sourcefile~~zonetemppredictorcorrector.f90~~EfferentGraph sourcefile~zonetemppredictorcorrector.f90 ZoneTempPredictorCorrector.f90 sourcefile~heatbalanceinternalheatgains.f90 HeatBalanceInternalHeatGains.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~roomairmodelcrossvent.f90 RoomAirModelCrossVent.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~roomairmodelusertemppattern.f90 RoomAirModelUserTempPattern.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~roomairmodelufad.f90 RoomAirModelUFAD.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelufad.f90 sourcefile~roomairmodeldisplacementvent.f90 RoomAirModelDisplacementVent.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~roomairmodelmundt.f90 RoomAirModelMundt.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelmundt.f90 sourcefile~datahvacglobals.f90 DataHVACGlobals.f90 sourcefile~datahvacglobals.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datazoneequipment.f90 DataZoneEquipment.f90 sourcefile~datahvacglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~thermalcomfort.f90 ThermalComfort.f90 sourcefile~datahvacglobals.f90->sourcefile~thermalcomfort.f90 sourcefile~zoneplenumcomponent.f90 ZonePlenumComponent.f90 sourcefile~datahvacglobals.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~general.f90 General.f90 sourcefile~datahvacglobals.f90->sourcefile~general.f90 sourcefile~outputreporttabular.f90 OutputReportTabular.f90 sourcefile~datahvacglobals.f90->sourcefile~outputreporttabular.f90 sourcefile~plantpipeheattransfer.f90 PlantPipeHeatTransfer.f90 sourcefile~datahvacglobals.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~plantwateruse.f90 PlantWaterUse.f90 sourcefile~datahvacglobals.f90->sourcefile~plantwateruse.f90 sourcefile~refrigeratedcase.f90 RefrigeratedCase.f90 sourcefile~datahvacglobals.f90->sourcefile~refrigeratedcase.f90 sourcefile~electricpowermanager.f90 ElectricPowerManager.f90 sourcefile~datahvacglobals.f90->sourcefile~electricpowermanager.f90 sourcefile~electricpowergenerators.f90 ElectricPowerGenerators.f90 sourcefile~datahvacglobals.f90->sourcefile~electricpowergenerators.f90 sourcefile~plantwaterthermaltank.f90 PlantWaterThermalTank.f90 sourcefile~datahvacglobals.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~radiantsystemlowtemp.f90 RadiantSystemLowTemp.f90 sourcefile~datahvacglobals.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~ventilatedslab.f90 VentilatedSlab.f90 sourcefile~datahvacglobals.f90->sourcefile~ventilatedslab.f90 sourcefile~pollutionanalysismodule.f90 PollutionAnalysisModule.f90 sourcefile~datahvacglobals.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~branchinputmanager.f90 BranchInputManager.f90 sourcefile~datahvacglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~hvacfancomponent.f90 HVACFanComponent.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~hvachxassistedcoolingcoil.f90 HVACHXAssistedCoolingCoil.f90 sourcefile~datahvacglobals.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~hvacheatingcoils.f90 HVACHeatingCoils.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacheatingcoils.f90 sourcefile~hvacwatercoilcomponent.f90 HVACWaterCoilComponent.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~hvacsteamcoilcomponent.f90 HVACSteamCoilComponent.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~runtimelanguageprocessor.f90 RuntimeLanguageProcessor.f90 sourcefile~datahvacglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dxcoil.f90 DXCoil.f90 sourcefile~datahvacglobals.f90->sourcefile~dxcoil.f90 sourcefile~heatrecovery.f90 HeatRecovery.f90 sourcefile~datahvacglobals.f90->sourcefile~heatrecovery.f90 sourcefile~watermanager.f90 WaterManager.f90 sourcefile~datahvacglobals.f90->sourcefile~watermanager.f90 sourcefile~standardratings.f90 StandardRatings.f90 sourcefile~datahvacglobals.f90->sourcefile~standardratings.f90 sourcefile~setpointmanager.f90 SetPointManager.f90 sourcefile~datahvacglobals.f90->sourcefile~setpointmanager.f90 sourcefile~photovoltaics.f90 Photovoltaics.f90 sourcefile~datahvacglobals.f90->sourcefile~photovoltaics.f90 sourcefile~windturbine.f90 WindTurbine.f90 sourcefile~datahvacglobals.f90->sourcefile~windturbine.f90 sourcefile~photovoltaicthermalcollectors.f90 PhotovoltaicThermalCollectors.f90 sourcefile~datahvacglobals.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~hvactranspiredcollector.f90 HVACTranspiredCollector.f90 sourcefile~datahvacglobals.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~plantsolarcollectors.f90 PlantSolarCollectors.f90 sourcefile~datahvacglobals.f90->sourcefile~plantsolarcollectors.f90 sourcefile~datahvacglobals.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~datahvacglobals.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~datahvacglobals.f90->sourcefile~roomairmodelufad.f90 sourcefile~datahvacglobals.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~poweredinductionunits.f90 PoweredInductionUnits.f90 sourcefile~datahvacglobals.f90->sourcefile~poweredinductionunits.f90 sourcefile~hvacmixercomponent.f90 HVACMixerComponent.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacmixercomponent.f90 sourcefile~dataheatbalsurface.f90 DataHeatBalSurface.f90 sourcefile~dataheatbalsurface.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataheatbalsurface.f90->sourcefile~thermalcomfort.f90 sourcefile~dataheatbalsurface.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataheatbalsurface.f90->sourcefile~ventilatedslab.f90 sourcefile~heatbalanceconvectioncoeffs.f90 HeatBalanceConvectionCoeffs.f90 sourcefile~dataheatbalsurface.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataheatbalsurface.f90->sourcefile~photovoltaics.f90 sourcefile~dataheatbalsurface.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataheatbalsurface.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataheatbalsurface.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataheatbalsurface.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataheatbalsurface.f90->sourcefile~roomairmodelmundt.f90 sourcefile~datazoneequipment.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datazoneequipment.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~roomairmanager.f90 RoomAirManager.f90 sourcefile~datazoneequipment.f90->sourcefile~roomairmanager.f90 sourcefile~datazoneequipment.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~datazoneequipment.f90->sourcefile~outputreporttabular.f90 sourcefile~datazoneequipment.f90->sourcefile~refrigeratedcase.f90 sourcefile~datazoneequipment.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datazoneequipment.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~datazoneequipment.f90->sourcefile~ventilatedslab.f90 sourcefile~datazoneequipment.f90->sourcefile~hvacfancomponent.f90 sourcefile~datazoneequipment.f90->sourcefile~setpointmanager.f90 sourcefile~datazoneequipment.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~datazoneequipment.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~datazoneequipment.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~datazoneequipment.f90->sourcefile~roomairmodelufad.f90 sourcefile~datazoneequipment.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~datazoneequipment.f90->sourcefile~roomairmodelmundt.f90 sourcefile~datazoneequipment.f90->sourcefile~poweredinductionunits.f90 sourcefile~dataipshortcuts.f90 DataIPShortCuts.f90 sourcefile~dataipshortcuts.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataipshortcuts.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataipshortcuts.f90->sourcefile~thermalcomfort.f90 sourcefile~dataipshortcuts.f90->sourcefile~roomairmanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~schedulemanager.f90 ScheduleManager.f90 sourcefile~dataipshortcuts.f90->sourcefile~schedulemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90 InputProcessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~inputprocessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~outputreporttabular.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantwateruse.f90 sourcefile~dataipshortcuts.f90->sourcefile~electricpowermanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~electricpowergenerators.f90 sourcefile~daylightingdevices.f90 DaylightingDevices.f90 sourcefile~dataipshortcuts.f90->sourcefile~daylightingdevices.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~outputprocessor.f90 OutputProcessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~outputprocessor.f90 sourcefile~exteriorenergyusemanager.f90 ExteriorEnergyUseManager.f90 sourcefile~dataipshortcuts.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~curvemanager.f90 CurveManager.f90 sourcefile~dataipshortcuts.f90->sourcefile~curvemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataipshortcuts.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataipshortcuts.f90->sourcefile~heatrecovery.f90 sourcefile~dataipshortcuts.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataipshortcuts.f90->sourcefile~photovoltaics.f90 sourcefile~dataipshortcuts.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataipshortcuts.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataipshortcuts.f90->sourcefile~poweredinductionunits.f90 sourcefile~thermalcomfort.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datazonecontrols.f90 DataZoneControls.f90 sourcefile~datazonecontrols.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~emsmanager.f90 EMSManager.f90 sourcefile~datazonecontrols.f90->sourcefile~emsmanager.f90 sourcefile~datazonecontrols.f90->sourcefile~setpointmanager.f90 sourcefile~datainterfaces.f90 DataInterfaces.f90 sourcefile~datainterfaces.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datainterfaces.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~datainterfaces.f90->sourcefile~datazoneequipment.f90 sourcefile~datainterfaces.f90->sourcefile~thermalcomfort.f90 sourcefile~datainterfaces.f90->sourcefile~roomairmanager.f90 sourcefile~datainterfaces.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~dataenvironment.f90 DataEnvironment.f90 sourcefile~datainterfaces.f90->sourcefile~dataenvironment.f90 sourcefile~dataheatbalance.f90 DataHeatBalance.f90 sourcefile~datainterfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~psychroutines.f90 PsychRoutines.f90 sourcefile~datainterfaces.f90->sourcefile~psychroutines.f90 sourcefile~datainterfaces.f90->sourcefile~schedulemanager.f90 sourcefile~datainterfaces.f90->sourcefile~general.f90 sourcefile~datainterfaces.f90->sourcefile~inputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~outputreporttabular.f90 sourcefile~datainterfaces.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~datainterfaces.f90->sourcefile~plantwateruse.f90 sourcefile~datainterfaces.f90->sourcefile~refrigeratedcase.f90 sourcefile~datainterfaces.f90->sourcefile~electricpowermanager.f90 sourcefile~datainterfaces.f90->sourcefile~electricpowergenerators.f90 sourcefile~datainterfaces.f90->sourcefile~daylightingdevices.f90 sourcefile~datainterfaces.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datainterfaces.f90->sourcefile~outputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~datainterfaces.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~sqlitefortranroutines.f90 SQLiteFortranRoutines.f90 sourcefile~datainterfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datainterfaces.f90->sourcefile~ventilatedslab.f90 sourcefile~datainterfaces.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~plantutilities.f90 PlantUtilities.f90 sourcefile~datainterfaces.f90->sourcefile~plantutilities.f90 sourcefile~datasurfacelists.f90 DataSurfaceLists.f90 sourcefile~datainterfaces.f90->sourcefile~datasurfacelists.f90 sourcefile~reportsizingmanager.f90 ReportSizingManager.f90 sourcefile~datainterfaces.f90->sourcefile~reportsizingmanager.f90 sourcefile~branchnodeconnections.f90 BranchNodeConnections.f90 sourcefile~datainterfaces.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataplant.f90 DataPlant.f90 sourcefile~datainterfaces.f90->sourcefile~dataplant.f90 sourcefile~nodeinputmanager.f90 NodeInputManager.f90 sourcefile~datainterfaces.f90->sourcefile~nodeinputmanager.f90 sourcefile~fluidproperties.f90 FluidProperties.f90 sourcefile~datainterfaces.f90->sourcefile~fluidproperties.f90 sourcefile~datainterfaces.f90->sourcefile~branchinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~curvemanager.f90 sourcefile~datainterfaces.f90->sourcefile~hvacfancomponent.f90 sourcefile~datainterfaces.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~datainterfaces.f90->sourcefile~hvacheatingcoils.f90 sourcefile~outairnodemanager.f90 OutAirNodeManager.f90 sourcefile~datainterfaces.f90->sourcefile~outairnodemanager.f90 sourcefile~datainterfaces.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datainterfaces.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~datainterfaces.f90->sourcefile~emsmanager.f90 sourcefile~datainterfaces.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataruntimelanguage.f90 DataRuntimeLanguage.f90 sourcefile~datainterfaces.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datainterfaces.f90->sourcefile~dxcoil.f90 sourcefile~datainterfaces.f90->sourcefile~heatrecovery.f90 sourcefile~globalnames.f90 GlobalNames.f90 sourcefile~datainterfaces.f90->sourcefile~globalnames.f90 sourcefile~datainterfaces.f90->sourcefile~watermanager.f90 sourcefile~datainterfaces.f90->sourcefile~standardratings.f90 sourcefile~datainterfaces.f90->sourcefile~setpointmanager.f90 sourcefile~datainterfaces.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~vectorutilities.f90 VectorUtilities.f90 sourcefile~datainterfaces.f90->sourcefile~vectorutilities.f90 sourcefile~datainterfaces.f90->sourcefile~photovoltaics.f90 sourcefile~datainterfaces.f90->sourcefile~windturbine.f90 sourcefile~datainterfaces.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~datainterfaces.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~datainterfaces.f90->sourcefile~plantsolarcollectors.f90 sourcefile~datainterfaces.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~datainterfaces.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~datainterfaces.f90->sourcefile~roomairmodelufad.f90 sourcefile~datainterfaces.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~datainterfaces.f90->sourcefile~roomairmodelmundt.f90 sourcefile~datainterfaces.f90->sourcefile~poweredinductionunits.f90 sourcefile~datainterfaces.f90->sourcefile~hvacmixercomponent.f90 sourcefile~dataloopnode.f90 DataLoopNode.f90 sourcefile~dataloopnode.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataloopnode.f90->sourcefile~datazoneequipment.f90 sourcefile~dataloopnode.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~dataloopnode.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataloopnode.f90->sourcefile~plantwateruse.f90 sourcefile~dataloopnode.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataloopnode.f90->sourcefile~electricpowermanager.f90 sourcefile~dataloopnode.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataloopnode.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataloopnode.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataloopnode.f90->sourcefile~ventilatedslab.f90 sourcefile~dataloopnode.f90->sourcefile~plantutilities.f90 sourcefile~dataloopnode.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataloopnode.f90->sourcefile~dataplant.f90 sourcefile~dataloopnode.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataloopnode.f90->sourcefile~branchinputmanager.f90 sourcefile~dataloopnode.f90->sourcefile~curvemanager.f90 sourcefile~dataloopnode.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataloopnode.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataloopnode.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataloopnode.f90->sourcefile~outairnodemanager.f90 sourcefile~dataloopnode.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataloopnode.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~dataloopnode.f90->sourcefile~emsmanager.f90 sourcefile~dataloopnode.f90->sourcefile~dxcoil.f90 sourcefile~dataloopnode.f90->sourcefile~heatrecovery.f90 sourcefile~dataloopnode.f90->sourcefile~setpointmanager.f90 sourcefile~dataloopnode.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataloopnode.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataloopnode.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataloopnode.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataloopnode.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataloopnode.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataloopnode.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataloopnode.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataloopnode.f90->sourcefile~roomairmodelmundt.f90 sourcefile~dataloopnode.f90->sourcefile~poweredinductionunits.f90 sourcefile~dataloopnode.f90->sourcefile~hvacmixercomponent.f90 sourcefile~roomairmanager.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataheatbalfansys.f90 DataHeatBalFanSys.f90 sourcefile~dataheatbalfansys.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataheatbalfansys.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataheatbalfansys.f90->sourcefile~thermalcomfort.f90 sourcefile~dataheatbalfansys.f90->sourcefile~roomairmanager.f90 sourcefile~dataheatbalfansys.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataheatbalfansys.f90->sourcefile~plantwateruse.f90 sourcefile~dataheatbalfansys.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataheatbalfansys.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataheatbalfansys.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataheatbalfansys.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataheatbalfansys.f90->sourcefile~ventilatedslab.f90 sourcefile~dataheatbalfansys.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataheatbalfansys.f90->sourcefile~photovoltaics.f90 sourcefile~dataheatbalfansys.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataheatbalfansys.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataheatbalfansys.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataheatbalfansys.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataheatbalfansys.f90->sourcefile~roomairmodelmundt.f90 sourcefile~dataheatbalfansys.f90->sourcefile~poweredinductionunits.f90 sourcefile~datadefineequip.f90 Datadefineequip.f90 sourcefile~datadefineequip.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datadefineequip.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~datadefineequip.f90->sourcefile~poweredinductionunits.f90 sourcefile~zoneplenumcomponent.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~zoneplenumcomponent.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~zoneplenumcomponent.f90->sourcefile~outputreporttabular.f90 sourcefile~dataenvironment.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataenvironment.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataenvironment.f90->sourcefile~thermalcomfort.f90 sourcefile~dataenvironment.f90->sourcefile~roomairmanager.f90 sourcefile~dataenvironment.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~dataenvironment.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90->sourcefile~psychroutines.f90 sourcefile~dataenvironment.f90->sourcefile~schedulemanager.f90 sourcefile~dataenvironment.f90->sourcefile~outputreporttabular.f90 sourcefile~dataenvironment.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataenvironment.f90->sourcefile~plantwateruse.f90 sourcefile~dataenvironment.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataenvironment.f90->sourcefile~electricpowermanager.f90 sourcefile~dataenvironment.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataenvironment.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataenvironment.f90->sourcefile~outputprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataenvironment.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~dataenvironment.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataenvironment.f90->sourcefile~ventilatedslab.f90 sourcefile~dataenvironment.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~dataenvironment.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataenvironment.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataenvironment.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataenvironment.f90->sourcefile~outairnodemanager.f90 sourcefile~dataenvironment.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataenvironment.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~dataenvironment.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~dxcoil.f90 sourcefile~dataenvironment.f90->sourcefile~heatrecovery.f90 sourcefile~dataenvironment.f90->sourcefile~watermanager.f90 sourcefile~dataenvironment.f90->sourcefile~setpointmanager.f90 sourcefile~dataenvironment.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataenvironment.f90->sourcefile~photovoltaics.f90 sourcefile~dataenvironment.f90->sourcefile~windturbine.f90 sourcefile~dataenvironment.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataenvironment.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataenvironment.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataenvironment.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataenvironment.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataenvironment.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataenvironment.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataenvironment.f90->sourcefile~roomairmodelmundt.f90 sourcefile~dataenvironment.f90->sourcefile~poweredinductionunits.f90 sourcefile~dataenvironment.f90->sourcefile~hvacmixercomponent.f90 sourcefile~dataheatbalance.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataheatbalance.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataheatbalance.f90->sourcefile~datazoneequipment.f90 sourcefile~dataheatbalance.f90->sourcefile~thermalcomfort.f90 sourcefile~dataheatbalance.f90->sourcefile~roomairmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~dataheatbalance.f90->sourcefile~outputreporttabular.f90 sourcefile~dataheatbalance.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataheatbalance.f90->sourcefile~plantwateruse.f90 sourcefile~dataheatbalance.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataheatbalance.f90->sourcefile~electricpowermanager.f90 sourcefile~dataheatbalance.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataheatbalance.f90->sourcefile~daylightingdevices.f90 sourcefile~dataheatbalance.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataheatbalance.f90->sourcefile~outputprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataheatbalance.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataheatbalance.f90->sourcefile~ventilatedslab.f90 sourcefile~dataheatbalance.f90->sourcefile~datasurfacelists.f90 sourcefile~dataheatbalance.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataheatbalance.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataheatbalance.f90->sourcefile~emsmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~dxcoil.f90 sourcefile~dataheatbalance.f90->sourcefile~watermanager.f90 sourcefile~dataheatbalance.f90->sourcefile~setpointmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataheatbalance.f90->sourcefile~photovoltaics.f90 sourcefile~dataheatbalance.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataheatbalance.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataheatbalance.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataheatbalance.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataheatbalance.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataheatbalance.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataheatbalance.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataheatbalance.f90->sourcefile~roomairmodelmundt.f90 sourcefile~datazoneenergydemands.f90 DataZoneEnergyDemands.f90 sourcefile~datazoneenergydemands.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datazoneenergydemands.f90->sourcefile~thermalcomfort.f90 sourcefile~datazoneenergydemands.f90->sourcefile~refrigeratedcase.f90 sourcefile~datazoneenergydemands.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~datazoneenergydemands.f90->sourcefile~ventilatedslab.f90 sourcefile~datazoneenergydemands.f90->sourcefile~setpointmanager.f90 sourcefile~datazoneenergydemands.f90->sourcefile~poweredinductionunits.f90 sourcefile~psychroutines.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~psychroutines.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~psychroutines.f90->sourcefile~thermalcomfort.f90 sourcefile~psychroutines.f90->sourcefile~roomairmanager.f90 sourcefile~psychroutines.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~psychroutines.f90->sourcefile~outputreporttabular.f90 sourcefile~psychroutines.f90->sourcefile~plantwateruse.f90 sourcefile~psychroutines.f90->sourcefile~refrigeratedcase.f90 sourcefile~psychroutines.f90->sourcefile~electricpowergenerators.f90 sourcefile~psychroutines.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~psychroutines.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~psychroutines.f90->sourcefile~ventilatedslab.f90 sourcefile~psychroutines.f90->sourcefile~nodeinputmanager.f90 sourcefile~psychroutines.f90->sourcefile~hvacfancomponent.f90 sourcefile~psychroutines.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~psychroutines.f90->sourcefile~hvacheatingcoils.f90 sourcefile~psychroutines.f90->sourcefile~outairnodemanager.f90 sourcefile~psychroutines.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~psychroutines.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~psychroutines.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~psychroutines.f90->sourcefile~dxcoil.f90 sourcefile~psychroutines.f90->sourcefile~heatrecovery.f90 sourcefile~psychroutines.f90->sourcefile~setpointmanager.f90 sourcefile~psychroutines.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~psychroutines.f90->sourcefile~windturbine.f90 sourcefile~psychroutines.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~psychroutines.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~psychroutines.f90->sourcefile~plantsolarcollectors.f90 sourcefile~psychroutines.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~psychroutines.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~psychroutines.f90->sourcefile~roomairmodelufad.f90 sourcefile~psychroutines.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~psychroutines.f90->sourcefile~roomairmodelmundt.f90 sourcefile~psychroutines.f90->sourcefile~poweredinductionunits.f90 sourcefile~psychroutines.f90->sourcefile~hvacmixercomponent.f90 sourcefile~schedulemanager.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~schedulemanager.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~schedulemanager.f90->sourcefile~datazoneequipment.f90 sourcefile~schedulemanager.f90->sourcefile~thermalcomfort.f90 sourcefile~schedulemanager.f90->sourcefile~roomairmanager.f90 sourcefile~schedulemanager.f90->sourcefile~outputreporttabular.f90 sourcefile~schedulemanager.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~schedulemanager.f90->sourcefile~plantwateruse.f90 sourcefile~schedulemanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~schedulemanager.f90->sourcefile~electricpowermanager.f90 sourcefile~schedulemanager.f90->sourcefile~electricpowergenerators.f90 sourcefile~schedulemanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~schedulemanager.f90->sourcefile~outputprocessor.f90 sourcefile~schedulemanager.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~schedulemanager.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~schedulemanager.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~schedulemanager.f90->sourcefile~ventilatedslab.f90 sourcefile~schedulemanager.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~schedulemanager.f90->sourcefile~nodeinputmanager.f90 sourcefile~schedulemanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~schedulemanager.f90->sourcefile~hvacheatingcoils.f90 sourcefile~schedulemanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~schedulemanager.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~schedulemanager.f90->sourcefile~emsmanager.f90 sourcefile~schedulemanager.f90->sourcefile~dxcoil.f90 sourcefile~schedulemanager.f90->sourcefile~heatrecovery.f90 sourcefile~schedulemanager.f90->sourcefile~watermanager.f90 sourcefile~schedulemanager.f90->sourcefile~setpointmanager.f90 sourcefile~schedulemanager.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~schedulemanager.f90->sourcefile~photovoltaics.f90 sourcefile~schedulemanager.f90->sourcefile~windturbine.f90 sourcefile~schedulemanager.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~schedulemanager.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~schedulemanager.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~schedulemanager.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~schedulemanager.f90->sourcefile~roomairmodelufad.f90 sourcefile~schedulemanager.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~schedulemanager.f90->sourcefile~poweredinductionunits.f90 sourcefile~general.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~general.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~general.f90->sourcefile~datazoneequipment.f90 sourcefile~general.f90->sourcefile~thermalcomfort.f90 sourcefile~general.f90->sourcefile~roomairmanager.f90 sourcefile~general.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~general.f90->sourcefile~dataenvironment.f90 sourcefile~general.f90->sourcefile~dataheatbalance.f90 sourcefile~general.f90->sourcefile~psychroutines.f90 sourcefile~general.f90->sourcefile~schedulemanager.f90 sourcefile~general.f90->sourcefile~outputreporttabular.f90 sourcefile~general.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~general.f90->sourcefile~plantwateruse.f90 sourcefile~general.f90->sourcefile~refrigeratedcase.f90 sourcefile~general.f90->sourcefile~electricpowermanager.f90 sourcefile~general.f90->sourcefile~electricpowergenerators.f90 sourcefile~general.f90->sourcefile~daylightingdevices.f90 sourcefile~general.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~general.f90->sourcefile~outputprocessor.f90 sourcefile~general.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~general.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~general.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~general.f90->sourcefile~ventilatedslab.f90 sourcefile~general.f90->sourcefile~plantutilities.f90 sourcefile~general.f90->sourcefile~datasurfacelists.f90 sourcefile~general.f90->sourcefile~reportsizingmanager.f90 sourcefile~general.f90->sourcefile~branchnodeconnections.f90 sourcefile~general.f90->sourcefile~dataplant.f90 sourcefile~general.f90->sourcefile~nodeinputmanager.f90 sourcefile~general.f90->sourcefile~fluidproperties.f90 sourcefile~general.f90->sourcefile~branchinputmanager.f90 sourcefile~general.f90->sourcefile~curvemanager.f90 sourcefile~general.f90->sourcefile~hvacfancomponent.f90 sourcefile~general.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~general.f90->sourcefile~hvacheatingcoils.f90 sourcefile~general.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~general.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~general.f90->sourcefile~emsmanager.f90 sourcefile~general.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~general.f90->sourcefile~dxcoil.f90 sourcefile~general.f90->sourcefile~heatrecovery.f90 sourcefile~general.f90->sourcefile~watermanager.f90 sourcefile~general.f90->sourcefile~standardratings.f90 sourcefile~general.f90->sourcefile~setpointmanager.f90 sourcefile~general.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~general.f90->sourcefile~vectorutilities.f90 sourcefile~general.f90->sourcefile~photovoltaics.f90 sourcefile~general.f90->sourcefile~windturbine.f90 sourcefile~general.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~general.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~general.f90->sourcefile~plantsolarcollectors.f90 sourcefile~general.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~general.f90->sourcefile~roomairmodelufad.f90 sourcefile~general.f90->sourcefile~poweredinductionunits.f90 sourcefile~general.f90->sourcefile~hvacmixercomponent.f90 sourcefile~dataroomair.f90 DataRoomAir.f90 sourcefile~dataroomair.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataroomair.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataroomair.f90->sourcefile~thermalcomfort.f90 sourcefile~dataroomair.f90->sourcefile~roomairmanager.f90 sourcefile~dataroomair.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataroomair.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataroomair.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataroomair.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataroomair.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataroomair.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataroomair.f90->sourcefile~roomairmodelmundt.f90 sourcefile~datasurfaces.f90 DataSurfaces.f90 sourcefile~datasurfaces.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~datasurfaces.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~datasurfaces.f90->sourcefile~thermalcomfort.f90 sourcefile~datasurfaces.f90->sourcefile~roomairmanager.f90 sourcefile~datasurfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datasurfaces.f90->sourcefile~general.f90 sourcefile~datasurfaces.f90->sourcefile~outputreporttabular.f90 sourcefile~datasurfaces.f90->sourcefile~daylightingdevices.f90 sourcefile~datacontaminantbalance.f90 DataContaminantBalance.f90 sourcefile~datasurfaces.f90->sourcefile~datacontaminantbalance.f90 sourcefile~datasurfaces.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datasurfaces.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~datasurfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasurfaces.f90->sourcefile~ventilatedslab.f90 sourcefile~datasurfaces.f90->sourcefile~datasurfacelists.f90 sourcefile~datasurfaces.f90->sourcefile~emsmanager.f90 sourcefile~datasurfaces.f90->sourcefile~watermanager.f90 sourcefile~datasurfaces.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~datasurfaces.f90->sourcefile~vectorutilities.f90 sourcefile~datasurfaces.f90->sourcefile~photovoltaics.f90 sourcefile~datasurfaces.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~datasurfaces.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~datasurfaces.f90->sourcefile~plantsolarcollectors.f90 sourcefile~datasurfaces.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~datasurfaces.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~datasurfaces.f90->sourcefile~roomairmodelufad.f90 sourcefile~datasurfaces.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~datasurfaces.f90->sourcefile~roomairmodelmundt.f90 sourcefile~dataprecisionglobals.f90 DataPrecisionGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataprecisionglobals.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalsurface.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~thermalcomfort.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datainterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataprecisionglobals.f90->sourcefile~roomairmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalfansys.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datadefineequip.f90 sourcefile~dataprecisionglobals.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazoneenergydemands.f90 sourcefile~dataprecisionglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataprecisionglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~general.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90 DataGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataglobals.f90 sourcefile~dataairflownetwork.f90 DataAirflowNetwork.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairflownetwork.f90 sourcefile~dataprecisionglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputreporttabular.f90 sourcefile~datasizing.f90 DataSizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantwateruse.f90 sourcefile~dataprecisionglobals.f90->sourcefile~refrigeratedcase.f90 sourcefile~datadaylighting.f90 DataDaylighting.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datadaylighting.f90 sourcefile~outputreportpredefined.f90 OutputReportPredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~electricpowermanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataprecisionglobals.f90->sourcefile~daylightingdevices.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataprecisionglobals.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datawater.f90 DataWater.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datawater.f90 sourcefile~dataerrortracking.f90 DataErrorTracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataerrortracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~datacostestimate.f90 DataCostEstimate.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacostestimate.f90 sourcefile~datasystemvariables.f90 DataSystemVariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfacelists.f90 sourcefile~dataprecisionglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataplant.f90 sourcefile~databranchairloopplant.f90 DataBranchAirLoopPlant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataprecisionglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~emsmanager.f90 sourcefile~dataairloop.f90 DataAirLoop.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairloop.f90 sourcefile~dataprecisionglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataairsystems.f90 DataAirSystems.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dxcoil.f90 sourcefile~dataprecisionglobals.f90->sourcefile~heatrecovery.f90 sourcefile~dataprecisionglobals.f90->sourcefile~globalnames.f90 sourcefile~dataprecisionglobals.f90->sourcefile~watermanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~standardratings.f90 sourcefile~dataprecisionglobals.f90->sourcefile~setpointmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataprecisionglobals.f90->sourcefile~vectorutilities.f90 sourcefile~datavectortypes.f90 DataVectorTypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datavectortypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~photovoltaics.f90 sourcefile~dataprecisionglobals.f90->sourcefile~windturbine.f90 sourcefile~dataprecisionglobals.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataphotovoltaics.f90 DataPhotovoltaics.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataphotovoltaics.f90 sourcefile~datagenerators.f90 DataGenerators.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datagenerators.f90 sourcefile~datadaylightingdevices.f90 DataDaylightingDevices.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datadaylightingdevices.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataprecisionglobals.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataprecisionglobals.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataucsdshareddata.f90 DataUCSDSharedData.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataucsdshareddata.f90 sourcefile~dataprecisionglobals.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~roomairmodelmundt.f90 sourcefile~dataprecisionglobals.f90->sourcefile~poweredinductionunits.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacmixercomponent.f90 sourcefile~databsdfwindow.f90 DataBSDFWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~datacomplexfenestration.f90 DataComplexFenestration.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataequivalentlayerwindow.f90 DataEquivalentLayerWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataglobals.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataglobals.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~dataglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataglobals.f90->sourcefile~thermalcomfort.f90 sourcefile~dataglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~dataglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataglobals.f90->sourcefile~roomairmanager.f90 sourcefile~dataglobals.f90->sourcefile~datadefineequip.f90 sourcefile~dataglobals.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~dataglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataglobals.f90->sourcefile~general.f90 sourcefile~dataglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90->sourcefile~dataairflownetwork.f90 sourcefile~dataglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~outputreporttabular.f90 sourcefile~dataglobals.f90->sourcefile~datasizing.f90 sourcefile~dataglobals.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataglobals.f90->sourcefile~plantwateruse.f90 sourcefile~dataglobals.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataglobals.f90->sourcefile~datadaylighting.f90 sourcefile~dataglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataglobals.f90->sourcefile~electricpowermanager.f90 sourcefile~dataglobals.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataglobalconstants.f90 DataGlobalConstants.f90 sourcefile~dataglobals.f90->sourcefile~dataglobalconstants.f90 sourcefile~dataglobals.f90->sourcefile~daylightingdevices.f90 sourcefile~dataglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataglobals.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataglobals.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~dataoutputs.f90 DataOutputs.f90 sourcefile~dataglobals.f90->sourcefile~dataoutputs.f90 sourcefile~dataglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataglobals.f90->sourcefile~datawater.f90 sourcefile~dataglobals.f90->sourcefile~ventilatedslab.f90 sourcefile~dataglobals.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~dataglobals.f90->sourcefile~datacostestimate.f90 sourcefile~sortandstringutilities.f90 SortAndStringUtilities.f90 sourcefile~dataglobals.f90->sourcefile~sortandstringutilities.f90 sourcefile~dataglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataglobals.f90->sourcefile~datasurfacelists.f90 sourcefile~dataglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataglobals.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~dataplant.f90 sourcefile~dataglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~fluidproperties.f90 sourcefile~databranchnodeconnections.f90 DataBranchNodeConnections.f90 sourcefile~dataglobals.f90->sourcefile~databranchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataglobals.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataglobals.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataglobals.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataglobals.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~dataglobals.f90->sourcefile~emsmanager.f90 sourcefile~dataglobals.f90->sourcefile~dataairloop.f90 sourcefile~dataglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataglobals.f90->sourcefile~dxcoil.f90 sourcefile~dataglobals.f90->sourcefile~heatrecovery.f90 sourcefile~dataglobals.f90->sourcefile~globalnames.f90 sourcefile~dataglobals.f90->sourcefile~watermanager.f90 sourcefile~dataglobals.f90->sourcefile~standardratings.f90 sourcefile~dataglobals.f90->sourcefile~setpointmanager.f90 sourcefile~dataglobals.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataglobals.f90->sourcefile~vectorutilities.f90 sourcefile~dataglobals.f90->sourcefile~photovoltaics.f90 sourcefile~dataglobals.f90->sourcefile~windturbine.f90 sourcefile~dataglobals.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataglobals.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataglobals.f90->sourcefile~dataphotovoltaics.f90 sourcefile~dataglobals.f90->sourcefile~datagenerators.f90 sourcefile~dataglobals.f90->sourcefile~datadaylightingdevices.f90 sourcefile~dataglobals.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataglobals.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataglobals.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~dataglobals.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataglobals.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~dataglobals.f90->sourcefile~roomairmodelmundt.f90 sourcefile~dataglobals.f90->sourcefile~poweredinductionunits.f90 sourcefile~dataglobals.f90->sourcefile~hvacmixercomponent.f90 sourcefile~dataglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataairflownetwork.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~dataairflownetwork.f90->sourcefile~roomairmanager.f90 sourcefile~dataairflownetwork.f90->sourcefile~outputreporttabular.f90 sourcefile~dataairflownetwork.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataairflownetwork.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataairflownetwork.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~inputprocessor.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~inputprocessor.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~inputprocessor.f90->sourcefile~datazoneequipment.f90 sourcefile~inputprocessor.f90->sourcefile~thermalcomfort.f90 sourcefile~inputprocessor.f90->sourcefile~roomairmanager.f90 sourcefile~inputprocessor.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~inputprocessor.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90->sourcefile~schedulemanager.f90 sourcefile~inputprocessor.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90->sourcefile~outputreporttabular.f90 sourcefile~inputprocessor.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~inputprocessor.f90->sourcefile~plantwateruse.f90 sourcefile~inputprocessor.f90->sourcefile~refrigeratedcase.f90 sourcefile~inputprocessor.f90->sourcefile~electricpowermanager.f90 sourcefile~inputprocessor.f90->sourcefile~electricpowergenerators.f90 sourcefile~inputprocessor.f90->sourcefile~dataglobalconstants.f90 sourcefile~inputprocessor.f90->sourcefile~daylightingdevices.f90 sourcefile~inputprocessor.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~inputprocessor.f90->sourcefile~outputprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~inputprocessor.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~inputprocessor.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~inputprocessor.f90->sourcefile~ventilatedslab.f90 sourcefile~inputprocessor.f90->sourcefile~pollutionanalysismodule.f90 sourcefile~inputprocessor.f90->sourcefile~datasurfacelists.f90 sourcefile~inputprocessor.f90->sourcefile~branchnodeconnections.f90 sourcefile~inputprocessor.f90->sourcefile~dataplant.f90 sourcefile~inputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~fluidproperties.f90 sourcefile~inputprocessor.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~curvemanager.f90 sourcefile~inputprocessor.f90->sourcefile~hvacfancomponent.f90 sourcefile~inputprocessor.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~inputprocessor.f90->sourcefile~hvacheatingcoils.f90 sourcefile~inputprocessor.f90->sourcefile~outairnodemanager.f90 sourcefile~inputprocessor.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~inputprocessor.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~inputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~inputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~dxcoil.f90 sourcefile~inputprocessor.f90->sourcefile~heatrecovery.f90 sourcefile~inputprocessor.f90->sourcefile~globalnames.f90 sourcefile~inputprocessor.f90->sourcefile~watermanager.f90 sourcefile~inputprocessor.f90->sourcefile~setpointmanager.f90 sourcefile~inputprocessor.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~inputprocessor.f90->sourcefile~photovoltaics.f90 sourcefile~inputprocessor.f90->sourcefile~windturbine.f90 sourcefile~inputprocessor.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~inputprocessor.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~inputprocessor.f90->sourcefile~plantsolarcollectors.f90 sourcefile~inputprocessor.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~inputprocessor.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~inputprocessor.f90->sourcefile~roomairmodelufad.f90 sourcefile~inputprocessor.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~inputprocessor.f90->sourcefile~roomairmodelmundt.f90 sourcefile~inputprocessor.f90->sourcefile~poweredinductionunits.f90 sourcefile~inputprocessor.f90->sourcefile~hvacmixercomponent.f90 sourcefile~outputreporttabular.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~outputreporttabular.f90->sourcefile~thermalcomfort.f90 sourcefile~outputreporttabular.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~datasizing.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~datasizing.f90->sourcefile~datazoneequipment.f90 sourcefile~datasizing.f90->sourcefile~inputprocessor.f90 sourcefile~datasizing.f90->sourcefile~outputreporttabular.f90 sourcefile~datasizing.f90->sourcefile~electricpowergenerators.f90 sourcefile~datasizing.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datasizing.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~datasizing.f90->sourcefile~ventilatedslab.f90 sourcefile~datasizing.f90->sourcefile~plantutilities.f90 sourcefile~datasizing.f90->sourcefile~dataplant.f90 sourcefile~datasizing.f90->sourcefile~branchinputmanager.f90 sourcefile~datasizing.f90->sourcefile~hvacfancomponent.f90 sourcefile~datasizing.f90->sourcefile~hvacheatingcoils.f90 sourcefile~datasizing.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datasizing.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~datasizing.f90->sourcefile~dxcoil.f90 sourcefile~datasizing.f90->sourcefile~heatrecovery.f90 sourcefile~datasizing.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~datasizing.f90->sourcefile~roomairmodelufad.f90 sourcefile~datasizing.f90->sourcefile~poweredinductionunits.f90 sourcefile~plantpipeheattransfer.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~plantwateruse.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~refrigeratedcase.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~refrigeratedcase.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~refrigeratedcase.f90->sourcefile~hvacheatingcoils.f90 sourcefile~datadaylighting.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~datadaylighting.f90->sourcefile~daylightingdevices.f90 sourcefile~outputreportpredefined.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~outputreportpredefined.f90->sourcefile~thermalcomfort.f90 sourcefile~outputreportpredefined.f90->sourcefile~outputreporttabular.f90 sourcefile~outputreportpredefined.f90->sourcefile~electricpowermanager.f90 sourcefile~outputreportpredefined.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~outputreportpredefined.f90->sourcefile~outputprocessor.f90 sourcefile~outputreportpredefined.f90->sourcefile~exteriorenergyusemanager.f90 sourcefile~outputreportpredefined.f90->sourcefile~reportsizingmanager.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacfancomponent.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacheatingcoils.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~outputreportpredefined.f90->sourcefile~dxcoil.f90 sourcefile~outputreportpredefined.f90->sourcefile~standardratings.f90 sourcefile~outputreportpredefined.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~electricpowermanager.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~electricpowermanager.f90->sourcefile~outputreporttabular.f90 sourcefile~electricpowergenerators.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~electricpowergenerators.f90->sourcefile~electricpowermanager.f90 sourcefile~dataglobalconstants.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~dataglobalconstants.f90->sourcefile~outputreporttabular.f90 sourcefile~dataglobalconstants.f90->sourcefile~electricpowermanager.f90 sourcefile~dataglobalconstants.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataglobalconstants.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobalconstants.f90->sourcefile~photovoltaics.f90 sourcefile~dataglobalconstants.f90->sourcefile~windturbine.f90 sourcefile~daylightingdevices.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~datacontaminantbalance.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~datacontaminantbalance.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~nodeinputmanager.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacfancomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacheatingcoils.f90 sourcefile~datacontaminantbalance.f90->sourcefile~outairnodemanager.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~dxcoil.f90 sourcefile~datacontaminantbalance.f90->sourcefile~heatrecovery.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacmixercomponent.f90 sourcefile~plantwaterthermaltank.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~outputprocessor.f90->sourcefile~outputreporttabular.f90 sourcefile~outputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~outputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~outputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~radiantsystemlowtemp.f90->sourcefile~outputreporttabular.f90 sourcefile~exteriorenergyusemanager.f90->sourcefile~outputreporttabular.f90 sourcefile~dataoutputs.f90->sourcefile~inputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~outputreporttabular.f90 sourcefile~dataoutputs.f90->sourcefile~outputprocessor.f90 sourcefile~datashadowingcombinations.f90 DataShadowingCombinations.f90 sourcefile~datashadowingcombinations.f90->sourcefile~outputreporttabular.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~outputreporttabular.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~outputprocessor.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~reportsizingmanager.f90 sourcefile~datawater.f90->sourcefile~outputreporttabular.f90 sourcefile~datawater.f90->sourcefile~plantwateruse.f90 sourcefile~datawater.f90->sourcefile~refrigeratedcase.f90 sourcefile~datawater.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datawater.f90->sourcefile~dxcoil.f90 sourcefile~datawater.f90->sourcefile~watermanager.f90 sourcefile~dataerrortracking.f90->sourcefile~roomairmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~outputreporttabular.f90 sourcefile~dataerrortracking.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~branchinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~dataerrortracking.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~ventilatedslab.f90->sourcefile~outputreporttabular.f90 sourcefile~pollutionanalysismodule.f90->sourcefile~outputreporttabular.f90 sourcefile~datacostestimate.f90->sourcefile~outputreporttabular.f90 sourcefile~datastringglobals.f90 DataStringGlobals.f90 sourcefile~datastringglobals.f90->sourcefile~schedulemanager.f90 sourcefile~datastringglobals.f90->sourcefile~general.f90 sourcefile~datastringglobals.f90->sourcefile~inputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~outputreporttabular.f90 sourcefile~datastringglobals.f90->sourcefile~outputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datastringglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~sortandstringutilities.f90->sourcefile~inputprocessor.f90 sourcefile~sortandstringutilities.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~schedulemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~inputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~daylightingdevices.f90 sourcefile~datasystemvariables.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasystemvariables.f90->sourcefile~curvemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~plantutilities.f90->sourcefile~plantwateruse.f90 sourcefile~plantutilities.f90->sourcefile~refrigeratedcase.f90 sourcefile~plantutilities.f90->sourcefile~electricpowergenerators.f90 sourcefile~plantutilities.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~plantutilities.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~plantutilities.f90->sourcefile~ventilatedslab.f90 sourcefile~plantutilities.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~plantutilities.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~plantutilities.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~plantutilities.f90->sourcefile~plantsolarcollectors.f90 sourcefile~plantutilities.f90->sourcefile~poweredinductionunits.f90 sourcefile~datasurfacelists.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~datasurfacelists.f90->sourcefile~ventilatedslab.f90 sourcefile~reportsizingmanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~reportsizingmanager.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~reportsizingmanager.f90->sourcefile~ventilatedslab.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacheatingcoils.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~reportsizingmanager.f90->sourcefile~dxcoil.f90 sourcefile~reportsizingmanager.f90->sourcefile~heatrecovery.f90 sourcefile~reportsizingmanager.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~reportsizingmanager.f90->sourcefile~roomairmodelufad.f90 sourcefile~reportsizingmanager.f90->sourcefile~poweredinductionunits.f90 sourcefile~branchnodeconnections.f90->sourcefile~datazoneequipment.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantwateruse.f90 sourcefile~branchnodeconnections.f90->sourcefile~refrigeratedcase.f90 sourcefile~branchnodeconnections.f90->sourcefile~electricpowergenerators.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~branchnodeconnections.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~branchnodeconnections.f90->sourcefile~ventilatedslab.f90 sourcefile~branchnodeconnections.f90->sourcefile~nodeinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~branchinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacfancomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacheatingcoils.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~dxcoil.f90 sourcefile~branchnodeconnections.f90->sourcefile~heatrecovery.f90 sourcefile~branchnodeconnections.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantsolarcollectors.f90 sourcefile~branchnodeconnections.f90->sourcefile~poweredinductionunits.f90 sourcefile~dataplant.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~dataplant.f90->sourcefile~plantwateruse.f90 sourcefile~dataplant.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataplant.f90->sourcefile~electricpowermanager.f90 sourcefile~dataplant.f90->sourcefile~electricpowergenerators.f90 sourcefile~dataplant.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataplant.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~dataplant.f90->sourcefile~ventilatedslab.f90 sourcefile~dataplant.f90->sourcefile~plantutilities.f90 sourcefile~dataplant.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataplant.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~dataplant.f90->sourcefile~dataairsystems.f90 sourcefile~dataplant.f90->sourcefile~standardratings.f90 sourcefile~dataplant.f90->sourcefile~setpointmanager.f90 sourcefile~dataplant.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataplant.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataplant.f90->sourcefile~poweredinductionunits.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~databranchairloopplant.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantutilities.f90 sourcefile~databranchairloopplant.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~curvemanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~databranchairloopplant.f90->sourcefile~standardratings.f90 sourcefile~nodeinputmanager.f90->sourcefile~datazoneequipment.f90 sourcefile~nodeinputmanager.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantwateruse.f90 sourcefile~nodeinputmanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~nodeinputmanager.f90->sourcefile~electricpowergenerators.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~nodeinputmanager.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~nodeinputmanager.f90->sourcefile~ventilatedslab.f90 sourcefile~nodeinputmanager.f90->sourcefile~branchinputmanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacheatingcoils.f90 sourcefile~nodeinputmanager.f90->sourcefile~outairnodemanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~dxcoil.f90 sourcefile~nodeinputmanager.f90->sourcefile~heatrecovery.f90 sourcefile~nodeinputmanager.f90->sourcefile~setpointmanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantsolarcollectors.f90 sourcefile~nodeinputmanager.f90->sourcefile~poweredinductionunits.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacmixercomponent.f90 sourcefile~fluidproperties.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~fluidproperties.f90->sourcefile~refrigeratedcase.f90 sourcefile~fluidproperties.f90->sourcefile~electricpowergenerators.f90 sourcefile~fluidproperties.f90->sourcefile~daylightingdevices.f90 sourcefile~fluidproperties.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~fluidproperties.f90->sourcefile~radiantsystemlowtemp.f90 sourcefile~fluidproperties.f90->sourcefile~ventilatedslab.f90 sourcefile~fluidproperties.f90->sourcefile~plantutilities.f90 sourcefile~fluidproperties.f90->sourcefile~nodeinputmanager.f90 sourcefile~fluidproperties.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~fluidproperties.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~fluidproperties.f90->sourcefile~standardratings.f90 sourcefile~fluidproperties.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~fluidproperties.f90->sourcefile~plantsolarcollectors.f90 sourcefile~fluidproperties.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~fluidproperties.f90->sourcefile~poweredinductionunits.f90 sourcefile~databranchnodeconnections.f90->sourcefile~branchnodeconnections.f90 sourcefile~databranchnodeconnections.f90->sourcefile~dxcoil.f90 sourcefile~branchinputmanager.f90->sourcefile~dataplant.f90 sourcefile~curvemanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~curvemanager.f90->sourcefile~electricpowermanager.f90 sourcefile~curvemanager.f90->sourcefile~electricpowergenerators.f90 sourcefile~curvemanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~curvemanager.f90->sourcefile~branchinputmanager.f90 sourcefile~curvemanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~curvemanager.f90->sourcefile~hvacheatingcoils.f90 sourcefile~curvemanager.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~curvemanager.f90->sourcefile~dxcoil.f90 sourcefile~curvemanager.f90->sourcefile~standardratings.f90 sourcefile~curvemanager.f90->sourcefile~setpointmanager.f90 sourcefile~curvemanager.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~hvacfancomponent.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~hvacfancomponent.f90->sourcefile~ventilatedslab.f90 sourcefile~hvacfancomponent.f90->sourcefile~dxcoil.f90 sourcefile~hvacfancomponent.f90->sourcefile~poweredinductionunits.f90 sourcefile~hvachxassistedcoolingcoil.f90->sourcefile~ventilatedslab.f90 sourcefile~hvacheatingcoils.f90->sourcefile~ventilatedslab.f90 sourcefile~hvacheatingcoils.f90->sourcefile~poweredinductionunits.f90 sourcefile~outairnodemanager.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~outairnodemanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~outairnodemanager.f90->sourcefile~electricpowergenerators.f90 sourcefile~outairnodemanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~outairnodemanager.f90->sourcefile~ventilatedslab.f90 sourcefile~outairnodemanager.f90->sourcefile~emsmanager.f90 sourcefile~outairnodemanager.f90->sourcefile~dxcoil.f90 sourcefile~outairnodemanager.f90->sourcefile~setpointmanager.f90 sourcefile~hvacwatercoilcomponent.f90->sourcefile~ventilatedslab.f90 sourcefile~hvacwatercoilcomponent.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~hvacwatercoilcomponent.f90->sourcefile~poweredinductionunits.f90 sourcefile~hvacsteamcoilcomponent.f90->sourcefile~ventilatedslab.f90 sourcefile~hvacsteamcoilcomponent.f90->sourcefile~poweredinductionunits.f90 sourcefile~emsmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~emsmanager.f90->sourcefile~hvacheatingcoils.f90 sourcefile~emsmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~emsmanager.f90->sourcefile~dxcoil.f90 sourcefile~emsmanager.f90->sourcefile~heatrecovery.f90 sourcefile~emsmanager.f90->sourcefile~setpointmanager.f90 sourcefile~emsmanager.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~emsmanager.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~dataairloop.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataairloop.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataairloop.f90->sourcefile~emsmanager.f90 sourcefile~dataairloop.f90->sourcefile~dxcoil.f90 sourcefile~dataairloop.f90->sourcefile~setpointmanager.f90 sourcefile~dataairloop.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~runtimelanguageprocessor.f90->sourcefile~emsmanager.f90 sourcefile~dataairsystems.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dataairsystems.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataairsystems.f90->sourcefile~emsmanager.f90 sourcefile~dataairsystems.f90->sourcefile~dxcoil.f90 sourcefile~dataairsystems.f90->sourcefile~setpointmanager.f90 sourcefile~dataairsystems.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~dataruntimelanguage.f90->sourcefile~general.f90 sourcefile~dataruntimelanguage.f90->sourcefile~emsmanager.f90 sourcefile~dataruntimelanguage.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dxcoil.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dxcoil.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dxcoil.f90->sourcefile~hvacheatingcoils.f90 sourcefile~dxcoil.f90->sourcefile~heatrecovery.f90 sourcefile~heatrecovery.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~globalnames.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~globalnames.f90->sourcefile~hvacheatingcoils.f90 sourcefile~globalnames.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~globalnames.f90->sourcefile~hvacsteamcoilcomponent.f90 sourcefile~globalnames.f90->sourcefile~dxcoil.f90 sourcefile~watermanager.f90->sourcefile~plantwateruse.f90 sourcefile~watermanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~watermanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~watermanager.f90->sourcefile~dxcoil.f90 sourcefile~standardratings.f90->sourcefile~dxcoil.f90 sourcefile~setpointmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~heatbalanceconvectioncoeffs.f90->sourcefile~plantpipeheattransfer.f90 sourcefile~heatbalanceconvectioncoeffs.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~heatbalanceconvectioncoeffs.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~heatbalanceconvectioncoeffs.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~heatbalanceconvectioncoeffs.f90->sourcefile~roomairmodelufad.f90 sourcefile~heatbalanceconvectioncoeffs.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~vectorutilities.f90->sourcefile~daylightingdevices.f90 sourcefile~vectorutilities.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~datavectortypes.f90->sourcefile~dataheatbalance.f90 sourcefile~datavectortypes.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90->sourcefile~heatbalanceconvectioncoeffs.f90 sourcefile~datavectortypes.f90->sourcefile~vectorutilities.f90 sourcefile~datavectortypes.f90->sourcefile~hvactranspiredcollector.f90 sourcefile~datavectortypes.f90->sourcefile~databsdfwindow.f90 sourcefile~photovoltaics.f90->sourcefile~electricpowermanager.f90 sourcefile~windturbine.f90->sourcefile~electricpowermanager.f90 sourcefile~photovoltaicthermalcollectors.f90->sourcefile~photovoltaics.f90 sourcefile~hvactranspiredcollector.f90->sourcefile~photovoltaics.f90 sourcefile~dataphotovoltaics.f90->sourcefile~photovoltaics.f90 sourcefile~dataphotovoltaics.f90->sourcefile~photovoltaicthermalcollectors.f90 sourcefile~datagenerators.f90->sourcefile~electricpowergenerators.f90 sourcefile~datagenerators.f90->sourcefile~windturbine.f90 sourcefile~datadaylightingdevices.f90->sourcefile~daylightingdevices.f90 sourcefile~plantsolarcollectors.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~roomairmodelcrossvent.f90->sourcefile~roomairmanager.f90 sourcefile~roomairmodelusertemppattern.f90->sourcefile~roomairmanager.f90 sourcefile~roomairmodelufad.f90->sourcefile~roomairmanager.f90 sourcefile~dataucsdshareddata.f90->sourcefile~roomairmanager.f90 sourcefile~dataucsdshareddata.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~dataucsdshareddata.f90->sourcefile~roomairmodelufad.f90 sourcefile~dataucsdshareddata.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~roomairmodeldisplacementvent.f90->sourcefile~roomairmanager.f90 sourcefile~roomairmodelmundt.f90->sourcefile~roomairmanager.f90 sourcefile~poweredinductionunits.f90->sourcefile~zoneplenumcomponent.f90 sourcefile~hvacmixercomponent.f90->sourcefile~poweredinductionunits.f90 sourcefile~databsdfwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90->sourcefile~datasurfaces.f90 sourcefile~datacomplexfenestration.f90->sourcefile~dataheatbalance.f90 sourcefile~dataequivalentlayerwindow.f90->sourcefile~dataheatbalance.f90
Help

