemp) THEN

      ! run at min flow
      DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMin
      CALL SetComponentFlowRate(DmdSideMdot,                      &
                 FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                 FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                 FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                 FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                 FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                 FluidHX(CompNum)%DemandSideLoop%CompNum)
    ENDIF
  CASE (CoolingSupplySideLoop)
    IF ((LeavingTempFullFlow < TargetSupplySideLoopLeavingTemp) &
        .AND. (TargetSupplySideLoopLeavingTemp <  LeavingTempMinFlow )) THEN
      ! need to solve
      Par(1) = REAL( CompNum , r64) ! HX index
      Par(2) = TargetSupplySideLoopLeavingTemp

      CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, DmdSideMdot, HXDemandSideLoopFlowResidual,&
                            FluidHX(CompNum)%DemandSideLoop%MassFlowRateMin , &
                            FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax, Par)

      IF (SolFla == -1) THEN ! no convergence
        IF (.NOT. WarmupFlag) THEN
          IF (FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorCount < 1) THEN
            FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorCount = FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorCount + 1
            CALL ShowWarningError(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Iteration Limit exceeded calculating demand side loop flow rate' )
            CALL ShowContinueError('Simulation continues with calculated demand side mass flow rate = ' &
                                    //RoundSigDigits(DmdSideMdot, 7) )
          ENDIF
          CALL ShowRecurringWarningErrorAtEnd(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Iteration Limit exceeded calculating demand side loop flow rate continues.', &
                                  FluidHX(CompNum)%DmdSideModulatSolvNoConvergeErrorIndex, DmdSideMdot, DmdSideMdot)
        ENDIF
      ELSEIF (SolFla == -2) THEN !f(x0) and f(x1) have the same sign
        DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax * &
                       (LeavingTempFullFlow - TargetSupplySideLoopLeavingTemp) &
                       /(LeavingTempFullFlow - LeavingTempMinFlow)
        IF (.NOT. WarmupFlag) THEN
          IF (FluidHX(CompNum)%DmdSideModulatSolvFailErrorCount < 1) THEN
            FluidHX(CompNum)%DmdSideModulatSolvFailErrorCount = FluidHX(CompNum)%DmdSideModulatSolvFailErrorCount + 1
            CALL ShowWarningError(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Solver failed to calculate demand side loop flow rate' )
            CALL ShowContinueError('Simulation continues with estimated demand side mass flow rate = ' &
                                    //RoundSigDigits(DmdSideMdot, 7) )
          ENDIF
          CALL ShowRecurringWarningErrorAtEnd(ComponentClassName//' named '//TRIM(FluidHX(CompNum)%Name)// &
                                  ' - Solver failed to calculate demand side loop flow rate continues.' ,&
                                  FluidHX(CompNum)%DmdSideModulatSolvFailErrorIndex, DmdSideMdot, DmdSideMdot)
        ENDIF
      ENDIF
      CALL SetComponentFlowRate(DmdSideMdot,                      &
                 FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                 FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                 FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                 FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                 FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                 FluidHX(CompNum)%DemandSideLoop%CompNum)
    ELSEIF ( ( TargetSupplySideLoopLeavingTemp <= LeavingTempFullFlow ) &
         .AND. (LeavingTempFullFlow < LeavingTempMinFlow) ) THEN
      ! run at full flow
      DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMax
      CALL SetComponentFlowRate(DmdSideMdot,                      &
                   FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                   FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                   FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                   FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                   FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                   FluidHX(CompNum)%DemandSideLoop%CompNum)
    ELSEIF ( LeavingTempMinFlow <=  TargetSupplySideLoopLeavingTemp) THEN

        ! run at min flow
      DmdSideMdot = FluidHX(CompNum)%DemandSideLoop%MassFlowRateMin
      CALL SetComponentFlowRate(DmdSideMdot,                      &
                 FluidHX(CompNum)%DemandSideLoop%InletNodeNum,  &
                 FluidHX(CompNum)%DemandSideLoop%OutletNodeNum, &
                 FluidHX(CompNum)%DemandSideLoop%LoopNum,       &
                 FluidHX(CompNum)%DemandSideLoop%LoopSideNum,   &
                 FluidHX(CompNum)%DemandSideLoop%BranchNum,     &
                 FluidHX(CompNum)%DemandSideLoop%CompNum)
    ENDIF

  END SELECT

  RETURN

END SUBROUTINE FindHXDemandSideLoopFlow

FUNCTION HXDemandSideLoopFlowResidual(DmdSideMassFlowRate, Par ) RESULT (Residuum)

          ! FUNCTION INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   December 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          ! calculate residual value for regula falsi solver

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE PlantUtilities,   ONLY: SetComponentFlowRate

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! FUNCTION ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN) :: DmdSideMassFlowRate
  REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! Par(1) = HX index number
                                                    ! Par(2) = desired supply side loop outlet temperature [C]
  REAL(r64)         :: Residuum                   ! Residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER :: CompNum
  REAL(r64) :: SupSideLoopOutletTemp
  REAL(r64) :: MdotTrial
  REAL(r64)  :: SupSideMdot ! mass flow rate of fluid entering from supply side loop