Files Dependent On This One

sourcefile~~zonetemppredictorcorrector.f90~~AfferentGraph sourcefile~zonetemppredictorcorrector.f90 ZoneTempPredictorCorrector.f90 sourcefile~zonecontaminantpredictorcorrector.f90 ZoneContaminantPredictorCorrector.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~zonecontaminantpredictorcorrector.f90 sourcefile~zoneequipmentmanager.f90 Zoneequipmentmanager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~simulationmanager.f90 SimulationManager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~simulationmanager.f90 sourcefile~hvacmanager.f90 HVACManager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~hvacmanager.f90 sourcefile~zonecontaminantpredictorcorrector.f90->sourcefile~simulationmanager.f90 sourcefile~zonecontaminantpredictorcorrector.f90->sourcefile~hvacmanager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~hvacmanager.f90 sourcefile~sizingmanager.f90 SizingManager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~sizingmanager.f90 sourcefile~energyplus.f90 EnergyPlus.f90 sourcefile~simulationmanager.f90->sourcefile~energyplus.f90 sourcefile~utilityroutines.f90 UtilityRoutines.f90 sourcefile~simulationmanager.f90->sourcefile~utilityroutines.f90 sourcefile~hvacmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90 HeatBalanceAirManager.f90 sourcefile~hvacmanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~sizingmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancesurfacemanager.f90 HeatBalanceSurfaceManager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancemanager.f90 HeatBalanceManager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~sizingmanager.f90
Help


Source Code

MODULE ZoneTempPredictorCorrector

          ! MODULE INFORMATION:
          !       AUTHOR         Russell D. Taylor
          !       DATE WRITTEN   1997
          !       MODIFIED       Aug 2001(FW): make SNLoadHeatRate public
          !                      Nov 2010  BN(FSEC) added TemperatureAndHumidity Control
          !       RE-ENGINEERED  July 2003 (Peter Graham Ellis)
          !                      July 2006 (BG) added operative temp control
          !                      February 2008 (BG) reworked zone air temp histories

          ! PURPOSE OF THIS MODULE:
          ! This module contains routines to predict and correct zone temperatures.
          !  also includes zone thermostatic controlling
          !  Model the "Air Heat Balance" part of the the "Zone Heat Balance Method."

          ! METHODOLOGY EMPLOYED:
          ! apply model equations for air heat balance solved for zone air temp.
          !    sum up values for the terms (e.g SUMHAT, SUMHA etc. )
          !    "Predict" step is used to get zone loads for HVAC equipment
          !    "correct" step determines zone air temp with available HVAC

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
USE DataPrecisionGlobals
USE DataGlobals
USE DataHVACGlobals
USE DataHeatBalance
USE DataHeatBalFanSys
USE DataEnvironment, ONLY: OutHumRat, OutBaroPress
USE DataZoneEnergyDemands, ONLY: ZoneSysEnergyDemand, ZoneSysMoistureDemand, DeadbandOrSetback, CurDeadbandOrSetback, &
                                  SetBack
USE Psychrometrics
USE DataAirflowNetwork,ONLY:SimulateAirflowNetwork,AirflowNetworkExchangeData,AirflowNetworkZoneExhaustFan, &
                            AirflowNetworkNumOfExhFan,AirflowNetworkFanActivated,AirflowNetworkControlMultizone, &
                            AirflowNetworkControlSimpleADS,AirflowNetworkControlMultiADS
USE DataRoomAirModel
USE DataZoneControls
USE DataInterfaces

IMPLICIT NONE ! Enforce explicit typing of all variables

PRIVATE

          ! MODULE PARAMETER DEFINITIONS:
! Controls for PredictorCorrector
!INTEGER, PUBLIC, PARAMETER :: iGetZoneSetpoints             = 1
!INTEGER, PUBLIC, PARAMETER :: iPredictStep                  = 2
!INTEGER, PUBLIC, PARAMETER :: iCorrectStep                  = 3
!INTEGER, PUBLIC, PARAMETER :: iRevertZoneTimestepHistories  = 4
!INTEGER, PUBLIC, PARAMETER :: iPushZoneTimestepHistories    = 5
!INTEGER, PUBLIC, PARAMETER :: iPushSystemTimestepHistories  = 6

  CHARACTER(len=*), PARAMETER, DIMENSION(4) ::   &
     ValidControlTypes=(/'ThermostatSetpoint:SingleHeating         ', &
                         'ThermostatSetpoint:SingleCooling         ', &
                         'ThermostatSetpoint:SingleHeatingOrCooling', &
                         'ThermostatSetpoint:DualSetpoint          '/)

  CHARACTER(len=*), PARAMETER, DIMENSION(12) :: &
     ValidComfortControlTypes=(/'ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating         ', &
                                'ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling         ', &
                                'ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling', &
                                'ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint          ', &
                                'ThermostatSetpoint:ThermalComfort:Pierce:SingleHeating         ', &
                                'ThermostatSetpoint:ThermalComfort:Pierce:SingleCooling         ', &
                                'ThermostatSetpoint:ThermalComfort:Pierce:SingleHeatingOrCooling', &
                                'ThermostatSetpoint:ThermalComfort:Pierce:DualSetpoint          ', &
                                'ThermostatSetpoint:ThermalComfort:KSU:SingleHeating            ', &
                                'ThermostatSetpoint:ThermalComfort:KSU:SingleCooling            ', &
                                'ThermostatSetpoint:ThermalComfort:KSU:SingleHeatingOrCooling   ', &
                                'ThermostatSetpoint:ThermalComfort:KSU:DualSetpoint             '/)

  CHARACTER(len=*), PARAMETER, DIMENSION(6) ::   &
          cZControlTypes=(/'ZoneControl:Thermostat                       ',    &
                           'ZoneControl:Thermostat:ThermalComfort        ',    &
                           'ZoneControl:Thermostat:OperativeTemperature  ',    &
                           'ZoneControl:Humidistat                       ',    &
                           'ZoneControl:Thermostat:TemperatureAndHumidity',    &
                           'ZoneControl:Thermostat:StagedDualSetpoint    '/)

  INTEGER, PARAMETER :: iZC_TStat=1
  INTEGER, PARAMETER :: iZC_TCTStat=2
  INTEGER, PARAMETER :: iZC_OTTStat=3
  INTEGER, PARAMETER :: iZC_HStat=4
  INTEGER, PARAMETER :: iZC_TandHStat=5
  INTEGER, PARAMETER :: iZC_StagedDual=6
  INTEGER, PARAMETER, DIMENSION(6) ::  &
          iZControlTypes=(/iZC_TStat,iZC_TCTStat,iZC_OTTStat,iZC_HStat,iZC_TandHStat,iZC_StagedDual/)

INTEGER, PARAMETER :: SglHeatSetPoint =1
INTEGER, PARAMETER :: SglCoolSetPoint =2
INTEGER, PARAMETER :: SglHCSetPoint   =3
INTEGER, PARAMETER :: DualSetPoint    =4
INTEGER, PARAMETER :: SglHeatSetPointFanger =1
INTEGER, PARAMETER :: SglCoolSetPointFanger =2
INTEGER, PARAMETER :: SglHCSetPointFanger   =3
INTEGER, PARAMETER :: DualSetPointFanger    =4
INTEGER, PARAMETER :: SglHeatSetPointPierce =5
INTEGER, PARAMETER :: SglCoolSetPointPierce =6
INTEGER, PARAMETER :: SglHCSetPointPierce   =7
INTEGER, PARAMETER :: DualSetPointPierce    =8
INTEGER, PARAMETER :: SglHeatSetPointKSU    =9
INTEGER, PARAMETER :: SglCoolSetPointKSU    =10
INTEGER, PARAMETER :: SglHCSetPointKSU      =11
INTEGER, PARAMETER :: DualSetPointKSU       =12

! Average method parameter with multiple people objects in a zone
INTEGER, PARAMETER :: AverageMethodNum_NO =0 ! No multiple people objects
INTEGER, PARAMETER :: AverageMethodNum_SPE=1 ! Specific people object
INTEGER, PARAMETER :: AverageMethodNum_OBJ=2 ! People object average
INTEGER, PARAMETER :: AverageMethodNum_PEO=3 ! People number average

          ! DERIVED TYPE DEFINITIONS:
TYPE ZoneTempControlType
  CHARACTER(len=MaxNameLength) :: Name                  =' ' ! Name of the zone
  CHARACTER(len=MaxNameLength) :: TempSchedName         =' ' ! Name of the schedule which determines the zone temp setpoint
  INTEGER                      :: TempSchedIndex        =0
  CHARACTER(len=MaxNameLength) :: HeatTempSetptSchedName=' '
  INTEGER                      :: HeatTempSchedIndex    =0
  CHARACTER(len=MaxNameLength) :: CoolTempSetptSchedName=' '
  INTEGER                      :: CoolTempSchedIndex    =0
END TYPE ZoneTempControlType

TYPE ZoneComfortFangerControlType
  CHARACTER(len=MaxNameLength) :: Name                 =' ' ! Name of the zone
  CHARACTER(len=MaxNameLength) :: PMVSchedName         =' ' ! Name of the schedule which determines the zone temp setpoint
  INTEGER                      :: PMVSchedIndex        =0   ! Index to PMV dual set point schedule
  CHARACTER(len=MaxNameLength) :: HeatPMVSetptSchedName=' ' ! Name of PMV heating set point schedule
  INTEGER                      :: HeatPMVSchedIndex    =0   ! Index to PMV heating set point schedule
  CHARACTER(len=MaxNameLength) :: CoolPMVSetptSchedName=' ' ! Name of PMV cooling set point schedule
  INTEGER                      :: CoolPMVSchedIndex    =0   ! INdex to PMV cooling set point schedule
END TYPE ZoneComfortFangerControlType

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! MODULE VARIABLE DECLARATIONS:

TYPE (ZoneTempControlType), ALLOCATABLE, DIMENSION(:) :: SetPointSingleHeating
TYPE (ZoneTempControlType), ALLOCATABLE, DIMENSION(:) :: SetPointSingleCooling
TYPE (ZoneTempControlType), ALLOCATABLE, DIMENSION(:) :: SetPointSingleHeatCool
TYPE (ZoneTempControlType), ALLOCATABLE, DIMENSION(:) :: SetPointDualHeatCool

TYPE (ZoneComfortFangerControlType), ALLOCATABLE, DIMENSION(:) :: SetPointSingleHeatingFanger
TYPE (ZoneComfortFangerControlType), ALLOCATABLE, DIMENSION(:) :: SetPointSingleCoolingFanger
TYPE (ZoneComfortFangerControlType), ALLOCATABLE, DIMENSION(:) :: SetPointSingleHeatCoolFanger
TYPE (ZoneComfortFangerControlType), ALLOCATABLE, DIMENSION(:) :: SetPointDualHeatCoolFanger

INTEGER :: NumSingleTempHeatingControls    =0
INTEGER :: NumSingleTempCoolingControls    =0
INTEGER :: NumSingleTempHeatCoolControls   =0
INTEGER :: NumDualTempHeatCoolControls     =0

! Number of Thermal comfort control types
INTEGER :: NumSingleFangerHeatingControls  =0
INTEGER :: NumSingleFangerCoolingControls  =0
INTEGER :: NumSingleFangerHeatCoolControls =0
INTEGER :: NumDualFangerHeatCoolControls   =0

! Number of zone with staged controlled objects
INTEGER :: NumStageCtrZone                 =0

REAL(r64),DIMENSION(:),ALLOCATABLE  :: ZoneSetPointLast
REAL(r64),DIMENSION(:),ALLOCATABLE  :: TempIndZnLd
REAL(r64),DIMENSION(:),ALLOCATABLE  :: TempDepZnLd
REAL(r64),DIMENSION(:),ALLOCATABLE  :: ZoneAirRelHum  ! Zone relative humidity in percent

! Zone temperature history - used only for oscillation test
REAL(r64),DIMENSION(:,:),ALLOCATABLE ::  ZoneTempHist
REAL(r64),DIMENSION(:),ALLOCATABLE   ::  ZoneTempOscillate
REAL(r64)                       ::  AnyZoneTempOscillate


          ! SUBROUTINE SPECIFICATIONS:
PUBLIC ManageZoneAirUpdates
PRIVATE CorrectZoneAirTemp
PRIVATE PredictSystemLoads
PRIVATE CalcPredictedSystemLoad
PRIVATE CalcZoneAirTempSetpoints
PRIVATE InitZoneAirSetpoints
PRIVATE GetZoneAirSetpoints ! get input routines for all types of zone controls
PRIVATE CorrectZoneHumRat
PRIVATE CalcPredictedHumidityRatio
PRIVATE CalcZoneSums
PUBLIC  VerifyThermostatInZone
PUBLIC DetectOscillatingZoneTemp
PRIVATE CalcZoneComponentLoadSums

PRIVATE CalcZoneAirComfortSetpoints !sets the thermal comfort setpoints
PRIVATE GetComfortSetpoints !
PRIVATE PMVResidual

PUBLIC DownInterpolate4HistoryValues
PRIVATE AdjustAirSetpointsforOpTempCntrl
PRIVATE PushZoneTimestepHistories
PRIVATE PushSystemTimestepHistories
PRIVATE RevertZoneTimestepHistories ! not now being used can remove...
PRIVATE AdjustCoolingSetPointforTempAndHumidityControl ! resets cooling setpoint temp based on high RH

CONTAINS

SUBROUTINE ManageZoneAirUpdates(UpdateType, ZoneTempChange, ShortenTimeStepSys,   &
                                UseZoneTimeStepHistory, PriorTimeStep )

          ! SUBROUTINE INFORMATION
          !       AUTHOR         Russ Taylor
          !       DATE WRITTEN   September 1998
          !       MODIFIED       na
          !       RE-ENGINEERED  Brent Griffith Feb. 2008,  added arguments

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine predicts or corrects the zone air temperature
          ! depending on the simulation status and determines the correct
          ! temperature setpoint for each zone from the schedule manager.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: UpdateType             ! Can be iGetZoneSetpoints, iPredictStep, iCorrectStep
  REAL(r64), INTENT(INOUT) :: ZoneTempChange    ! Temp change in zone air btw previous and current timestep
  LOGICAL, INTENT(IN) :: ShortenTimeStepSys
  LOGICAL, INTENT(IN) :: UseZoneTimeStepHistory      ! if true then use zone timestep history, if false use system time step
  REAL(r64),    INTENT(IN) :: PriorTimeStep  ! the old value for timestep length is passed for possible use in interpolating

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
!unused1208  INTEGER :: zoneloop

  IF (GetZoneAirStatsInputFlag) THEN
    CALL GetZoneAirSetpoints
    GetZoneAirStatsInputFlag = .FALSE.
  END IF

  CALL InitZoneAirSetpoints

  SELECT CASE(UpdateType)

    CASE(iGetZoneSetpoints)
      CALL CalcZoneAirTempSetpoints

    CASE(iPredictStep)
      CALL PredictSystemLoads(ShortenTimeStepSys, UseZoneTimeStepHistory,&
                               PriorTimeStep )

    CASE(iCorrectStep)
      CALL CorrectZoneAirTemp(ZoneTempChange, ShortenTimeStepSys, &
            UseZoneTimeStepHistory, PriorTimeStep)

    CASE (iRevertZoneTimestepHistories)
      Call RevertZoneTimestepHistories

    CASE (iPushZoneTimestepHistories)
      Call PushZoneTimestepHistories

    CASE (iPushSystemTimestepHistories)
      Call PushSystemTimestepHistories

  END SELECT

  RETURN

END SUBROUTINE ManageZoneAirUpdates

SUBROUTINE GetZoneAirSetpoints

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Russell Taylor
          !       DATE WRITTEN   September 1998
          !       MODIFIED       L.Gu, May 2006, B. Griffith June 2006
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine gets the inputs related to thermostatic control.

          ! METHODOLOGY EMPLOYED:
          ! Uses the status flags to trigger events.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataIPShortCuts
  USE InputProcessor
  USE ScheduleManager, ONLY: GetScheduleIndex, CheckScheduleValueMinMax, GetScheduleMinValue, GetScheduleMaxValue,  &
                             CheckScheduleValue
  USE General, ONLY: TrimSigDigits, FindNumberInList, RoundSigDigits, CheckCreatedZoneItemName

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
  CHARACTER(len=*), PARAMETER :: RoutineName='GetZoneAirSetpoints: '

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
  TYPE NeededControlTypes
    LOGICAL, DIMENSION(4) :: MustHave=.false.  ! 4= the four control types
    LOGICAL, DIMENSION(4) :: DidHave =.false.
  END TYPE

  TYPE NeededComfortControlTypes
    LOGICAL, DIMENSION(12) :: MustHave=.false.  ! 4= the four control types
    LOGICAL, DIMENSION(12) :: DidHave =.false.
  END TYPE

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: TempControlledZoneNum      ! The Splitter that you are currently loading input into
  INTEGER :: NumAlphas
  INTEGER :: NumNums
  INTEGER :: SingleTempHeatingControlNum
  INTEGER :: SingleTempCoolingControlNum
  INTEGER :: SingleTempHeatCoolControlNum
  INTEGER :: DualTempHeatCoolControlNum
  INTEGER :: ControlTypeNum
  INTEGER :: IOSTAT
!unused1208  REAL(r64), DIMENSION(2) :: NumArray
!unused1208  CHARACTER(len=MaxNameLength), DIMENSION(29) :: AlphArray
  LOGICAL :: ErrorsFound = .FALSE.
  LOGICAL :: ErrFlag
  LOGICAL :: IsNotOK               ! Flag to verify name
  LOGICAL :: IsBlank               ! Flag for blank name
  INTEGER :: CTIndex
  INTEGER :: HumidControlledZoneNum      ! The Humidity Controller that information is being loaded into
  LOGICAL :: ValidScheduleControlType
  LOGICAL :: ValidRadFractSched          ! check for if radiative fraction schedule has valid numbers
  LOGICAL :: ValidZoneOvercoolRangeSched ! check for if Zone Overcool range schedule has valid numbers
  INTEGER :: TempIndex
  INTEGER :: SchedMin
  INTEGER :: SchedMax
  INTEGER :: ActualZoneNum
  INTEGER :: SchedTypeIndex

  INTEGER :: ComfortControlledZoneNum      ! The Splitter that you are currently loading input into
  INTEGER :: I, IZoneCount

  INTEGER :: OpTempContrlNum  ! do loop index
  INTEGER :: found

  INTEGER :: TempHumidityCntrlNum   ! do loop index for overcooled controlled zone

  INTEGER :: SingleFangerHeatingControlNum
  INTEGER :: SingleFangerCoolingControlNum
  INTEGER :: SingleFangerHeatCoolControlNum
  INTEGER :: DualFangerHeatCoolControlNum
  INTEGER :: ComfortIndex
  INTEGER :: ZoneAssigned

  INTEGER :: NumStageControlledZones ! Number of staged controlled objects
  INTEGER :: StageControlledZoneNum  ! Index for staged controlled zones

  TYPE (NeededControlTypes), ALLOCATABLE, DIMENSION(:) :: TStatControlTypes
  TYPE (NeededComfortControlTypes), ALLOCATABLE, DIMENSION(:) :: TComfortControlTypes
  INTEGER, ALLOCATABLE, DIMENSION(:) :: CTSchedMapToControlledZone
  INTEGER, ALLOCATABLE, DIMENSION(:) :: CCmSchedMapToControlledZone
  INTEGER :: Item
  INTEGER :: Item1
  INTEGER :: ZLItem

          ! FLOW:
  cCurrentModuleObject=cZControlTypes(iZC_TStat)
  NumTStatStatements = GetNumObjectsFound(cCurrentModuleObject)
  ALLOCATE(TStatObjects(NumTStatStatements))

! Pre-scan for use of Zone lists in TStat statements (i.e. Global application of TStat)
  NumTempControlledZones=0
  DO Item=1,NumTStatStatements
    CALL GetObjectItem(cCurrentModuleObject,Item,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),TStatObjects%Name,Item-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    TStatObjects(Item)%Name=cAlphaArgs(1)
    Item1=FindItemInList(cAlphaArgs(2),Zone%Name,NumOfZones)
    ZLItem=0
    IF (Item1 == 0 .and. NumOfZoneLists > 0) &
        ZLItem=FindItemInList(cAlphaArgs(2),ZoneList%Name,NumOfZoneLists)
    IF (Item1 > 0) THEN
      TStatObjects(Item)%TempControlledZoneStartPtr=NumTempControlledZones+1
      NumTempControlledZones=NumTempControlledZones+1
      TStatObjects(Item)%NumOfZones=1
      TStatObjects(Item)%ZoneListActive=.false.
      TStatObjects(Item)%ZoneOrZoneListPtr=Item1
    ELSEIF (ZLItem > 0) THEN
      TStatObjects(Item)%TempControlledZoneStartPtr=NumTempControlledZones+1
      NumTempControlledZones=NumTempControlledZones+ZoneList(ZLItem)%NumOfZones
      TStatObjects(Item)%NumOfZones=ZoneList(ZLItem)%NumOfZones
      TStatObjects(Item)%ZoneListActive=.true.
      TStatObjects(Item)%ZoneOrZoneListPtr=ZLItem
    ELSE
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound=.true.
    ENDIF
  ENDDO

  IF (ErrorsFound) THEN
    CALL ShowSevereError('GetZoneAirSetpoints: Errors with invalid names in '//trim(cCurrentModuleObject)//  &
       ' objects.')
    CALL ShowContinueError('...These will not be read in.  Other errors may occur.')
    NumTempControlledZones=0
  ENDIF

  IF (NumTempControlledZones > 0) THEN
    ALLOCATE(TempControlledZone(NumTempControlledZones))
    ALLOCATE(TStatControlTypes(NumTempControlledZones))  ! Number of set point types
    ALLOCATE(CTSchedMapToControlledZone(NumTempControlledZones))
    CTSchedMapToControlledZone=0

    TempControlledZoneNum = 0
    DO Item = 1, NumTStatStatements
      CALL GetObjectItem(cCurrentModuleObject,Item,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                         NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                         AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      DO Item1=1,TStatObjects(Item)%NumOfZones
        TempControlledZoneNum=TempControlledZoneNum+1
        IF (TStatObjects(Item)%ZoneListActive) THEN
          cAlphaArgs(2)=Zone(ZoneList(TStatObjects(Item)%ZoneOrZoneListPtr)%Zone(Item1))%Name
        ENDIF
        ZoneAssigned=FindItemInList(cAlphaArgs(2),TempControlledZone%ZoneName,TempControlledZoneNum-1)
        IF (ZoneAssigned == 0) THEN
          TempControlledZone(TempControlledZoneNum)%ZoneName = cAlphaArgs(2)
          TempControlledZone(TempControlledZoneNum)%ActualZoneNum = FindIteminList(cAlphaArgs(2),Zone%Name,NumOfZones)
          IF (TempControlledZone(TempControlledZoneNum)%ActualZoneNum == 0) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
               trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
            ErrorsFound = .TRUE.
          ELSE
            Zone(TempControlledZone(TempControlledZoneNum)%ActualZoneNum)%TempControlledZoneIndex = TempControlledZoneNum
          END IF
        ELSE
          TempControlledZone(TempControlledZoneNum)%ZoneName = cAlphaArgs(2)  ! for continuity
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
             trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" zone previously assigned.')
          CALL ShowContinueError('...Zone was previously assigned to Thermostat="'//  &
             trim(TempControlledZone(ZoneAssigned)%Name)//'".')
          ErrorsFound = .TRUE.
          CYCLE
        ENDIF

        IF (.not. TStatObjects(Item)%ZoneListActive) THEN
          TempControlledZone(TempControlledZoneNum)%Name = cAlphaArgs(1)
        ELSE
          CALL CheckCreatedZoneItemName(RoutineName,cCurrentModuleObject,  &
                                        Zone(ZoneList(TStatObjects(Item)%ZoneOrZoneListPtr)%Zone(Item1))%Name,  &
                                        ZoneList(TStatObjects(Item)%ZoneOrZoneListPtr)%MaxZoneNameLength,  &
                                        TStatObjects(Item)%Name,     &
                                        TempControlledZone%Name,           &
                                        TempControlledZoneNum-1,                       &
                                        TempControlledZone(TempControlledZoneNum)%Name,            &
                                        ErrFlag)
          IF (ErrFlag) ErrorsFound=.true.
        ENDIF

        TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName = cAlphaArgs(3)
        TempControlledZone(TempControlledZoneNum)%CTSchedIndex=GetScheduleIndex(cAlphaArgs(3))
        IF (Item1 == 1) THEN  ! only show error on first of several if zone list
          IF (TempControlledZone(TempControlledZoneNum)%CTSchedIndex == 0) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
               trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
            ErrorsFound = .TRUE.
          ELSE
            ! Check validity of control types.
            ValidScheduleControlType=CheckScheduleValueMinMax(TempControlledZone(TempControlledZoneNum)%CTSchedIndex,  &
                                                               '>=',0.0d0,'<=',4.0d0)
            IF (.not. ValidScheduleControlType) THEN
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid range '//  &
                 trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'"')
              CALL ShowContinueError('..contains values outside of range [0,4].')
              ErrorsFound=.TRUE.
            ENDIF
          END IF
        ENDIF

        TempControlledZone(TempControlledZoneNum)%NumControlTypes = NINT((NumAlphas - 3.0d0)/2.0d0)
        ALLOCATE(TempControlledZone(TempControlledZoneNum)%ControlType(TempControlledZone(  &
           TempControlledZoneNum)%NumControlTypes))
        ALLOCATE(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempControlledZone(  &
           TempControlledZoneNum)%NumControlTypes))
        ALLOCATE(TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempControlledZone(  &
                                                                                TempControlledZoneNum)%NumControlTypes))

        DO ControlTypeNum = 1, TempControlledZone(TempControlledZoneNum)%NumControlTypes

          TempControlledZone(TempControlledZoneNum)%ControlType(ControlTypeNum) = cAlphaArgs(NINT(2.0d0*ControlTypeNum-1+3))
          TempControlledZone(TempControlledZoneNum)%ControlTypeName(ControlTypeNum) = cAlphaArgs(NINT(2.0d0*ControlTypeNum+3))

          IF (TempControlledZone(TempControlledZoneNum)%ControlType(ControlTypeNum) /= ' ') THEN
            CTIndex=FindItem(TempControlledZone(TempControlledZoneNum)%ControlType(ControlTypeNum),ValidControlTypes,4)
            IF (CTIndex == 0) THEN
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
                 trim(cAlphaFieldNames(NINT(2.0d0*ControlTypeNum-1+3)))//'="'//  &
                    trim(cAlphaArgs(NINT(2.0d0*ControlTypeNum-1+3)))//'"')
              ErrorsFound = .TRUE.
            END IF
          ELSE
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
                 trim(cAlphaFieldNames(NINT(2.0d0*ControlTypeNum-1+3)))//'="<blank>"')
            ErrorsFound = .TRUE.
          ENDIF
          TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(ControlTypeNum) = 0
        END DO
      END DO
    END DO ! NumTStatStatements
  ENDIF ! Check on number of TempControlledZones

  cCurrentModuleObject=ValidControlTypes(SglHeatSetPoint)
  NumSingleTempHeatingControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumSingleTempHeatingControls .GT. 0) ALLOCATE(SetPointSingleHeating(NumSingleTempHeatingControls))

  DO SingleTempHeatingControlNum = 1, NumSingleTempHeatingControls
    CALL GetObjectItem(cCurrentModuleObject,SingleTempHeatingControlNum,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointSingleHeating%Name,SingleTempHeatingControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    SetPointSingleHeating(SingleTempHeatingControlNum)%Name = cAlphaArgs(1)
    SetPointSingleHeating(SingleTempHeatingControlNum)%TempSchedName = cAlphaArgs(2)
    SetPointSingleHeating(SingleTempHeatingControlNum)%TempSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointSingleHeating(SingleTempHeatingControlNum)%TempSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    END IF

  END DO ! SingleTempHeatingControlNum

  cCurrentModuleObject=ValidControlTypes(SglCoolSetPoint)
  NumSingleTempCoolingControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumSingleTempCoolingControls .GT. 0) ALLOCATE(SetPointSingleCooling(NumSingleTempCoolingControls))

  DO SingleTempCoolingControlNum = 1, NumSingleTempCoolingControls
    CALL GetObjectItem(cCurrentModuleObject,SingleTempCoolingControlNum,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointSingleCooling%Name,SingleTempCoolingControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    SetPointSingleCooling(SingleTempCoolingControlNum)%Name = cAlphaArgs(1)
    SetPointSingleCooling(SingleTempCoolingControlNum)%TempSchedName = cAlphaArgs(2)
    SetPointSingleCooling(SingleTempCoolingControlNum)%TempSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointSingleCooling(SingleTempCoolingControlNum)%TempSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    END IF

  END DO ! SingleTempCoolingControlNum

  cCurrentModuleObject=ValidControlTypes(SglHCSetPoint)
  NumSingleTempHeatCoolControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumSingleTempHeatCoolControls .GT. 0) ALLOCATE(SetPointSingleHeatCool(NumSingleTempHeatCoolControls))

  DO SingleTempHeatCoolControlNum = 1, NumSingleTempHeatCoolControls
    CALL GetObjectItem(cCurrentModuleObject,SingleTempHeatCoolControlNum,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    SetPointSingleHeatCool(SingleTempHeatCoolControlNum)%Name = cAlphaArgs(1)
    SetPointSingleHeatCool(SingleTempHeatCoolControlNum)%TempSchedName = cAlphaArgs(2)
    SetPointSingleHeatCool(SingleTempHeatCoolControlNum)%TempSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointSingleHeatCool(SingleTempHeatCoolControlNum)%TempSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    END IF

  END DO ! SingleTempHeatCoolControlNum

  cCurrentModuleObject=ValidControlTypes(DualSetPoint)
  NumDualTempHeatCoolControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumDualTempHeatCoolControls .GT. 0) ALLOCATE(SetPointDualHeatCool(NumDualTempHeatCoolControls))

  DO DualTempHeatCoolControlNum = 1, NumDualTempHeatCoolControls
    CALL GetObjectItem(cCurrentModuleObject,DualTempHeatCoolControlNum,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointDualHeatCool%Name,DualTempHeatCoolControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    SetPointDualHeatCool(DualTempHeatCoolControlNum)%Name = cAlphaArgs(1)
    SetPointDualHeatCool(DualTempHeatCoolControlNum)%HeatTempSetptSchedName = cAlphaArgs(2)
    SetPointDualHeatCool(DualTempHeatCoolControlNum)%HeatTempSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointDualHeatCool(DualTempHeatCoolControlNum)%HeatTempSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    END IF
    SetPointDualHeatCool(DualTempHeatCoolControlNum)%CoolTempSetptSchedName = cAlphaArgs(3)
    SetPointDualHeatCool(DualTempHeatCoolControlNum)%CoolTempSchedIndex = GetScheduleIndex(cAlphaArgs(3))
    IF (SetPointDualHeatCool(DualTempHeatCoolControlNum)%CoolTempSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
      ErrorsFound = .TRUE.
    END IF

  END DO ! DualTempHeatCoolControlNum

 ! Finish filling in Schedule pointing indexes
  DO TempControlledZoneNum = 1, NumTempControlledZones
    TempIndex = FindItem(trim(ValidControlTypes(SglHeatSetPoint)),   &
       TempControlledZone(TempControlledZoneNum)%ControlType,TempControlledZone(TempControlledZoneNum)%NumControlTypes)
    TempControlledZone(TempControlledZoneNum)%SchIndx_SingleHeatSetPoint = TempIndex
    IF (TempIndex > 0) THEN
      TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex) =   &
                           FindItem(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex), &
                                        SetPointSingleHeating%Name, NumSingleTempHeatingControls)
      TStatControlTypes(TempControlledZoneNum)%MustHave(SingleHeatingSetpoint)=.true.
    ENDIF

    TempIndex = FindItem(trim(ValidControlTypes(SglCoolSetPoint)),  &
      TempControlledZone(TempControlledZoneNum)%ControlType,TempControlledZone(TempControlledZoneNum)%NumControlTypes)
    TempControlledZone(TempControlledZoneNum)%SchIndx_SingleCoolSetPoint = TempIndex
    IF (TempIndex > 0) THEN
      TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex) =   &
                           FindItem(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex), &
                                        SetPointSingleCooling%Name, NumSingleTempCoolingControls)
      TStatControlTypes(TempControlledZoneNum)%MustHave(SingleCoolingSetpoint)=.true.
    ENDIF

    TempIndex = FindItem(trim(ValidControlTypes(SglHCSetPoint)),  &
      TempControlledZone(TempControlledZoneNum)%ControlType,TempControlledZone(TempControlledZoneNum)%NumControlTypes)
    TempControlledZone(TempControlledZoneNum)%SchIndx_SingleHeatCoolSetPoint = TempIndex
    IF (TempIndex > 0) THEN
      TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex) =   &
                           FindItem(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex), &
                                        SetPointSingleHeatCool%Name, NumSingleTempHeatCoolControls)
      TStatControlTypes(TempControlledZoneNum)%MustHave(SingleHeatCoolSetPoint)=.true.
    ENDIF

    TempIndex = FindItem(trim(ValidControlTypes(DualSetPoint)),  &
      TempControlledZone(TempControlledZoneNum)%ControlType,TempControlledZone(TempControlledZoneNum)%NumControlTypes)
    TempControlledZone(TempControlledZoneNum)%SchIndx_DualSetPointWDeadBand = TempIndex
    IF (TempIndex > 0) THEN
      TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex) =   &
                           FindItem(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex), &
                                        SetPointDualHeatCool%Name, NumDualTempHeatCoolControls)
      TStatControlTypes(TempControlledZoneNum)%MustHave(DualSetPointWithDeadBand)=.true.
    ENDIF
  ENDDO

  ! Now, Check the schedule values/indices for validity

  DO TempControlledZoneNum = 1, NumTempControlledZones

    ActualZoneNum = TempControlledZone(TempControlledZoneNum)%ActualZoneNum
    CTIndex = TempControlledZone(TempControlledZoneNum)%CTSchedIndex
    IF (CTIndex == 0) CYCLE   ! error will be caught elsewhere
    SchedMin=GetScheduleMinValue(CTIndex)
    SchedMax=GetScheduleMaxValue(CTIndex)

    IF (SchedMin == 0 .and. SchedMax == 0) THEN
      IF (FindNumberInList(CTIndex,CTSchedMapToControlledZone,NumTempControlledZones) == 0) THEN
        CALL ShowSevereError('Control Type Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
        CALL ShowContinueError('..specifies control type 0 for all entries.')
        CALL ShowContinueError('All zones using this Control Type Schedule have no heating or cooling available.')
      ENDIF
      CTSchedMapToControlledZone(TempControlledZoneNum)=CTIndex
    ENDIF

    DO ControlTypeNum=SchedMin,SchedMax

      SELECT CASE (ControlTypeNum)

        CASE (0) ! Uncontrolled

        CASE (SingleHeatingSetPoint)

          TempIndex=TempControlledZone(TempControlledZoneNum)%SchIndx_SingleHeatSetPoint
          TStatControlTypes(TempControlledZoneNum)%DidHave(SingleHeatingSetPoint)=.true.
          IF (TempIndex /= 0) THEN
            SchedTypeIndex = TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//trim(ValidControlTypes(SglHeatSetPoint))//  &
                 ' Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! TempIndex = 0
            IF (CheckScheduleValue(CTIndex,SingleHeatingSetPoint)) THEN
              CALL ShowSevereError('Control Type Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies control type 1 ('//trim(ValidControlTypes(SglHeatSetPoint))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                 TRIM(TempControlledZone(TempControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE (SingleCoolingSetPoint)

          TempIndex = TempControlledZone(TempControlledZoneNum)%SchIndx_SingleCoolSetPoint
          TStatControlTypes(TempControlledZoneNum)%DidHave(SingleCoolingSetPoint)=.true.
          IF (TempIndex /= 0) THEN
            SchedTypeIndex = TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//trim(ValidControlTypes(SglCoolSetPoint))//  &
                 ' Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! TempIndex = 0
            IF (CheckScheduleValue(CTIndex,SingleCoolingSetPoint)) THEN
              CALL ShowSevereError('Control Type Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies control type 2 ('//trim(ValidControlTypes(SglCoolSetPoint))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                 TRIM(TempControlledZone(TempControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE (SingleHeatCoolSetPoint)

          TempIndex = TempControlledZone(TempControlledZoneNum)%SchIndx_SingleHeatCoolSetPoint
          TStatControlTypes(TempControlledZoneNum)%DidHave(SingleHeatCoolSetPoint)=.true.
          IF (TempIndex /= 0) THEN
            SchedTypeIndex = TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//trim(ValidControlTypes(SglHCSetPoint))//  &
                 ' Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! TempIndex = 0
            IF (CheckScheduleValue(CTIndex,SingleHeatCoolSetPoint)) THEN
              CALL ShowSevereError('Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies control type 3 ('//trim(ValidControlTypes(SglHCSetPoint))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                 TRIM(TempControlledZone(TempControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE (DualSetPointWithDeadBand)

          TempIndex = TempControlledZone(TempControlledZoneNum)%SchIndx_DualSetPointWDeadBand
          TStatControlTypes(TempControlledZoneNum)%DidHave(DualSetPointWithDeadBand)=.true.
          IF (TempIndex /= 0) THEN
            SchedTypeIndex = TempControlledZone(TempControlledZoneNum)%ControlTypeSchIndx(TempIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//trim(ValidControlTypes(DualSetPoint))//  &
                 ' Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeName(TempIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! TempIndex = 0
            IF (CheckScheduleValue(CTIndex,DualSetPointWithDeadBand)) THEN
              CALL ShowSevereError('Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies control type 4 ('//trim(ValidControlTypes(DualSetPoint))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                 TRIM(TempControlledZone(TempControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE DEFAULT
          CALL ShowSevereError('GetZoneAirSetpoints: Illegal control type for Zone='//TRIM(Zone(ActualZoneNum)%Name)//  &
                               ', Found value='//TRIM(TrimSigDigits(ControlTypeNum))//', in Schedule='//        &
                               TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('..valid range values are [0,4].')
          ErrorsFound=.true.

      END SELECT
    END DO

  END DO

  DO TempControlledZoneNum = 1, NumTempControlledZones

    ActualZoneNum = TempControlledZone(TempControlledZoneNum)%ActualZoneNum
    CTIndex = TempControlledZone(TempControlledZoneNum)%CTSchedIndex
    IF (CTIndex == 0) CYCLE  ! error caught elsewhere -- would just be confusing here

    DO ControlTypeNum=1,4
      IF (TStatControlTypes(TempControlledZoneNum)%MustHave(ControlTypeNum) .and.  &
          TStatControlTypes(TempControlledZoneNum)%DidHave(ControlTypeNum)) CYCLE

      SELECT CASE (ControlTypeNum)

        CASE (SingleHeatingSetPoint)
          IF (.not. TStatControlTypes(TempControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 1 ('//trim(ValidControlTypes(SglHeatSetPoint))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                   TRIM(TempControlledZone(TempControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))

        CASE (SingleCoolingSetPoint)
          IF (.not. TStatControlTypes(TempControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 2 ('//trim(ValidControlTypes(SglCoolSetPoint))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                   TRIM(TempControlledZone(TempControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))

        CASE (SingleHeatCoolSetPoint)
          IF (.not. TStatControlTypes(TempControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 3 ('//trim(ValidControlTypes(SglHCSetPoint))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                   TRIM(TempControlledZone(TempControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))

        CASE (DualSetPointWithDeadBand)
          IF (.not. TStatControlTypes(TempControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(TempControlledZone(TempControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 4 ('//trim(ValidControlTypes(DualSetPoint))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TStat))//'='//  &
                   TRIM(TempControlledZone(TempControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(TempControlledZone(TempControlledZoneNum)%ZoneName))

        CASE DEFAULT
      END SELECT
    ENDDO
  ENDDO

  IF (ALLOCATED(TStatControlTypes)) DEALLOCATE(TStatControlTypes)
  ! This starts the Humidity Control Get Input section
  cCurrentModuleObject=cZControlTypes(iZC_HStat)
  NumHumidityControlZones = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumHumidityControlZones .GT. 0) ALLOCATE(HumidityControlZone(NumHumidityControlZones))

  DO HumidControlledZoneNum = 1, NumHumidityControlZones
    CALL GetObjectItem(cCurrentModuleObject,HumidControlledZoneNum,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),HumidityControlZone%ControlName,HumidControlledZoneNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    HumidityControlZone(HumidControlledZoneNum)%ControlName = cAlphaArgs(1)
    ! Ensure unique zone name
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(2),HumidityControlZone%ZoneName,HumidControlledZoneNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Zone Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(2) = 'xxxxx'
    END IF

    HumidityControlZone(HumidControlledZoneNum)%ZoneName = cAlphaArgs(2)
    HumidityControlZone(HumidControlledZoneNum)%ActualZoneNum = FindItem(cAlphaArgs(2),Zone%Name,NumOfZones)
    IF (HumidityControlZone(HumidControlledZoneNum)%ActualZoneNum == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    END IF
    HumidityControlZone(HumidControlledZoneNum)%HumidifyingSched = cAlphaArgs(3)
    HumidityControlZone(HumidControlledZoneNum)%HumidifyingSchedIndex = GetScheduleIndex(cAlphaArgs(3))
    IF (HumidityControlZone(HumidControlledZoneNum)%HumidifyingSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
         trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
      ErrorsFound = .TRUE.
    END IF
    If (NumAlphas .eq. 4) Then
      HumidityControlZone(HumidControlledZoneNum)%DehumidifyingSched = cAlphaArgs(4)
      HumidityControlZone(HumidControlledZoneNum)%DehumidifyingSchedIndex = GetScheduleIndex(cAlphaArgs(4))
      IF (HumidityControlZone(HumidControlledZoneNum)%DehumidifyingSchedIndex == 0) THEN
        CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
           trim(cAlphaFieldNames(4))//'="'//trim(cAlphaArgs(4))//'" not found.')
        ErrorsFound = .TRUE.
      END IF
    Else
      HumidityControlZone(HumidControlledZoneNum)%DehumidifyingSched = cAlphaArgs(3)
      HumidityControlZone(HumidControlledZoneNum)%DehumidifyingSchedIndex = GetScheduleIndex(cAlphaArgs(3))
    End If

  END DO ! HumidControlledZoneNum

  ! Start to read Thermal comfort control objects
  cCurrentModuleObject=cZControlTypes(iZC_TCTStat)
  NumComfortTStatStatements = GetNumObjectsFound(cCurrentModuleObject)
  ALLOCATE(ComfortTStatObjects(NumComfortTStatStatements))

! Pre-scan for use of Zone lists in TStat statements (i.e. Global application of TStat)
  NumComfortControlledZones=0
  ErrFlag=.false.
  DO Item=1,NumComfortTStatStatements
    CALL GetObjectItem(cCurrentModuleObject,Item,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    ! will not do much verifying -- that will come later.
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),ComfortTStatObjects%Name,Item-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrFlag = .TRUE.
      ErrorsFound=.true.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    Item1=FindItemInList(cAlphaArgs(2),Zone%Name,NumOfZones)
    ZLItem=0
    IF (Item1 == 0 .and. NumOfZoneLists > 0) &
      ZLItem=FindItemInList(cAlphaArgs(2),ZoneList%Name,NumOfZoneLists)
    ComfortTStatObjects(Item)%Name=cAlphaArgs(1)
    IF (Item1 > 0) THEN
      ComfortTStatObjects(Item)%ComfortControlledZoneStartPtr=NumComfortControlledZones+1
      NumComfortControlledZones=NumComfortControlledZones+1
      ComfortTStatObjects(Item)%NumOfZones=1
      ComfortTStatObjects(Item)%ZoneListActive=.false.
      ComfortTStatObjects(Item)%ZoneOrZoneListPtr=Item1
    ELSEIF (ZLItem > 0) THEN
      ComfortTStatObjects(Item)%ComfortControlledZoneStartPtr=NumComfortControlledZones+1
      NumComfortControlledZones=NumComfortControlledZones+ZoneList(ZLItem)%NumOfZones
      ComfortTStatObjects(Item)%NumOfZones=ZoneList(ZLItem)%NumOfZones
      ComfortTStatObjects(Item)%ZoneListActive=.true.
      ComfortTStatObjects(Item)%ZoneOrZoneListPtr=ZLItem
    ELSE
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrFlag=.true.
      ErrorsFound=.true.
    ENDIF
  ENDDO

  IF (ErrFlag) THEN
    CALL ShowSevereError('GetZoneAirSetpoints: Errors with invalid names in '//trim(cCurrentModuleObject)//  &
       ' objects.')
    CALL ShowContinueError('...These will not be read in.  Other errors may occur.')
    NumComfortControlledZones=0
  ENDIF

  IF (NumComfortControlledZones > 0) THEN
    ALLOCATE(ComfortControlledZone(NumComfortControlledZones))
    ALLOCATE(TComfortControlTypes(NumComfortControlledZones))  ! Number of set point types
    ALLOCATE(CCmSchedMapToControlledZone(NumComfortControlledZones))
    CCmSchedMapToControlledZone=0

    ComfortControlledZoneNum=0
    DO Item = 1, NumComfortTStatStatements
      CALL GetObjectItem(cCurrentModuleObject,Item,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                         NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                         AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      DO Item1=1,ComfortTStatObjects(Item)%NumOfZones
        ComfortControlledZoneNum=ComfortControlledZoneNum+1
        IF (ComfortTStatObjects(Item)%ZoneListActive) THEN
          cAlphaArgs(2)=Zone(ZoneList(ComfortTStatObjects(Item)%ZoneOrZoneListPtr)%Zone(Item1))%Name
        ENDIF
        ZoneAssigned=FindItemInList(cAlphaArgs(2),ComfortControlledZone%ZoneName,ComfortControlledZoneNum-1)
        IF (ZoneAssigned == 0) THEN
          ComfortControlledZone(ComfortControlledZoneNum)%ZoneName = cAlphaArgs(2)
          ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum = FindIteminList(cAlphaArgs(2),Zone%Name,NumOfZones)
          IF (ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum == 0) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
               trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
            ErrorsFound = .TRUE.
          END IF
        ELSE
          ComfortControlledZone(ComfortControlledZoneNum)%ZoneName = cAlphaArgs(2)  ! for continuity
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
             trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" zone previously assigned.')
          CALL ShowContinueError('...Zone was previously assigned to Thermostat="'//  &
             trim(ComfortControlledZone(ZoneAssigned)%Name)//'".')
          ErrorsFound = .TRUE.
          CYCLE
        ENDIF

        IF (.not. ComfortTStatObjects(Item)%ZoneListActive) THEN
          ComfortControlledZone(ComfortControlledZoneNum)%Name = cAlphaArgs(1)
        ELSE
          ComfortControlledZone(ComfortControlledZoneNum)%Name =   &
             trim(Zone(ZoneList(ComfortTStatObjects(Item)%ZoneOrZoneListPtr)%Zone(Item1))%Name)//  &
                ' '//trim(ComfortTStatObjects(Item)%Name)
        ENDIF

        ! Read Fields A3 and A4 for averaging method
        IZoneCount = 0
        Do i=1,TotPeople
          If (ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum == People(I)%ZonePtr) then
            IZoneCount = IZoneCount+1
          End If
        End Do
        ! Could not find a people object for this particular zone
        If (IZoneCount == 0 .and. ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum > 0) then
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' no PEOPLE in '//  &
             trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" - cannot use Comfort Control.')
          ErrorsFound=.true.
        End If
        ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodNum = AverageMethodNum_NO
        If (IZoneCount > 1) then
          ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodName = cAlphaArgs(3)
          If (SameString(cAlphaArgs(3),'SpecificObject')) then
            ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodNum = AverageMethodNum_SPE
          End If
          If (SameString(cAlphaArgs(3),'ObjectAverage')) then
            ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodNum = AverageMethodNum_OBJ
          End If
          If (SameString(cAlphaArgs(3),'PeopleAverage')) then
            ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodNum = AverageMethodNum_PEO
          End If
          If (ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodNum == 0) then
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
             trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'".')
            CALL ShowContinueError('Allowed keys are SpecificObject, ObjectAverage, or PeopleAverage')
            ErrorsFound=.true.
          End If
          If (ComfortControlledZone(ComfortControlledZoneNum)%AverageMethodNum == AverageMethodNum_SPE) then
            ComfortControlledZone(ComfortControlledZoneNum)%AverageObjectName = cAlphaArgs(4)
            If (FindItem(cAlphaArgs(4),People%Name,TotPeople) == 0) then
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
                 trim(cAlphaFieldNames(4))//'="'//trim(cAlphaArgs(4))//'".')
              ErrorsFound=.true.
            Else
              ComfortControlledZone(ComfortControlledZoneNum)%SpecificObjectNum =  &
                                  FindItem(cAlphaArgs(4),People%Name,TotPeople)
            End If
          End If
        Else
          Do i=1,TotPeople
            If (ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum == People(I)%ZonePtr) Exit
          End Do
          ComfortControlledZone(ComfortControlledZoneNum)%SpecificObjectNum = i
        End If
        ! Check values used for thermal comfort calculation
        Do i=1,TotPeople
          If (ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum == People(I)%ZonePtr) then
            ! Check activity level
            If (People(i)%ActivityLevelPtr > 0) then
              ValidScheduleControlType=CheckScheduleValueMinMax( &
                                   People(i)%ActivityLevelPtr, '>=',72.0d0, '<=',909.0d0)
              IF (.not. ValidScheduleControlType) THEN
                CALL ShowSevereError('GetPeople Activity Level: Invalid activity level values entered '// &
                                 'for thermal comfort calculation')
                CALL ShowContinueError('Outside of range values [72,909], Reference object='//TRIM(People(i)%Name))
                ErrorsFound=.TRUE.
              ENDIF
            Else
              CALL ShowSevereError('GetPeople Activity Level: Activity level schedule is not found='//TRIM(People(i)%Name))
              CALL ShowContinueError('Required when the zone has Thermal Comfort Controls.')
              ErrorsFound=.TRUE.
            End If
            ! Check Work Efficiency
            If (People(i)%WorkEffPtr > 0) then
              ValidScheduleControlType=CheckScheduleValueMinMax( &
                                     People(i)%WorkEffPtr, '>=',0.0d0, '<=',1.0d0)
              IF (.not. ValidScheduleControlType) THEN
                CALL ShowSevereError('GetPeople work efficiency: Invalid work efficiency values entered '// &
                                   'for thermal comfort calculation')
                CALL ShowContinueError('Outside of range values [0,1], Reference object='//TRIM(People(i)%Name))
                ErrorsFound=.TRUE.
              ENDIF
            Else
              CALL ShowSevereError('GetPeople work efficiency: Work efficiency schedule is not found='//TRIM(People(i)%Name))
              CALL ShowContinueError('Required when the zone has Thermal Comfort Controls.')
              ErrorsFound=.TRUE.
            End If
            ! Check Clothing Insulation
            If (People(i)%ClothingPtr > 0) then
              ValidScheduleControlType=CheckScheduleValueMinMax( &
                                     People(i)%ClothingPtr, '>',0.0d0, '<=',2.0d0)
              IF (.not. ValidScheduleControlType) THEN
                CALL ShowSevereError('GetPeople Clothing Insulation: Invalid Clothing Insulation values entered '// &
                                   'for thermal comfort calculation')
                CALL ShowContinueError('Outside of range values [0.0,2.0], Reference object='//TRIM(People(i)%Name))
                ErrorsFound=.TRUE.
              ENDIF
            Else
              CALL ShowSevereError('GetPeople Clothing Insulation: Clothing Insulation schedule is not found='//  &
                 TRIM(People(i)%Name))
              CALL ShowContinueError('Required when the zone has Thermal Comfort Controls.')
              ErrorsFound=.TRUE.
            End If
            ! Check Air velocity
            If (People(i)%AirVelocityPtr .LE. 0) then
              CALL ShowSevereError('GetPeople Air Velocity: Air velocity schedule is not found='//TRIM(People(i)%Name))
              CALL ShowContinueError('Required when the zone has Thermal Comfort Controls.')
              ErrorsFound=.TRUE.
            End If
          End If
        End Do

        ! Read Max and Min temperature setpoint
        If (NumNums > 0) then
          ComfortControlledZone(ComfortControlledZoneNum)%TdbMinSetPoint = rNumericArgs(1)
          If (rNumericArgs(1) > 50 .OR. rNumericArgs(1) < 0) then
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
             trim(cNumericFieldNames(1))//'=['//trim(TrimSigDigits(rNumericArgs(1),0))//'].')
            CALL ShowContinueError('..Allowable values must be between 0 C and 50 C')
            ErrorsFound = .TRUE.
          End If
        End If
        If (NumNums > 1) then
          ComfortControlledZone(ComfortControlledZoneNum)%TdbMaxSetPoint = rNumericArgs(2)
          If (rNumericArgs(2) > 50 .OR. rNumericArgs(2) < 0) then
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
             trim(cNumericFieldNames(2))//'=['//trim(TrimSigDigits(rNumericArgs(2),0))//'].')
            CALL ShowContinueError('..Allowable values must be between 0 C and 50 C')
            ErrorsFound = .TRUE.
          End If
        End If
        ! Ensure MaxTemp >= MinTemp
        If (ComfortControlledZone(ComfortControlledZoneNum)%TdbMinSetPoint > &
            ComfortControlledZone(ComfortControlledZoneNum)%TdbMaxSetPoint) then
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1)))
            CALL ShowContinueError('..'//trim(cNumericFieldNames(1))//' > '//trim(cNumericFieldNames(2)))
            CALL ShowContinueError('..['//trim(TrimSigDigits(rNumericArgs(1),0))//'] > ['//  &
               trim(TrimSigDigits(rNumericArgs(2),0))//'].')
            ErrorsFound = .TRUE.
        End If
        ! If MaxTemp = MinTemp, no thermal comfort control
        If (ComfortControlledZone(ComfortControlledZoneNum)%TdbMinSetPoint == &
            ComfortControlledZone(ComfortControlledZoneNum)%TdbMaxSetPoint) then
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1)))
          CALL ShowContinueError('..'//trim(cNumericFieldNames(1))//' = '//trim(cNumericFieldNames(2)))
          CALL ShowContinueError('The zone will be controlled using this dry-bulb temperature setpoint.')
        End If
        ! read Thermal comfort type schedule name
        ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName = cAlphaArgs(5)
        ComfortControlledZone(ComfortControlledZoneNum)%ComfortSchedIndex=GetScheduleIndex(cAlphaArgs(5))
        IF (ComfortControlledZone(ComfortControlledZoneNum)%ComfortSchedIndex == 0) THEN
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//' invalid '//  &
             trim(cAlphaFieldNames(5))//'="'//trim(cAlphaArgs(5))//'" not found.')
          ErrorsFound = .TRUE.
        ELSE
          ! Check validity of control types.
          ValidScheduleControlType=CheckScheduleValueMinMax(ComfortControlledZone(ComfortControlledZoneNum)%ComfortSchedIndex, &
                                                           '>=',0.0d0, '<=',4.0d0)
          IF (.not. ValidScheduleControlType) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid range '//  &
               trim(cAlphaFieldNames(5))//'="'//trim(cAlphaArgs(5))//'"')
            CALL ShowContinueError('..contains values outside of range [0,4].')
            ErrorsFound=.TRUE.
          ENDIF
        END IF
        ComfortControlledZone(ComfortControlledZoneNum)%NumControlTypes = NINT((NumAlphas - 5.0d0)/2.0d0)
        ALLOCATE(ComfortControlledZone(ComfortControlledZoneNum)%ControlType(ComfortControlledZone( &
                                       ComfortControlledZoneNum)%NumControlTypes))
        ALLOCATE(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortControlledZone( &
                                       ComfortControlledZoneNum)%NumControlTypes))
        ALLOCATE(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortControlledZone(  &
                                       ComfortControlledZoneNum)%NumControlTypes))

        DO ControlTypeNum = 1, ComfortControlledZone(ComfortControlledZoneNum)%NumControlTypes
          ComfortControlledZone(ComfortControlledZoneNum)%ControlType(ControlTypeNum) = cAlphaArgs(NINT(2.0d0*ControlTypeNum-1+5))
          ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ControlTypeNum) = cAlphaArgs(NINT(2.0d0*ControlTypeNum+5))
          IF (ComfortControlledZone(ComfortControlledZoneNum)%ControlType(ControlTypeNum) /= ' ') THEN
            CTIndex=FindItem(ComfortControlledZone(ComfortControlledZoneNum)%ControlType(ControlTypeNum), &
                                   ValidComfortControlTypes,12)
            IF (CTIndex == 0) THEN
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
                 trim(cAlphaFieldNames(NINT(2.0d0*ControlTypeNum-1+5)))//'="'//  &
                    trim(cAlphaArgs(NINT(2.0d0*ControlTypeNum-1+5)))//'"')
              ErrorsFound = .TRUE.
            END IF
            IF (CTIndex > 4) THEN ! For Fanger control only for the time being
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
                 trim(cAlphaFieldNames(NINT(2.0d0*ControlTypeNum-1+5)))//'="'//  &
                    trim(cAlphaArgs(NINT(2.0d0*ControlTypeNum-1+5)))//'"')
              CALL ShowContinueError('..Fanger is the only valid model.')
              ErrorsFound = .TRUE.
            END IF
          ELSE
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
                 trim(cAlphaFieldNames(NINT(2.0d0*ControlTypeNum-1+5)))//'="<blank>"')
            ErrorsFound = .TRUE.
          ENDIF
          ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ControlTypeNum) = 0
        END DO
      END DO
    END DO ! NumComfortTStatStatements
  ENDIF
  ! End of Thermal comfort control reading and checking

  cCurrentModuleObject=ValidComfortControlTypes(SglHeatSetPointFanger)
  NumSingleFangerHeatingControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumSingleFangerHeatingControls .GT. 0) ALLOCATE(SetPointSingleHeatingFanger(NumSingleFangerHeatingControls))

  DO SingleFangerHeatingControlNum = 1, NumSingleFangerHeatingControls
    CALL GetObjectItem(cCurrentModuleObject,SingleFangerHeatingControlNum,  &
                       cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointSingleHeatingFanger%Name,SingleFangerHeatingControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    SetPointSingleHeatingFanger(SingleFangerHeatingControlNum)%Name = cAlphaArgs(1)
    SetPointSingleHeatingFanger(SingleFangerHeatingControlNum)%PMVSchedName = cAlphaArgs(2)
    SetPointSingleHeatingFanger(SingleFangerHeatingControlNum)%PMVSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointSingleHeatingFanger(SingleFangerHeatingControlNum)%PMVSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    ELSE
      ValidScheduleControlType=CheckScheduleValueMinMax( &
         SetPointSingleHeatingFanger(SingleFangerHeatingControlNum)%PMVSchedIndex, '>=',-3.0d0, '<=',3.0d0)
      IF (.not. ValidScheduleControlType) THEN
        CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid PMV values '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" entered.')
        CALL ShowContinueError('..Values outside of range [-3,+3].')
        ErrorsFound=.TRUE.
      ENDIF
    END IF
  END DO ! SingleFangerHeatingControlNum

  cCurrentModuleObject=ValidComfortControlTypes(SglCoolSetPointFanger)
  NumSingleFangerCoolingControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumSingleFangerCoolingControls .GT. 0) ALLOCATE(SetPointSingleCoolingFanger(NumSingleFangerCoolingControls))

  DO SingleFangerCoolingControlNum = 1, NumSingleFangerCoolingControls
    CALL GetObjectItem(cCurrentModuleObject,SingleFangerCoolingControlNum,  &
                       cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointSingleCoolingFanger%Name,SingleFangerCoolingControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    SetPointSingleCoolingFanger(SingleFangerCoolingControlNum)%Name = cAlphaArgs(1)
    SetPointSingleCoolingFanger(SingleFangerCoolingControlNum)%PMVSchedName = cAlphaArgs(2)
    SetPointSingleCoolingFanger(SingleFangerCoolingControlNum)%PMVSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointSingleCoolingFanger(SingleFangerCoolingControlNum)%PMVSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    ELSE
      ValidScheduleControlType=CheckScheduleValueMinMax( &
         SetPointSingleCoolingFanger(SingleFangerCoolingControlNum)%PMVSchedIndex, '>=',-3.0d0, '<=',3.0d0)
      IF (.not. ValidScheduleControlType) THEN
        CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid PMV values '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" entered.')
        CALL ShowContinueError('..Values outside of range [-3,+3].')
        ErrorsFound=.TRUE.
      ENDIF
    END IF

  END DO ! SingleFangerCoolingControlNum

  cCurrentModuleObject=ValidComfortControlTypes(SglHCSetPointFanger)
  NumSingleFangerHeatCoolControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumSingleFangerHeatCoolControls .GT. 0) ALLOCATE(SetPointSingleHeatCoolFanger(NumSingleFangerHeatCoolControls))

  DO SingleFangerHeatCoolControlNum = 1, NumSingleFangerHeatCoolControls
    CALL GetObjectItem(cCurrentModuleObject,SingleFangerHeatCoolControlNum,  &
                       cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointSingleCoolingFanger%Name,SingleFangerCoolingControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF

    SetPointSingleHeatCoolFanger(SingleFangerHeatCoolControlNum)%Name = cAlphaArgs(1)
    SetPointSingleHeatCoolFanger(SingleFangerHeatCoolControlNum)%PMVSchedName = cAlphaArgs(2)
    SetPointSingleHeatCoolFanger(SingleFangerHeatCoolControlNum)%PMVSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointSingleHeatCoolFanger(SingleFangerHeatCoolControlNum)%PMVSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    ELSE
      ValidScheduleControlType=CheckScheduleValueMinMax( &
         SetPointSingleHeatCoolFanger(SingleFangerHeatCoolControlNum)%PMVSchedIndex, '>=',-3.0d0, '<=',3.0d0)
      IF (.not. ValidScheduleControlType) THEN
        CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid PMV values '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" entered.')
        CALL ShowContinueError('..Values outside of range [-3,+3].')
        ErrorsFound=.TRUE.
      ENDIF
    END IF

  END DO ! SingleFangerHeatCoolControlNum

  cCurrentModuleObject=ValidComfortControlTypes(DualSetPointFanger)
  NumDualFangerHeatCoolControls = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumDualFangerHeatCoolControls .GT. 0) ALLOCATE(SetPointDualHeatCoolFanger(NumDualFangerHeatCoolControls))

  DO DualFangerHeatCoolControlNum = 1, NumDualFangerHeatCoolControls
    CALL GetObjectItem(cCurrentModuleObject,DualFangerHeatCoolControlNum,  &
                       cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),SetPointDualHeatCoolFanger%Name,DualFangerHeatCoolControlNum-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%Name = cAlphaArgs(1)
    SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%HeatPMVSetptSchedName = cAlphaArgs(2)
    SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%HeatPMVSchedIndex = GetScheduleIndex(cAlphaArgs(2))
    IF (SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%HeatPMVSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound = .TRUE.
    END IF
    SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%CoolPMVSetptSchedName = cAlphaArgs(3)
    SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%CoolPMVSchedIndex = GetScheduleIndex(cAlphaArgs(3))
    IF (SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%CoolPMVSchedIndex == 0) THEN
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
         trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
      ErrorsFound = .TRUE.
    ELSE
      ValidScheduleControlType=CheckScheduleValueMinMax( &
         SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%HeatPMVSchedIndex, '>=',-3.0d0, '<=',3.0d0)
      IF (.not. ValidScheduleControlType) THEN
        CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid PMV values '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" entered.')
        CALL ShowContinueError('..Values outside of range [-3,+3].')
        ErrorsFound=.TRUE.
      ENDIF
      ValidScheduleControlType=CheckScheduleValueMinMax( &
         SetPointDualHeatCoolFanger(DualFangerHeatCoolControlNum)%CoolPMVSchedIndex, '>=',-3.0d0, '<=',3.0d0)
      IF (.not. ValidScheduleControlType) THEN
        CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid PMV values '//  &
           trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" entered.')
        CALL ShowContinueError('..Values outside of range [-3,+3].')
        ErrorsFound=.TRUE.
      ENDIF
    END IF

  END DO ! DualFangerHeatCoolControlNum

 ! Finish filling in Schedule pointing indexes for Thermal Comfort Control
  DO ComfortControlledZoneNum = 1, NumComfortControlledZones
    ComfortIndex = FindItem(trim(ValidComfortControlTypes(SglHeatSetPointFanger)),  &
                                  ComfortControlledZone(ComfortControlledZoneNum)%ControlType,   &
                                  ComfortControlledZone(ComfortControlledZoneNum)%NumControlTypes)
    ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_SglHeatSetPointFanger = ComfortIndex
    IF (ComfortIndex > 0) THEN
      ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex) =   &
            FindItem(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex), &
                                        SetPointSingleHeatingFanger%Name, NumSingleFangerHeatingControls)
      TComfortControlTypes(ComfortControlledZoneNum)%MustHave(SglHeatSetPointFanger)=.true.
    ENDIF

    ComfortIndex = FindItem(trim(ValidComfortControlTypes(SglCoolSetPointFanger)),  &
                                  ComfortControlledZone(ComfortControlledZoneNum)%ControlType,   &
                                  ComfortControlledZone(ComfortControlledZoneNum)%NumControlTypes)
    ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_SglCoolSetPointFanger = ComfortIndex
    IF (ComfortIndex > 0) THEN
      ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex) =   &
            FindItem(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex), &
                                        SetPointSingleCoolingFanger%Name, NumSingleFangerCoolingControls)
      TComfortControlTypes(ComfortControlledZoneNum)%MustHave(SglCoolSetpointFanger)=.true.
    ENDIF

    ComfortIndex = FindItem(trim(ValidComfortControlTypes(SglHCSetPointFanger)),  &
                                  ComfortControlledZone(ComfortControlledZoneNum)%ControlType,   &
                                  ComfortControlledZone(ComfortControlledZoneNum)%NumControlTypes)
    ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_SglHCSetPointFanger = ComfortIndex
    IF (ComfortIndex > 0) THEN
      ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex) =   &
            FindItem(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex), &
                                        SetPointSingleHeatCoolFanger%Name, NumSingleFangerHeatCoolControls)
      TComfortControlTypes(ComfortControlledZoneNum)%MustHave(SglHCSetPointFanger)=.true.
    ENDIF

    ComfortIndex = FindItem(trim(ValidComfortControlTypes(DualSetPointFanger)),  &
                                  ComfortControlledZone(ComfortControlledZoneNum)%ControlType,   &
                                  ComfortControlledZone(ComfortControlledZoneNum)%NumControlTypes)
    ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_DualSetPointFanger = ComfortIndex
    IF (ComfortIndex > 0) THEN
      ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex) =   &
            FindItem(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex), &
                                        SetPointDualHeatCoolFanger%Name, NumDualFangerHeatCoolControls)
      TComfortControlTypes(ComfortControlledZoneNum)%MustHave(DualSetPointFanger)=.true.
    ENDIF
  ENDDO

  ! Now, Check the schedule values/indices for validity for Thermal Comfort Control

   DO ComfortControlledZoneNum = 1, NumComfortControlledZones

    ActualZoneNum = ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum
    CTIndex = ComfortControlledZone(ComfortControlledZoneNum)%ComfortSchedIndex
    IF (CTIndex == 0) CYCLE   ! error will be caught elsewhere
    SchedMin=GetScheduleMinValue(CTIndex)
    SchedMax=GetScheduleMaxValue(CTIndex)

    IF (SchedMin == 0 .and. SchedMax == 0) THEN
      IF (FindNumberInList(CTIndex,CCmSchedMapToControlledZone,NumComfortControlledZones) == 0) THEN
        CALL ShowWarningError('Control Type Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
        CALL ShowContinueError('..specifies control type 0 for all entries.')
        CALL ShowContinueError('All zones using this Control Type Schedule have no thermal comfort control.')
      ENDIF
      CCmSchedMapToControlledZone(ComfortControlledZoneNum)=CTIndex
    END IF

    DO ControlTypeNum=SchedMin,SchedMax

      SELECT CASE (ControlTypeNum)

        CASE (0) ! Thermal comfort uncontrolled

        CASE (SglHeatSetpointFanger)

          ComfortIndex=ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_SglHeatSetPointFanger
          TComfortControlTypes(ComfortControlledZoneNum)%DidHave(SglHeatSetPointFanger)=.true.
          IF (ComfortIndex /= 0) THEN
            SchedTypeIndex = ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//  &
                 trim(ValidComfortControlTypes(SglHeatSetPointFanger))//  &
                 ' Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! ComfortIndex = 0
            IF (CheckScheduleValue(CTIndex,SglHeatSetPointFanger)) THEN
              CALL ShowSevereError('Control Type Schedule='// &
                   TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies thermal control type 1 ('//  &
                 trim(ValidComfortControlTypes(SglHeatSetPointFanger))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE (SglCoolSetPointFanger)

          ComfortIndex = ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_SglCoolSetPointFanger
          TComfortControlTypes(ComfortControlledZoneNum)%DidHave(SglCoolSetPointFanger)=.true.
          IF (ComfortIndex /= 0) THEN
            SchedTypeIndex = ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//  &
                 trim(ValidComfortControlTypes(SglCoolSetPointFanger))//  &
                 ' Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! ComfortIndex = 0
            IF (CheckScheduleValue(CTIndex,SglCoolSetPointFanger)) THEN
              CALL ShowSevereError('Control Type Schedule='// &
                                   TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies thermal control type 2 ('//  &
                 trim(ValidComfortControlTypes(SglCoolSetPointFanger))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE (SglHCSetPointFanger)

          ComfortIndex = ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_SglHCSetPointFanger
          TComfortControlTypes(ComfortControlledZoneNum)%DidHave(SglHCSetPointFanger)=.true.
          IF (ComfortIndex /= 0) THEN
            SchedTypeIndex = ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//trim(ValidComfortControlTypes(SglHCSetPointFanger))//  &
                      ' Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! ComfortIndex = 0
            IF (CheckScheduleValue(CTIndex,SglHCSetPointFanger)) THEN
              CALL ShowSevereError('Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies thermal control type 3 ('//  &
                 trim(ValidComfortControlTypes(SglHCSetPointFanger))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF

        CASE (DualSetPointFanger)

          ComfortIndex = ComfortControlledZone(ComfortControlledZoneNum)%SchIndx_DualSetPointFanger
          TComfortControlTypes(ComfortControlledZoneNum)%DidHave(DualSetPointFanger)=.true.
          IF (ComfortIndex /= 0) THEN
            SchedTypeIndex = ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchIndx(ComfortIndex)
            IF (SchedTypeIndex == 0) THEN
              CALL ShowSevereError('GetZoneAirSetpoints: Could not find '//trim(ValidComfortControlTypes(DualSetPointFanger))//  &
                      ' Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeName(ComfortIndex)))
              ErrorsFound=.true.
            END IF
          ELSE   ! ComfortIndex = 0
            IF (CheckScheduleValue(CTIndex,DualSetPointFanger)) THEN
              CALL ShowSevereError('Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
              CALL ShowContinueError('..specifies thermal control type 4 ('//trim(ValidComfortControlTypes(DualSetPointFanger))//  &
                 ') as the control type. Not valid for this zone.')
              CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
              CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))
              ErrorsFound=.true.
            ENDIF
          ENDIF
        ! CASE PIERCE
        ! CASE KSU

        CASE DEFAULT
          CALL ShowSevereError('GetZoneAirSetpoints: Illegal control type for Zone='//TRIM(Zone(ActualZoneNum)%Name)//  &
                               ', Found value='//TRIM(TrimSigDigits(ControlTypeNum))//', in Schedule='//        &
                               TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('..valid range values are [0,4].')
          ErrorsFound=.true.