  MdotTrial = DmdSideMassFlowRate
  CompNum = INT(Par(1))
  SupSideMdot = Node(FluidHX(CompNum)%SupplySideLoop%InletNodeNum)%MassFlowRate

  CALL CalcFluidHeatExchanger(CompNum,SupSideMdot ,MdotTrial )

  SupSideLoopOutletTemp = FluidHX(CompNum)%SupplySideLoop%OutletTemp

  Residuum = Par(2) - SupSideLoopOutletTemp

  RETURN

END FUNCTION HXDemandSideLoopFlowResidual

SUBROUTINE UpdateFluidHeatExchanger(CompNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   December 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! update calculate results

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN)  :: CompNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
          ! na

  Node(FluidHX(CompNum)%DemandSideLoop%OutletNodeNum)%Temp = FluidHX(CompNum)%DemandSideLoop%OutletTemp
  Node(FluidHX(CompNum)%SupplySideLoop%OutletNodeNum)%Temp = FluidHX(CompNum)%SupplySideLoop%OutletTemp

  RETURN

END SUBROUTINE UpdateFluidHeatExchanger

SUBROUTINE ReportFluidHeatExchanger(CompNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   December, 2012
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! update heat exchanger report variables

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHVACGlobals , ONLY: TimeStepSys, SmallLoad
  USE DataGlobals,      ONLY: SecInHour

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: CompNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
          ! na

  FluidHX(CompNum)%HeatTransferEnergy = FluidHX(CompNum)%HeatTransferRate *  TimeStepSys * SecInHour

  IF ( (ABS(FluidHX(CompNum)%HeatTransferRate) > SmallLoad) .AND. &
       (FluidHX(CompNum)%DemandSideLoop%InletMassFlowRate > 0.d0) .AND. &
       (FluidHX(CompNum)%SupplySideLoop%InletMassFlowRate > 0.d0) ) THEN
    FluidHX(CompNum)%OperationStatus = 1.d0
  ELSE
    FluidHX(CompNum)%OperationStatus = 0.d0
  ENDIF

  RETURN

END SUBROUTINE ReportFluidHeatExchanger

!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!
END MODULE PlantHeatExchangerFluidToFluid