      END SELECT
    END DO

  END DO

  DO ComfortControlledZoneNum = 1, NumComfortControlledZones

    ActualZoneNum = ComfortControlledZone(ComfortControlledZoneNum)%ActualZoneNum
    CTIndex = ComfortControlledZone(ComfortControlledZoneNum)%ComfortSchedIndex
    IF (CTIndex == 0) CYCLE  ! error caught elsewhere -- would just be confusing here

    DO ControlTypeNum=1,12
      IF (TComfortControlTypes(ComfortControlledZoneNum)%MustHave(ControlTypeNum) .and.  &
          TComfortControlTypes(ComfortControlledZoneNum)%DidHave(ControlTypeNum)) CYCLE

      SELECT CASE (ControlTypeNum)

        CASE (SglHeatSetpointFanger)
          IF (.not. TComfortControlTypes(ComfortControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 1 ('//trim(ValidComfortControlTypes(SglHeatSetpointFanger))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))

        CASE (SglCoolSetpointFanger)
          IF (.not. TComfortControlTypes(ComfortControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 2 ('//trim(ValidComfortControlTypes(SglCoolSetpointFanger))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))

        CASE (SglHCSetpointFanger)
          IF (.not. TComfortControlTypes(ComfortControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 3 ('//trim(ValidComfortControlTypes(SglHCSetpointFanger))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))

        CASE (DualSetPointFanger)
          IF (.not. TComfortControlTypes(ComfortControlledZoneNum)%MustHave(ControlTypeNum)) CYCLE
          CALL ShowWarningError('Schedule='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ControlTypeSchedName))
          CALL ShowContinueError('...should include control type 4 ('//trim(ValidComfortControlTypes(DualSetPointFanger))//  &
                      ') but does not.')
          CALL ShowContinueError('..reference '//trim(cZControlTypes(iZC_TCTStat))//'='//  &
                                 TRIM(ComfortControlledZone(ComfortControlledZoneNum)%Name))
          CALL ShowContinueError('..reference ZONE='//TRIM(ComfortControlledZone(ComfortControlledZoneNum)%ZoneName))

        ! CASE PIERCE
        ! CASE KSU

        CASE DEFAULT
      END SELECT
    ENDDO
  ENDDO

  IF (ALLOCATED(TComfortControlTypes)) DEALLOCATE(TComfortControlTypes)

  ! Get the Zone Air Capacitance Multiplier for use in the Predictor-Corrrector Procedure
  cCurrentModuleObject='ZoneCapacitanceMultiplier:ResearchSpecial'
  NumNums=GetNumObjectsFound(cCurrentModuleObject)
  IF (NumNums == 0) THEN
    ZoneVolCapMultpSens  = 1.d0
    ZoneVolCapMultpMoist = 1.d0
    ZoneVolCapMultpCO2   = 1.d0
    ZoneVolCapMultpGenContam = 1.0d0
  ELSE
    CALL GetObjectItem(cCurrentModuleObject,1,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOStat, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    ZoneVolCapMultpSens  = rNumericArgs(1)
    ZoneVolCapMultpMoist = rNumericArgs(2)
    ZoneVolCapMultpCO2   = rNumericArgs(3)
    ZoneVolCapMultpGenContam = rNumericArgs(4)
  END IF

  WRITE(OutputFileInits, 700)
  WRITE(OutputFileInits,701) ZoneVolCapMultpSens, ZoneVolCapMultpMoist, ZoneVolCapMultpCO2, ZoneVolCapMultpGenContam
700 FORMAT ('! <Zone Volume Capacitance Multiplier>, Sensible Heat Capacity Multiplier, Moisture Capacity Multiplier, ',  &
                   'Carbon Dioxide Capacity Multiplier, Generic Contaminant Capacity Multiplier')
701 FORMAT( 'Zone Volume Capacitance Multiplier,' , F8.3,' ,', F8.3,',', F8.3,',', F8.3)

  cCurrentModuleObject=cZControlTypes(iZC_OTTStat)
  NumOpTempControlledZones =  GetNumObjectsFound(cCurrentModuleObject)

  IF (NumOpTempControlledZones > 0) then
    AnyOpTempControl = .TRUE.

    DO OpTempContrlNum = 1, NumOpTempControlledZones
       CALL GetObjectItem(cCurrentModuleObject,OpTempContrlNum,  &
                       cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
       ! find matching name of  ZONECONTROL:THERMOSTAT object
       found = FindItem(cAlphaArgs(1),TStatObjects%Name,NumTStatStatements)
       IF (found == 0) THEN
         ! It might be in the TempControlledZones
         found=FindItem(cAlphaArgs(1),TempControlledZone%Name,NumTempControlledZones)
         IF (found == 0) THEN ! throw error
          CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
            trim(cZControlTypes(iZC_TStat))//' reference not found.')
          ErrorsFound = .TRUE.
         ELSE
           TempControlledZoneNum = found
           TempControlledZone(TempControlledZoneNum)%OperativeTempControl = .TRUE.
           IF (SameString(cAlphaArgs(2), 'Scheduled')) THEN
             TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled=.TRUE.
           ENDIF
           IF ( ( .NOT. (SameString(cAlphaArgs(2), 'Scheduled')))  .AND. ( .NOT. (SameString(cAlphaArgs(2), 'Constant'))) ) THEN
              CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'".')
             ErrorsFound = .TRUE.
           ENDIF

           TempControlledZone(TempControlledZoneNum)%FixedRadiativeFraction    = rNumericArgs(1)
           TempControlledZone(TempControlledZoneNum)%OpTempRadiativeFractionSched = GetScheduleIndex(cAlphaArgs(3))
           If ( (TempControlledZone(TempControlledZoneNum)%OpTempRadiativeFractionSched == 0) &
               .AND. (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled) ) THEN !throw error
             CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
             ErrorsFound = .TRUE.
           ENDIF

           !check validity of fixed radiative fraction
           IF ( (TempControlledZone(TempControlledZoneNum)%FixedRadiativeFraction < 0.0d0)  &
                .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled)) ) THEN
             CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                 trim(cNumericFieldNames(1))//'=['//trim(TrimSigDigits(rNumericArgs(1),2))//'" cannot be negative.')
             ErrorsFound = .TRUE.
           ENDIF
           IF ( (TempControlledZone(TempControlledZoneNum)%FixedRadiativeFraction >= 0.9d0) &
                .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled)) ) THEN
             CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                 trim(cNumericFieldNames(1))//'=['//trim(TrimSigDigits(rNumericArgs(1),2))//'" cannot >= .9.')
             ErrorsFound = .TRUE.
           ENDIF

           ! check schedule min max.
           IF (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled) THEN
             ValidRadFractSched =   &
                CheckScheduleValueMinMax(TempControlledZone(TempControlledZoneNum)%OpTempRadiativeFractionSched,  &
                                                '>=',0.0,'<',0.9)
             IF (.not. ValidRadFractSched) THEN
               CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid values '//  &
                  trim(cAlphaFieldNames(3))//'=['//trim(cAlphaArgs(3))//'".')
               CALL ShowContinueError('..Values outside of range [0.0,0.9).')
               ErrorsFound=.TRUE.
             ENDIF
           ENDIF

           ! CurrentModuleObject='ZoneControl:Thermostat:OperativeTemperature'
           CALL SetupOutputVariable('Zone Thermostat Operative Temperature [C]',  &
                                     ZnAirRpt(TempControlledZone(TempControlledZoneNum)%ActualZoneNum)%ThermOperativeTemp,  &
                                     'Zone','Average',Zone(TempControlledZone(TempControlledZoneNum)%ActualZoneNum)%Name)
         ENDIF
       ELSE
         DO Item=1,TStatObjects(found)%NumOfZones
           TempControlledZoneNum = TStatObjects(found)%TempControlledZoneStartPtr+Item-1
           IF (NumTempControlledZones == 0) CYCLE
           TempControlledZone(TempControlledZoneNum)%OperativeTempControl = .TRUE.
           IF (SameString(cAlphaArgs(2), 'Scheduled')) THEN
             TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled=.TRUE.
           ENDIF
           IF (Item == 1) THEN
             IF ( ( .NOT. (SameString(cAlphaArgs(2), 'Scheduled')))  .AND. ( .NOT. (SameString(cAlphaArgs(2), 'Constant'))) ) THEN
                CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                  trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'".')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF

           TempControlledZone(TempControlledZoneNum)%FixedRadiativeFraction    = rNumericArgs(1)
           TempControlledZone(TempControlledZoneNum)%OpTempRadiativeFractionSched = GetScheduleIndex(cAlphaArgs(3))
           IF (Item == 1) THEN
             If ( (TempControlledZone(TempControlledZoneNum)%OpTempRadiativeFractionSched == 0) &
                 .AND. (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled) ) THEN !throw error
                CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                  trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF

           !check validity of fixed radiative fraction
           IF (Item == 1) THEN
             IF ( (TempControlledZone(TempControlledZoneNum)%FixedRadiativeFraction < 0.0d0)  &
                  .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled)) ) THEN
                CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                  trim(cNumericFieldNames(1))//'=['//trim(TrimSigDigits(rNumericArgs(1),2))//'" cannot be negative.')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF
           IF (Item == 1) THEN
             IF ( (TempControlledZone(TempControlledZoneNum)%FixedRadiativeFraction >= 0.9d0) &
                  .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled)) ) THEN
                CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid '//  &
                  trim(cNumericFieldNames(1))//'=['//trim(TrimSigDigits(rNumericArgs(1),2))//'" cannot >= .9.')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF

           ! check schedule min max.
           IF (Item == 1) THEN
             IF (TempControlledZone(TempControlledZoneNum)%OpTempCntrlModeScheduled) THEN
               ValidRadFractSched =   &
                  CheckScheduleValueMinMax(TempControlledZone(TempControlledZoneNum)%OpTempRadiativeFractionSched,  &
                                                  '>=',0.0,'<',0.9)
               IF (.not. ValidRadFractSched) THEN
                  CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid values '//  &
                    trim(cAlphaFieldNames(3))//'=['//trim(cAlphaArgs(3))//'".')
                  CALL ShowContinueError('..Values outside of range [0.0,0.9).')
                  ErrorsFound=.TRUE.
               ENDIF
             ENDIF
           ENDIF

           ! CurrentModuleObject='ZoneControl:Thermostat:OperativeTemperature'
           CALL SetupOutputVariable('Zone Thermostat Operative Temperature [C]',  &
                                     ZnAirRpt(TempControlledZone(TempControlledZoneNum)%ActualZoneNum)%ThermOperativeTemp,  &
                                     'Zone','Average',Zone(TempControlledZone(TempControlledZoneNum)%ActualZoneNum)%Name)
        ENDDO  ! TStat Objects Loop
      ENDIF  ! found thermostat referene
    ENDDO !loop over NumOpTempControlledZones
  ENDIF ! NumOpTempControlledZones > 0


  ! Overcool dehumidificaton GetInput starts here
  cCurrentModuleObject=cZControlTypes(iZC_TandHStat)
  NumTempAndHumidityControlledZones =  GetNumObjectsFound(cCurrentModuleObject)

  IF (NumTempAndHumidityControlledZones > 0) THEN
    AnyZoneTempAndHumidityControl = .TRUE.

    DO TempHumidityCntrlNum = 1, NumTempAndHumidityControlledZones
       CALL GetObjectItem(cCurrentModuleObject,TempHumidityCntrlNum,  &
                       cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
       ! find matching name of  ZONECONTROL:THERMOSTAT object
       found = FindItem(cAlphaArgs(1),TStatObjects%Name,NumTStatStatements)
       IF (found == 0) THEN
         ! It might be in the TempControlledZones
         found=FindItem(cAlphaArgs(1),TempControlledZone%Name,NumTempControlledZones)
         IF (found == 0) THEN ! throw error
          CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
            TRIM(cZControlTypes(iZC_TStat))//' reference not found.')
          ErrorsFound = .TRUE.
         ELSE
           TempControlledZoneNum = found
           TempControlledZone(TempControlledZoneNum)%DehumidifyingSched = cAlphaArgs(2)
           TempControlledZone(TempControlledZoneNum)%DehumidifyingSchedIndex = GetScheduleIndex(cAlphaArgs(2))
           IF (TempControlledZone(TempControlledZoneNum)%DehumidifyingSchedIndex == 0) THEN
               CALL ShowSevereError(TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//' invalid '//  &
               TRIM(cAlphaFieldNames(2))//'="'//TRIM(cAlphaArgs(2))//'" not found.')
               ErrorsFound = .TRUE.
           END IF
           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControl =.TRUE.
           IF ( (SameString(cAlphaArgs(3), 'None')) ) THEN
             TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControl =.FALSE.
           ENDIF
           IF (SameString(cAlphaArgs(4), 'Scheduled')) THEN
             TempControlledZone(TempControlledZoneNum)%OverCoolCntrlModeScheduled=.TRUE.
           ENDIF
           IF ( ( .NOT. (SameString(cAlphaArgs(4), 'Scheduled')))  .AND. ( .NOT. (SameString(cAlphaArgs(4), 'Constant'))) ) THEN
              CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                trim(cAlphaFieldNames(4))//'="'//TRIM(cAlphaArgs(4))//'".')
             ErrorsFound = .TRUE.
           ENDIF

           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolConstRange = rNumericArgs(1)
           TempControlledZone(TempControlledZoneNum)%ZoneOverCoolRangeSchedIndex = GetScheduleIndex(cAlphaArgs(4))
           IF ( (TempControlledZone(TempControlledZoneNum)%ZoneOverCoolRangeSchedIndex == 0) &
               .AND. (TempControlledZone(TempControlledZoneNum)%OverCoolCntrlModeScheduled) ) THEN !throw error
             CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                trim(cAlphaFieldNames(5))//'="'//TRIM(cAlphaArgs(5))//'" not found.')
             ErrorsFound = .TRUE.
           ENDIF

           !check validity of zone Overcool constant range
           IF ( (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolConstRange < 0.0d0)  &
                .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OverCoolCntrlModeScheduled)) ) THEN
             CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                 TRIM(cNumericFieldNames(1))//'=['//TRIM(TrimSigDigits(rNumericArgs(1),2))//'" cannot be negative.')
             ErrorsFound = .TRUE.
           ENDIF
           IF ( (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolConstRange > 3.0d0) &
                .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled)) ) THEN
             CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                 TRIM(cNumericFieldNames(1))//'=['//TRIM(TrimSigDigits(rNumericArgs(1),2))//'" cannot be > 3.0')
             ErrorsFound = .TRUE.
           ENDIF

           ! check zone Overcool range schedule min/max values.
           IF (TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled) THEN
             ValidZoneOvercoolRangeSched =   &
                CheckScheduleValueMinMax(TempControlledZone(TempControlledZoneNum)%ZoneOvercoolRangeSchedIndex,  &
                                                '>=',0.0d0,'<=',3.0d0)
             IF (.not. ValidZoneOvercoolRangeSched) THEN
               CALL ShowSevereError(trim(cCurrentModuleObject)//'='//trim(cAlphaArgs(1))//' invalid values '//  &
                  trim(cAlphaFieldNames(5))//'=['//trim(cAlphaArgs(5))//'".')
               CALL ShowContinueError('..Values outside of range [0.0,3.0].')
               ErrorsFound=.TRUE.
             ENDIF
           ENDIF
           ! check Overcool Control Ratio limits
           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControlRatio = rNumericArgs(2)
           IF (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControlRatio < 0.0d0) THEN
             CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(2))//' invalid '//  &
                 trim(cNumericFieldNames(2))//'=['//TRIM(TrimSigDigits(rNumericArgs(2),2))//'" cannot be negative.')
             ErrorsFound = .TRUE.
           ENDIF
         ENDIF
       ELSE
         DO Item=1,TStatObjects(found)%NumOfZones
           TempControlledZoneNum = TStatObjects(found)%TempControlledZoneStartPtr+Item-1
           TempControlledZone(TempControlledZoneNum)%DehumidifyingSched = cAlphaArgs(2)
           TempControlledZone(TempControlledZoneNum)%DehumidifyingSchedIndex = GetScheduleIndex(cAlphaArgs(2))
           IF (TempControlledZone(TempControlledZoneNum)%DehumidifyingSchedIndex == 0) THEN
               CALL ShowSevereError(TRIM(cCurrentModuleObject)//'="'//TRIM(cAlphaArgs(1))//' invalid '//  &
               TRIM(cAlphaFieldNames(2))//'="'//TRIM(cAlphaArgs(2))//'" not found.')
               ErrorsFound = .TRUE.
           ENDIF
           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControl =.TRUE.
           IF ( (SameString(cAlphaArgs(3), 'None'))) THEN
             TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControl =.FALSE.
           ENDIF
           IF (SameString(cAlphaArgs(4), 'Scheduled')) THEN
             TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled =.FALSE.
           ENDIF
           IF (Item == 1) THEN
             IF ( ( .NOT. (SameString(cAlphaArgs(4), 'Scheduled')))  .AND. ( .NOT. (SameString(cAlphaArgs(4), 'Constant'))) ) THEN
                CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                  TRIM(cAlphaFieldNames(4))//'="'//TRIM(cAlphaArgs(4))//'".')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF
           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolConstRange = rNumericArgs(1)
           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolRangeSchedIndex = GetScheduleIndex(cAlphaArgs(6))
           IF (Item == 1) THEN
             If ( (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolRangeSchedIndex == 0) &
                 .AND. (TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled) ) THEN !throw error
                CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                  TRIM(cAlphaFieldNames(5))//'="'//TRIM(cAlphaArgs(5))//'" not found.')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF
           !check validity of zone Overcool constant range
           IF (Item == 1) THEN
             IF ( (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolConstRange < 0.0d0)  &
                  .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled)) ) THEN
                CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                  TRIM(cNumericFieldNames(1))//'=['//TRIM(TrimSigDigits(rNumericArgs(1),2))//'" cannot be negative.')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF
           IF (Item == 1) THEN
             IF ( (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolConstRange > 3.0d0) &
                  .AND. (.NOT. (TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled)) ) THEN
                CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid '//  &
                  TRIM(cNumericFieldNames(1))//'=['//TRIM(TrimSigDigits(rNumericArgs(1),2))//'" cannot > 3.0')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF
           ! check zone Overcool range schedule min/max values.
           IF (Item == 1) THEN
             IF (TempControlledZone(TempControlledZoneNum)%OvercoolCntrlModeScheduled) THEN
               ValidZoneOverCoolRangeSched =   &
                  CheckScheduleValueMinMax(TempControlledZone(TempControlledZoneNum)%ZoneOvercoolRangeSchedIndex,  &
                                                  '>=',0.0d0,'<=',3.0d0)
               IF (.not. ValidZoneOverCoolRangeSched) THEN
                  CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1))//' invalid values '//  &
                    TRIM(cAlphaFieldNames(5))//'=['//TRIM(cAlphaArgs(5))//'".')
                  CALL ShowContinueError('..Values outside of range [0.0,3.0].')
                  ErrorsFound=.TRUE.
               ENDIF
             ENDIF
           ENDIF
           TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControlRatio = rNumericArgs(2)
           ! check Overcool Control Ratio limits
           IF (Item == 1) THEN
             IF (TempControlledZone(TempControlledZoneNum)%ZoneOvercoolControlRatio < 0.0d0) THEN
               CALL ShowSevereError(TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(2))//' invalid '//  &
                  trim(cNumericFieldNames(2))//'=['//TRIM(TrimSigDigits(rNumericArgs(2),2))//'" cannot be negative.')
               ErrorsFound = .TRUE.
             ENDIF
           ENDIF

        ENDDO  ! TStat Objects Loop
      ENDIF  ! found thermostat reference
    ENDDO !loop over NumTempAndHumidityControlledZones
  ENDIF ! NumTempAndHumidityControlledZones > 0

  ! Staged thermostat control inputs start
  cCurrentModuleObject=cZControlTypes(iZC_StagedDual)
  NumStageControlledZones =  GetNumObjectsFound(cCurrentModuleObject)
  If (NumStageControlledZones > 0) ALLOCATE(StagedTStatObjects(NumStageControlledZones))

! Pre-scan for use of Zone lists in TStat statements (i.e. Global application of TStat)
  NumStageCtrZone=0
  DO Item=1,NumStageControlledZones
    CALL GetObjectItem(cCurrentModuleObject,Item,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                       NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                       AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
    IsNotOK = .FALSE.
    IsBlank = .FALSE.
    CALL VerifyName(cAlphaArgs(1),StagedTStatObjects%Name,Item-1,IsNotOK,IsBlank, &
                    trim(cCurrentModuleObject)//' Name')
    IF (IsNotOK) THEN
      ErrorsFound = .TRUE.
      IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
    END IF
    StagedTStatObjects(Item)%Name=cAlphaArgs(1)
    Item1=FindItemInList(cAlphaArgs(2),Zone%Name,NumOfZones)
    ZLItem=0
    IF (Item1 == 0 .and. NumOfZoneLists > 0) &
        ZLItem=FindItemInList(cAlphaArgs(2),ZoneList%Name,NumOfZoneLists)
    IF (Item1 > 0) THEN
      StagedTStatObjects(Item)%StageControlledZoneStartPtr=NumStageCtrZone+1
      NumStageCtrZone=NumStageCtrZone+1
      StagedTStatObjects(Item)%NumOfZones=1
      StagedTStatObjects(Item)%ZoneListActive=.false.
      StagedTStatObjects(Item)%ZoneOrZoneListPtr=Item1
    ELSEIF (ZLItem > 0) THEN
      StagedTStatObjects(Item)%TempControlledZoneStartPtr=NumStageCtrZone+1
      NumStageCtrZone=NumStageCtrZone+ZoneList(ZLItem)%NumOfZones
      StagedTStatObjects(Item)%NumOfZones=ZoneList(ZLItem)%NumOfZones
      StagedTStatObjects(Item)%ZoneListActive=.true.
      StagedTStatObjects(Item)%ZoneOrZoneListPtr=ZLItem
    ELSE
      CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
           trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
      ErrorsFound=.true.
    ENDIF
  ENDDO

  IF (ErrorsFound) THEN
    CALL ShowSevereError('GetStagedDualSetpoint: Errors with invalid names in '//trim(cCurrentModuleObject)//  &
       ' objects.')
    CALL ShowContinueError('...These will not be read in.  Other errors may occur.')
    NumStageCtrZone=0
  ENDIF

  IF (NumStageCtrZone > 0) THEN
    ALLOCATE(StageControlledZone(NumStageCtrZone))
    ALLOCATE(StageZoneLogic(NumOfZones))
    StageZoneLogic = .FALSE.

    StageControlledZoneNum = 0
    DO Item = 1, NumStageControlledZones
      CALL GetObjectItem(cCurrentModuleObject,Item,cAlphaArgs,NumAlphas,rNumericArgs,NumNums,IOSTAT, &
                         NumBlank=lNumericFieldBlanks,AlphaBlank=lAlphaFieldBlanks, &
                         AlphaFieldNames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      DO Item1=1,StagedTStatObjects(Item)%NumOfZones
        StageControlledZoneNum=StageControlledZoneNum+1
        IF (StagedTStatObjects(Item)%ZoneListActive) THEN
          cAlphaArgs(2)=Zone(ZoneList(StagedTStatObjects(Item)%ZoneOrZoneListPtr)%Zone(Item1))%Name
        ENDIF
        ZoneAssigned=FindItemInList(cAlphaArgs(2),StageControlledZone%ZoneName,StageControlledZoneNum-1)
        IF (ZoneAssigned == 0) THEN
          StageControlledZone(StageControlledZoneNum)%ZoneName = cAlphaArgs(2)
          StageControlledZone(StageControlledZoneNum)%ActualZoneNum = FindIteminList(cAlphaArgs(2),Zone%Name,NumOfZones)
          IF (StageControlledZone(StageControlledZoneNum)%ActualZoneNum == 0) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
               trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" not found.')
            ErrorsFound = .TRUE.
          ELSE
 !           Zone(StageControlledZone(StageControlledZoneNum)%ActualZoneNum)%StageControlledZoneIndex = StageControlledZoneNum
          END IF
          StageZoneLogic(StageControlledZone(StageControlledZoneNum)%ActualZoneNum) = .TRUE.
        ELSE
          StageControlledZone(StageControlledZoneNum)%ZoneName = cAlphaArgs(2)  ! for continuity
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
             trim(cAlphaFieldNames(2))//'="'//trim(cAlphaArgs(2))//'" zone previously assigned.')
          CALL ShowContinueError('...Zone was previously assigned to Thermostat="'//  &
             trim(StageControlledZone(ZoneAssigned)%Name)//'".')
          ErrorsFound = .TRUE.
          CYCLE
        ENDIF

        IF (.not. StagedTStatObjects(Item)%ZoneListActive) THEN
          StageControlledZone(StageControlledZoneNum)%Name = cAlphaArgs(1)
        ELSE
          CALL CheckCreatedZoneItemName(RoutineName,cCurrentModuleObject,  &
                                        Zone(ZoneList(StagedTStatObjects(Item)%ZoneOrZoneListPtr)%Zone(Item1))%Name,  &
                                        ZoneList(StagedTStatObjects(Item)%ZoneOrZoneListPtr)%MaxZoneNameLength,  &
                                        StagedTStatObjects(Item)%Name,     &
                                        StageControlledZone%Name,           &
                                        StageControlledZoneNum-1,                       &
                                        StageControlledZone(StageControlledZoneNum)%Name,            &
                                        ErrFlag)
          IF (ErrFlag) ErrorsFound=.true.
        ENDIF

        StageControlledZone(StageControlledZoneNum)%NumOfHeatStages = rNumericArgs(1)
        If (rNumericArgs(1) .LT. 1 .or. rNumericArgs(1) .GT. 4) Then
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid range '//  &
                 trim(cNumericFieldNames(1))//'="'//trim(RoundSigDigits(rNumericArgs(1),0))//'"')
          CALL ShowContinueError('..contains values outside of range [1,4].')
          ErrorsFound=.TRUE.
        End If

        StageControlledZone(StageControlledZoneNum)%HeatSetBaseSchedName = cAlphaArgs(3)
        StageControlledZone(StageControlledZoneNum)%HSBchedIndex=GetScheduleIndex(cAlphaArgs(3))
        IF (Item1 == 1) THEN  ! only show error on first of several if zone list
          IF (StageControlledZone(StageControlledZoneNum)%HSBchedIndex == 0) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
               trim(cAlphaFieldNames(3))//'="'//trim(cAlphaArgs(3))//'" not found.')
            ErrorsFound = .TRUE.
          END IF
        ENDIF

        StageControlledZone(StageControlledZoneNum)%HeatThroRange = rNumericArgs(2)
        If (rNumericArgs(1) .LT. 0.d0) Then
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" negative value is found at '//  &
                 trim(cNumericFieldNames(2))//'="'//trim(RoundSigDigits(rNumericArgs(2),1))//'"')
          CALL ShowContinueError('.. The minumum value is 0.')
          ErrorsFound=.TRUE.
        End If

        If (StageControlledZone(StageControlledZoneNum)%NumOfHeatStages .GT. 0) Then
          ALLOCATE(StageControlledZone(StageControlledZoneNum)%HeatTOffset( &
                   StageControlledZone(StageControlledZoneNum)%NumOfHeatStages))
          Do i=1, StageControlledZone(StageControlledZoneNum)%NumOfHeatStages
            StageControlledZone(StageControlledZoneNum)%HeatTOffset(i) = rNumericArgs(2+i)
            If (rNumericArgs(2+i) .GT. 0.d0) Then
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" positive value is found at '//  &
                 trim(cNumericFieldNames(2+i))//'="'//trim(RoundSigDigits(rNumericArgs(2+i),1))//'"')
              CALL ShowContinueError('.. The maximum value is 0.')
              ErrorsFound=.TRUE.
            End If
            If (lNumericFieldBlanks(2+i)) Then
              CALL ShowSevereError(trim(cCurrentModuleObject)//' object ='//TRIM(cAlphaArgs(1))// &
                '. The input of ' //TRIM(cNumericFieldNames(2+i))//' is required, but a blank is found.')
              ErrorsFound=.TRUE.
            End If
            If (i > 1) Then
              If (rNumericArgs(2+i) >= rNumericArgs(1+i)) Then
                CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" The value at '//  &
                 trim(cNumericFieldNames(2+i))//'="'//trim(RoundSigDigits(rNumericArgs(2+i),1))//'" has to be less than ')
                CALL ShowContinueError(trim(cNumericFieldNames(1+i))//'="'//trim(RoundSigDigits(rNumericArgs(1+i),1)))
                ErrorsFound=.TRUE.
              End If
            End If
          End Do
        End If

        StageControlledZone(StageControlledZoneNum)%NumOfCoolStages = rNumericArgs(7)
        If (rNumericArgs(7) .LT. 1 .or. rNumericArgs(7) .GT. 4) Then
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid range '//  &
                 trim(cNumericFieldNames(7))//'="'//trim(RoundSigDigits(rNumericArgs(7),0))//'"')
          CALL ShowContinueError('..contains values outside of range [1,4].')
          ErrorsFound=.TRUE.
        End If

        StageControlledZone(StageControlledZoneNum)%CoolSetBaseSchedName = cAlphaArgs(4)
        StageControlledZone(StageControlledZoneNum)%CSBchedIndex=GetScheduleIndex(cAlphaArgs(4))
        IF (Item1 == 1) THEN  ! only show error on first of several if zone list
          IF (StageControlledZone(StageControlledZoneNum)%CSBchedIndex == 0) THEN
            CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" invalid '//  &
               trim(cAlphaFieldNames(4))//'="'//trim(cAlphaArgs(4))//'" not found.')
            ErrorsFound = .TRUE.
          END IF
        ENDIF

        StageControlledZone(StageControlledZoneNum)%CoolThroRange = rNumericArgs(8)
        If (rNumericArgs(8) .LT. 0.d0) Then
          CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" negative value is found at '//  &
                 trim(cNumericFieldNames(8))//'="'//trim(RoundSigDigits(rNumericArgs(8),1))//'"')
          CALL ShowContinueError('.. The minumum value is 0.')
          ErrorsFound=.TRUE.
        End If

        If (StageControlledZone(StageControlledZoneNum)%NumOfCoolStages .GT. 0) Then
          ALLOCATE(StageControlledZone(StageControlledZoneNum)%CoolTOffset( &
            StageControlledZone(StageControlledZoneNum)%NumOfCoolStages))
          Do i=1, StageControlledZone(StageControlledZoneNum)%NumOfCoolStages
            StageControlledZone(StageControlledZoneNum)%CoolTOffset(i) = rNumericArgs(8+i)
            If (rNumericArgs(8+i) .LT. 0.d0) Then
              CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" negative value is found at '//  &
                 trim(cNumericFieldNames(8+i))//'="'//trim(RoundSigDigits(rNumericArgs(8+i),1))//'"')
              CALL ShowContinueError('.. The minimum value is 0.')
              ErrorsFound=.TRUE.
            End If
            If (lNumericFieldBlanks(8+i)) Then
              CALL ShowSevereError(trim(cCurrentModuleObject)//' object ='//TRIM(cAlphaArgs(1))// &
                '. The input of ' //TRIM(cNumericFieldNames(8+i))//' is required, but a blank is found.')
              ErrorsFound=.TRUE.
            End If
            If (i > 1) Then
              If (rNumericArgs(8+i) <= rNumericArgs(7+i)) Then
                CALL ShowSevereError(trim(cCurrentModuleObject)//'="'//trim(cAlphaArgs(1))//'" The value at '//  &
                 trim(cNumericFieldNames(8+i))//'="'//trim(RoundSigDigits(rNumericArgs(8+i),1))//'" has to be greater than ')
                CALL ShowContinueError(trim(cNumericFieldNames(7+i))//'="'//trim(RoundSigDigits(rNumericArgs(7+i),1)))
                ErrorsFound=.TRUE.
              End If
            End If
          End Do
        End If
      End Do
    ENDDO !loop over NumStageControlledZones
    If ((GetNumObjectsFound('AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed') .EQ. 0) .AND. &
        (GetNumObjectsFound('AirLoopHVAC:UnitarySystem') .EQ. 0) .AND. &
        (GetNumObjectsFound('SetpointManager:SingleZone:OneStageCooling') == 0) .AND. &
        (GetNumObjectsFound('SetpointManager:SingleZone:OneStageHeating') == 0) )     THEN
      CALL ShowWarningError(Trim(cCurrentModuleObject)// &
        ' is applicable to only selected HVAC objects which are missing from input.' )
      CALL ShowContinueError('Model should include one or more of the following objects:  ')
      CALL ShowContinueError('AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitarySystem, ')
      CALL ShowContinueError('SetpointManager:SingleZone:OneStageCooling, '// &
                             'and/or SetpointManager:SingleZone:OneStageHeating. The simulation continues...')
    End If
  ENDIF ! NumStageControlledZones > 0

  IF (ErrorsFound) THEN
    CALL ShowFatalError('Errors getting Zone Control input data.  Preceding condition(s) cause termination.')
  END IF

  RETURN

END SUBROUTINE GetZoneAirSetpoints

SUBROUTINE InitZoneAirSetpoints

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Russell Taylor
          !       DATE WRITTEN   September 1998
          !       MODIFIED       November 2004, M. J. Witte additional report variables
          !       MODIFIED       L.Gu, May 2006
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine initializes the data for the zone air setpoints.

          ! METHODOLOGY EMPLOYED:
          ! Uses the status flags to trigger events.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataZoneEquipment, ONLY: ZoneEquipConfig, ZoneEquipInputsFilled
  USE DataSurfaces, ONLY: Surface

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
  CHARACTER(len=*), PARAMETER :: RoutineName='InitZoneAirSetpoints: '

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: Loop, ZoneNum
  LOGICAL,SAVE  :: MyOneTimeFlag = .TRUE.
  LOGICAL,SAVE  :: MyEnvrnFlag = .TRUE.
  LOGICAL,SAVE  :: MyDayFlag = .TRUE.
  LOGICAL, SAVE :: ErrorsFound=.false.
  LOGICAL, SAVE :: ControlledZonesChecked=.false.
  LOGICAL :: FirstSurfFlag
  INTEGER :: TRefFlag  ! Flag for Reference Temperature process in Zones
  INTEGER :: SurfNum

          ! FLOW:
  IF (MyOneTimeFlag) THEN
    ALLOCATE(TempZoneThermostatSetPoint(NumOfZones))
    TempZoneThermostatSetPoint=0.0d0
    ALLOCATE(ZoneThermostatSetPointHi(NumOfZones))
    ZoneThermostatSetPointHi=0.0d0
    ALLOCATE(ZoneThermostatSetPointLo(NumOfZones))
    ZoneThermostatSetPointLo=0.0d0

    ALLOCATE(LoadCorrectionFactor(NumOfZones))  !PH 3/3/04
    LoadCorrectionFactor=0.0d0
    ALLOCATE(TempControlType(NumOfZones))
    TempControlType=0
    If (NumComfortControlledZones > 0) then
      ALLOCATE(ComfortControlType(NumOfZones))
      ComfortControlType=0
      ALLOCATE(ZoneComfortControlsFanger(NumOfZones))
    End If
    ALLOCATE(ZoneSetPointLast(NumOfZones))
    ZoneSetPointLast=0.0d0
    ALLOCATE(Setback(NumOfZones))
    Setback=.false.
    ALLOCATE(DeadbandOrSetback(NumOfZones))
    DeadbandOrSetback=.false.
    ALLOCATE(CurDeadbandOrSetback(NumOfZones))
    CurDeadbandOrSetback=.false.
    ALLOCATE(SNLoadHeatEnergy(NumOfZones))
    SNLoadHeatEnergy=0.0d0
    ALLOCATE(SNLoadCoolEnergy(NumOfZones))
    SNLoadCoolEnergy=0.0d0
    ALLOCATE(SNLoadHeatRate(NumOfZones))
    SNLoadHeatRate=0.0d0
    ALLOCATE(SNLoadCoolRate(NumOfZones))
    SNLoadCoolRate=0.0d0
    ALLOCATE(SNLoadPredictedRate(NumOfZones))
    SNLoadPredictedRate=0.0d0
    ALLOCATE(SNLoadPredictedHSPRate(NumOfZones))
    SNLoadPredictedHSPRate=0.0d0
    ALLOCATE(SNLoadPredictedCSPRate(NumOfZones))
    SNLoadPredictedCSPRate=0.0d0
    ALLOCATE(MoisturePredictedRate(NumOfZones))
    MoisturePredictedRate=0.0d0
    ALLOCATE(WZoneTimeMinus1(NumOfZones))
    WZoneTimeMinus1=0.0d0
    ALLOCATE(WZoneTimeMinus2(NumOfZones))
    WZoneTimeMinus2=0.0d0
    ALLOCATE(WZoneTimeMinus3(NumOfZones))
    WZoneTimeMinus3=0.0d0
    ALLOCATE(WZoneTimeMinus4(NumOfZones))
    WZoneTimeMinus4=0.0d0
    ALLOCATE(DSWZoneTimeMinus1(NumOfZones))
    DSWZoneTimeMinus1=0.0d0
    ALLOCATE(DSWZoneTimeMinus2(NumOfZones))
    DSWZoneTimeMinus2=0.0d0
    ALLOCATE(DSWZoneTimeMinus3(NumOfZones))
    DSWZoneTimeMinus3=0.0d0
    ALLOCATE(DSWZoneTimeMinus4(NumOfZones))
    DSWZoneTimeMinus4=0.0d0
    ALLOCATE(ZoneAirHumRatTemp(NumOfZones))
    ZoneAirHumRatTemp=0.0d0
    ALLOCATE(WZoneTimeMinus1Temp(NumOfZones))
    WZoneTimeMinus1Temp=0.0d0
    ALLOCATE(WZoneTimeMinus2Temp(NumOfZones))
    WZoneTimeMinus2Temp=0.0d0
    ALLOCATE(WZoneTimeMinus3Temp(NumOfZones))
    WZoneTimeMinus3Temp=0.0d0
    ALLOCATE(WZoneTimeMinusP(NumOfZones))
    WZoneTimeMinusP=0.0d0
    ALLOCATE(TempIndZnLd(NumOfZones))
    TempIndZnLd=0.0d0
    ALLOCATE(TempDepZnLd(NumOfZones))
    TempDepZnLd=0.0d0
    ALLOCATE(NonAirSystemResponse(NumOfZones))
    NonAirSystemResponse=0.0d0
    ALLOCATE(SysDepZoneLoads(NumOfZones))
    SysDepZoneLoads=0.0d0
    ALLOCATE(SysDepZoneLoadsLagged(NumOfZones))
    SysDepZoneLoadsLagged=0.0d0
    ALLOCATE(ZoneAirRelHum(NumOfZones))
    ZoneAirRelHum=0.0d0
    ALLOCATE(ZoneWMX(NumOfZones))
    ZoneWMX = 0.0d0
    ALLOCATE(ZoneWM2(NumOfZones))
    ZoneWM2 = 0.0d0
    ALLOCATE(ZoneT1(NumOfZones))
    ZoneT1=0.0d0
    ALLOCATE(ZoneW1(NumOfZones))
    ZoneW1=0.0d0

    ALLOCATE(ListSNLoadHeatEnergy(NumOfZoneLists))
    ListSNLoadHeatEnergy=0.0d0
    ALLOCATE(ListSNLoadCoolEnergy(NumOfZoneLists))
    ListSNLoadCoolEnergy=0.0d0
    ALLOCATE(ListSNLoadHeatRate(NumOfZoneLists))
    ListSNLoadHeatRate=0.0d0
    ALLOCATE(ListSNLoadCoolRate(NumOfZoneLists))
    ListSNLoadCoolRate=0.0d0

    ALLOCATE(GroupSNLoadHeatEnergy(NumOfZoneGroups))
    GroupSNLoadHeatEnergy=0.0d0
    ALLOCATE(GroupSNLoadCoolEnergy(NumOfZoneGroups))
    GroupSNLoadCoolEnergy=0.0d0
    ALLOCATE(GroupSNLoadHeatRate(NumOfZoneGroups))
    GroupSNLoadHeatRate=0.0d0
    ALLOCATE(GroupSNLoadCoolRate(NumOfZoneGroups))
    GroupSNLoadCoolRate=0.0d0
    ALLOCATE(AIRRAT(NumOfZones))
    AIRRAT = 0.0d0
    ALLOCATE(ZTM1(NumOfZones))
    ZTM1 = 0.0d0
    ALLOCATE(ZTM2(NumOfZones))
    ZTM2 = 0.0d0
    ALLOCATE(ZTM3(NumOfZones))
    ZTM3 = 0.0d0

    ! Allocate Derived Types
    ALLOCATE(ZoneSysEnergyDemand(NumOfZones))
    ALLOCATE(ZoneSysMoistureDemand(NumOfZones))

    DO Loop = 1, NumOfZones
      FirstSurfFlag=.true.
      DO SurfNum = Zone(Loop)%SurfaceFirst,Zone(Loop)%SurfaceLast
        IF (.NOT. Surface(SurfNum)%HeatTransSurf) CYCLE ! Skip non-heat transfer surfaces

        IF (FirstSurfFlag) THEN
          TrefFlag = Surface(SurfNum)%TAirRef
          FirstSurfFlag=.false.
        END IF
        ! for each particular zone, the reference air temperature(s) should be the same
        ! (either mean air, bulk air, or supply air temp).
        IF (Surface(SurfNum)%TAirRef /= TrefFlag) THEN
          CALL ShowWarningError('Different reference air temperatures for difference surfaces encountered in zone '//  &
                                  TRIM(Zone(Loop)%Name))
        END IF

      ENDDO
    ENDDO

    ! CurrentModuleObject='Zone'
    DO Loop = 1, NumOfZones
      CALL SetupOutputVariable('Zone Air System Sensible Heating Energy [J]',SNLoadHeatEnergy(Loop), &
                               'System','Sum',Zone(Loop)%Name,ResourceTypeKey='ENERGYTRANSFER', &
                                EndUseKey='Heating',GroupKey='Building',ZoneKey=Zone(Loop)%Name, &
                                ZoneMult=Zone(Loop)%Multiplier, &
                                ZoneListMult=Zone(Loop)%ListMultiplier)
      CALL SetupOutputVariable('Zone Air System Sensible Cooling Energy [J]',SNLoadCoolEnergy(Loop), &
                               'System','Sum',Zone(Loop)%Name,ResourceTypeKey='ENERGYTRANSFER', &
                                EndUseKey='Cooling',GroupKey='Building',ZoneKey=Zone(Loop)%Name, &
                                ZoneMult=Zone(Loop)%Multiplier, &
                                ZoneListMult=Zone(Loop)%ListMultiplier)
      CALL SetupOutputVariable('Zone Air System Sensible Heating Rate [W]',SNLoadHeatRate(Loop),'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Air System Sensible Cooling Rate [W]',SNLoadCoolRate(Loop),'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Air Temperature [C]',Zt(Loop),'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Thermostat Air Temperature [C]',TempTstatAir(Loop),'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Air Humidity Ratio []',ZoneAirHumRat(Loop),'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Air Relative Humidity [%]',ZoneAirRelHum(Loop),'System', &
                               'Average',Zone(Loop)%Name)
      ! This output variable is for the predicted Heating/Cooling load for the zone which can be compared to actual load
      ! These report variables are not multiplied by zone and group multipliers
      CALL SetupOutputVariable('Zone Predicted Sensible Load to Setpoint Heat Transfer Rate [W]', SNLoadPredictedRate(Loop), &
                               'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Predicted Sensible Load to Heating Setpoint Heat Transfer Rate [W]', &
                                SNLoadPredictedHSPRate(Loop), &
                               'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Predicted Sensible Load to Cooling Setpoint Heat Transfer Rate [W]', &
                                SNLoadPredictedCSPRate(Loop), &
                               'System','Average',Zone(Loop)%Name)
      ! This output variable is for the predicted moisture load for the zone with humidity controlled specified.
      CALL SetupOutputVariable('Zone Predicted Moisture Load Moisture Transfer Rate [kgWater/s]', MoisturePredictedRate(Loop), &
                               'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Predicted Moisture Load to Humidifying Setpoint Moisture Transfer Rate [kgWater/s]', &
                               ZoneSysMoistureDemand(Loop)%OutputRequiredToHumidifyingSP,'System','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Predicted Moisture Load to Dehumidifying Setpoint Moisture Transfer Rate [kgWater/s]', &
                               ZoneSysMoistureDemand(Loop)%OutputRequiredToDehumidifyingSP,'System','Average',Zone(Loop)%Name)
      ! Zone thermostat setpoints
      CALL SetupOutputVariable('Zone Thermostat Control Type []', &
                                TempControlType(Loop), &
                               'Zone','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Thermostat Heating Setpoint Temperature [C]', &
                                ZoneThermostatSetPointLo(Loop), &
                               'Zone','Average',Zone(Loop)%Name)
      CALL SetupOutputVariable('Zone Thermostat Cooling Setpoint Temperature [C]', &
                                ZoneThermostatSetPointHi(Loop), &
                               'Zone','Average',Zone(Loop)%Name)

      CALL SetupOutputVariable('Zone Predicted Sensible Load Room Air Correction Factor [ ]', &
                                LoadCorrectionFactor(loop), &
                               'System','Average',Zone(Loop)%Name)

      If (ALLOCATED(StageZoneLogic)) Then
        If (StageZoneLogic(Loop)) Then
          CALL SetupOutputVariable('Zone Thermostat Staged Number []',  &
                                     ZoneSysEnergyDemand(Loop)%StageNum,'System','Average',Zone(Loop)%Name)
        End If
      End If

    END DO ! Loop

    ! Thermal comfort control output
    If (NumComfortControlledZones > 0) then
     ! CurrentModuleObject='ZoneControl:Thermostat:ThermalComfort'
      DO Loop = 1, NumComfortControlledZones
        ZoneNum = ComfortControlledZone(Loop)%ActualZoneNum
        CALL SetupOutputVariable('Zone Thermal Comfort Control Type []', &
                                ComfortControlType(ZoneNum), 'Zone','Average',Zone(ZoneNum)%Name)
        CALL SetupOutputVariable('Zone Thermal Comfort Control Fanger Low Setpoint PMV []', &
                                ZoneComfortControlsFanger(ZoneNum)%LowPMV, 'Zone','Average',Zone(ZoneNum)%Name)
        CALL SetupOutputVariable('Zone Thermal Comfort Control Fanger High Setpoint PMV []', &
                                ZoneComfortControlsFanger(ZoneNum)%HighPMV, 'Zone','Average',Zone(ZoneNum)%Name)
      END DO
    End If

    ! CurrentModuleObject='ZoneList'
    DO Loop = 1, NumOfZoneLists
      CALL SetupOutputVariable('Zone List Sensible Heating Energy [J]',ListSNLoadHeatEnergy(Loop), &
                               'System','Sum',ZoneList(Loop)%Name)
      CALL SetupOutputVariable('Zone List Sensible Cooling Energy [J]',ListSNLoadCoolEnergy(Loop), &
                               'System','Sum',ZoneList(Loop)%Name)
      CALL SetupOutputVariable('Zone List Sensible Heating Rate [W]',ListSNLoadHeatRate(Loop),'System','Average',  &
                                ZoneList(Loop)%Name)
      CALL SetupOutputVariable('Zone List Sensible Cooling Rate [W]',ListSNLoadCoolRate(Loop),'System','Average',  &
                                ZoneList(Loop)%Name)
    END DO ! Loop

    ! CurrentModuleObject='ZoneGroup'
    DO Loop = 1, NumOfZoneGroups
      CALL SetupOutputVariable('Zone Group Sensible Heating Energy [J]',GroupSNLoadHeatEnergy(Loop), &
                               'System','Sum',ZoneGroup(Loop)%Name)
      CALL SetupOutputVariable('Zone Group Sensible Cooling Energy [J]',GroupSNLoadCoolEnergy(Loop), &
                               'System','Sum',ZoneGroup(Loop)%Name)
      CALL SetupOutputVariable('Zone Group Sensible Heating Rate [W]',GroupSNLoadHeatRate(Loop),'System','Average',  &
                                   ZoneGroup(Loop)%Name)
      CALL SetupOutputVariable('Zone Group Sensible Cooling Rate [W]',GroupSNLoadCoolRate(Loop),'System','Average',  &
                                   ZoneGroup(Loop)%Name)
    END DO ! Loop

    MyOneTimeFlag = .FALSE.
  END IF

  ! Do the Begin Environment initializations
  IF (MyEnvrnFlag .AND. BeginEnvrnFlag) THEN
    AIRRAT = 0.0d0
    ZTM1 = 0.0d0
    ZTM2 = 0.0d0
    ZTM3 = 0.0d0
    WZoneTimeMinus1 = OutHumRat
    WZoneTimeMinus2 = OutHumRat
    WZoneTimeMinus3 = OutHumRat
    WZoneTimeMinus4 = OutHumRat
    WZoneTimeMinusP = OutHumRat
    DSWZoneTimeMinus1 = OutHumRat
    DSWZoneTimeMinus2 = OutHumRat
    DSWZoneTimeMinus3 = OutHumRat
    DSWZoneTimeMinus4 = OutHumRat
    WZoneTimeMinus1Temp = 0.0d0
    WZoneTimeMinus2Temp = 0.0d0
    WZoneTimeMinus3Temp = 0.0d0
    ZoneAirHumRatTemp = 0.0d0
    TempZoneThermostatSetPoint = 0.0d0
    ZoneThermostatSetPointHi = 0.0d0
    ZoneThermostatSetPointLo = 0.0d0

    LoadCorrectionFactor = 1.d0 !PH 3/3/04
    TempControlType = 0
    ZoneSysEnergyDemand(1:NumOfZones)%RemainingOutputRequired = 0.0d0
    ZoneSysEnergyDemand(1:NumOfZones)%TotalOutputRequired = 0.0d0
    ZoneSysMoistureDemand(1:NumOfZones)%RemainingOutputRequired = 0.0d0
    ZoneSysMoistureDemand(1:NumOfZones)%TotalOutputRequired = 0.0d0
    DO ZoneNum = 1, NumOfZones
      IF (ALLOCATED(ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequired)) &
        ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequired = 0.d0
      IF (ALLOCATED(ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToHeatingSP)) &
        ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToHeatingSP = 0.d0
      IF (ALLOCATED(ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToCoolingSP)) &
        ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToCoolingSP = 0.d0
      IF (ALLOCATED(ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequired)) &
        ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequired = 0.d0
      IF (ALLOCATED(ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToHumidSP)) &
        ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToHumidSP = 0.d0
      IF (ALLOCATED(ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToDehumidSP)) &
        ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToDehumidSP = 0.d0
    ENDDO


    DeadbandOrSetback = .FALSE.
    SNLoadHeatEnergy = 0.0d0
    SNLoadCoolEnergy = 0.0d0
    SNLoadHeatRate = 0.0d0
    SNLoadCoolRate = 0.0d0
    SNLoadPredictedRate = 0.0d0
    SNLoadPredictedHSPRate = 0.0d0
    SNLoadPredictedCSPRate = 0.0d0
    MoisturePredictedRate = 0.0d0
    TempIndZnLd = 0.0d0
    TempDepZnLd = 0.0d0
    NonAirSystemResponse = 0.0d0
    SysDepZoneLoads = 0.0d0
    SysDepZoneLoadsLagged = 0.0d0
    ZoneAirRelHum = 0.0d0
    Zone%NoHeatToReturnAir = .FALSE.
    ZoneT1 = 0.0d0
    ZoneW1 = OutHumRat
    ZoneWMX = OutHumRat
    ZoneWM2 = OutHumRat

    MyEnvrnFlag = .FALSE.
  END IF

  IF (.NOT. BeginEnvrnFlag) THEN
    MyEnvrnFlag=.TRUE.
  END IF

  ! Do the Begin Day initializations
  IF (MyDayFlag .AND. BeginDayFlag) THEN
    MyDayFlag=.FALSE.
  END IF

  IF (.NOT. BeginDayFlag) THEN
    MyDayFlag=.TRUE.
  END IF

  DO Loop = 1, NumTempControlledZones
    IF (ZoneEquipInputsFilled .and. .not. ControlledZonesChecked) THEN
      IF (.not. VerifyControlledZoneForThermostat(TempControlledZone(Loop)%ZoneName)) THEN
        CALL ShowSevereError(RoutineName//'Zone="'//TRIM(TempControlledZone(Loop)%ZoneName)//'" has specified a'//  &
                             ' Thermostatic control but is not a controlled zone.')
        CALL ShowContinueError('...must have a ZoneHVAC:EquipmentConnections specification for this zone.')
        ErrorsFound=.true.
      ENDIF
    ENDIF

    IF (TempControlledZone(Loop)%ManageDemand) THEN
      ZoneNum = TempControlledZone(Loop)%ActualZoneNum


      SELECT CASE(TempControlType(ZoneNum))

        CASE (0) ! Uncontrolled

        CASE (SingleHeatingSetPoint)
          IF (TempZoneThermostatSetPoint(ZoneNum) > TempControlledZone(Loop)%HeatingResetLimit) THEN
            TempZoneThermostatSetPoint(ZoneNum) = TempControlledZone(Loop)%HeatingResetLimit
            ZoneThermostatSetPointLo(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)
          END IF

        CASE (SingleCoolingSetPoint)
          IF (TempZoneThermostatSetPoint(ZoneNum) < TempControlledZone(Loop)%CoolingResetLimit) THEN
            TempZoneThermostatSetPoint(ZoneNum) = TempControlledZone(Loop)%CoolingResetLimit
            ZoneThermostatSetPointHi(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)
          END IF

        CASE (SingleHeatCoolSetPoint)
          IF ((TempZoneThermostatSetPoint(ZoneNum) > TempControlledZone(Loop)%HeatingResetLimit) &
            .OR. (TempZoneThermostatSetPoint(ZoneNum) < TempControlledZone(Loop)%CoolingResetLimit)) THEN

            TempControlType(ZoneNum) = DualSetPointWithDeadBand
            ZoneThermostatSetPointLo(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)
            ZoneThermostatSetPointHi(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)

            IF (ZoneThermostatSetPointLo(ZoneNum) > TempControlledZone(Loop)%HeatingResetLimit) &
              ZoneThermostatSetPointLo(ZoneNum) = TempControlledZone(Loop)%HeatingResetLimit
            IF (ZoneThermostatSetPointHi(ZoneNum) < TempControlledZone(Loop)%CoolingResetLimit) &
              ZoneThermostatSetPointHi(ZoneNum) = TempControlledZone(Loop)%CoolingResetLimit

          END IF

        CASE (DualSetPointWithDeadBand)
          IF (ZoneThermostatSetPointLo(ZoneNum) > TempControlledZone(Loop)%HeatingResetLimit) &
            ZoneThermostatSetPointLo(ZoneNum) = TempControlledZone(Loop)%HeatingResetLimit
          IF (ZoneThermostatSetPointHi(ZoneNum) < TempControlledZone(Loop)%CoolingResetLimit) &
            ZoneThermostatSetPointHi(ZoneNum) = TempControlledZone(Loop)%CoolingResetLimit

        CASE DEFAULT
          ! Do nothing

      END SELECT
    END IF
  END DO

  DO Loop = 1, NumComfortControlledZones
    IF (ZoneEquipInputsFilled .and. .not. ControlledZonesChecked) THEN
      IF (.not. VerifyControlledZoneForThermostat(ComfortControlledZone(Loop)%ZoneName)) THEN
        CALL ShowSevereError(RoutineName//'Zone="'//TRIM(ComfortControlledZone(Loop)%ZoneName)//'" has specified a'//  &
                             ' Comfort control but is not a controlled zone.')
        CALL ShowContinueError('...must have a ZoneHVAC:EquipmentConnections specification for this zone.')
        ErrorsFound=.true.
      ENDIF
    ENDIF
    IF (ComfortControlledZone(Loop)%ManageDemand) THEN
      ZoneNum = ComfortControlledZone(Loop)%ActualZoneNum

      SELECT CASE(ComfortControlType(ZoneNum))

        CASE (0) ! Uncontrolled

        CASE (SglHeatSetPointFanger)
          IF (TempZoneThermostatSetPoint(ZoneNum) >= ComfortControlledZone(Loop)%HeatingResetLimit) THEN
            TempZoneThermostatSetPoint(ZoneNum) = ComfortControlledZone(Loop)%HeatingResetLimit
            ZoneThermostatSetPointLo(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)
            TempControlType(ZoneNum) = SingleHeatingSetPoint
          END IF

        CASE (SglCoolSetPointFanger)
          IF (TempZoneThermostatSetPoint(ZoneNum) <= ComfortControlledZone(Loop)%CoolingResetLimit) THEN
            TempZoneThermostatSetPoint(ZoneNum) = ComfortControlledZone(Loop)%CoolingResetLimit
            ZoneThermostatSetPointHi(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)
            TempControlType(ZoneNum) = SingleCoolingSetPoint
          END IF

        CASE (SglHCSetPointFanger)
          IF ((TempZoneThermostatSetPoint(ZoneNum) >= ComfortControlledZone(Loop)%HeatingResetLimit) &
            .OR. (TempZoneThermostatSetPoint(ZoneNum) <= ComfortControlledZone(Loop)%CoolingResetLimit)) THEN

            TempControlType(ZoneNum) = DualSetPointWithDeadBand
            ZoneThermostatSetPointLo(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)
            ZoneThermostatSetPointHi(ZoneNum) = TempZoneThermostatSetPoint(ZoneNum)

            IF (ZoneThermostatSetPointLo(ZoneNum) >= ComfortControlledZone(Loop)%HeatingResetLimit) &
              ZoneThermostatSetPointLo(ZoneNum) = ComfortControlledZone(Loop)%HeatingResetLimit
            IF (ZoneThermostatSetPointHi(ZoneNum) <= ComfortControlledZone(Loop)%CoolingResetLimit) &
              ZoneThermostatSetPointHi(ZoneNum) = ComfortControlledZone(Loop)%CoolingResetLimit

          END IF

        CASE (DualSetPointFanger)
          TempControlType(ZoneNum) = DualSetPointWithDeadBand
          IF (ZoneThermostatSetPointLo(ZoneNum) >= ComfortControlledZone(Loop)%HeatingResetLimit) &
            ZoneThermostatSetPointLo(ZoneNum) = ComfortControlledZone(Loop)%HeatingResetLimit
          IF (ZoneThermostatSetPointHi(ZoneNum) <= ComfortControlledZone(Loop)%CoolingResetLimit) &
            ZoneThermostatSetPointHi(ZoneNum) = ComfortControlledZone(Loop)%CoolingResetLimit

        CASE DEFAULT
          ! Do nothing

      END SELECT
    END IF !Demand manager
  END DO

  DO Loop = 1, NumTempControlledZones
    IF (TempControlledZone(Loop)%EMSOverrideHeatingSetpointOn) THEN
      ZoneNum = TempControlledZone(Loop)%ActualZoneNum

      SELECT CASE(TempControlType(ZoneNum))

      CASE (0) ! Uncontrolled

      CASE (SingleHeatingSetPoint)
        TempZoneThermostatSetPoint(ZoneNum) = TempControlledZone(Loop)%EMSOverrideHeatingSetpointValue
        ZoneThermostatSetPointLo(ZoneNum)   = TempControlledZone(Loop)%EMSOverrideHeatingSetpointValue
      CASE (SingleCoolingSetPoint)
        ! do nothing
      CASE (SingleHeatCoolSetPoint)
        TempZoneThermostatSetPoint(ZoneNum) = TempControlledZone(Loop)%EMSOverrideHeatingSetpointValue
        ZoneThermostatSetPointLo(ZoneNum)   = TempControlledZone(Loop)%EMSOverrideHeatingSetpointValue
      CASE (DualSetPointWithDeadBand)
        ZoneThermostatSetPointLo(ZoneNum)   = TempControlledZone(Loop)%EMSOverrideHeatingSetpointValue
      CASE DEFAULT
          ! Do nothing
      END SELECT
    ENDIF
    IF (TempControlledZone(Loop)%EMSOverrideCoolingSetpointOn) THEN
      ZoneNum = TempControlledZone(Loop)%ActualZoneNum

      SELECT CASE(TempControlType(ZoneNum))

      CASE (0) ! Uncontrolled

      CASE (SingleHeatingSetPoint)
        ! do nothing
      CASE (SingleCoolingSetPoint)
        TempZoneThermostatSetPoint(ZoneNum) = TempControlledZone(Loop)%EMSOverrideCoolingSetpointValue
        ZoneThermostatSetPointHi(ZoneNum)   = TempControlledZone(Loop)%EMSOverrideCoolingSetpointValue
      CASE (SingleHeatCoolSetPoint)
        TempZoneThermostatSetPoint(ZoneNum) = TempControlledZone(Loop)%EMSOverrideCoolingSetpointValue
        ZoneThermostatSetPointHi(ZoneNum)   = TempControlledZone(Loop)%EMSOverrideCoolingSetpointValue
      CASE (DualSetPointWithDeadBand)
        ZoneThermostatSetPointHi(ZoneNum)   = TempControlledZone(Loop)%EMSOverrideCoolingSetpointValue
      CASE DEFAULT
          ! Do nothing
      END SELECT
    ENDIF
  ENDDO
  DO Loop = 1, NumComfortControlledZones
    IF (ComfortControlledZone(Loop)%EMSOverrideHeatingSetpointOn) THEN
      ZoneNum = ComfortControlledZone(Loop)%ActualZoneNum
      SELECT CASE(ComfortControlType(ZoneNum))

      CASE (0) ! Uncontrolled

      CASE (SglHeatSetPointFanger)
        TempZoneThermostatSetPoint(ZoneNum) = ComfortControlledZone(Loop)%EMSOverrideHeatingSetpointValue
        ZoneThermostatSetPointLo(ZoneNum)   = ComfortControlledZone(Loop)%EMSOverrideHeatingSetpointValue
      CASE (SglCoolSetPointFanger)
        ! do nothing
      CASE (SglHCSetPointFanger)
        TempZoneThermostatSetPoint(ZoneNum) = ComfortControlledZone(Loop)%EMSOverrideHeatingSetpointValue
        ZoneThermostatSetPointLo(ZoneNum)   = ComfortControlledZone(Loop)%EMSOverrideHeatingSetpointValue
      CASE (DualSetPointFanger)
        ZoneThermostatSetPointLo(ZoneNum)   = ComfortControlledZone(Loop)%EMSOverrideHeatingSetpointValue
      CASE DEFAULT
          ! Do nothing
      END SELECT
    ENDIF
    IF (ComfortControlledZone(Loop)%EMSOverrideCoolingSetpointOn) THEN
      ZoneNum = ComfortControlledZone(Loop)%ActualZoneNum
      SELECT CASE(ComfortControlType(ZoneNum))

      CASE (0) ! Uncontrolled

      CASE (SglHeatSetPointFanger)
        ! do nothing
      CASE (SglCoolSetPointFanger)
        TempZoneThermostatSetPoint(ZoneNum) = ComfortControlledZone(Loop)%EMSOverrideCoolingSetpointValue
        ZoneThermostatSetPointHi(ZoneNum)   = ComfortControlledZone(Loop)%EMSOverrideCoolingSetpointValue
      CASE (SglHCSetPointFanger)
        TempZoneThermostatSetPoint(ZoneNum) = ComfortControlledZone(Loop)%EMSOverrideCoolingSetpointValue
        ZoneThermostatSetPointHi(ZoneNum)   = ComfortControlledZone(Loop)%EMSOverrideCoolingSetpointValue
      CASE (DualSetPointFanger)
        ZoneThermostatSetPointHi(ZoneNum)   = ComfortControlledZone(Loop)%EMSOverrideCoolingSetpointValue
      CASE DEFAULT
          ! Do nothing
      END SELECT
    ENDIF

  ENDDO



  IF (ErrorsFound) THEN
    CALL ShowFatalError('InitZoneAirSetpoints - program terminates due to previous condition.')
  ENDIF

  IF (ZoneEquipInputsFilled) THEN
    ControlledZonesChecked=.true.
  ENDIF

  RETURN

END SUBROUTINE InitZoneAirSetpoints

SUBROUTINE PredictSystemLoads(ShortenTimeStepSys, UseZoneTimeStepHistory, PriorTimeStep )

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Russ Taylor
          !       DATE WRITTEN   May 1997
          !       MODIFIED       na
          !       RE-ENGINEERED  July 2003 (Peter Graham Ellis)

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine is responsible for determining
          ! how much of each type of energy every zone requires.
          ! In effect, this subroutine defines and simulates all
          ! the system types and in the case of hybrid systems
          ! which use more than one type of energy must determine
          ! how to apportion the load. An example of a hybrid system
          ! is a water loop heat pump with supplemental air.  In
          ! this case, a zone will require water from the loop and
          ! cooled or heated air from the air system. A simpler
          ! example would be a VAV system with baseboard heaters.

          !  Basic Air System Types
          !  1) Constant Volume Single Duct
          !  2) Variable Volume Single Duct
          !  3) Constant Volume Dual Duct
          !  4) Variable Volume Dual Duct

          ! METHODOLOGY EMPLOYED:
          ! 0.  Determine if simulation has downstepped and readjust history and revert node results
          ! 1.  Determine zone load - this is zone temperature dependent
          ! 2.  Determine balance point - the temperature at which the
          !     zone load is balanced by the system output. The way the
          !     balance point is determined will be different depending on
          !     the type of system being simulated.
          ! 3.  Calculate zone energy requirements

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:

  USE DataRoomAirModel,     ONLY: AirModel,RoomAirModel_Mixing,RoomAirModel_UCSDDV,IsZoneDV,ZoneDVMixedFlag,IsZoneUI, &
                                  ZTFloor,MATFloor,XMATFloor,XM2TFloor,XM3TFloor,XM4TFloor, &
                                  ZTOC,ZTM1OC,MATOC,XMATOC,XM2TOC,XM3TOC,XM4TOC, &
                                  ZTMX,ZTM1MX,MATMX,XMATMX,XM2TMX,XM3TMX,XM4TMX, RoomAirModel_Mundt, RoomAirModel_UserDefined

  USE General, ONLY: TrimSigDigits
  USE DataEnvironment, ONLY: Month, DayOfMonth
  USE DataLoopNode, ONLY: Node
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE DataGlobals,     ONLY: CurrentTime
  Use DataEnvironment, ONLY: DayOfYear

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  LOGICAL, INTENT(IN) :: ShortenTimeStepSys
  LOGICAL, INTENT(IN) :: UseZoneTimeStepHistory      ! if true then use zone timestep history, if false use system time step
  REAL(r64),    INTENT(IN) :: PriorTimeStep  ! the old value for timestep length is passed for possible use in interpolating

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)      :: SumIntGain                  ! Zone sum of convective internal gains
  REAL(r64)      :: SumHA                       ! Zone sum of Hc*Area
  REAL(r64)      :: SumHATsurf                  ! Zone sum of Hc*Area*Tsurf
  REAL(r64)      :: SumHATref                   ! Zone sum of Hc*Area*Tref, for ceiling diffuser convection correlation
  REAL(r64)      :: SumMCp                      ! Zone sum of MassFlowRate*Cp
  REAL(r64)      :: SumMCpT                     ! Zone sum of MassFlowRate*Cp*T
  REAL(r64)      :: SumSysMCp                   ! Zone sum of air system MassFlowRate*Cp
  REAL(r64)      :: SumSysMCpT                  ! Zone sum of air system MassFlowRate*Cp*T
  REAL(r64)      :: TempDepCoef                 ! Formerly CoefSumha
  REAL(r64)      :: TempIndCoef                 ! Formerly CoefSumhat
  REAL(r64)      :: AirCap                      ! Formerly CoefAirrat
!unused1208  REAL(r64)      :: TimeStepSeconds
  REAL(r64)      :: TempHistoryTerm
  INTEGER        :: ZoneNum
  REAL(r64)      :: ZoneT                       ! Zone temperature at previous time step
  INTEGER        :: RelativeZoneNum
  INTEGER        :: ActualZoneNum
  INTEGER :: I
  INTEGER :: Itemp
  REAL(r64)      :: SetpointOffset


  ! Staged thermostat setpoint
  IF (NumStageCtrZone > 0) THEN
    DO RelativeZoneNum = 1, NumStageCtrZone
      ActualZoneNum = StageControlledZone(RelativeZoneNum)%ActualZoneNum
      ZoneT = MAT(ActualZoneNum)
      IF (ShortenTimeStepSys) ZoneT = XMPT(ActualZoneNum)
      StageControlledZone(RelativeZoneNum)%HeatSetpoint=GetCurrentScheduleValue(StageControlledZone(RelativeZoneNum)%HSBchedIndex)
      StageControlledZone(RelativeZoneNum)%CoolSetpoint=GetCurrentScheduleValue(StageControlledZone(RelativeZoneNum)%CSBchedIndex)
      If (StageControlledZone(RelativeZoneNum)%HeatSetpoint .GE. StageControlledZone(RelativeZoneNum)%CoolSetpoint) Then
        StageControlledZone(RelativeZoneNum)%StageErrCount = StageControlledZone(RelativeZoneNum)%StageErrCount + 1
        if (StageControlledZone(RelativeZoneNum)%StageErrCount < 2) then
          CALL ShowWarningError('ZoneControl:Thermostat:StagedDualSetpoint: The heating setpoint is equal to or above '// &
              'the cooling setpoint in '//TRIM(StageControlledZone(RelativeZoneNum)%Name))
          CALL ShowContinueError('The zone heating setpoint is set to the cooling setpoint - 0.1C.')
          CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
        else
          CALL ShowRecurringWarningErrorAtEnd('The heating setpoint is still above '// &
              'the cooling setpoint',StageControlledZone(RelativeZoneNum)%StageErrIndex, &
               StageControlledZone(RelativeZoneNum)%HeatSetpoint, StageControlledZone(RelativeZoneNum)%HeatSetpoint)
        end if
        StageControlledZone(RelativeZoneNum)%HeatSetpoint = StageControlledZone(RelativeZoneNum)%CoolSetpoint-0.1 !???????????
      End If
      ! Determine either cooling or heating
      If (StageControlledZone(RelativeZoneNum)%CoolSetpoint < ZoneT) Then ! Cooling
        SetpointOffset = ZoneT - StageControlledZone(RelativeZoneNum)%CoolSetpoint
        Itemp = 0
        Do I=1, StageControlledZone(RelativeZoneNum)%NumOfCoolStages
          If (SetpointOffset >=  StageControlledZone(RelativeZoneNum)%CoolTOffset(I)) Then
            Itemp = -I
          End If
        End Do
        ZoneSysEnergyDemand(ActualZoneNum)%StageNum = Itemp
        If (SetpointOffset >= 0.5d0* StageControlledZone(RelativeZoneNum)%CoolThroRange) Then
          ZoneThermostatSetPointHi(ActualZoneNum) = StageControlledZone(RelativeZoneNum)%CoolSetpoint - &
             0.5d0*StageControlledZone(RelativeZoneNum)%CoolThroRange
        Else
          ZoneThermostatSetPointHi(ActualZoneNum) = StageControlledZone(RelativeZoneNum)%CoolSetpoint + &
             0.5d0*StageControlledZone(RelativeZoneNum)%CoolThroRange
        End If
        ZoneThermostatSetPointLo(ActualZoneNum) = ZoneThermostatSetPointHi(ActualZoneNum)
      Else If (StageControlledZone(RelativeZoneNum)%HeatSetpoint > ZoneT) Then ! heating
        SetpointOffset = ZoneT - StageControlledZone(RelativeZoneNum)%HeatSetpoint
        Itemp = 0
        Do I=1,StageControlledZone(RelativeZoneNum)%NumOfHeatStages
          If (ABS(SetpointOffset) >=  ABS(StageControlledZone(RelativeZoneNum)%HeatTOffset(I))) Then
            Itemp = I
          End If
        End Do
        ZoneSysEnergyDemand(ActualZoneNum)%StageNum = Itemp
        If (ABS(SetpointOffset) >= 0.5d0* StageControlledZone(RelativeZoneNum)%CoolThroRange) Then
          ZoneThermostatSetPointLo(ActualZoneNum) = StageControlledZone(RelativeZoneNum)%HeatSetpoint + &
             0.5d0*StageControlledZone(RelativeZoneNum)%HeatThroRange
        Else
          ZoneThermostatSetPointLo(ActualZoneNum) = StageControlledZone(RelativeZoneNum)%HeatSetpoint - &
             0.5d0*StageControlledZone(RelativeZoneNum)%HeatThroRange
        End If
        ZoneThermostatSetPointHi(ActualZoneNum) = ZoneThermostatSetPointLo(ActualZoneNum)
      Else
        ZoneThermostatSetPointHi(ActualZoneNum) = StageControlledZone(RelativeZoneNum)%CoolSetpoint + &
                                                0.5* StageControlledZone(RelativeZoneNum)%CoolThroRange
        ZoneThermostatSetPointLo(ActualZoneNum) = StageControlledZone(RelativeZoneNum)%HeatSetpoint - &
                                                0.5* StageControlledZone(RelativeZoneNum)%HeatThroRange
        ZoneSysEnergyDemand(ActualZoneNum)%StageNum = 0
      End If
    End Do
  End If

  ! Update zone temperatures
  DO ZoneNum = 1, NumofZones

    IF (ShortenTimeStepSys) THEN  !
      ! timestep has just shifted from full zone timestep to a new shorter system timestep
      !throw away last updates in corrector and rewind for resimulating smaller timestep
      IF (Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN ! roll back result for zone air node,
        Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Temp     = XMAT(ZoneNum)
        TempTstatAir(ZoneNum) = XMAT(ZoneNum)
        Node(Zone(ZoneNum)%SystemZoneNodeNumber)%HumRat   = WZoneTimeMinus1(ZoneNum)
        Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Enthalpy = PsyHFnTdbW(XMAT(ZoneNum),WZoneTimeMinus1(ZoneNum))
      ENDIF

      IF (NumOfSysTimeSteps /= NumOfSysTimeStepsLastZoneTimeStep) THEN ! cannot reuse existing DS data, interpolate from zone time

        Call DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                           !  MAT(ZoneNum),   XMAT(ZoneNum),   XM2T(ZoneNum),   XM3T(ZoneNum),   XM4T(ZoneNum), &
                             XMAT(ZoneNum),  XM2T(ZoneNum),   XM3T(ZoneNum),   XM4T(ZoneNum), XM4T(ZoneNum),  &
                             MAT(ZoneNum), DSXMAT(ZoneNum), DSXM2T(ZoneNum), DSXM3T(ZoneNum), DSXM4T(ZoneNum))
        Call DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                        !     ZoneAirHumRat(ZoneNum),   WZoneTimeMinus1(ZoneNum),   WZoneTimeMinus2(ZoneNum),   &
                        !                                 WZoneTimeMinus3(ZoneNum),   WZoneTimeMinus4(ZoneNum), &
                            WZoneTimeMinus1(ZoneNum),   WZoneTimeMinus2(ZoneNum),   &
                                          WZoneTimeMinus3(ZoneNum),   WZoneTimeMinus4(ZoneNum),  WZoneTimeMinus4(ZoneNum),&
                             ZoneAirHumRat(ZoneNum), DSWZoneTimeMinus1(ZoneNum), DSWZoneTimeMinus2(ZoneNum), &
                             DSWZoneTimeMinus3(ZoneNum), DSWZoneTimeMinus4(ZoneNum))


        IF (IsZoneDV(ZoneNum) .or. IsZoneUI(ZoneNum)) THEN

          CALL DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                             !   MATFloor(ZoneNum),   XMATFloor(ZoneNum),    XM2TFloor(ZoneNum),  &
                             !                        XM3TFloor(ZoneNum),    XM4TFloor(ZoneNum) ,   &
                                XMATFloor(ZoneNum),    XM2TFloor(ZoneNum),  &
                                                     XM3TFloor(ZoneNum),    XM4TFloor(ZoneNum) ,  XM4TFloor(ZoneNum) , &
                                MATFloor(ZoneNum), DSXMATFloor(ZoneNum),  DSXM2TFloor(ZoneNum),  &
                                                   DSXM3TFloor(ZoneNum),  DSXM4TFloor(ZoneNum))
          CALL DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                          !      MATOC(ZoneNum),   XMATOC(ZoneNum),    XM2TOC(ZoneNum),  &
                          !                        XM3TOC(ZoneNum),    XM4TOC(ZoneNum) ,   &
                                XMATOC(ZoneNum),    XM2TOC(ZoneNum),  &
                                                  XM3TOC(ZoneNum),    XM4TOC(ZoneNum) ,   XM4TOC(ZoneNum) , &
                                MATOC(ZoneNum), DSXMATOC(ZoneNum),  DSXM2TOC(ZoneNum),  &
                                                DSXM3TOC(ZoneNum),  DSXM4TOC(ZoneNum))
          CALL DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                              !  MATMX(ZoneNum),   XMATMX(ZoneNum),    XM2TMX(ZoneNum),  &
                              !                    XM3TMX(ZoneNum),    XM4TMX(ZoneNum) ,   &
                                XMATMX(ZoneNum),    XM2TMX(ZoneNum),  &
                                                  XM3TMX(ZoneNum),    XM4TMX(ZoneNum) ,  XM4TMX(ZoneNum) , &
                                MATMX(ZoneNum), DSXMATMX(ZoneNum),  DSXM2TMX(ZoneNum),  &
                                                DSXM3TMX(ZoneNum),  DSXM4TMX(ZoneNum))
        ENDIF

      ELSE ! reuse history data in DS terms from last zone time step to preserve information that would be lost
         ! do nothing because DS history would have been pushed prior and should be ready

      ENDIF

    ENDIF
    ! now update the variables actually used in the balance equations.
    IF(UseZoneTimeStepHistory) THEN
      ZTM1(ZoneNum)                = XMAT(ZoneNum)
      ZTM2(ZoneNum)                = XM2T(ZoneNum)
      ZTM3(ZoneNum)                = XM3T(ZoneNum)

      WZoneTimeMinus1Temp(ZoneNum) = WZoneTimeMinus1(ZoneNum)
      WZoneTimeMinus2Temp(ZoneNum) = WZoneTimeMinus2(ZoneNum)
      WZoneTimeMinus3Temp(ZoneNum) = WZoneTimeMinus3(ZoneNum)

    ELSE  ! use down-stepped history
      ZTM1(ZoneNum)                = DSXMAT(ZoneNum)
      ZTM2(ZoneNum)                = DSXM2T(ZoneNum)
      ZTM3(ZoneNum)                = DSXM3T(ZoneNum)

      WZoneTimeMinus1Temp(ZoneNum) = DSWZoneTimeMinus1(ZoneNum)
      WZoneTimeMinus2Temp(ZoneNum) = DSWZoneTimeMinus2(ZoneNum)
      WZoneTimeMinus3Temp(ZoneNum) = DSWZoneTimeMinus3(ZoneNum)

    END IF

    AIRRAT(ZoneNum) = Zone(ZoneNum)%Volume*ZoneVolCapMultpSens* &
               PsyRhoAirFnPbTdbW(OutBaroPress,MAT(ZoneNum),ZoneAirHumRat(ZoneNum))* &
               PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum),MAT(ZoneNum))/(TimeStepSys*SecInHour)
    AirCap = AIRRAT(ZoneNum)


    ! Calculate the various heat balance sums

    ! NOTE: SumSysMCp and SumSysMCpT are not used in the predict step
    CALL CalcZoneSums(ZoneNum, SumIntGain, SumHA, SumHATsurf, SumHATref, SumMCp, SumMCpT, SumSysMCp, SumSysMCpT)

    TempDepCoef = SumHA + SumMCp
    TempIndCoef = SumIntGain + SumHATsurf - SumHATref + SumMCpT + SysDepZoneLoadsLagged(ZoneNum)
    IF (AirModel(ZoneNum)%AirModelType.EQ.RoomAirModel_Mixing) THEN
        TempHistoryTerm = AirCap * (3.0d0 * ZTM1(ZoneNum) - (3.0d0/2.0d0) * ZTM2(ZoneNum) + (1.0d0/3.0d0) * ZTM3(ZoneNum))
        TempDepZnLd(ZoneNum) = (11.0d0/6.0d0) * AirCap + TempDepCoef
        TempIndZnLd(ZoneNum) = TempHistoryTerm + TempIndCoef
    ELSEIF (IsZoneDV(ZoneNum)) THEN
       ! UCSD displacement ventilation model - make dynamic term independent of TimeStepSys
        TempHistoryTerm = AirCap * (3.0d0 * ZTM1(ZoneNum) - (3.0d0/2.0d0) * ZTM2(ZoneNum) + (1.0d0/3.0d0) * ZTM3(ZoneNum))
        TempDepZnLd(ZoneNum) = (11.0d0/6.0d0) * AirCap + TempDepCoef
        TempIndZnLd(ZoneNum) = TempHistoryTerm + TempIndCoef
    ELSEIF (IsZoneUI(ZoneNum)) THEN
       ! UCSD UFAD model - make dynamic term independent of TimeStepSys
        TempHistoryTerm = AirCap * (3.0d0 * ZTM1(ZoneNum) - (3.0d0/2.0d0) * ZTM2(ZoneNum) + (1.0d0/3.0d0) * ZTM3(ZoneNum))
        TempDepZnLd(ZoneNum) = (11.0d0/6.0d0) * AirCap + TempDepCoef
        TempIndZnLd(ZoneNum) = TempHistoryTerm + TempIndCoef
    ELSE ! other imperfectly mixed room models
        TempHistoryTerm = AirCap * (3.0d0 * ZTM1(ZoneNum) - (3.0d0/2.0d0) * ZTM2(ZoneNum) + (1.0d0/3.0d0) * ZTM3(ZoneNum))
        TempDepZnLd(ZoneNum) = (11.0d0/6.0d0) * AirCap + TempDepCoef
        TempIndZnLd(ZoneNum) = TempHistoryTerm + TempIndCoef
    END IF

    ! Exact solution or Euler method
    ShortenTimeStepSysRoomAir = .FALSE.
    If (ZoneAirSolutionAlgo .NE. Use3rdOrder) Then
      If (ShortenTimeStepSys .and. TimeStepSys .LT. TimeStepZone) Then
        If (PreviousTimeStep < TimeStepZone) Then
          ZoneT1(ZoneNum) = ZoneTM2(ZoneNum)
          ZoneW1(ZoneNum) = ZoneWM2(ZoneNum)
        Else
          ZoneT1(ZoneNum) = ZoneTMX(ZoneNum)
          ZoneW1(ZoneNum) = ZoneWMX(ZoneNum)
        End If
        ShortenTimeStepSysRoomAir = .TRUE.
      Else
        ZoneT1(ZoneNum) = ZT(ZoneNum)
        ZoneW1(ZoneNum) = ZoneAirHumRat(ZoneNum)
      End If
      TempDepZnLd(ZoneNum) = TempDepCoef
      TempIndZnLd(ZoneNum) = TempIndCoef
    End If

    ! Calculate the predicted zone load to be provided by the system with the given desired zone air temperature
    CALL CalcPredictedSystemLoad(ZoneNum)

    ! Calculate the predicted zone load to be provided by the system with the given desired humidity ratio
    CALL CalcPredictedHumidityRatio(ZoneNum)

  END DO

  RETURN

END SUBROUTINE PredictSystemLoads

SUBROUTINE CalcZoneAirTempSetpoints

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Russ Taylor
          !       DATE WRITTEN   Nov 1997
          !       MODIFIED       Aug 2013, Xiufeng Pang (XP) - Added code for updating set points during
          !                      optimum start period
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This routine sets what the setpoints for each controlled zone should be based on schedules.
          ! This is called each time step.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE ScheduleManager, ONLY: GetCurrentScheduleValue, GetScheduleValuesForDay
  USE General, ONLY: TrimSigDigits
  USE DataZoneControls, ONLY: OccRoomTSetPointHeat, OccRoomTSetPointCool

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: RelativeZoneNum
  INTEGER :: ActualZoneNum
  INTEGER :: TempControlSchedIndex
  INTEGER :: SetPointTempSchedIndex
  INTEGER :: SetPointTempSchedIndexHot
  INTEGER :: SetPointTempSchedIndexCold
  INTEGER :: SchedNameIndex
  INTEGER :: SchedTypeIndex
  REAL(r64), ALLOCATABLE, DIMENSION(:,:) :: DaySPValues !Day room temp setpoint values - for optimum start
  REAL(r64) :: OccRoomSP !Occupied room temp set point - for optimum start
  INTEGER :: OccStartTime ! Occupancy start time - for optimum start

          ! FLOW:
   TempControlType = 0 ! Default

   ! Place holder for occupied heating and cooling set points - for optimum start
   IF (.NOT. ALLOCATED(OccRoomTSetPointHeat)) THEN
        ALLOCATE(OccRoomTSetPointHeat(NumOfZones))
   END IF
   IF (.NOT. ALLOCATED(OccRoomTSetPointCool)) THEN
        ALLOCATE(OccRoomTSetPointCool(NumOfZones))
   END IF
   OccRoomTSetPointHeat = 0.0d0
   OccRoomTSetPointCool = 100.0d0