AirflowNetworkBalanceManager.f90 AirflowNetworkSolver.f90 BaseboardRadiator.f90 BaseboardRadiatorElectric.f90 BaseboardRadiatorSteam.f90 BaseboardRadiatorWater.f90 BranchInputManager.f90 BranchNodeConnections.f90 ConductionTransferFunctionCalc.f90 CoolTower.f90 CostEstimateManager.f90 CurveManager.f90 CVFOnlyRoutines.f90 DataAirflowNetwork.f90 DataAirLoop.f90 DataAirSystems.f90 DataBranchAirLoopPlant.f90 DataBranchNodeConnections.f90 DataBSDFWindow.f90 DataComplexFenestration.f90 DataContaminantBalance.f90 DataConvergParams.f90 DataConversions.f90 DataCostEstimate.f90 DataDaylighting.f90 DataDaylightingDevices.f90 Datadefineequip.f90 DataDElight.f90 DataEnvironment.f90 DataEquivalentLayerWindow.f90 DataErrorTracking.f90 DataGenerators.f90 DataGlobalConstants.f90 DataGlobals.f90 DataHeatBalance.f90 DataHeatBalFanSys.f90 DataHeatBalSurface.f90 DataHVACControllers.f90 DataHVACGlobals.f90 DataInterfaces.f90 DataIPShortCuts.f90 DataLoopNode.f90 DataMoistureBalance.f90 DataMoistureBalanceEMPD.f90 DataOutputs.f90 DataPhotovoltaics.f90 DataPlant.f90 DataPlantPipingSystems.f90 DataPrecisionGlobals.f90 DataReportingFlags.f90 DataRoomAir.f90 DataRootFinder.f90 DataRuntimeLanguage.f90 DataShadowingCombinations.f90 DataSizing.f90 DataStringGlobals.f90 DataSurfaceColors.f90 DataSurfaceLists.f90 DataSurfaces.f90 DataSystemVariables.f90 DataTimings.f90 DataUCSDSharedData.f90 DataVectorTypes.f90 DataViewFactorInformation.f90 DataWater.f90 DataZoneControls.f90 DataZoneEnergyDemands.f90 DataZoneEquipment.f90 DaylightingDevices.f90 DaylightingManager.f90 DElightManagerF.f90 DElightManagerF_NO.f90 DemandManager.f90 DesiccantDehumidifiers.f90 DirectAir.f90 DisplayRoutines.f90 DXCoil.f90 EarthTube.f90 EconomicLifeCycleCost.f90 EconomicTariff.f90 EcoRoof.f90 ElectricPowerGenerators.f90 ElectricPowerManager.f90 EMSManager.f90 EnergyPlus.f90 ExteriorEnergyUseManager.f90 ExternalInterface_NO.f90 FanCoilUnits.f90 FaultsManager.f90 FluidProperties.f90 General.f90 GeneralRoutines.f90 GlobalNames.f90 HeatBalanceAirManager.f90 HeatBalanceConvectionCoeffs.f90 HeatBalanceHAMTManager.f90 HeatBalanceInternalHeatGains.f90 HeatBalanceIntRadExchange.f90 HeatBalanceManager.f90 HeatBalanceMovableInsulation.f90 HeatBalanceSurfaceManager.f90 HeatBalFiniteDifferenceManager.f90 HeatRecovery.f90 Humidifiers.f90 HVACControllers.f90 HVACCooledBeam.f90 HVACDualDuctSystem.f90 HVACDuct.f90 HVACDXSystem.f90 HVACEvapComponent.f90 HVACFanComponent.f90 HVACFurnace.f90 HVACHeatingCoils.f90 HVACHXAssistedCoolingCoil.f90 HVACInterfaceManager.f90 HVACManager.f90 HVACMixerComponent.f90 HVACMultiSpeedHeatPump.f90 HVACSingleDuctInduc.f90 HVACSingleDuctSystem.f90 HVACSplitterComponent.f90 HVACStandAloneERV.f90 HVACSteamCoilComponent.f90 HVACTranspiredCollector.f90 HVACUnitaryBypassVAV.f90 HVACUnitarySystem.f90 HVACVariableRefrigerantFlow.f90 HVACWaterCoilComponent.f90 HVACWatertoAir.f90 HVACWatertoAirMultiSpeedHP.f90 InputProcessor.f90 MatrixDataManager.f90 MixedAir.f90 MoistureBalanceEMPDManager.f90 NodeInputManager.f90 NonZoneEquipmentManager.f90 OutAirNodeManager.f90 OutdoorAirUnit.f90 OutputProcessor.f90 OutputReportPredefined.f90 OutputReports.f90 OutputReportTabular.f90 PackagedTerminalHeatPump.f90 PackagedThermalStorageCoil.f90 Photovoltaics.f90 PhotovoltaicThermalCollectors.f90 PlantAbsorptionChillers.f90 PlantBoilers.f90 PlantBoilersSteam.f90 PlantCentralGSHP.f90 PlantChillers.f90 PlantCondLoopOperation.f90 PlantCondLoopTowers.f90 PlantEIRChillers.f90 PlantEvapFluidCoolers.f90 PlantExhaustAbsorptionChiller.f90 PlantFluidCoolers.f90 PlantGasAbsorptionChiller.f90 PlantGroundHeatExchangers.f90 PlantHeatExchanger.f90 PlantIceThermalStorage.f90 PlantLoadProfile.f90 PlantLoopEquipment.f90 PlantLoopSolver.f90 PlantManager.f90 PlantOutsideEnergySources.f90 PlantPipeHeatTransfer.f90 PlantPipes.f90 PlantPipingSystemManager.f90 PlantPondGroundHeatExchanger.f90 PlantPressureSystem.f90 PlantPumps.f90 PlantSolarCollectors.f90 PlantSurfaceGroundHeatExchanger.f90 PlantUtilities.f90 PlantValves.f90 PlantWaterSources.f90 PlantWaterThermalTank.f90 PlantWatertoWaterGSHP.f90 PlantWaterUse.f90 PollutionAnalysisModule.f90 PoweredInductionUnits.f90 PsychRoutines.f90 Purchasedairmanager.f90 RadiantSystemHighTemp.f90 RadiantSystemLowTemp.f90 RefrigeratedCase.f90 ReportSizingManager.f90 ReturnAirPath.f90 RoomAirManager.f90 RoomAirModelCrossVent.f90 RoomAirModelDisplacementVent.f90 RoomAirModelMundt.f90 RoomAirModelUFAD.f90 RoomAirModelUserTempPattern.f90 RootFinder.f90 RuntimeLanguageProcessor.f90 ScheduleManager.f90 SetPointManager.f90 SimAirServingZones.f90 SimulationManager.f90 SizingManager.f90 SolarReflectionManager.f90 SolarShading.f90 SortAndStringUtilities.f90 sqlite3.c SQLiteCRoutines.c SQLiteFortranRoutines.f90 SQLiteFortranRoutines_NO.f90 StandardRatings.f90 SurfaceGeometry.f90 SystemAvailabilityManager.f90 SystemReports.f90 TarcogComplexFenestration.f90 ThermalChimney.f90 ThermalComfort.f90 UnitHeater.f90 UnitVentilator.f90 UserDefinedComponents.f90 UtilityRoutines.f90 VectorUtilities.f90 VentilatedSlab.f90 WaterManager.f90 WeatherManager.f90 WindowAC.f90 WindowComplexManager.f90 WindowEquivalentLayer.f90 WindowManager.f90 WindTurbine.f90 Zoneairloopequipmentmanager.f90 ZoneContaminantPredictorCorrector.f90 ZoneDehumidifier.f90 Zoneequipmentmanager.f90 ZonePlenumComponent.f90 ZoneTempPredictorCorrector.f90