   DO RelativeZoneNum = 1, NumTempControlledZones

    ! What if this zone not controlled???
    ActualZoneNum = TempControlledZone(RelativeZoneNum)%ActualZoneNum
    TempControlSchedIndex = TempControlledZone(RelativeZoneNum)%CTSchedIndex
    TempControlType(ActualZoneNum) = GetCurrentScheduleValue(TempControlSchedIndex)

    ! Error detection for these values is done in the Get routine

    SELECT CASE (TempControlType(ActualZoneNum)) ! Is this missing the possibility of sometimes having no control on a zone
                                                 ! during the simulation?
      CASE (0) ! Uncontrolled

      CASE (SingleHeatingSetPoint)

        SchedNameIndex = TempControlledZone(RelativeZoneNum)%SchIndx_SingleHeatSetPoint

        SchedTypeIndex = TempControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)

        SetPointTempSchedIndex = SetPointSingleHeating(SchedTypeIndex)%TempSchedIndex
        TempZoneThermostatSetPoint(ActualZoneNum) = GetCurrentScheduleValue(SetPointTempSchedIndex)
        Call AdjustAirSetpointsforOpTempCntrl(RelativeZoneNum, ActualZoneNum, TempZoneThermostatSetPoint(ActualZoneNum))

        ZoneThermostatSetPointLo(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
!        ZoneThermostatSetPointHi(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)

      CASE (SingleCoolingSetPoint)

        SchedNameIndex = TempControlledZone(RelativeZoneNum)%SchIndx_SingleCoolSetPoint

        SchedTypeIndex = TempControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)

        SetPointTempSchedIndex = SetPointSingleCooling(SchedTypeIndex)%TempSchedIndex
        TempZoneThermostatSetPoint(ActualZoneNum) = GetCurrentScheduleValue(SetPointTempSchedIndex)
        Call AdjustAirSetpointsforOpTempCntrl(RelativeZoneNum, ActualZoneNum, TempZoneThermostatSetPoint(ActualZoneNum))
        ZoneThermostatSetPointHi(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
!        ZoneThermostatSetPointLo(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)

        CALL AdjustCoolingSetPointforTempAndHumidityControl(RelativeZoneNum,ActualZoneNum)

      CASE (SingleHeatCoolSetPoint)

        SchedNameIndex = TempControlledZone(RelativeZoneNum)%SchIndx_SingleHeatCoolSetPoint

        SchedTypeIndex = TempControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)

        SetPointTempSchedIndex = SetPointSingleHeatCool(SchedTypeIndex)%TempSchedIndex
        TempZoneThermostatSetPoint(ActualZoneNum) = GetCurrentScheduleValue(SetPointTempSchedIndex)
        Call AdjustAirSetpointsforOpTempCntrl(RelativeZoneNum, ActualZoneNum, TempZoneThermostatSetPoint(ActualZoneNum))

        ZoneThermostatSetPointHi(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
        ZoneThermostatSetPointLo(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)

        !Change the room set point to occupied set point during optimum start period--------------

         IF (Allocated(OptStartData%OptStartFlag)) THEN
            IF (.not. allocated(DaySPValues)) THEN
                ALLOCATE (DaySPValues(24,NumOfTimeStepInHour))
            END IF
            IF (OptStartData%ActualZoneNum(ActualZoneNum)==ActualZoneNum) THEN
              Call GetScheduleValuesForDay(SetPointTempSchedIndexCold,DaySPValues)
              OccStartTime = ceiling(OptStartData%OccStartTime(ActualZoneNum)) + 1
              TempZoneThermostatSetPoint(ActualZoneNum)=DaySPValues(OccStartTime,1)
            END IF

        IF (OptStartData%OptStartFlag(ActualZoneNum)) THEN
           ZoneThermostatSetPointHi(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
           ZoneThermostatSetPointLo(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
        END IF
        END IF
        !--------------------------------------------------------------------------------------------


      CASE (DualSetPointWithDeadBand)

        SchedNameIndex = TempControlledZone(RelativeZoneNum)%SchIndx_DualSetPointWDeadBand

        SchedTypeIndex = TempControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)

        SetPointTempSchedIndexHot = SetPointDualHeatCool(SchedTypeIndex)%HeatTempSchedIndex
        SetPointTempSchedIndexCold = SetPointDualHeatCool(SchedTypeIndex)%CoolTempSchedIndex
        ZoneThermostatSetPointHi(ActualZoneNum) = GetCurrentScheduleValue(SetPointTempSchedIndexCold)
        Call AdjustAirSetpointsforOpTempCntrl(RelativeZoneNum, ActualZoneNum, ZoneThermostatSetPointHi(ActualZoneNum))

        ZoneThermostatSetPointLo(ActualZoneNum) = GetCurrentScheduleValue(SetPointTempSchedIndexHot)
        Call AdjustAirSetpointsforOpTempCntrl(RelativeZoneNum, ActualZoneNum, ZoneThermostatSetPointLo(ActualZoneNum))

        !Change the room set point to occupied set point during optimum start period--------------

        IF (Allocated(OptStartData%OptStartFlag)) THEN
            IF (.not. allocated(DaySPValues)) THEN
                ALLOCATE (DaySPValues(24,NumOfTimeStepInHour))
            END IF
            IF (OptStartData%ActualZoneNum(ActualZoneNum)==ActualZoneNum) THEN
              Call GetScheduleValuesForDay(SetPointTempSchedIndexCold,DaySPValues)
              OccStartTime = ceiling(OptStartData%OccStartTime(ActualZoneNum)) + 1
              OccRoomTSetPointCool(ActualZoneNum) = DaySPValues(OccStartTime,1)
              Call GetScheduleValuesForDay(SetPointTempSchedIndexHot,DaySPValues)
              OccRoomTSetPointHeat(ActualZoneNum) = DaySPValues(OccStartTime,1)
            END IF

        IF (OptStartData%OptStartFlag(ActualZoneNum)) THEN
           ZoneThermostatSetPointHi(ActualZoneNum) = OccRoomTSetPointCool(ActualZoneNum)
           ZoneThermostatSetPointLo(ActualZoneNum) = OccRoomTSetPointHeat(ActualZoneNum)
        END IF
        END IF
        !--------------------------------------------------------------------------------------------

        CALL AdjustCoolingSetPointforTempAndHumidityControl(RelativeZoneNum,ActualZoneNum)

      CASE DEFAULT
        CALL ShowSevereError('CalcZoneAirTempSetpoints: Illegal control type for Zone='//TRIM(Zone(ActualZoneNum)%Name)//  &
                               ', Found value='//TRIM(TrimSigDigits(TempControlType(ActualZoneNum)))//  &
                               ', in Schedule='//TRIM(TempControlledZone(RelativeZoneNum)%ControlTypeSchedName))

    END SELECT

  END DO

  If (NumComfortControlledZones > 0) Call CalcZoneAirComfortSetpoints
  RETURN

END SUBROUTINE CalcZoneAirTempSetpoints

SUBROUTINE CalcPredictedSystemLoad(ZoneNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Russ Taylor
          !       DATE WRITTEN   Nov 1997
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine calculates the predicted system load for a time step.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE DataLoopNode, ONLY: Node
  USE General, ONLY: RoundSigDigits

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN)  :: ZoneNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: LoadToHeatingSetPoint
  REAL(r64) :: LoadToCoolingSetPoint
  REAL(r64) :: ZoneSetPoint

          ! FLOW:
  DeadBandOrSetback(ZoneNum) = .FALSE.
  ZoneSetPoint = 0.0d0
  LoadToHeatingSetPoint=0.0d0
  LoadToCoolingSetPoint=0.0d0

  SELECT CASE (TempControlType(ZoneNum))

    CASE (0)
      ! Uncontrolled Zone
      LoadToHeatingSetPoint = 0.0d0
      LoadToCoolingSetPoint = 0.0d0
      ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0d0

    CASE (SingleHeatingSetPoint)
      ! Determine zone load based on
      ! Qload + Qsys = 0 and Qsys = mCp(Tsys-Tzone)
      ! System Load Sign Convention:
      !     - -> Cooling required to reach setpoint
      !     + -> Heating required to reach setpoint

!PH 3/2/04      LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) * TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum))
      SELECT CASE (ZoneAirSolutionAlgo)
        CASE (Use3rdOrder)
          LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) * TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum))
      ! Exact solution
        CASE (UseAnalyticalSolution)
          If (TempDepZnLd(ZoneNum) .eq. 0.0d0) Then ! B=0
            LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) - &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
          Else
            LoadToHeatingSetPoint = TempDepZnLd(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) &
            -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum))))/ &
            (1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum))))-TempIndZnLd(ZoneNum)
          End If
        CASE (UseEulerMethod)
          LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum)- &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum)) &
                                - TempIndZnLd(ZoneNum)
      END SELECT
      ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint
      ZoneSetPoint = TempZoneThermostatSetPoint(ZoneNum)
      LoadToCoolingSetPoint = LoadToHeatingSetPoint
        ! for consistency with the other cases, use LE instead of LT and don't subtract 1.0 Watt as a way of pushing the zero load
        ! case over the threshold
      IF ((ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired) .LE. 0.0d0) DeadBandOrSetback(ZoneNum) = .TRUE.

    CASE (SingleCoolingSetPoint)

!PH 3/2/04      LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) * TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum))
      SELECT CASE (ZoneAirSolutionAlgo)
        CASE (Use3rdOrder)
          LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) * &
                              (TempZoneThermostatSetPoint(ZoneNum)) - TempIndZnLd(ZoneNum))
        CASE (UseAnalyticalSolution)
          If (TempDepZnLd(ZoneNum) .eq. 0.0d0) Then ! B=0
            LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum)- &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
          Else
            LoadToCoolingSetPoint = TempDepZnLd(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) &
                  -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) &
                                /(1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) - TempIndZnLd(ZoneNum)
          End If
        CASE (UseEulerMethod)
          LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum)- &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum)
      END SELECT
      ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
      ZoneSetPoint = TempZoneThermostatSetPoint(ZoneNum)
      LoadToHeatingSetPoint = LoadToCoolingSetPoint
        ! for consistency with the other cases, use GE instead of GT and don't add 1.0 Watt as a way of pushing the zero load
        ! case over the threshold
      IF ((ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired) .GE. 0.0d0) DeadBandOrSetback(ZoneNum) = .TRUE.

    CASE (SingleHeatCoolSetPoint)

!PH 3/2/04      LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) * TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum))
!PH 3/2/04      !LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) * TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum))
      SELECT CASE (ZoneAirSolutionAlgo)
        CASE (Use3rdOrder)
          LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) * &
                              (TempZoneThermostatSetPoint(ZoneNum)) - TempIndZnLd(ZoneNum))
          LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) * &
                              (TempZoneThermostatSetPoint(ZoneNum)) - TempIndZnLd(ZoneNum))
      ! Exact solution
        CASE (UseAnalyticalSolution)
          If (TempDepZnLd(ZoneNum) .eq. 0.0d0) Then ! B=0
            LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum)- &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
            LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum)- &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
          Else
            LoadToHeatingSetPoint = TempDepZnLd(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) &
                         -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) &
                                  /(1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) - TempIndZnLd(ZoneNum)
            LoadToCoolingSetPoint = TempDepZnLd(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) &
                         -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) &
                                /(1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) - TempIndZnLd(ZoneNum)
          End If
        CASE (UseEulerMethod)
          LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) - &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum)
          LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(TempZoneThermostatSetPoint(ZoneNum) - &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*TempZoneThermostatSetPoint(ZoneNum) - TempIndZnLd(ZoneNum)
      END SELECT
      ZoneSetPoint = TempZoneThermostatSetPoint(ZoneNum)

!PH 3/2/04      ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint ! = LoadToCoolingSetPoint
! Note that LoadToHeatingSetPoint is generally not equal to LoadToCoolingSetPoint
! when the heating and cooling set-points are equal if the zone is unmixed,
! e.g. displacement ventilation or UFAD, since the stratification is generally not the same in heating and cooling modes

      ! Possible combinations:
      ! 1/  LoadToHeatingSetPoint > 0 & LoadToCoolingSetPoint > 0 -->  Heating required
      ! 2/  LoadToHeatingSetPoint  >  LoadToCoolingSetPoint       -->  Possible in the unmixed case but should be trapped
      !                                                                 as a poor choice of set-points
      ! 3/  LoadToHeatingSetPoint < 0 & LoadToCoolingSetPoint < 0 -->  Cooling Required
      ! 4/  LoadToHeatingSetPoint <=0 & LoadToCoolingSetPoint >=0 -->  Dead Band Operation ! includes zero load cases
! First trap bad set-points
      IF (LoadToHeatingSetPoint .GT. LoadToCoolingSetPoint ) THEN
         CALL ShowSevereError('SingleHeatCoolSetPoint: Effective heating set-point higher than effective cooling set-point - '// &
                             'use DualSetPointWithDeadBand if using unmixed air model')
         CALL ShowContinueErrorTimeStamp('occurs in Zone='//TRIM(Zone(ZoneNum)%Name))
         CALL ShowContinueError('LoadToHeatingSetPoint='//TRIM(RoundSigDigits(LoadToHeatingSetPoint,3))//  &
                                ', LoadToCoolingSetPoint='//TRIM(RoundSigDigits(LoadToCoolingSetPoint,3)))
         CALL ShowContinueError('Zone TempDepZnLd='//TRIM(RoundSigDigits(TempDepZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone TempIndZnLd='//TRIM(RoundSigDigits(TempIndZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone ThermostatSetPoint='//TRIM(RoundSigDigits(TempZoneThermostatSetPoint(ZoneNum),2)))
         CALL ShowFatalError('Program terminates due to above conditions.')
      END IF

      IF (LoadToHeatingSetPoint .GT. 0.0d0 .AND. LoadToCoolingSetPoint .GT. 0.0d0) THEN
         ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint
      ELSE IF (LoadToHeatingSetPoint .LT. 0.0d0 .AND. LoadToCoolingSetPoint .LT. 0.0d0) THEN
         ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
      ELSE IF (LoadToHeatingSetPoint .LE. 0.0d0 .AND. LoadToCoolingSetPoint .GE. 0.0d0) THEN ! deadband includes zero loads
         ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0d0
         IF(Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN
            ZoneSetPoint = Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Temp
            ZoneSetPoint = MAX(ZoneSetPoint, ZoneThermostatSetPointLo(ZoneNum)) ! trap out of deadband
            ZoneSetPoint = MIN(ZoneSetPoint, ZoneThermostatSetPointHi(ZoneNum)) ! trap out of deadband
         END IF
         DeadBandOrSetback(ZoneNum) = .TRUE.
      ELSE  ! this should never occur!
         CALL ShowSevereError('SingleHeatCoolSetPoint: Unanticipated combination of heating and cooling loads - '// &
                             'report to EnergyPlus Development Team')
         CALL ShowContinueErrorTimeStamp('occurs in Zone='//TRIM(Zone(ZoneNum)%Name))
         CALL ShowContinueError('LoadToHeatingSetPoint='//TRIM(RoundSigDigits(LoadToHeatingSetPoint,3))//  &
                                ', LoadToCoolingSetPoint='//TRIM(RoundSigDigits(LoadToCoolingSetPoint,3)))
         CALL ShowContinueError('Zone TempDepZnLd='//TRIM(RoundSigDigits(TempDepZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone TempIndZnLd='//TRIM(RoundSigDigits(TempIndZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone ThermostatSetPoint='//TRIM(RoundSigDigits(TempZoneThermostatSetPoint(ZoneNum),2)))
         CALL ShowFatalError('Program terminates due to above conditions.')
      END IF

    CASE (DualSetPointWithDeadBand)

      SELECT CASE (ZoneAirSolutionAlgo)
        CASE (Use3rdOrder)
          LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) * &
                              (ZoneThermostatSetPointLo(ZoneNum)) - TempIndZnLd(ZoneNum))
          LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) * &
                              (ZoneThermostatSetPointHi(ZoneNum)) - TempIndZnLd(ZoneNum))
      ! Exact solution
        CASE (UseAnalyticalSolution)
          If (TempDepZnLd(ZoneNum) .eq. 0.0d0) Then ! B=0
            LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum)- &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
            LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointHi(ZoneNum)- &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
          Else
            LoadToHeatingSetPoint = TempDepZnLd(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum) &
                    -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum))))/ &
                                (1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) - TempIndZnLd(ZoneNum)
            LoadToCoolingSetPoint = TempDepZnLd(ZoneNum)*(ZoneThermostatSetPointHi(ZoneNum) &
                    -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum))))/ &
                                (1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) - TempIndZnLd(ZoneNum)
          End If
        CASE (UseEulerMethod)
          LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum)- &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*ZoneThermostatSetPointLo(ZoneNum) - TempIndZnLd(ZoneNum)
          LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointHi(ZoneNum)- &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*ZoneThermostatSetPointHi(ZoneNum) - TempIndZnLd(ZoneNum)
      END SELECT

      ! Possible combinations:
      ! 1/  LoadToHeatingSetPoint > 0 & LoadToCoolingSetPoint > 0 -->  Heating required
      ! 2/  LoadToHeatingSetPoint  >  LoadToCoolingSetPoint       -->  Possible in the unmixed case but should be trapped
      !                                                                  as a poor choice of set-points
      ! 3/  LoadToHeatingSetPoint < 0 & LoadToCoolingSetPoint < 0 -->  Cooling Required
      ! 4/  LoadToHeatingSetPoint <=0 & LoadToCoolingSetPoint >=0 -->  Dead Band Operation - includes zero load cases
! First trap bad set-points
      IF (LoadToHeatingSetPoint .GT. LoadToCoolingSetPoint ) THEN
         CALL ShowSevereError('DualSetPointWithDeadBand: Effective heating set-point higher than effective cooling set-point - '// &
                             'increase deadband if using unmixed air model')
         CALL ShowContinueErrorTimeStamp('occurs in Zone='//TRIM(Zone(ZoneNum)%Name))
         CALL ShowContinueError('LoadToHeatingSetPoint='//TRIM(RoundSigDigits(LoadToHeatingSetPoint,3))//  &
                                ', LoadToCoolingSetPoint='//TRIM(RoundSigDigits(LoadToCoolingSetPoint,3)))
         CALL ShowContinueError('Zone TempDepZnLd='//TRIM(RoundSigDigits(TempDepZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone TempIndZnLd='//TRIM(RoundSigDigits(TempIndZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone Heating ThermostatSetPoint='//TRIM(RoundSigDigits(ZoneThermostatSetPointLo(ZoneNum),2)))
         CALL ShowContinueError('Zone Cooling ThermostatSetPoint='//TRIM(RoundSigDigits(ZoneThermostatSetPointHi(ZoneNum),2)))
         CALL ShowFatalError('Program terminates due to above conditions.')
      END IF
      IF (LoadToHeatingSetPoint .GT. 0.0d0 .AND. LoadToCoolingSetPoint .GT. 0.0d0) THEN
         ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint
         ZoneSetPoint = ZoneThermostatSetPointLo(ZoneNum)
      ELSE IF (LoadToHeatingSetPoint .LT. 0.0d0 .AND. LoadToCoolingSetPoint .LT. 0.0d0) THEN
         ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
         ZoneSetPoint = ZoneThermostatSetPointHi(ZoneNum)
      ELSE IF (LoadToHeatingSetPoint .LE. 0.0d0 .AND. LoadToCoolingSetPoint .GE. 0.0d0) THEN ! deadband includes zero loads
        ! this turns out to cause instabilities sometimes? that lead to setpoint errors if predictor is off.
         ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0d0
         IF(Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN
            ZoneSetPoint = Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Temp
            ZoneSetPoint = MAX(ZoneSetPoint, ZoneThermostatSetPointLo(ZoneNum)) ! trap out of deadband
            ZoneSetPoint = MIN(ZoneSetPoint, ZoneThermostatSetPointHi(ZoneNum)) ! trap out of deadband
         END IF
         DeadBandOrSetback(ZoneNum) = .TRUE.
      ELSE  ! this should never occur!
         CALL ShowSevereError('DualSetPointWithDeadBand: Unanticipated combination of heating and cooling loads - '// &
                             'report to EnergyPlus Development Team')
         CALL ShowContinueErrorTimeStamp('occurs in Zone='//TRIM(Zone(ZoneNum)%Name))
         CALL ShowContinueError('LoadToHeatingSetPoint='//TRIM(RoundSigDigits(LoadToHeatingSetPoint,3))//  &
                                ', LoadToCoolingSetPoint='//TRIM(RoundSigDigits(LoadToCoolingSetPoint,3)))
         CALL ShowContinueError('Zone Heating Set-point='//TRIM(RoundSigDigits(ZoneThermostatSetPointLo(ZoneNum),2)))
         CALL ShowContinueError('Zone Cooling Set-point='//TRIM(RoundSigDigits(ZoneThermostatSetPointHi(ZoneNum),2)))
         CALL ShowContinueError('Zone TempDepZnLd='//TRIM(RoundSigDigits(TempDepZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone TempIndZnLd='//TRIM(RoundSigDigits(TempIndZnLd(ZoneNum),2)))
         CALL ShowContinueError('Zone ThermostatSetPoint='//TRIM(RoundSigDigits(TempZoneThermostatSetPoint(ZoneNum),2)))

         CALL ShowFatalError('Program terminates due to above conditions.')
      END IF

  END SELECT

    ! Staged control zone
    IF (NumStageCtrZone > 0) THEN
      If (StageZoneLogic(ZoneNum)) Then
        If (ZoneSysEnergyDemand(ZoneNum)%StageNum ==0) Then ! No load
          LoadToHeatingSetPoint = 0.0d0
          LoadToCoolingSetPoint = 0.0d0
          ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0d0
          IF(Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN
            ZoneSetPoint = Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Temp
            ZoneSetPoint = MAX(ZoneSetPoint, ZoneThermostatSetPointLo(ZoneNum)) ! trap out of deadband
            ZoneSetPoint = MIN(ZoneSetPoint, ZoneThermostatSetPointHi(ZoneNum)) ! trap out of deadband
          END IF
          DeadBandOrSetback(ZoneNum) = .TRUE.
        Else If (ZoneSysEnergyDemand(ZoneNum)%StageNum <0) Then ! Cooling load
          SELECT CASE (ZoneAirSolutionAlgo)
            CASE (Use3rdOrder)
              LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) * &
                              (ZoneThermostatSetPointHi(ZoneNum)) - TempIndZnLd(ZoneNum))
            CASE (UseAnalyticalSolution)
              If (TempDepZnLd(ZoneNum) .eq. 0.0d0) Then ! B=0
                LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointHi(ZoneNum)- &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
              Else
                LoadToCoolingSetPoint = TempDepZnLd(ZoneNum)*(ZoneThermostatSetPointHi(ZoneNum) &
                  -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) &
                                /(1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum)))) - TempIndZnLd(ZoneNum)
              End If
            CASE (UseEulerMethod)
              LoadToCoolingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointHi(ZoneNum)- &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*ZoneThermostatSetPointHi(ZoneNum) - TempIndZnLd(ZoneNum)
          END SELECT
          ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
          ZoneSetPoint = ZoneThermostatSetPointHi(ZoneNum)
          LoadToHeatingSetPoint = LoadToCoolingSetPoint
          IF ((ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired) .GE. 0.0) DeadBandOrSetback(ZoneNum) = .TRUE.
        Else ! Heating load
          SELECT CASE (ZoneAirSolutionAlgo)
            CASE (Use3rdOrder)
              LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) * ZoneThermostatSetPointLo(ZoneNum) - TempIndZnLd(ZoneNum))
            ! Exact solution
            CASE (UseAnalyticalSolution)
              If (TempDepZnLd(ZoneNum) .eq. 0.0d0) Then ! B=0
                LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum) - &
                                ZoneT1(ZoneNum)) - TempIndZnLd(ZoneNum)
              Else
                LoadToHeatingSetPoint = TempDepZnLd(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum) &
                 -ZoneT1(ZoneNum)*exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum))))/ &
                 (1.0d0-exp(MIN(700.d0,-TempDepZnLd(ZoneNum)/AIRRAT(ZoneNum))))-TempIndZnLd(ZoneNum)
              End If
            CASE (UseEulerMethod)
              LoadToHeatingSetPoint = AIRRAT(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum)- &
                                ZoneT1(ZoneNum)) + TempDepZnLd(ZoneNum)*(ZoneThermostatSetPointLo(ZoneNum)) &
                                - TempIndZnLd(ZoneNum)
          END SELECT
          ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint
          ZoneSetPoint = ZoneThermostatSetPointLo(ZoneNum)
          LoadToCoolingSetPoint = LoadToHeatingSetPoint
          IF ((ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired) .LE. 0.0) DeadBandOrSetback(ZoneNum) = .TRUE.
        End If
      End If
    End If

  !If the ZoneNodeNum has been set for a Controlled Zone, then the zone setpoint is placed on the node.
  IF(Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN
     Node(Zone(ZoneNum)%SystemZoneNodeNumber)%TempSetPoint = ZoneSetPoint
  END IF

  IF(ZoneSetPoint .GT. ZoneSetPointLast(ZoneNum))THEN
    SetBack(ZoneNum) = .TRUE.
  ELSE
    SetBack(ZoneNum) = .FALSE.
  END IF

  ZoneSetPointLast(ZoneNum) = ZoneSetPoint

  ! Save the unmultiplied zone load to a report variable
  SNLoadPredictedRate(ZoneNum) = ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired * LoadCorrectionFactor(ZoneNum)
  SNLoadPredictedHSPRate(ZoneNum) = LoadToHeatingSetPoint * LoadCorrectionFactor(ZoneNum)
  SNLoadPredictedCSPRate(ZoneNum) = LoadToCoolingSetPoint * LoadCorrectionFactor(ZoneNum)
  CurDeadBandOrSetback(ZoneNum) = DeadBandOrSetback(ZoneNum)

  ! Apply the Zone Multiplier and Load Correction factor to the total zone load
  ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired &
    * Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier * LoadCorrectionFactor(ZoneNum)
  ZoneSysEnergyDemand(ZoneNum)%OutputRequiredToHeatingSP = LoadToHeatingSetPoint &
    * Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier * LoadCorrectionFactor(ZoneNum)
  ZoneSysEnergyDemand(ZoneNum)%OutputRequiredToCoolingSP = LoadToCoolingSetPoint &
    * Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier * LoadCorrectionFactor(ZoneNum)

  !init each sequenced demand to the full output
  IF (ALLOCATED(ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequired)) &
      ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequired = & ! array assignment
                        ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired
  IF (ALLOCATED(ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToHeatingSP)) &
      ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToHeatingSP = & ! array assignment
                        ZoneSysEnergyDemand(ZoneNum)%OutputRequiredToHeatingSP
  IF (ALLOCATED(ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToCoolingSP)) &
      ZoneSysEnergyDemand(ZoneNum)%SequencedOutputRequiredToCoolingSP = & ! array assignment
                        ZoneSysEnergyDemand(ZoneNum)%OutputRequiredToCoolingSP

  RETURN

END SUBROUTINE CalcPredictedSystemLoad

SUBROUTINE CalcPredictedHumidityRatio(ZoneNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   May 2001
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine does the prediction step for humidity control

          ! METHODOLOGY EMPLOYED:
          ! This solves for the required system moisture required to try and achieve the desired
          ! Humidity Ratio in the Zone

          ! REFERENCES:
          ! Routine FinalZnCalcs - FINAL ZONE CALCULATIONS, authored by Dale Herron
          ! for BLAST.

          ! USE STATEMENTS:
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE General,         ONLY: RoundSigDigits
  USE DataSurfaces,    ONLY: Surface, HeatTransferModel_EMPD, HeatTransferModel_HAMT

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: ZoneNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: LatentGain ! Zone latent load
  REAL(r64) :: RhoAir
  REAL(r64) :: A
  REAL(r64) :: B
  REAL(r64) :: C
  REAL(r64) :: SysTimeStepInSeconds
  REAL(r64) :: H2OHtOfVap
  REAL(r64) :: RHSetPoint             ! Relative Humidity in percent
  REAL(r64) :: WZoneSetPoint
  INTEGER   :: HumidControlledZoneNum
  LOGICAL   :: ControlledHumidZoneFlag     ! This determines whether this is a humidity controlled zone or not
  REAL(r64) :: ZoneRHHumidifyingSetPoint   ! Zone humidifying set point (%)
  REAL(r64) :: ZoneRHDehumidifyingSetPoint ! Zone dehumidifying set point (%)
  REAL(r64) :: LoadToHumidifySetPoint      ! Moisture load at humidifying set point
  REAL(r64) :: LoadToDehumidifySetPoint    ! Moisture load at dehumidifying set point
  REAL(r64) :: ZoneAirRH                   ! Zone air relative humidity
  LOGICAL   :: SingleSetpoint              ! This determines whether both setpoint are equal or not

          ! FLOW:
  LoadToHumidifySetPoint=0.0d0
  LoadToDehumidifySetPoint=0.0d0
  SingleSetpoint = .FALSE.
  ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired = 0.0d0
  ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToHumidifyingSP = 0.0d0
  ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToDehumidifyingSP = 0.0d0

  ! Check to see if this is a "humidity controlled zone"
  ControlledHumidZoneFlag = .FALSE.
  ! Check all the controlled zones to see if it matches the zone simulated
  DO HumidControlledZoneNum = 1, NumHumidityControlZones
    IF (HumidityControlZone(HumidControlledZoneNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneAirRH = PsyRhFnTdbWPb(MAT(ZoneNum),ZoneAirHumRat(ZoneNum),OutBaroPress)*100.d0
    ZoneRHHumidifyingSetPoint = GetCurrentScheduleValue(HumidityControlZone(HumidControlledZoneNum)%HumidifyingSchedIndex)
    ZoneRHDehumidifyingSetPoint = GetCurrentScheduleValue(HumidityControlZone(HumidControlledZoneNum)%DehumidifyingSchedIndex)
    IF (HumidityControlZone(HumidControlledZoneNum)%EMSOverrideHumidifySetpointOn) THEN
      ZoneRHHumidifyingSetPoint = HumidityControlZone(HumidControlledZoneNum)%EMSOverrideHumidifySetpointValue
    ENDIF
    IF (HumidityControlZone(HumidControlledZoneNum)%EMSOverrideDehumidifySetpointOn) THEN
      ZoneRHDehumidifyingSetPoint = HumidityControlZone(HumidControlledZoneNum)%EMSOverrideDehumidifySetpointValue
    ENDIF

    ! Run-time error check
    If (ZoneRHHumidifyingSetPoint > ZoneRHDehumidifyingSetPoint) then
!      HumidityControlZone(HumidControlledZoneNum)%ErrorCount = HumidityControlZone(HumidControlledZoneNum)%ErrorCount + 1
      if (HumidityControlZone(HumidControlledZoneNum)%ErrorIndex == 0) then
        CALL ShowWarningMessage('HUMIDISTAT: The humidifying setpoint is above '// &
                'the dehumidifying setpoint in '//TRIM(HumidityControlZone(HumidControlledZoneNum)%ControlName))
        CALL ShowContinueError('The zone humidifying setpoint is set to the dehumidifying setpoint.')
        CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
      endif
      CALL ShowRecurringWarningErrorAtEnd('The humidifying setpoint is still above '// &
            'the dehumidifying setpoint',HumidityControlZone(HumidControlledZoneNum)%ErrorIndex, &
             ZoneRHHumidifyingSetPoint, ZoneRHHumidifyingSetPoint)
      ZoneRHHumidifyingSetPoint = ZoneRHDehumidifyingSetPoint
    End If
    IF (ZoneRHHumidifyingSetPoint == ZoneRHDehumidifyingSetPoint) SingleSetpoint = .TRUE.
    ControlledHumidZoneFlag = .TRUE.


    EXIT
  END DO ! HumidControlledZoneNum

  If (ControlledHumidZoneFlag) Then

    ! Calculate hourly humidity ratio from infiltration + humidity added from latent load
    ! to determine system added/subtracted moisture.
    LatentGain = ZoneLatentGain(ZoneNum) + SumLatentHTRadSys(ZoneNum)

    SysTimeStepInSeconds = SecInHour * TimeStepSys

    ! Calculate the coefficients for the 3rd Order derivative for final
    ! zone humidity ratio.  The A, B, C coefficients are analogous to the heat balance.
    ! SumHmARaW and SumHmARa will be used with the Moisture Balance on the building elements and
    ! are currently set to zero when the CTF only version is used.

    ! if no surface in the zone uses EMPD or HAMT then zero
    IF ((.NOT. ANY(Surface(Zone(ZoneNum)%SurfaceFirst:Zone(ZoneNum)%SurfaceLast)%HeatTransferAlgorithm == HeatTransferModel_EMPD))&
      .AND. &
      (.NOT. ANY(Surface(Zone(ZoneNum)%SurfaceFirst:Zone(ZoneNum)%SurfaceLast)%HeatTransferAlgorithm == HeatTransferModel_HAMT))) &
       THEN
      SumHmARaW(ZoneNum) = 0.0d0
      SumHmARa(ZoneNum) = 0.0d0
    END IF

    ! The density of air and latent heat of vaporization are calculated as functions.
    RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,ZT(ZoneNum),ZoneAirHumRat(ZoneNum),'CalcPredictedHumidityRatio')
    H2OHtOfVap = PsyHgAirFnWTdb(ZoneAirHumRat(ZoneNum),ZT(ZoneNum),'CalcPredictedHumidityRatio')

    ! Assume that the system will have flow
    if (SimulateAirflowNetwork == AirflowNetworkControlMultizone.OR.SimulateAirflowNetwork == AirflowNetworkControlMultiADS .OR. &
       (SimulateAirflowNetwork == AirflowNetworkControlSimpleADS .AND. AirflowNetworkFanActivated)) then
      ! Multizone airflow calculated in AirflowNetwork
      B = (LatentGain / H2OHtOfVap) + AirflowNetworkExchangeData(ZoneNum)%SumMHrW + &
          AirflowNetworkExchangeData(ZoneNum)%SumMMHrW+SumHmARaW(ZoneNum)
      A = AirflowNetworkExchangeData(ZoneNum)%SumMHr+AirflowNetworkExchangeData(ZoneNum)%SumMMHr + &
          SumHmARa(ZoneNum)
    else
      B = (LatentGain / H2OHtOfVap) + ((oamfl(ZoneNum) + vamfl(ZoneNum) + eamfl(ZoneNum) + ctmfl(ZoneNum)) * OutHumRat) + &
             SumHmARaW(ZoneNum) + MixingMassFlowXHumRat(ZoneNum) + MDotOA(ZoneNum)* OutHumRat
      A = oamfl(ZoneNum) + vamfl(ZoneNum) + eamfl(ZoneNum) + ctmfl(ZoneNum) + SumHmARa(ZoneNum) + MixingMassFlowZone(ZoneNum) &
          + MDotOA(ZoneNum)
    end if
    C = RhoAir * Zone(ZoneNum)%Volume * ZoneVolCapMultpMoist / SysTimeStepInSeconds

    ! Use a 3rd Order derivative to predict zone moisture addition or removal and
    ! smooth the changes using the zone air capacitance.  Positive values of Moist Load means that
    ! this amount of moisture must be added to the zone to reach the setpoint.  Negative values represent
    ! the amount of moisture that must be removed by the system.
    !MoistLoadHumidSetPoint = massflow * HumRat = kg air/sec  * kg H2O/kg Air = kg H2O/sec
    WZoneSetPoint = PsyWFnTdbRhPb(ZT(ZoneNum),(ZoneRHHumidifyingSetPoint/100.0d0),OutBaroPress,'CalcPredictedHumidityRatio')
    SELECT CASE (ZoneAirSolutionAlgo)
      CASE (Use3rdOrder)
        LoadToHumidifySetPoint = ((11.0d0/6.0d0) * C + A) * WZoneSetPoint - &
           (B + C * (3.0d0 * WZoneTimeMinus1Temp(ZoneNum) - (3.0d0/2.0d0) * WZoneTimeMinus2Temp(ZoneNum) + &
           (1.0d0/3.0d0) * WZoneTimeMinus3Temp(ZoneNum)))
      ! Exact solution
      CASE (UseAnalyticalSolution)
        If (A .eq. 0.0d0) Then ! B=0
          LoadToHumidifySetPoint = C*(WZoneSetPoint-ZoneW1(ZoneNum)) - B
        Else
          LoadToHumidifySetPoint = A*(WZoneSetPoint-ZoneW1(ZoneNum)*exp(MIN(700.d0,-A/C)))/(1.0d0-exp(MIN(700.d0,-A/C))) - B
        End If
      CASE (UseEulerMethod)
        LoadToHumidifySetPoint = C*(WZoneSetPoint-ZoneW1(ZoneNum)) + A*WZoneSetPoint - B
    END SELECT
    ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToHumidifyingSP = LoadToHumidifySetPoint
    WZoneSetPoint = PsyWFnTdbRhPb(ZT(ZoneNum),(ZoneRHDehumidifyingSetPoint / 100.0d0),OutBaroPress,'CalcPredictedHumidityRatio')
    SELECT CASE (ZoneAirSolutionAlgo)
      CASE (Use3rdOrder)
        LoadToDehumidifySetPoint = ((11.0d0/6.0d0) * C + A) * WZoneSetPoint - &
           (B + C * (3.0d0 * WZoneTimeMinus1Temp(ZoneNum) - (3.0d0/2.0d0) * WZoneTimeMinus2Temp(ZoneNum) + &
           (1.0d0/3.0d0) * WZoneTimeMinus3Temp(ZoneNum)))
      ! Exact solution
      CASE (UseAnalyticalSolution)
        If (A .eq. 0.0d0) Then ! B=0
          LoadToDehumidifySetPoint = C*(WZoneSetPoint-ZoneW1(ZoneNum)) - B
        Else
          LoadToDehumidifySetPoint = A*(WZoneSetPoint-ZoneW1(ZoneNum)*exp(MIN(700.d0,-A/C)))/(1.0d0-exp(MIN(700.d0,-A/C))) - B
        End If
      CASE (UseEulerMethod)
        LoadToDehumidifySetPoint = C*(WZoneSetPoint-ZoneW1(ZoneNum)) + A*WZoneSetPoint - B
    END SELECT
    ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToDehumidifyingSP = LoadToDehumidifySetPoint

    ! The load is added to the TotalOutputRequired as in the Temperature Predictor.  There is also the remaining
    ! output variable for those who will use this for humidity control and stored in DataZoneEnergyDemands with the
    ! analogous temperature terms.
    If (SingleSetpoint) Then
      ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired = LoadToHumidifySetPoint
    Else
      IF (LoadToHumidifySetPoint .GT. 0.0d0 .AND. LoadToDehumidifySetPoint .GT. 0.0d0) THEN
        ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired = LoadToHumidifySetPoint
        RHSetPoint = ZoneRHHumidifyingSetPoint
      ELSE IF (LoadToHumidifySetPoint .LT. 0.0d0 .AND. LoadToDehumidifySetPoint .LT. 0.0d0) THEN
        ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired = LoadToDehumidifySetPoint
        RHSetPoint = ZoneRHDehumidifyingSetPoint
      ELSE IF (LoadToHumidifySetPoint .LE. 0.0d0 .AND. LoadToDehumidifySetPoint .GE. 0.0d0) THEN ! deadband includes zero loads
        ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired = 0.0d0
      ELSE  ! this should never occur!
        CALL ShowSevereError('Humidistat: Unanticipated combination of humidifying and dehumidifying loads - '// &
                           'report to EnergyPlus Development Team')
        CALL ShowContinueErrorTimeStamp('occurs in Zone='//TRIM(Zone(ZoneNum)%Name))
        CALL ShowContinueError('LoadToHumidifySetPoint='//TRIM(RoundSigDigits(LoadToHumidifySetPoint,5))//  &
                             ', LoadToDehumidifySetPoint='//TRIM(RoundSigDigits(LoadToDehumidifySetPoint,5)))
        CALL ShowContinueError('Zone RH Humidifying Set-point='//TRIM(RoundSigDigits(ZoneRHHumidifyingSetPoint,1)))
        CALL ShowContinueError('Zone RH Dehumidifying Set-point='//TRIM(RoundSigDigits(ZoneRHDehumidifyingSetPoint,2)))
        CALL ShowFatalError('Program terminates due to above conditions.')
      END IF
    End If
  End If

  ! Save the unmultiplied zone moisture load to a report variable
  MoisturePredictedRate(ZoneNum) = ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired

  ! Apply the Zone Multiplier to the total zone moisture load
  ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired = ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired &
    * Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier
  ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToHumidifyingSP = ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToHumidifyingSP &
    * Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier
  ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToDehumidifyingSP = ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToDehumidifyingSP &
    * Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier

  !init each sequenced demand to the full output
  IF (ALLOCATED(ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequired)) &
    ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequired = & ! array assignment
                        ZoneSysMoistureDemand(ZoneNum)%TotalOutputRequired
  IF (ALLOCATED(ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToHumidSP))  &
    ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToHumidSP = & ! array assignment
                        ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToHumidifyingSP
  IF (ALLOCATED(ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToDehumidSP))  &
    ZoneSysMoistureDemand(ZoneNum)%SequencedOutputRequiredToDehumidSP = & ! array assignment
                        ZoneSysMoistureDemand(ZoneNum)%OutputRequiredToDehumidifyingSP

  RETURN

END SUBROUTINE CalcPredictedHumidityRatio

SUBROUTINE CorrectZoneAirTemp(ZoneTempChange, ShortenTimeStepSys,  &
                                UseZoneTimeStepHistory,  PriorTimeStep )

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Russell Taylor
          !       DATE WRITTEN   ???
          !       MODIFIED       November 1999, LKL;
          !       RE-ENGINEERED  July 2003 (Peter Graham Ellis)
          !                      February 2008 (Brent Griffith reworked history )

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine updates the zone air temperature and modifies the system
          ! time step.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataLoopNode, ONLY: Node
  USE DataRoomAirModel,     ONLY: AirModel,RoomAirModel_Mixing,RoomAirModel_UCSDDV,IsZoneDV,ZoneDVMixedFlag,IsZoneUI, &
                                  ZTFloor,MATFloor,XMATFloor,XM2TFloor,XM3TFloor,XM4TFloor, &
                                  ZTOC,ZTM1OC,MATOC,XMATOC,XM2TOC,XM3TOC,XM4TOC, &
                                  ZTMX,ZTM1MX,MATMX,XMATMX,XM2TMX,XM3TMX,XM4TMX, RoomAirModel_Mundt, RoomAirModel_UserDefined
  USE RoomAirModelManager , ONLY: ManageAirModel
 USE DataEnvironment, ONLY: Month, DayOfMonth
 USE General, ONLY: TrimSigDigits
  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  REAL(r64) , INTENT(OUT) :: ZoneTempChange     ! Temperature change in zone air between previous and current timestep
  LOGICAL, INTENT(IN)  :: ShortenTimeStepSys
  LOGICAL, INTENT(IN)  :: UseZoneTimeStepHistory  ! if true then use zone timestep history, if false use system time step history
  REAL(r64),  INTENT(IN)  :: PriorTimeStep  ! the old value for timestep length is passed for possible use in interpolating

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)               :: CpAir                           !specific heat of air
  REAL(r64)      :: SumIntGain =0.0d0                 ! Zone sum of convective internal gains
  REAL(r64)      :: SumHA      =0.0d0                 ! Zone sum of Hc*Area
  REAL(r64)      :: SumHATsurf =0.0d0                 ! Zone sum of Hc*Area*Tsurf
  REAL(r64)      :: SumHATref  =0.0d0                 ! Zone sum of Hc*Area*Tref, for ceiling diffuser convection correlation
  REAL(r64)      :: SumMCp     =0.0d0                 ! Zone sum of MassFlowRate*Cp
  REAL(r64)      :: SumMCpT    =0.0d0                 ! Zone sum of MassFlowRate*Cp*T
  REAL(r64)      :: SumSysMCp  =0.0d0                 ! Zone sum of air system MassFlowRate*Cp
  REAL(r64)      :: SumSysMCpT =0.0d0                 ! Zone sum of air system MassFlowRate*Cp*T
  REAL(r64)      :: ZoneEnthalpyIn =0.0d0             ! Zone inlet air enthalpy
  REAL(r64)      :: TempDepCoef=0.0d0                 ! Formerly CoefSumha, coef in zone temp equation with dimensions of h*A
  REAL(r64)      :: TempIndCoef=0.0d0                 ! Formerly CoefSumhat, coef in zone temp equation with dimensions of h*A(T1
  REAL(r64)      :: AirCap     =0.0d0                 ! Formerly CoefAirrat, coef in zone temp eqn with dim of "air power capacity"
  REAL(r64)      :: SNLoad     =0.0d0                 ! Sensible load calculated for zone in watts and then loaded in report variables
  INTEGER :: ZoneNum   =0
  INTEGER :: ZoneNodeNum=0                        ! System node number for air flow through zone either by system or as a plenum
!  LOGICAL,SAVE   :: OneTimeFlag = .TRUE.
!unusd1208  LOGICAL,SAVE   :: MyEnvrnFlag = .TRUE.
  REAL(r64)      :: TempSupplyAir
  REAL(r64)      :: ZoneMult
!unused1208  REAL(r64)           :: TimeStepSeconds  ! dt term for denominator under Cz in Seconds

          ! FLOW:
  ! Initializations
  ZoneTempChange                      = constant_zero

  ! Update zone temperatures
  DO ZoneNum = 1, NumOfZones

    ZoneMult = Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier

    IF (ShortenTimeStepSys) THEN
      !time step has gotten smaller, use zone timestep history to interpolate new set of "DS" history terms.
      If (NumOfSysTimeSteps /= NumOfSysTimeStepsLastZoneTimeStep)  then ! cannot reuse existing DS data, interpolate from zone time
        Call DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                                MAT(ZoneNum),   XMAT(ZoneNum),    XM2T(ZoneNum),   XM3T(ZoneNum), XM4T(ZoneNum) ,   &  !
                                MAT(ZoneNum), DSXMAT(ZoneNum), DSXM2T(ZoneNum), DSXM3T(ZoneNum), DSXM4T(ZoneNum))
        Call DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                                ZoneAirHumRat(ZoneNum),   WZoneTimeMinus1(ZoneNum),   WZoneTimeMinus2(ZoneNum),   & !
                                                          WZoneTimeMinus3(ZoneNum),   WZoneTimeMinus4(ZoneNum), & !
                                ZoneAirHumRat(ZoneNum), DSWZoneTimeMinus1(ZoneNum), DSWZoneTimeMinus2(ZoneNum), &
                                                        DSWZoneTimeMinus3(ZoneNum), DSWZoneTimeMinus4(ZoneNum))
        IF (IsZoneDV(ZoneNum) .or. IsZoneUI(ZoneNum)) THEN
          CALL DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                                MATFloor(ZoneNum),   XMATFloor(ZoneNum),    XM2TFloor(ZoneNum),  &
                                                     XM3TFloor(ZoneNum),    XM4TFloor(ZoneNum) ,   &
                                MATFloor(ZoneNum), DSXMATFloor(ZoneNum),  DSXM2TFloor(ZoneNum),  &
                                                   DSXM3TFloor(ZoneNum),  DSXM4TFloor(ZoneNum))
          CALL DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                                MATOC(ZoneNum),   XMATOC(ZoneNum),    XM2TOC(ZoneNum),  &
                                                  XM3TOC(ZoneNum),    XM4TOC(ZoneNum) ,   &
                                MATOC(ZoneNum), DSXMATOC(ZoneNum),  DSXM2TOC(ZoneNum),  &
                                                DSXM3TOC(ZoneNum),  DSXM4TOC(ZoneNum))
          CALL DownInterpolate4HistoryValues(PriorTimeStep,TimeStepSys, &
                                MATMX(ZoneNum),   XMATMX(ZoneNum),    XM2TMX(ZoneNum),  &
                                                  XM3TMX(ZoneNum),    XM4TMX(ZoneNum) ,   &
                                MATMX(ZoneNum), DSXMATMX(ZoneNum),  DSXM2TMX(ZoneNum),  &
                                                DSXM3TMX(ZoneNum),  DSXM4TMX(ZoneNum))
        ENDIF

      ELSE ! reuse history data in DS terms from last zone time step to preserve information that would be lost
         ! do nothing because DS history would have been pushed prior and should be ready?

      ENDIF
    ENDIF

    ! now update the variables actually used in the balance equations.
    IF(.not. UseZoneTimeStepHistory) THEN
      ZTM1(ZoneNum)                = DSXMAT(ZoneNum)
      ZTM2(ZoneNum)                = DSXM2T(ZoneNum)
      ZTM3(ZoneNum)                = DSXM3T(ZoneNum)

      WZoneTimeMinus1Temp(ZoneNum) = DSWZoneTimeMinus1(ZoneNum)
      WZoneTimeMinus2Temp(ZoneNum) = DSWZoneTimeMinus2(ZoneNum)
      WZoneTimeMinus3Temp(ZoneNum) = DSWZoneTimeMinus3(ZoneNum)
    ELSE
      ZTM1(ZoneNum)                = XMAT(ZoneNum)
      ZTM2(ZoneNum)                = XM2T(ZoneNum)
      ZTM3(ZoneNum)                = XM3T(ZoneNum)

      WZoneTimeMinus1Temp(ZoneNum) = WZoneTimeMinus1(ZoneNum)
      WZoneTimeMinus2Temp(ZoneNum) = WZoneTimeMinus2(ZoneNum)
      WZoneTimeMinus3Temp(ZoneNum) = WZoneTimeMinus3(ZoneNum)

    END IF

    AIRRAT(ZoneNum) = Zone(ZoneNum)%Volume*ZoneVolCapMultpSens*   &
               PsyRhoAirFnPbTdbW(OutBaroPress,MAT(ZoneNum),ZoneAirHumRat(ZoneNum),'CorrectZoneAirTemp')*   &
               PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum),MAT(ZoneNum),'CorrectZoneAirTemp')/(TimeStepSys*SecInHour)

    AirCap = AIRRAT(ZoneNum)

    CALL ManageAirModel(ZoneNum)

    ! Calculate the various heat balance sums
    CALL CalcZoneSums(ZoneNum, SumIntGain, SumHA, SumHATsurf, SumHATref, SumMCp, SumMCpT, SumSysMCp, SumSysMCpT)
!    ZoneTempHistoryTerm = (3.0D0 * ZTM1(ZoneNum) - (3.0D0/2.0D0) * ZTM2(ZoneNum) + (1.0D0/3.0D0) * ZTM3(ZoneNum))
    ZoneNodeNum = Zone(ZoneNum)%SystemZoneNodeNumber

    SNLOAD=0.0d0

    IF (ZoneNodeNum > 0) THEN ! This zone is controlled by a zone equipment configuration or zone plenum

       ! Heat balance coefficients for controlled zone, i.e. with system air flow
       TempDepCoef = SumHA + SumMCp + SumSysMCp
       TempIndCoef = SumIntGain + SumHATsurf - SumHATref + SumMCpT + SumSysMCpT + (NonAirSystemResponse(ZoneNum) / ZoneMult + &
                     SysDepZoneLoadsLagged(ZoneNum))
   !    TempHistoryTerm = AirCap * (3.0 * ZTM1(ZoneNum) - (3.0/2.0) * ZTM2(ZoneNum) + (1.0/3.0) * ZTM3(ZoneNum)) !debug only

       if (SimulateAirflowNetwork .GT. AirflowNetworkControlMultizone) then
          TempIndCoef = TempIndCoef+AirflowNetworkExchangeData(ZoneNum)%TotalSen
       end if
   !    TempDepZnLd(ZoneNum) = (11.0/6.0) * AirCap + TempDepCoef
   !    TempIndZnLd(ZoneNum) = TempHistoryTerm + TempIndCoef
       ! Solve for zone air temperature
       SELECT CASE (ZoneAirSolutionAlgo)
         CASE (Use3rdOrder)
           ZT(ZoneNum) = (TempIndCoef + AirCap*(3.0d0*ZTM1(ZoneNum) - (3.0d0/2.0d0)*ZTM2(ZoneNum) + (1.0d0/3.0d0)*ZTM3(ZoneNum))) &
                   / ((11.0d0/6.0d0) * AirCap + TempDepCoef)
         ! Exact solution
         CASE (UseAnalyticalSolution)
           If (TempDepCoef .eq. 0.0d0) Then ! B=0
             ZT(ZoneNum) = ZoneT1(ZoneNum) + TempIndCoef/AirCap
           Else
             ZT(ZoneNum) = (ZoneT1(ZoneNum)-TempIndCoef/TempDepCoef)*exp(MIN(700.d0,-TempDepCoef/AirCap))+TempIndCoef/TempDepCoef
           End If
         CASE (UseEulerMethod)
           ZT(ZoneNum) = (AirCap*ZoneT1(ZoneNum)+TempIndCoef)/(AirCap+TempDepCoef)
       END SELECT
       ! Update zone node temperature and thermostat temperature unless already updated in Room Air Model,
       ! calculate load correction factor
       IF ((AirModel(ZoneNum)%AirModelType ==  RoomAirModel_Mixing) .or. (.not.AirModel(ZoneNum)%SimAirModel)) THEN
           ! Fully mixed
           Node(ZoneNodeNum)%Temp  = ZT(ZoneNum)
           TempTstatAir(ZoneNum)   = ZT(ZoneNum)
           LoadCorrectionFactor(ZoneNum) = 1.0d0
       ELSEIF (IsZoneDV(ZoneNum) .or. IsZoneUI(ZoneNum)) THEN
           ! UCSDDV: Not fully mixed - calculate factor to correct load for fully mixed assumption
           IF (SumSysMCp > SmallMassFlow) THEN
               TempSupplyAir = SumSysMCpT / SumSysMCp   ! Non-negligible flow, calculate supply air temperature
               IF (ABS(TempSupplyAir - ZT(ZoneNum)) > TempConvergTol) THEN
                 LoadCorrectionFactor(ZoneNum) = (TempSupplyAir-Node(ZoneNodeNum)%Temp)/(TempSupplyAir-ZT(ZoneNum))
                 ! constrain value to something reasonable
                 LoadCorrectionFactor(ZoneNum) = MAX(-3.d0, LoadCorrectionFactor(ZoneNum))
                 LoadCorrectionFactor(ZoneNum) = MIN(3.d0, LoadCorrectionFactor(ZoneNum))

               ELSE
                 LoadCorrectionFactor(ZoneNum) = 1.0d0  ! Indeterminate
               ENDIF
           ELSE
               ! Negligible flow, assume mixed - reasonable lagged starting value for first step time with significant flow
               LoadCorrectionFactor(ZoneNum) = 1.0d0
           ENDIF
       ELSEIF (AirModel(ZoneNum)%SimAirModel .AND.               &
               ((AirModel(ZoneNum)%AirModelType == RoomAirModel_UserDefined)  &
                 .OR. (AirModel(ZoneNum)%AirModelType == RoomAirModel_Mundt)) ) THEN
           IF (SumSysMCp > SmallMassFlow) THEN
               TempSupplyAir = SumSysMCpT / SumSysMCp   ! Non-negligible flow, calculate supply air temperature
               IF (ABS(TempSupplyAir - ZT(ZoneNum)) > TempConvergTol) THEN
                 LoadCorrectionFactor(ZoneNum) = (TempSupplyAir-Node(ZoneNodeNum)%Temp)/(TempSupplyAir-ZT(ZoneNum))
                 ! constrain value
                 LoadCorrectionFactor(ZoneNum) = MAX(-3.d0, LoadCorrectionFactor(ZoneNum))
                 LoadCorrectionFactor(ZoneNum) = MIN(3.d0, LoadCorrectionFactor(ZoneNum))

               ELSE
                 LoadCorrectionFactor(ZoneNum) = 1.0d0  ! Indeterminate
               ENDIF
           ELSE
               ! Negligible flow, assume mixed - reasonable lagged starting value for first step time with significant flow
               LoadCorrectionFactor(ZoneNum) = 1.0d0
           ENDIF
       ELSE
         Node(ZoneNodeNum)%Temp  = ZT(ZoneNum)
         TempTstatAir(ZoneNum)   = ZT(ZoneNum)
         LoadCorrectionFactor(ZoneNum) = 1.0d0
       ENDIF

       ! Sensible load is the enthalpy into the zone minus the enthalpy that leaves the zone.
       CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), Node(ZoneNodeNum)%Temp)
       ZoneEnthalpyIn = SumSysMCpT

       ! SNLOAD is the single zone load, without Zone Multiplier or Zone List Multiplier
       SNLOAD = ZoneEnthalpyIn - (Node(ZoneNodeNum)%MassFlowRate / ZoneMult) * CpAir * Node(ZoneNodeNum)%Temp &
              + NonAirSystemResponse(ZoneNum) / ZoneMult + SysDepZoneLoadsLagged(ZoneNum)

    ELSE

        ! Heat balance coefficients for uncontrolled zone, i.e. without system air flow
       TempDepCoef = SumHA + SumMCp
       TempIndCoef = SumIntGain + SumHATsurf - SumHATref + SumMCpT

  !      TempHistoryTerm = AirCap * (3.0 * ZTM1(ZoneNum) - (3.0/2.0) * ZTM2(ZoneNum) + (1.0/3.0) * ZTM3(ZoneNum)) !debug only

       if (SimulateAirflowNetwork > AirflowNetworkControlMultizone) then
          TempIndCoef = TempIndCoef+AirflowNetworkExchangeData(ZoneNum)%TotalSen
       end if
  !      TempDepZnLd(ZoneNum) = (11.0/6.0) * AirCap + TempDepCoef
  !      TempIndZnLd(ZoneNum) = TempHistoryTerm + TempIndCoef

        ! Solve for zone air temperature
       SELECT CASE (ZoneAirSolutionAlgo)
         CASE (Use3rdOrder)
           ZT(ZoneNum) = (TempIndCoef + AirCap*(3.0d0*ZTM1(ZoneNum) - (3.0d0/2.0d0)*ZTM2(ZoneNum) + (1.0d0/3.0d0)*ZTM3(ZoneNum))) &
                    / ((11.0d0/6.0d0)*AirCap + TempDepCoef)
         ! Exact solution
         CASE (UseAnalyticalSolution)
           If (TempDepCoef .eq. 0.0d0) Then ! B=0
             ZT(ZoneNum) = ZoneT1(ZoneNum) + TempIndCoef/AirCap
           Else
             ZT(ZoneNum) = (ZoneT1(ZoneNum)-TempIndCoef/TempDepCoef)*exp(MIN(700.d0,-TempDepCoef/AirCap))+TempIndCoef/TempDepCoef
           End If
         CASE (UseEulerMethod)
           ZT(ZoneNum) = (AirCap*ZoneT1(ZoneNum)+TempIndCoef)/(AirCap+TempDepCoef)
       END SELECT

        ! No sensible load
        SNLOAD = 0.0d0
    END IF

    MAT(ZoneNum)  = ZT(ZoneNum)

    ! Determine sensible load heating/cooling rate and energy
    SNLoadHeatRate(ZoneNum) = MAX(SNLOAD,0.0d0)
    SNLoadCoolRate(ZoneNum) = ABS(MIN(SNLOAD,0.0d0))
    SNLoadHeatEnergy(ZoneNum) = MAX(SNLOAD,0.0d0) * TimeStepSys * SecInHour
    SNLoadCoolEnergy(ZoneNum) = ABS(MIN(SNLOAD,0.0d0) * TimeStepSys * SecInHour)

    ! Final humidity calcs
    CALL CorrectZoneHumRat(ZoneNum)

    ZoneAirHumRat(ZoneNum) = ZoneAirHumRatTemp(ZoneNum)
    ZoneAirRelHum(ZoneNum) = 100.0d0 * PsyRhFnTdbWPb(ZT(ZoneNum),ZoneAirHumRat(ZoneNum),OutBaroPress,'CorrectZoneAirTemp')

    ! ZoneTempChange is used by HVACManager to determine if the timestep needs to be shortened.
    SELECT CASE (ZoneAirSolutionAlgo)
      CASE (Use3rdOrder)
        IF (IsZoneDV(ZoneNum)) THEN
          IF (ZoneDVMixedFlag(ZoneNum)==0) THEN
            ZoneTempChange = MAX(ZoneTempChange,MAX(ABS(ZTOC(ZoneNum) - ZTM1OC(ZoneNum)),ABS(ZTMX(ZoneNum) - ZTM1MX(ZoneNum))))
          ELSE
            ZoneTempChange = MAX(ZoneTempChange, ABS(ZT(ZoneNum) - ZTM1(ZoneNum)))
          ENDIF
        ELSE IF (IsZoneUI(ZoneNum)) THEN
          IF (ZoneUFMixedFlag(ZoneNum)==0) THEN
            ZoneTempChange = MAX(ZoneTempChange,MAX(ABS(ZTOC(ZoneNum) - ZTM1OC(ZoneNum)),ABS(ZTMX(ZoneNum) - ZTM1MX(ZoneNum))))
          ELSE
            ZoneTempChange = MAX(ZoneTempChange, ABS(ZT(ZoneNum) - ZTM1(ZoneNum)))
          ENDIF
        ELSE
          ZoneTempChange = MAX(ZoneTempChange, ABS(ZT(ZoneNum) - ZTM1(ZoneNum)))
        ENDIF
      CASE (UseAnalyticalSolution,UseEulerMethod)
        IF (IsZoneDV(ZoneNum)) THEN
          IF (ZoneDVMixedFlag(ZoneNum)==0) THEN
             ZoneTempChange = MAX(ZoneTempChange,MAX(ABS(ZTOC(ZoneNum) - Zone1OC(ZoneNum)),ABS(ZTMX(ZoneNum) - Zone1MX(ZoneNum))))
           ELSE
             ZoneTempChange = MAX(ZoneTempChange, ABS(ZT(ZoneNum) - ZoneT1(ZoneNum)))
          ENDIF
        ELSE IF (IsZoneUI(ZoneNum)) THEN
          IF (ZoneUFMixedFlag(ZoneNum)==0) THEN
            ZoneTempChange = MAX(ZoneTempChange,MAX(ABS(ZTOC(ZoneNum) - Zone1OC(ZoneNum)),ABS(ZTMX(ZoneNum) - Zone1MX(ZoneNum))))
          ELSE
            ZoneTempChange = MAX(ZoneTempChange, ABS(ZT(ZoneNum) - ZoneT1(ZoneNum)))
          ENDIF
        ELSE
          ZoneTempChange = MAX(ZoneTempChange, ABS(ZT(ZoneNum) - ZoneT1(ZoneNum)))
        ENDIF
   END SELECT

   Call CalcZoneComponentLoadSums(ZoneNum,  TempDepCoef, TempIndCoef,         &
                                            ZnAirRPT(ZoneNum)%SumIntGains,    & ! convection part of internal gains
                                            ZnAirRPT(ZoneNum)%SumHADTsurfs,   & ! surface convection heat transfer
                                            ZnAirRPT(ZoneNum)%SumMCpDTzones,  & ! interzone mixing
                                            ZnAirRPT(ZoneNum)%SumMCpDtInfil,  & ! OA of various kinds except via system
                                            ZnAirRPT(ZoneNum)%SumMCpDTsystem, & ! air system
                                            ZnAirRpt(ZoneNum)%SumNonAirSystem, & ! non air system
                                            ZnAirRPT(ZoneNum)%CzdTdt ,        & ! air mass energy storage term
                                            ZnAirRPT(ZoneNum)%imBalance )       ! measure of imbalance in zone air heat balance


  END DO ! ZoneNum

  RETURN

END SUBROUTINE CorrectZoneAirTemp

SUBROUTINE PushZoneTimestepHistories

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   February 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! push histories for timestep advancing

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: ZoneNum

        ! Push the temperature and humidity ratio histories

  DO ZoneNum = 1, NumOfZones
        XM4T(ZoneNum) = XM3T(ZoneNum)
        XM3T(ZoneNum) = XM2T(ZoneNum)
        XM2T(ZoneNum) = XMAT(ZoneNum)
        XMAT(ZoneNum) = ZTAV(ZoneNum) ! using average for whole zone time step.
        XMPT(ZoneNum)  = ZT(ZoneNum)
  !      MAT(ZoneNum)  = ZT(ZoneNum)

        WZoneTimeMinus4(ZoneNum) = WZoneTimeMinus3(ZoneNum)
        WZoneTimeMinus3(ZoneNum) = WZoneTimeMinus2(ZoneNum)
        WZoneTimeMinus2(ZoneNum) = WZoneTimeMinus1(ZoneNum)
        WZoneTimeMinus1(ZoneNum) = ZoneAirHumRatAvg(ZoneNum) ! using average for whole zone time step.
        ZoneAirHumRat(ZoneNum) = ZoneAirHumRatTemp(ZoneNum)
        WZoneTimeMinusP(ZoneNum) = ZoneAirHumRatTemp(ZoneNum)
        ZoneAirRelHum(ZoneNum) = 100.0d0 * PsyRhFnTdbWPb(ZT(ZoneNum),ZoneAirHumRat(ZoneNum),OutBaroPress,'CorrectZoneAirTemp')

        IF (AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDDV .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFI &
            .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFE) THEN
          XM4TFloor(ZoneNum) = XM3TFloor(ZoneNum)
          XM3TFloor(ZoneNum) = XM2TFloor(ZoneNum)
          XM2TFloor(ZoneNum) = XMATFloor(ZoneNum)
          XMATFloor(ZoneNum) = ZTFloor(ZoneNum)
          MATFloor(ZoneNum) = ZTFloor(ZoneNum)

          XM4TOC(ZoneNum) = XM3TOC(ZoneNum)
          XM3TOC(ZoneNum) = XM2TOC(ZoneNum)
          XM2TOC(ZoneNum) = XMATOC(ZoneNum)
          XMATOC(ZoneNum) = ZTOC(ZoneNum)
          MATOC(ZoneNum) = ZTOC(ZoneNum)

          XM4TMX(ZoneNum) = XM3TMX(ZoneNum)
          XM3TMX(ZoneNum) = XM2TMX(ZoneNum)
          XM2TMX(ZoneNum) = XMATMX(ZoneNum)
          XMATMX(ZoneNum) = ZTMX(ZoneNum)
          MATMX(ZoneNum) = ZTMX(ZoneNum)
        ENDIF

        If (ZoneAirSolutionAlgo .NE. Use3rdOrder) Then
          ZoneTM2(ZoneNum) = ZoneTMX(ZoneNum)
          ZoneTMX(ZoneNum) = ZTAV(ZoneNum) ! using average for whole zone time step.
          ZoneWM2(ZoneNum) = ZoneWMX(ZoneNum)
          ZoneWMX(ZoneNum) = ZoneAirHumRatAvg(ZoneNum) ! using average for whole zone time step.
          IF (AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDDV .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFI &
            .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFE) THEN
            ZoneM2Floor(ZoneNum) = ZoneMXFloor(ZoneNum)
            ZoneMXFloor(ZoneNum) = ZTFloor(ZoneNum) ! using average for whole zone time step.
            ZoneM2OC(ZoneNum) = ZoneMXOC(ZoneNum)
            ZoneMXOC(ZoneNum) = ZTOC(ZoneNum) ! using average for whole zone time step.
            ZoneM2MX(ZoneNum) = ZoneMXMX(ZoneNum)
            ZoneMXMX(ZoneNum) = ZTMX(ZoneNum) ! using average for whole zone time step.
          END IF
        End If
  ENDDO ! zone loop
  RETURN

END SUBROUTINE PushZoneTimestepHistories

SUBROUTINE PushSystemTimestepHistories

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   April 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! push histories

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: ZoneNum

  ! Push the temperature and humidity ratio histories back in time

  DO ZoneNum = 1, NumOfZones
    DSXM4T(ZoneNum) = DSXM3T(ZoneNum)
    DSXM3T(ZoneNum) = DSXM2T(ZoneNum)
    DSXM2T(ZoneNum) = DSXMAT(ZoneNum)
    DSXMAT(ZoneNum) = MAT(ZoneNum)

    DSWZoneTimeMinus4(ZoneNum) = DSWZoneTimeMinus3(ZoneNum)
    DSWZoneTimeMinus3(ZoneNum) = DSWZoneTimeMinus2(ZoneNum)
    DSWZoneTimeMinus2(ZoneNum) = DSWZoneTimeMinus1(ZoneNum)
    DSWZoneTimeMinus1(ZoneNum) = ZoneAirHumRat(ZoneNum)

    IF (IsZoneDV(ZoneNum) .or. IsZoneUI(ZoneNum)) Then
      DSXM4TFloor(ZoneNum)  = DSXM3TFloor(ZoneNum)
      DSXM3TFloor(ZoneNum)  = DSXM2TFloor(ZoneNum)
      DSXM2TFloor(ZoneNum)  = DSXMATFloor(ZoneNum)
      DSXMATFloor(ZoneNum)  = MATFloor(ZoneNum)

      DSXM4TOC(ZoneNum)     = DSXM3TOC(ZoneNum)
      DSXM3TOC(ZoneNum)     = DSXM2TOC(ZoneNum)
      DSXM2TOC(ZoneNum)     = DSXMATOC(ZoneNum)
      DSXMATOC(ZoneNum)     = MATOC(ZoneNum)

      DSXM4TMX(ZoneNum)     = DSXM3TMX(ZoneNum)
      DSXM3TMX(ZoneNum)     = DSXM2TMX(ZoneNum)
      DSXM2TMX(ZoneNum)     = DSXMATMX(ZoneNum)
      DSXMATMX(ZoneNum)     = MATMX(ZoneNum)
    ENDIF

  ENDDO ! zone loop

  If (ZoneAirSolutionAlgo .NE. Use3rdOrder) Then
    DO ZoneNum = 1, NumOfZones
      ZoneTM2(ZoneNum) = ZoneTMX(ZoneNum)
      ZoneTMX(ZoneNum) = MAT(ZoneNum) ! using average for whole zone time step.
      ZoneWM2(ZoneNum) = ZoneWMX(ZoneNum)
      ZoneWMX(ZoneNum) = ZoneAirHumRatTemp(ZoneNum) ! using average for whole zone time step.

      IF (AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDDV .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFI &
            .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFE) THEN
        ZoneM2Floor(ZoneNum) = ZoneMXFloor(ZoneNum)
        ZoneMXFloor(ZoneNum) = ZTFloor(ZoneNum) ! using average for whole zone time step.
        ZoneM2OC(ZoneNum) = ZoneMXOC(ZoneNum)
        ZoneMXOC(ZoneNum) = ZTOC(ZoneNum) ! using average for whole zone time step.
        ZoneM2MX(ZoneNum) = ZoneMXMX(ZoneNum)
        ZoneMXMX(ZoneNum) = ZTMX(ZoneNum) ! using average for whole zone time step.
      ENDIF
    ENDDO ! zone loop
  End If

  RETURN

END SUBROUTINE PushSystemTimestepHistories

SUBROUTINE RevertZoneTimestepHistories
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   February 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! rewind histories to undo inadvertent pushing

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: ZoneNum

  ! REvert the temperature and humidity ratio histories

  DO ZoneNum = 1, NumOfZones
   !  MAT(ZoneNum)  = XMAT(ZoneNum)
     XMAT(ZoneNum) = XM2T(ZoneNum)
     XM2T(ZoneNum) = XM3T(ZoneNum)
     XM3T(ZoneNum) = XM4T(ZoneNum)

  !   ZoneAirHumRat(ZoneNum)  = WZoneTimeMinus1(ZoneNum)
     WZoneTimeMinus1(ZoneNum) = WZoneTimeMinus2(ZoneNum)
     WZoneTimeMinus2(ZoneNum) = WZoneTimeMinus3(ZoneNum)
     WZoneTimeMinus3(ZoneNum) = WZoneTimeMinus4(ZoneNum)

     IF (AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDDV .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFI &
            .or. AirModel(ZoneNum)%AirModelType ==  RoomAirModel_UCSDUFE) THEN

    !      MATFloor(ZoneNum)= XMATFloor(ZoneNum)
          XMATFloor(ZoneNum)=XM2TFloor(ZoneNum)
          XM2TFloor(ZoneNum)=XM3TFloor(ZoneNum)
          XM3TFloor(ZoneNum)=XM4TFloor(ZoneNum)
    !      MATOC(ZoneNum) = XMATOC(ZoneNum)
          XMATOC(ZoneNum)=XM2TOC(ZoneNum)
          XM2TOC(ZoneNum)=  XM3TOC(ZoneNum)
          XM3TOC(ZoneNum)=XM4TOC(ZoneNum)

     !     MATMX(ZoneNum)=  XMATMX(ZoneNum)
          XMATMX(ZoneNum)=XM2TMX(ZoneNum)
          XM2TMX(ZoneNum)=XM3TMX(ZoneNum)
          XM3TMX(ZoneNum)=XM4TMX(ZoneNum)

    ENDIF

  ENDDO ! zone loop
  RETURN

END SUBROUTINE RevertZoneTimestepHistories

SUBROUTINE CorrectZoneHumRat(ZoneNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard Liesen
          !       DATE WRITTEN   2000
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine updates the zone humidities.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! Routine FinalZnCalcs - FINAL ZONE CALCULATIONS, authored by Dale Herron
          ! for BLAST.

          ! USE STATEMENTS:
  USE DataLoopNode, ONLY: Node
  USE DataZoneEquipment, ONLY: ZoneEquipConfig
  USE ZonePlenum, ONLY: ZoneRetPlenCond, ZoneSupPlenCond, NumZoneReturnPlenums, NumZoneSupplyPlenums
  USE DataDefineEquip, ONLY: AirDistUnit, NumAirDistUnits
  USE DataSurfaces,  ONLY: Surface, HeatTransferModel_HAMT, HeatTransferModel_EMPD

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: ZoneNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: NodeNum
  INTEGER :: ZoneNodeNum
  INTEGER :: ZoneEquipConfigNum
  LOGICAL :: ControlledZoneAirFlag
  INTEGER :: ZoneRetPlenumNum
  INTEGER :: ZoneSupPlenumNum
  LOGICAL :: ZoneRetPlenumAirFlag
  LOGICAL :: ZoneSupPlenumAirFlag
  REAL(r64) :: LatentGain ! Zone latent load
  REAL(r64) :: RhoAir
  REAL(r64) :: A
  REAL(r64) :: B
  REAL(r64) :: C
  REAL(r64) :: WZSat
  REAL(r64) :: MoistureMassFlowRate
  REAL(r64) :: ExhMassFlowRate
  REAL(r64) :: TotExitMassFlowRate
  REAL(r64) :: ZoneMassFlowRate
  REAL(r64) :: SysTimeStepInSeconds
  REAL(r64) :: H2OHtOfVap
  REAL(r64) :: ZoneMult
  INTEGER :: ADUListIndex
  INTEGER :: ADUNum
  INTEGER :: ADUInNode
  INTEGER :: ADUOutNode

          ! FLOW:
  MoistureMassFlowRate = 0.0d0
  ZoneMassFlowRate = 0.0d0
  ExhMassFlowRate = 0.0d0
  TotExitMassFlowRate = 0.0d0
  ZoneMult = Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier

  ! Check to see if this is a controlled zone
  ControlledZoneAirFlag = .FALSE.
  DO ZoneEquipConfigNum = 1, NumOfZones
    IF (.not. Zone(ZoneEquipConfigNum)%IsControlled) CYCLE
    IF (ZoneEquipConfig(ZoneEquipConfigNum)%ActualZoneNum /= ZoneNum) CYCLE
    ControlledZoneAirFlag = .TRUE.
    EXIT
  END DO ! ZoneEquipConfigNum

  ! Check to see if this is a plenum zone
  ZoneRetPlenumAirFlag = .FALSE.
  DO ZoneRetPlenumNum = 1, NumZoneReturnPlenums
    IF (ZoneRetPlenCond(ZoneRetPlenumNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneRetPlenumAirFlag = .TRUE.
    EXIT
  END DO ! ZoneRetPlenumNum
  ZoneSupPlenumAirFlag = .FALSE.
  DO ZoneSupPlenumNum = 1, NumZoneSupplyPlenums
    IF (ZoneSupPlenCond(ZoneSupPlenumNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneSupPlenumAirFlag = .TRUE.
    EXIT
  END DO ! ZoneSupPlenumNum

  IF (ControlledZoneAirFlag) THEN ! If there is system flow then calculate the flow rates

    ! Calculate moisture flow rate into each zone
    DO NodeNum = 1, ZoneEquipConfig(ZoneEquipConfigNum)%NumInletNodes

      MoistureMassFlowRate = MoistureMassFlowRate + &
                           (Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%MassFlowRate * &
                            Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%HumRat) / ZoneMult
      ZoneMassFlowRate = ZoneMassFlowRate + &
                            Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%MassFlowRate / ZoneMult
    END DO ! NodeNum

    DO NodeNum = 1, ZoneEquipConfig(ZoneEquipConfigNum)%NumExhaustNodes
      ExhMassFlowRate = ExhMassFlowRate + Node(ZoneEquipConfig(ZoneEquipConfigNum)%ExhaustNode(NodeNum))%MassFlowRate / ZoneMult
    END DO ! NodeNum

    IF (ZoneEquipConfig(ZoneEquipConfigNum)%ReturnAirNode > 0) THEN
      TotExitMassFlowRate = ExhMassFlowRate + Node(ZoneEquipConfig(ZoneEquipConfigNum)%ReturnAirNode)%MassFlowRate / ZoneMult
    END IF

  ! Do the calculations for the plenum zone
  ELSE IF (ZoneRetPlenumAirFlag) THEN
    DO NodeNum = 1, ZoneRetPlenCond(ZoneRetPlenumNum)%NumInletNodes

     MoistureMassFlowRate = MoistureMassFlowRate + &
                           (Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%MassFlowRate * &
                            Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%HumRat) / ZoneMult
     ZoneMassFlowRate = ZoneMassFlowRate + &
                            Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%MassFlowRate / ZoneMult
    END DO ! NodeNum
    ! add in the leak flow
    DO ADUListIndex=1,ZoneRetPlenCond(ZoneRetPlenumNum)%NumADUs
      ADUNum = ZoneRetPlenCond(ZoneRetPlenumNum)%ADUIndex(ADUListIndex)
      IF (AirDistUnit(ADUNum)%UpStreamLeak) THEN
        ADUInNode = AirDistUnit(ADUNum)%InletNodeNum
        MoistureMassFlowRate = MoistureMassFlowRate + &
                               (AirDistUnit(ADUNum)%MassFlowRateUpStrLk * Node(ADUInNode)%HumRat) / ZoneMult
        ZoneMassFlowRate = ZoneMassFlowRate + AirDistUnit(ADUNum)%MassFlowRateUpStrLk / ZoneMult
      END IF
      IF (AirDistUnit(ADUNum)%DownStreamLeak) THEN
        ADUOutNode = AirDistUnit(ADUNum)%OutletNodeNum
        MoistureMassFlowRate = MoistureMassFlowRate + &
                               (AirDistUnit(ADUNum)%MassFlowRateDnStrLk * Node(ADUOutNode)%HumRat) / ZoneMult
        ZoneMassFlowRate = ZoneMassFlowRate + AirDistUnit(ADUNum)%MassFlowRateDnStrLk / ZoneMult
      END IF
    END DO
    ! Do not allow exhaust mass flow for a plenum zone
    ExhMassFlowRate = 0.0d0
    TotExitMassFlowRate = ExhMassFlowRate + ZoneMassFlowRate

  ELSE IF (ZoneSupPlenumAirFlag) THEN

    MoistureMassFlowRate = MoistureMassFlowRate + &
                           (Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%MassFlowRate * &
                           Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%HumRat) / ZoneMult
    ZoneMassFlowRate = ZoneMassFlowRate + &
                           Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%MassFlowRate / ZoneMult
    ! Do not allow exhaust mass flow for a plenum zone
    ExhMassFlowRate = 0.0d0
    TotExitMassFlowRate = ExhMassFlowRate + ZoneMassFlowRate
  END IF

  ! Calculate hourly humidity ratio from infiltration + humdidity added from latent load + system added moisture
  LatentGain = ZoneLatentGain(ZoneNum) + SumLatentHTRadSys(ZoneNum)

  SysTimeStepInSeconds = SecInHour * TimeStepSys

  ! Calculate the coefficients for the 3rd order derivative for final
  ! zone humidity ratio.  The A, B, C coefficients are analogous to the
  ! heat balance.  There are 2 cases that should be considered, system
  ! operating and system shutdown.
  ! SumHmARaW and SumHmARa will be used with the moisture balance on the building elements and
  ! are currently set to zero to remind us where they need to be in the future
  IF ((.NOT. ANY(Surface(Zone(ZoneNum)%SurfaceFirst:Zone(ZoneNum)%SurfaceLast)%HeatTransferAlgorithm == HeatTransferModel_EMPD))&
      .AND. &
      (.NOT. ANY(Surface(Zone(ZoneNum)%SurfaceFirst:Zone(ZoneNum)%SurfaceLast)%HeatTransferAlgorithm == HeatTransferModel_HAMT)))&
     THEN
    SumHmARaW(ZoneNum) = 0.0d0
    SumHmARa(ZoneNum) = 0.0d0
  END IF

  RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,ZT(ZoneNum),ZoneAirHumRat(ZoneNum),'CorrectZoneHumRat')
  H2OHtOfVap = PsyHgAirFnWTdb(ZoneAirHumRat(ZoneNum),ZT(ZoneNum),'CorrectZoneHumRat')

  ! Check for the flow and NO flow condition
  IF (ZoneMassFlowRate .GT. 0.0d0) THEN
    B = (LatentGain/H2OHtOfVap)+((oamfl(ZoneNum)+vamfl(ZoneNum)+eamfl(ZoneNum)+ctmfl(ZoneNum))* OutHumRat) &
                               +(MoistureMassFlowRate) &
                               +SumHmARaW(ZoneNum)  &
                               +MixingMassFlowXHumRat(ZoneNum) + MDotOA(ZoneNum) * OutHumRat
    A = TotExitMassFlowRate + oamfl(ZoneNum) + vamfl(ZoneNum) + eamfl(ZoneNum) + ctmfl(ZoneNum) &
                            + SumHmARa(ZoneNum) + MixingMassFlowZone(ZoneNum) + MDotOA(ZoneNum)
    if (SimulateAirflowNetwork == AirflowNetworkControlMultizone .OR. SimulateAirflowNetwork == AirflowNetworkControlMultiADS.OR. &
       (SimulateAirflowNetwork == AirflowNetworkControlSimpleADS .AND. AirflowNetworkFanActivated)) then
      ! Multizone airflow calculated in AirflowNetwork
      B = (LatentGain/H2OHtOfVap)+(AirflowNetworkExchangeData(ZoneNum)%SumMHrW+AirflowNetworkExchangeData(ZoneNum)%SumMMHrW)+ &
          (MoistureMassFlowRate)+SumHmARaW(ZoneNum)
      A = TotExitMassFlowRate + AirflowNetworkExchangeData(ZoneNum)%SumMHr +AirflowNetworkExchangeData(ZoneNum)%SumMMHr + &
          SumHmARa(ZoneNum)
    end if
    C = RhoAir*Zone(ZoneNum)%Volume*ZoneVolCapMultpMoist/SysTimeStepInSeconds
  ELSE IF (ZoneMassFlowRate .LE. 0.0d0) THEN
    B = (LatentGain/H2OHtOfVap)+((oamfl(ZoneNum)+vamfl(ZoneNum)+eamfl(ZoneNum)+ctmfl(ZoneNum)+ExhMassFlowRate)* OutHumRat) &
                               +SumHmARaW(ZoneNum) + MixingMassFlowXHumRat(ZoneNum)
    A = oamfl(ZoneNum) + vamfl(ZoneNum) + eamfl(ZoneNum) +ctmfl(ZoneNum) + ExhMassFlowRate + SumHmARa(ZoneNum) &
                       + MixingMassFlowZone(ZoneNum)
    if (SimulateAirflowNetwork == AirflowNetworkControlMultizone .OR. SimulateAirflowNetwork == AirflowNetworkControlMultiADS .OR. &
       (SimulateAirflowNetwork == AirflowNetworkControlSimpleADS .AND. AirflowNetworkFanActivated)) then
      ! Multizone airflow calculated in AirflowNetwork
      B = (LatentGain/H2OHtOfVap) + SumHmARaW(ZoneNum)+ &
          AirflowNetworkExchangeData(ZoneNum)%SumMHrW+AirflowNetworkExchangeData(ZoneNum)%SumMMHrW
      A = AirflowNetworkExchangeData(ZoneNum)%SumMHr+AirflowNetworkExchangeData(ZoneNum)%SumMMHr+ &
          SumHmARa(ZoneNum)
    end if
    C = RhoAir*Zone(ZoneNum)%Volume*ZoneVolCapMultpMoist/SysTimeStepInSeconds
  END IF

  if (SimulateAirflowNetwork > AirflowNetworkControlMultizone) then
     B = B+AirflowNetworkExchangeData(ZoneNum)%TotalLat
  end if

  ! Use a 3rd order derivative to predict final zone humidity ratio and
  ! smooth the changes using the zone air capacitance.
  SELECT CASE (ZoneAirSolutionAlgo)
    CASE (Use3rdOrder)
      ZoneAirHumRatTemp(ZoneNum)=(B+C*(3.0d0*WZoneTimeMinus1Temp(ZoneNum)-(3.0d0/2.0d0)*WZoneTimeMinus2Temp(ZoneNum)+ &
                             (1.0d0/3.0d0)*WZoneTimeMinus3Temp(ZoneNum)))/((11.0d0/6.0d0)*C+A)
    ! Exact solution
    CASE (UseAnalyticalSolution)
      If (A .eq. 0.0d0) Then ! B=0
        ZoneAirHumRatTemp(ZoneNum)= ZoneW1(ZoneNum) + B/C
      Else
        ZoneAirHumRatTemp(ZoneNum)= (ZoneW1(ZoneNum)-B/A)*exp(MIN(700.d0,-A/C))+B/A
      End If
    CASE (UseEulerMethod)
      ZoneAirHumRatTemp(ZoneNum) = (C*ZoneW1(ZoneNum)+B)/(C+A)
  END SELECT

  ! Set the humidity ratio to zero if the zone has been dried out
  IF (ZoneAirHumRatTemp(ZoneNum) .LT. 0.0d0) ZoneAirHumRatTemp(ZoneNum) = 0.0d0

  ! Check to make sure that is saturated there is condensation in the zone
  ! by resetting to saturation conditions.
  Wzsat = PsyWFnTdbRhPb(Zt(ZoneNum),1.0d0,OutBaroPress,'CorrectZoneHumRat')

  IF (ZoneAirHumRatTemp(ZoneNum) .GT. Wzsat) ZoneAirHumRatTemp(ZoneNum) = Wzsat

  ! Now put the calculated info into the actual zone nodes; ONLY if there is zone air flow, i.e. controlled zone or plenum zone
  ZoneNodeNum = Zone(ZoneNum)%SystemZoneNodeNumber
  IF (ZoneNodeNum > 0) THEN
    Node(ZoneNodeNum)%HumRat = ZoneAirHumRatTemp(ZoneNum)
    Node(ZoneNodeNum)%Enthalpy = PsyHFnTdbW(ZT(ZoneNum),ZoneAirHumRatTemp(ZoneNum))
  END IF

  RETURN

END SUBROUTINE CorrectZoneHumRat

SUBROUTINE DownInterpolate4HistoryValues ( OldTimeStep, NewTimeStep,                   &
                                        oldVal0, oldVal1, oldVal2, oldVal3, oldVal4,   &
                                        newVal0, newVal1, newVal2, newVal3, newVal4)
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   Feb 2008
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! provide a reusable routine for the various places that need to
          ! interpolate a new set of history values on a different time scale
          ! Once the systemtimestep has shortened, the new history terms need to be interpolated
          !

          ! METHODOLOGY EMPLOYED:
          ! This routine assumes that the direction is to a shorter timestep.
          ! The down step ratio, DSRatio = OldTimeStep/ NewTimeStep
          !  is expected to be roughly integer-valued and near 2.0 or 3.0 or 4.0 or more.
          !

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN)    :: OldTimeStep
  REAL(r64), INTENT(IN)    :: NewTimeStep
  REAL(r64), INTENT(INOUT) :: oldVal0
  REAL(r64), INTENT(INOUT) :: oldVal1
  REAL(r64), INTENT(INOUT) :: oldVal2
  REAL(r64), INTENT(INOUT) :: oldVal3
  REAL(r64), INTENT(INOUT) :: oldVal4
  REAL(r64), INTENT(INOUT) :: newVal0
  REAL(r64), INTENT(INOUT) :: newVal1
  REAL(r64), INTENT(INOUT) :: newVal2
  REAL(r64), INTENT(INOUT) :: newVal3  ! unused 1208
  REAL(r64), INTENT(INOUT) :: newVal4  ! unused 1208

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: oldTime0
  REAL(r64) :: oldTime1
  REAL(r64) :: oldTime2
  REAL(r64) :: oldTime3
  REAL(r64) :: oldTime4
  REAL(r64) :: newTime0
  REAL(r64) :: newTime1
  REAL(r64) :: newTime2
  REAL(r64) :: newTime3
  REAL(r64) :: newTime4

  REAL(r64) :: DSRatio

  ! first construct data on timestamps for interpolating with later
  oldTime0 = 0.0D0
  oldTime1 = oldTime0 - OldTimeStep
  oldTime2 = oldTime1 - OldTimeStep
  oldTime3 = oldTime2 - OldTimeStep
  oldTime4 = oldTime3 - OldTimeStep

  newTime0 = 0.0D0
  newTime1 = newTime0 - NewTimeStep
  newTime2 = newTime1 - NewTimeStep
  newTime3 = newTime2 - NewTimeStep
  newTime4 = newTime3 - NewTimeStep

  DSRatio = OldTimeStep/ NewTimeStep ! should pretty much be an integer value 2, 3, 4, etc.

  newVal0 = oldVal0

  IF (ABS(DSRatio - 2.0D0) < 0.01D0) THEN  ! DSRatio = 2
    ! first two points lie between oldVal0 and oldVal1
    newVal1 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime1) / (OldTimeStep))
    newVal2 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime2) / (OldTimeStep))
    ! last two points lie between oldVal1 and oldVal2
    newVal3 = oldVal1 + (oldVal2 - oldVal1) * ((oldTime1 - newTime3)/ (OldTimeStep))
    newVal4 = oldVal1 + (oldVal2 - oldVal1) * ((oldTime1 - newTime4)/ (OldTimeStep))
  ELSE IF (ABS(DSRatio - 3.0D0) < 0.01D0) THEN  ! DSRatio = 3
    ! first three points lie between oldVal0 and oldVal1
    newVal1 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime1) / (OldTimeStep))
    newVal2 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime2) / (OldTimeStep))
    newVal3 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime3) / (OldTimeStep))
    ! last point lie between oldVal1 and oldVal2
    newVal4 = oldVal1 + (oldVal2 - oldVal1) * ((oldTime1 - newTime4)/ (OldTimeStep))

  ELSE IF (DSRatio > 3.99D0) THEN ! DSRatio = 4 or more
    !all new points lie between oldVal0 and oldVal1
    newVal1 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime1) / (OldTimeStep))
    newVal2 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime2) / (OldTimeStep))
    newVal3 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime3) / (OldTimeStep))
    newVal4 = oldVal0 + (oldVal1 - oldVal0) * ((oldTime0 - newTime4) / (OldTimeStep))
  ENDIF

  RETURN
END SUBROUTINE DownInterpolate4HistoryValues

SUBROUTINE CalcZoneSums(ZoneNum, SumIntGain, SumHA, SumHATsurf, SumHATref, SumMCp, SumMCpT, SumSysMCp, SumSysMCpT)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   July 2003
          !       MODIFIED       Aug 2003, FCW: add SumHA contributions from window frame and divider
          !                      Aug 2003, CC: change how the reference temperatures are used
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine calculates the various sums that go into the zone heat balance
          ! equation.  This replaces the SUMC, SUMHA, and SUMHAT calculations that were
          ! previously done in various places throughout the program.
          ! The SumHAT portion of the code is reproduced in RadiantSystemHighTemp and
          ! RadiantSystemLowTemp and should be updated accordingly.
          !
          ! A reference temperature (Tref) is specified for use with the ceiling diffuser
          ! convection correlation.  A bogus value of Tref = -999.9 defaults to using
          ! the zone air (i.e. outlet) temperature for the reference temperature.
          ! If Tref is applied to all surfaces, SumHA = 0, and SumHATref /= 0.
          ! If Tref is not used at all, SumHATref = 0, and SumHA /= 0.
          !
          ! For future implementations, Tref can be easily converted into an array to
          ! allow a different reference temperature to be specified for each surface.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataSurfaces
  USE DataHeatBalance
  USE DataHeatBalSurface
  USE DataLoopNode, ONLY: Node
  USE DataZoneEquipment, ONLY: ZoneEquipConfig
  USE ZonePlenum, ONLY: ZoneRetPlenCond, ZoneSupPlenCond, NumZoneReturnPlenums, NumZoneSupplyPlenums
  USE DataDefineEquip, ONLY: AirDistUnit, NumAirDistUnits
  USE InternalHeatGains, ONLY: SumAllInternalConvectionGains, SumAllReturnAirConvectionGains

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: ZoneNum               ! Zone number
  REAL(r64), INTENT(OUT)   :: SumIntGain            ! Zone sum of convective internal gains
  REAL(r64), INTENT(OUT)   :: SumHA                 ! Zone sum of Hc*Area
  REAL(r64), INTENT(OUT)   :: SumHATsurf            ! Zone sum of Hc*Area*Tsurf
  REAL(r64), INTENT(OUT)   :: SumHATref             ! Zone sum of Hc*Area*Tref, for ceiling diffuser convection correlation
  REAL(r64), INTENT(OUT)   :: SumMCp                ! Zone sum of MassFlowRate*Cp
  REAL(r64), INTENT(OUT)   :: SumMCpT               ! Zone sum of MassFlowRate*Cp*T
  REAL(r64), INTENT(OUT)   :: SumSysMCp             ! Zone sum of air system MassFlowRate*Cp
  REAL(r64), INTENT(OUT)   :: SumSysMCpT            ! Zone sum of air system MassFlowRate*Cp*T

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER             :: NodeNum               ! System node number
  REAL(r64)           :: NodeTemp              ! System node temperature
  REAL(r64)           :: MassFlowRate          ! System node mass flow rate
  INTEGER             :: ZoneEquipConfigNum
  LOGICAL             :: ControlledZoneAirFlag
  INTEGER             :: ZoneRetPlenumNum
  INTEGER             :: ZoneSupPlenumNum
  LOGICAL             :: ZoneRetPlenumAirFlag
  LOGICAL             :: ZoneSupPlenumAirFlag
  REAL(r64)           :: CpAir                 ! Specific heat of air
  INTEGER             :: SurfNum               ! Surface number
  REAL(r64)           :: HA                    ! Hc*Area
  REAL(r64)           :: Area                  ! Effective surface area
  REAL(r64)           :: RefAirTemp            ! Reference air temperature for surface convection calculations
  REAL(r64)           :: ZoneMult
  INTEGER             :: ADUListIndex
  INTEGER             :: ADUNum
  INTEGER             :: ADUInNode
  INTEGER             :: ADUOutNode
  REAL(r64)           :: RetAirGain

          ! FLOW:
  SumIntGain = 0.0d0
  SumHA = 0.0d0
  SumHATsurf = 0.0d0
  SumHATref = 0.0d0
  SumMCp = 0.0d0
  SumMCpT = 0.0d0
  SumSysMCp = 0.0d0
  SumSysMCpT = 0.0d0

  ! Sum all convective internal gains: SumIntGain

  CALL SumAllInternalConvectionGains(ZoneNum, SumIntGain)
  SumIntGain = SumIntGain   + SumConvHTRadSys(ZoneNum)

  ! Add heat to return air if zonal system (no return air) or cycling system (return air frequently very
  ! low or zero)
  IF (Zone(ZoneNum)%NoHeatToReturnAir) THEN
    CALL SumAllReturnAirConvectionGains(ZoneNum, RetAirGain)
    SumIntGain = SumIntGain + RetAirGain
  END IF

  ! Sum all non-system air flow, i.e. infiltration, simple ventilation, mixing, earth tube: SumMCp, SumMCpT
  SumMCp = MCPI(ZoneNum) + MCPV(ZoneNum) + MCPM(ZoneNum) + MCPE(ZoneNum) + MCPC(ZoneNum) + MdotCPOA(ZoneNum)
  SumMCpT = MCPTI(ZoneNum) + MCPTV(ZoneNum) + MCPTM(ZoneNum) + MCPTE(ZoneNum) + MCPTC(ZoneNum) + &
            MdotCPOA(ZoneNum)*Zone(ZoneNum)%OutDryBulbTemp

  ! Sum all multizone air flow calculated from AirflowNetwork by assuming no simple air infiltration model
  if (SimulateAirflowNetwork == AirflowNetworkControlMultizone .OR. SimulateAirflowNetwork == AirflowNetworkControlMultiADS .OR. &
     (SimulateAirflowNetwork == AirflowNetworkControlSimpleADS .AND. AirflowNetworkFanActivated)) then
    ! Multizone airflow calculated in AirflowNetwork
    SumMCp = AirflowNetworkExchangeData(ZoneNum)%SumMCp+AirflowNetworkExchangeData(ZoneNum)%SumMMCp
    SumMCpT = AirflowNetworkExchangeData(ZoneNum)%SumMCpT+AirflowNetworkExchangeData(ZoneNum)%SumMMCpT
  end if

  ! Sum all system air flow: SumSysMCp, SumSysMCpT
  ! Check to see if this is a controlled zone

  ControlledZoneAirFlag = .FALSE.
!  If (Zone(ZoneNum)%IsControlled) Then   ! more CR 7384
!    ControlledZoneAirFlag = .TRUE.       ! more CR 7384
!    ZoneEquipConfigNum = ZoneNum         ! more CR 7384
!  endif
    ! BG feb 2008 repeating this do loop every time seems crazy, store ControlledZoneAirFlag in Zone structure?
  DO ZoneEquipConfigNum = 1, NumOfZones
    IF (.not. Zone(ZoneEquipConfigNum)%IsControlled) CYCLE
    IF (ZoneEquipConfig(ZoneEquipConfigNum)%ActualZoneNum /= ZoneNum) CYCLE
    ControlledZoneAirFlag = .TRUE.
    EXIT !sloppy way of finding ZoneEquipConfigNum for later use.
  END DO ! ZoneEquipConfigNum

  ! Check to see if this is a plenum zone
  ! BG feb 2008 repeating this do loop every time seems crazy, store ControlledZoneAirFlag in Zone structure?
  ZoneRetPlenumAirFlag = .FALSE.
  DO ZoneRetPlenumNum = 1, NumZoneReturnPlenums
    IF (ZoneRetPlenCond(ZoneRetPlenumNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneRetPlenumAirFlag = .TRUE.
    EXIT
  END DO ! ZoneRetPlenumNum
  ZoneSupPlenumAirFlag = .FALSE.
  DO ZoneSupPlenumNum = 1, NumZoneSupplyPlenums
    IF (ZoneSupPlenCond(ZoneSupPlenumNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneSupPlenumAirFlag = .TRUE.
    EXIT
  END DO ! ZoneSupPlenumNum

  ! Plenum and controlled zones have a different set of inlet nodes which must be calculated.
  IF (ControlledZoneAirFlag) THEN
    DO NodeNum = 1, ZoneEquipConfig(ZoneEquipConfigNum)%NumInletNodes
      ! Get node conditions
      !  this next block is of interest to irratic system loads... maybe nodes are not accurate at time of call?
      !  how can we tell?  predict step must be lagged ?  correct step, systems have run.
      NodeTemp = Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%Temp
      MassFlowRate = Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%MassFlowRate
      CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

      SumSysMCp = SumSysMCp + MassFlowRate * CpAir
      SumSysMCpT = SumSysMCpT + MassFlowRate * CpAir * NodeTemp
    END DO ! NodeNum

  ELSE IF (ZoneRetPlenumAirFlag) THEN
    DO NodeNum = 1, ZoneRetPlenCond(ZoneRetPlenumNum)%NumInletNodes
      ! Get node conditions
      NodeTemp = Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%Temp
      MassFlowRate = Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%MassFlowRate
      CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

      SumSysMCp = SumSysMCp + MassFlowRate * CpAir
      SumSysMCpT = SumSysMCpT + MassFlowRate * CpAir * NodeTemp
    END DO ! NodeNum
    ! add in the leaks
    DO ADUListIndex=1,ZoneRetPlenCond(ZoneRetPlenumNum)%NumADUs
      ADUNum = ZoneRetPlenCond(ZoneRetPlenumNum)%ADUIndex(ADUListIndex)
      IF (AirDistUnit(ADUNum)%UpStreamLeak) THEN
        ADUInNode = AirDistUnit(ADUNum)%InletNodeNum
        NodeTemp = Node(ADUInNode)%Temp
        MassFlowRate = AirDistUnit(ADUNum)%MassFlowRateUpStrLk
        CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)
        SumSysMCp = SumSysMCp + MassFlowRate * CpAir
        SumSysMCpT = SumSysMCpT + MassFlowRate * CpAir * NodeTemp
      END IF
      IF (AirDistUnit(ADUNum)%DownStreamLeak) THEN
        ADUOutNode = AirDistUnit(ADUNum)%OutletNodeNum
        NodeTemp = Node(ADUOutNode)%Temp
        MassFlowRate = AirDistUnit(ADUNum)%MassFlowRateDnStrLk
        CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)
        SumSysMCp = SumSysMCp + MassFlowRate * CpAir
        SumSysMCpT = SumSysMCpT + MassFlowRate * CpAir * NodeTemp
      END IF
    END DO

  ELSE IF (ZoneSupPlenumAirFlag) THEN
    ! Get node conditions
    NodeTemp = Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%Temp
    MassFlowRate = Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%MassFlowRate
    CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

    SumSysMCp = SumSysMCp + MassFlowRate * CpAir
    SumSysMCpT = SumSysMCpT + MassFlowRate * CpAir * NodeTemp

  END IF

  ZoneMult = Zone(ZoneNum)%Multiplier * Zone(ZoneNum)%ListMultiplier

  SumSysMCp = SumSysMCp / ZoneMult
  SumSysMCpT = SumSysMCpT / ZoneMult

  ! Sum all surface convection: SumHA, SumHATsurf, SumHATref (and additional contributions to SumIntGain)
  DO SurfNum = Zone(ZoneNum)%SurfaceFirst,Zone(ZoneNum)%SurfaceLast

    IF (.NOT. Surface(SurfNum)%HeatTransSurf) CYCLE ! Skip non-heat transfer surfaces

    HA = 0.0d0
    Area = Surface(SurfNum)%Area  ! For windows, this is the glazing area

    IF (Surface(SurfNum)%Class == SurfaceClass_Window) THEN

      ! Add to the convective internal gains
      IF (SurfaceWindow(SurfNum)%ShadingFlag == IntShadeOn .OR. SurfaceWindow(SurfNum)%ShadingFlag == IntBlindOn) THEN
        ! The shade area covers the area of the glazing plus the area of the dividers.
        Area = Area + SurfaceWindow(SurfNum)%DividerArea
        ! If interior shade or blind is present it is assumed that both the convective and IR radiative gain
        ! from the inside surface of the divider goes directly into the zone air -- i.e., the IR radiative
        ! interaction between divider and shade or blind is ignored due to the difficulty of calculating this interaction
        ! at the same time that the interaction between glass and shade is calculated.
        SumIntGain = SumIntGain + SurfaceWindow(SurfNum)%DividerConduction
      END IF

      ! Other convection term is applicable to equivalent layer window (ASHWAT) model
      IF (Construct(Surface(SurfNum)%Construction)%WindowTypeEQL) &
         SumIntGain = SumIntGain + SurfaceWindow(SurfNum)%OtherConvHeatGain

      ! Convective heat gain from natural convection in gap between glass and interior shade or blind
      IF (SurfaceWindow(SurfNum)%ShadingFlag == IntShadeOn &
        .OR. SurfaceWindow(SurfNum)%ShadingFlag == IntBlindOn) &
        SumIntGain = SumIntGain + SurfaceWindow(SurfNum)%ConvHeatFlowNatural

      ! Convective heat gain from airflow window
      IF (SurfaceWindow(SurfNum)%AirFlowThisTS > 0.0d0) THEN
        SumIntGain = SumIntGain + SurfaceWindow(SurfNum)%ConvHeatGainToZoneAir
        IF (Zone(ZoneNum)%NoHeatToReturnAir) THEN
          SumIntGain = SumIntGain + SurfaceWindow(SurfNum)%RetHeatGainToZoneAir
          WinHeatGain(SurfNum) = WinHeatGain(SurfNum) + SurfaceWindow(SurfNum)%RetHeatGainToZoneAir
          IF(WinHeatGain(SurfNum) >= 0.0d0) THEN
            WinHeatGainRep(SurfNum) = WinHeatGain(SurfNum)
            WinHeatGainRepEnergy(SurfNum) = WinHeatGainRep(SurfNum) * TimeStepZone * SecInHour
          ELSE
            WinHeatLossRep(SurfNum) = -WinHeatGain(SurfNum)
            WinHeatLossRepEnergy(SurfNum) = WinHeatLossRep(SurfNum) * TimeStepZone * SecInHour
          END IF
        END IF
      END IF

      ! Add to the surface convection sums
      IF (SurfaceWindow(SurfNum)%FrameArea > 0.0d0) THEN
        ! Window frame contribution
        SumHATsurf = SumHATsurf + HConvIn(SurfNum) * SurfaceWindow(SurfNum)%FrameArea &
          * (1.0d0 + SurfaceWindow(SurfNum)%ProjCorrFrIn) * SurfaceWindow(SurfNum)%FrameTempSurfIn
        HA = HA + HConvIn(SurfNum) * SurfaceWindow(SurfNum)%FrameArea * (1.0d0 + SurfaceWindow(SurfNum)%ProjCorrFrIn)
      END IF

      IF (SurfaceWindow(SurfNum)%DividerArea > 0.0d0 .AND. SurfaceWindow(SurfNum)%ShadingFlag /= IntShadeOn &
           .AND. SurfaceWindow(SurfNum)%ShadingFlag /= IntBlindOn) THEN
        ! Window divider contribution (only from shade or blind for window with divider and interior shade or blind)
        SumHATsurf = SumHATsurf + HConvIn(SurfNum) * SurfaceWindow(SurfNum)%DividerArea &
          * (1.0d0 + 2.0d0 * SurfaceWindow(SurfNum)%ProjCorrDivIn) * SurfaceWindow(SurfNum)%DividerTempSurfIn
        HA = HA + HConvIn(SurfNum) * SurfaceWindow(SurfNum)%DividerArea * (1.0d0 + 2.0d0 * SurfaceWindow(SurfNum)%ProjCorrDivIn)
      END IF

    END IF  ! End of check if window

    HA = HA + HConvIn(SurfNum) * Area
    SumHATsurf = SumHATsurf + HConvIn(SurfNum) * Area * TempSurfInTmp(SurfNum)

    ! determine reference air temperature for this surface
    SELECT CASE (Surface(SurfNum)%TAirRef)
        CASE (ZoneMeanAirTemp)
            ! The zone air is the reference temperature (which is to be solved for in CorrectZoneAirTemp).
            RefAirTemp = MAT(ZoneNum)
            SumHA      = SumHA + HA
        CASE (AdjacentAirTemp)
            RefAirTemp = TempEffBulkAir(SurfNum)
            SumHATref = SumHATref + HA * RefAirTemp
        CASE (ZoneSupplyAirTemp)
            ! check whether this zone is a controlled zone or not
            IF (.NOT.ControlledZoneAirFlag) THEN
                CALL ShowFatalError('Zones must be controlled for Ceiling-Diffuser Convection model. No system serves zone '//  &
                                    TRIM(Zone(ZoneNum)%Name))
                RETURN
            END IF
            ! determine supply air temperature as a weighted average of the inlet temperatures.
            IF (SumSysMCp > 0.0d0) THEN
              RefAirTemp = SumSysMCpT/SumSysMCp
            ELSE
              ! no system flow (yet) so just use last value for inlet node temp, this can happen early in the environment
              RefAirTemp = NodeTemp
            ENDIF
            SumHATref = SumHATref + HA * RefAirTemp
        CASE DEFAULT
            ! currently set to mean air temp but should add error warning here
            RefAirTemp = MAT(ZoneNum)
            SumHA      = SumHA + HA
    END SELECT

  END DO ! SurfNum

  RETURN

END SUBROUTINE CalcZoneSums

SUBROUTINE CalcZoneComponentLoadSums(ZoneNum, TempDepCoef, TempIndCoef, SumIntGains, SumHADTsurfs, SumMCpDTzones, &
          SumMCpDtInfil, SumMCpDTsystem, SumNonAirSystem, CzdTdt , imBalance )

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   Feb 2008
          !       MODIFIED
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine calculates the various sums that go into the zone heat balance
          ! equation for reporting (and diagnostic) purposes only.
          ! It was derived from CalcZoneSums but differs in that that routine
          ! breaks up the component's dependence on zone air temp in order to *solve* for zone air temp,
          ! but here we *use* the result for zone air temp and calculate the terms of the heat balance
          ! Go back and calculate each of the 6 terms in Equation 5 and fill report variables.
          ! notes on these raw terms for zone air heat balance model :
          !  these are state variables at the end of the last system timestep.
          !  they are not necessarily proper averages for what happend over entire zone time step
          !  these are not mulitplied by zone multipliers.
          !  The values are all Watts.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! Equation 5 in Engineering Reference.
          !

          ! USE STATEMENTS:
  USE DataSurfaces
  USE DataHeatBalance
  USE DataHeatBalSurface
  USE DataLoopNode, ONLY: Node
  USE DataZoneEquipment, ONLY: ZoneEquipConfig
  USE ZonePlenum, ONLY: ZoneRetPlenCond, ZoneSupPlenCond, NumZoneReturnPlenums, NumZoneSupplyPlenums
  USE DataDefineEquip, ONLY: AirDistUnit, NumAirDistUnits
  USE General, ONLY: RoundSigDigits
  USE InternalHeatGains, ONLY: SumAllInternalConvectionGains, SumAllReturnAirConvectionGains

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: ZoneNum            ! Zone number
  REAL(r64), INTENT(IN)  :: TempDepCoef     ! Dependent coefficient
  REAL(r64), INTENT(IN)  :: TempIndCoef     ! Independent coefficient
  REAL(r64), INTENT(OUT) :: SumIntGains     ! Zone sum of convective internal gains
  REAL(r64), INTENT(OUT) :: SumHADTsurfs    ! Zone sum of Hc*Area*(Tsurf - Tz)
  REAL(r64), INTENT(OUT) :: SumMCpDTzones   ! zone sum of MassFlowRate*cp*(TremotZone - Tz) transfer air from other zone, Mixing
  REAL(r64), INTENT(OUT) :: SumMCpDtInfil   ! Zone sum of MassFlowRate*Cp*(Tout - Tz) transfer from outside, ventil, earth tube
  REAL(r64), INTENT(OUT) :: SumMCpDTsystem  ! Zone sum of air system MassFlowRate*Cp*(Tsup - Tz)
  REAL(r64), INTENT(OUT) :: SumNonAirSystem ! Zone sum of non air system convective heat gains
  REAL(r64), INTENT(OUT) :: CzdTdt          ! Zone air energy storage term.
  REAL(r64), INTENT(OUT) :: imBalance       ! put all terms in eq. 5 on RHS , should be zero

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER             :: NodeNum               ! System node number
  REAL(r64)           :: NodeTemp              ! System node temperature
  REAL(r64)           :: MassFlowRate          ! System node mass flow rate
  INTEGER             :: ZoneEquipConfigNum
  LOGICAL             :: ControlledZoneAirFlag
  INTEGER             :: ZoneRetPlenumNum
  INTEGER             :: ZoneSupPlenumNum
  LOGICAL             :: ZoneRetPlenumAirFlag
  LOGICAL             :: ZoneSupPlenumAirFlag
  REAL(r64)           :: RhoAir
  REAL(r64)           :: CpAir                 ! Specific heat of air
  INTEGER             :: SurfNum               ! Surface number
!unused  REAL(r64)           :: HA                    ! Hc*Area
  REAL(r64)           :: Area                  ! Effective surface area
  REAL(r64)           :: RefAirTemp            ! Reference air temperature for surface convection calculations
!unused  LOGICAL             :: FirstTimeFlag
!unused  INTEGER             :: Tref           ! Used to check if reference air temp for all surfaces in the zone are the same
!unused  REAL(r64)           :: ZoneMult
  INTEGER             :: ADUListIndex
  INTEGER             :: ADUNum
  INTEGER             :: ADUInNode
  INTEGER             :: ADUOutNode
  REAL(r64)           :: SumSysMCp
  REAL(r64)           :: SumSysMCpT
  REAL(r64)           :: Threshold
  REAL(r64)           :: SumRetAirGains

  SumIntGains    = 0.0D0    ! Zone sum of convective internal gains
  SumHADTsurfs   = 0.0D0    ! Zone sum of Hc*Area*(Tsurf - Tz)
  SumMCpDTzones  = 0.0D0    ! zone sum of MassFlowRate*cp*(TremotZone - Tz) transfer air from other zone, Mixing
  SumMCpDtInfil  = 0.0D0    ! Zone sum of MassFlowRate*Cp*(Tout - Tz)
  SumMCpDTsystem = 0.0D0    ! Zone sum of air system MassFlowRate*Cp*(Tsup - Tz)
  SumNonAirSystem= 0.0D0    !
  CzdTdt         = 0.0D0    !
  imBalance      = 0.0D0
  SumSysMCp      = 0.0d0
  SumSysMCpT     = 0.0d0

  ! Sum all convective internal gains: SumIntGain
  Call SumAllInternalConvectionGains(ZoneNum, SumIntGains)

  ! Add heat to return air if zonal system (no return air) or cycling system (return air frequently very
  ! low or zero)
  IF (Zone(ZoneNum)%NoHeatToReturnAir) THEN
   Call SumAllReturnAirConvectionGains(ZoneNum, SumRetAirGains)
   SumIntGains = SumIntGains + SumRetAirGains
  END IF

  ! sum non-system air flow transfers between zones
  SumMCpDTzones = MCPTM(ZoneNum) - MCPM(ZoneNum)* MAT(ZoneNum)  ! but maybe it should be ZTAV(ZoneNum)

  ! Sum non-system air flow, i.e. infiltration, simple ventilation, earth tube
  !  reuse SumMCp, SumMCpT from CalcZoneSum but use MAT (or maybe ZTAV?) to complete
  SumMCpDtInfil =  (MCPTI(ZoneNum) -  MCPI(ZoneNum)* MAT(ZoneNum)) &  ! infiltration
                 + (MCPTV(ZoneNum) -  MCPV(ZoneNum)* MAT(ZoneNum)) &  ! Ventilation (simple)
                 + (MCPTE(ZoneNum) -  MCPE(ZoneNum)* MAT(ZoneNum)) &  ! Earth tube.
                 + (MCPTC(ZoneNum) -  MCPC(ZoneNum)* MAT(ZoneNum)) &   ! Cooltower
                 + (MDotCPOA(ZoneNum)*Zone(ZoneNum)%OutDryBulbTemp -  MDotCPOA(ZoneNum)* MAT(ZoneNum))   ! combined OA flow

  ! Sum all multizone air flow calculated from AirflowNetwork by assuming no simple air infiltration model (if used)
  IF (SimulateAirflowNetwork == AirflowNetworkControlMultizone .OR. SimulateAirflowNetwork == AirflowNetworkControlMultiADS .OR. &
     (SimulateAirflowNetwork == AirflowNetworkControlSimpleADS .AND. AirflowNetworkFanActivated)) THEN
    ! Multizone airflow calculated in AirflowNetwork
    SumMCpDtInfil = AirflowNetworkExchangeData(ZoneNum)%SumMCpT - AirflowNetworkExchangeData(ZoneNum)%SumMCp * MAT(ZoneNum)
    SumMCpDTzones = AirflowNetworkExchangeData(ZoneNum)%SumMMCpT - AirflowNetworkExchangeData(ZoneNum)%SumMMCp * MAT(ZoneNum)
  END IF

  ! Sum all system air flow: reusing how SumSysMCp, SumSysMCpT are calculated in CalcZoneSums
  ! Check to see if this is a controlled zone

  ! CR 7384 continuation needed below.  eliminate do loop for speed and clarity
  ControlledZoneAirFlag = .FALSE.
  DO ZoneEquipConfigNum = 1, NumOfZones
    IF (.not. ZoneEquipConfig(ZoneEquipConfigNum)%IsControlled) CYCLE
    IF (ZoneEquipConfig(ZoneEquipConfigNum)%ActualZoneNum /= ZoneNum) CYCLE
    ControlledZoneAirFlag = .TRUE.
    EXIT
  END DO ! ZoneEquipConfigNum

  ! Check to see if this is a plenum zone
  ZoneRetPlenumAirFlag = .FALSE.
  DO ZoneRetPlenumNum = 1, NumZoneReturnPlenums
    IF (ZoneRetPlenCond(ZoneRetPlenumNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneRetPlenumAirFlag = .TRUE.
    EXIT
  END DO ! ZoneRetPlenumNum
  ZoneSupPlenumAirFlag = .FALSE.
  DO ZoneSupPlenumNum = 1, NumZoneSupplyPlenums
    IF (ZoneSupPlenCond(ZoneSupPlenumNum)%ActualZoneNum /= ZoneNum) CYCLE
    ZoneSupPlenumAirFlag = .TRUE.
    EXIT
  END DO ! ZoneSupPlenumNum

  ! Plenum and controlled zones have a different set of inlet nodes which must be calculated.
  IF (ControlledZoneAirFlag) THEN
    DO NodeNum = 1, ZoneEquipConfig(ZoneEquipConfigNum)%NumInletNodes
      ! Get node conditions
      NodeTemp = Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%Temp
      MassFlowRate = Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%MassFlowRate
      CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

      SumMCpDTsystem = SumMCpDTsystem + MassFlowRate * CpAir * (NodeTemp - MAT(ZoneNum))

    END DO ! NodeNum

  ELSE IF (ZoneRetPlenumAirFlag) THEN
    DO NodeNum = 1, ZoneRetPlenCond(ZoneRetPlenumNum)%NumInletNodes
      ! Get node conditions
      NodeTemp = Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%Temp
      MassFlowRate = Node(ZoneRetPlenCond(ZoneRetPlenumNum)%InletNode(NodeNum))%MassFlowRate
      CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

      SumMCpDTsystem = SumMCpDTsystem + MassFlowRate * CpAir * (NodeTemp - MAT(ZoneNum))

    END DO ! NodeNum
    ! add in the leaks
    DO ADUListIndex=1,ZoneRetPlenCond(ZoneRetPlenumNum)%NumADUs
      ADUNum = ZoneRetPlenCond(ZoneRetPlenumNum)%ADUIndex(ADUListIndex)
      IF (AirDistUnit(ADUNum)%UpStreamLeak) THEN
        ADUInNode = AirDistUnit(ADUNum)%InletNodeNum
        NodeTemp = Node(ADUInNode)%Temp
        MassFlowRate = AirDistUnit(ADUNum)%MassFlowRateUpStrLk
        CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)
        SumMCpDTsystem = SumMCpDTsystem + MassFlowRate * CpAir * (NodeTemp - MAT(ZoneNum))
      END IF
      IF (AirDistUnit(ADUNum)%DownStreamLeak) THEN
        ADUOutNode = AirDistUnit(ADUNum)%OutletNodeNum
        NodeTemp = Node(ADUOutNode)%Temp
        MassFlowRate = AirDistUnit(ADUNum)%MassFlowRateDnStrLk
        CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)
        SumMCpDTsystem = SumMCpDTsystem + MassFlowRate * CpAir * (NodeTemp - MAT(ZoneNum))
      END IF
    END DO

  ELSE IF (ZoneSupPlenumAirFlag) THEN
    ! Get node conditions
    NodeTemp = Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%Temp
    MassFlowRate = Node(ZoneSupPlenCond(ZoneSupPlenumNum)%InletNode)%MassFlowRate
    CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

    SumMCpDTsystem = SumMCpDTsystem + MassFlowRate * CpAir * (NodeTemp - MAT(ZoneNum))

  END IF

  ! non air system response.
  SumNonAirSystem  = NonAirSystemResponse(ZoneNum) + SumConvHTRadSys(ZoneNum)

  ! Sum all surface convection: SumHA, SumHATsurf, SumHATref (and additional contributions to SumIntGain)
  DO SurfNum = Zone(ZoneNum)%SurfaceFirst,Zone(ZoneNum)%SurfaceLast

    IF (.NOT. Surface(SurfNum)%HeatTransSurf) CYCLE ! Skip non-heat transfer surfaces

    Area = Surface(SurfNum)%Area  ! For windows, this is the glazing area
    ! determine reference air temperature for this surface's convective heat transfer model
    SELECT CASE (Surface(SurfNum)%TAirRef)
        CASE (ZoneMeanAirTemp)
            ! The zone air is the reference temperature
            RefAirTemp = MAT(ZoneNum)
        CASE (AdjacentAirTemp)
            RefAirTemp = TempEffBulkAir(SurfNum)
        CASE (ZoneSupplyAirTemp)
            ! check whether this zone is a controlled zone or not
            IF (.NOT.ControlledZoneAirFlag) THEN
                CALL ShowFatalError('Zones must be controlled for Ceiling-Diffuser Convection model. No system serves zone '//  &
                                    TRIM(Zone(ZoneNum)%Name))
                RETURN
            END IF
            ! determine supply air temperature as a weighted average of the inlet temperatures.
            DO NodeNum = 1, ZoneEquipConfig(ZoneEquipConfigNum)%NumInletNodes
               ! Get node conditions
               NodeTemp = Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%Temp
               MassFlowRate = Node(ZoneEquipConfig(ZoneEquipConfigNum)%InletNode(NodeNum))%MassFlowRate
               CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), NodeTemp)

               SumSysMCp = SumSysMCp + MassFlowRate * CpAir
               SumSysMCpT = SumSysMCpT + MassFlowRate * CpAir * NodeTemp

            END DO ! NodeNum
            IF (SumSysMCp > 0.0d0) THEN
              RefAirTemp = SumSysMCpT/SumSysMCp
            ELSE
              ! no system flow (yet) so just use last value for inlet node temp, this can happen early in the environment
              RefAirTemp = NodeTemp
            ENDIF

        CASE DEFAULT
            ! currently set to mean air temp but should add error warning here
            RefAirTemp = MAT(ZoneNum)

    END SELECT

    IF (Surface(SurfNum)%Class == SurfaceClass_Window) THEN

      ! Add to the convective internal gains
      IF (SurfaceWindow(SurfNum)%ShadingFlag == IntShadeOn .OR. SurfaceWindow(SurfNum)%ShadingFlag == IntBlindOn) THEN
        ! The shade area covers the area of the glazing plus the area of the dividers.
        Area = Area + SurfaceWindow(SurfNum)%DividerArea
        ! If interior shade or blind is present it is assumed that both the convective and IR radiative gain
        ! from the inside surface of the divider goes directly into the zone air -- i.e., the IR radiative
        ! interaction between divider and shade or blind is ignored due to the difficulty of calculating this interaction
        ! at the same time that the interaction between glass and shade is calculated.
        SumIntGains = SumIntGains + SurfaceWindow(SurfNum)%DividerConduction
      END IF

      ! Other convection term is applicable to equivalent layer window (ASHWAT) model
      IF (Construct(Surface(SurfNum)%Construction)%WindowTypeEQL) &
        SumIntGains = SumIntGains + SurfaceWindow(SurfNum)%OtherConvHeatGain

      ! Convective heat gain from natural convection in gap between glass and interior shade or blind
      IF (SurfaceWindow(SurfNum)%ShadingFlag == IntShadeOn &
        .OR. SurfaceWindow(SurfNum)%ShadingFlag == IntBlindOn) &
        SumIntGains = SumIntGains + SurfaceWindow(SurfNum)%ConvHeatFlowNatural

      ! Convective heat gain from airflow window
      IF (SurfaceWindow(SurfNum)%AirFlowThisTS > 0.0d0) THEN
        SumIntGains = SumIntGains + SurfaceWindow(SurfNum)%ConvHeatGainToZoneAir
        IF (Zone(ZoneNum)%NoHeatToReturnAir) THEN
          SumIntGains = SumIntGains + SurfaceWindow(SurfNum)%RetHeatGainToZoneAir
        END IF
      ENDIF

      ! Add to the surface convection sums
      IF (SurfaceWindow(SurfNum)%FrameArea > 0.0d0) THEN
        ! Window frame contribution

        SumHADTsurfs = SumHADTsurfs + HConvIn(SurfNum) * SurfaceWindow(SurfNum)%FrameArea *   &
                                 (1.0d0 + SurfaceWindow(SurfNum)%ProjCorrFrIn) &
                                       * (SurfaceWindow(SurfNum)%FrameTempSurfIn - RefAirTemp)

      END IF

      IF (SurfaceWindow(SurfNum)%DividerArea > 0.0d0 .AND. SurfaceWindow(SurfNum)%ShadingFlag /= IntShadeOn &
           .AND. SurfaceWindow(SurfNum)%ShadingFlag /= IntBlindOn) THEN
        ! Window divider contribution (only from shade or blind for window with divider and interior shade or blind)
        SumHADTsurfs = SumHADTsurfs +  HConvIn(SurfNum) * SurfaceWindow(SurfNum)%DividerArea *   &
                                 (1.0d0 + 2.0d0 * SurfaceWindow(SurfNum)%ProjCorrDivIn) &
                                       * (SurfaceWindow(SurfNum)%DividerTempSurfIn - RefAirTemp)

      END IF

    END IF  ! End of check if window

    SumHADTsurfs = SumHADTsurfs + HConvIn(SurfNum) * Area * ( TempSurfInTmp(SurfNum) - RefAirTemp)

  END DO ! SurfNum

  ! now calculate air energy storage source term.
   ! capacitance is volume * density * heat capacity
  CpAir = PsyCpAirFnWTdb(ZoneAirHumRat(ZoneNum), MAT(ZoneNum))
  RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,MAT(ZoneNum),ZoneAirHumRat(ZoneNum))

  SELECT CASE (ZoneAirSolutionAlgo)
    CASE (Use3rdOrder)
      CzdTdt = RhoAir *  CpAir  * Zone(ZoneNum)%Volume*ZoneVolCapMultpSens                &
          * ( MAT(ZoneNum) - ZTM1(ZoneNum))   &
            / (TimeStepSys*SecInHour)
    ! Exact solution
    CASE (UseAnalyticalSolution)
      CzdTdt = TempIndCoef-TempDepCoef*MAT(ZoneNum)
    CASE (UseEulerMethod)
      CzdTdt = AIRRAT(ZoneNum)*(MAT(ZoneNum) - ZoneT1(ZoneNum))
  END SELECT

  IF (DisplayZoneAirHeatBalanceOffBalance) THEN
    imBalance      = SumIntGains + SumHADTsurfs + SumMCpDTzones + SumMCpDtInfil + SumMCpDTsystem + SumNonAirSystem - CzdTdt

    ! throw warning if seriously out of balance (this may need to be removed if too noisy... )
    ! formulate dynamic threshold value based on 20% of quadrature sum of components
    Threshold   =  0.2D0 * SQRT(SumIntGains**2 + SumHADTsurfs**2 + SumMCpDTzones**2 + SumMCpDtInfil**2 &
                                + SumMCpDTsystem**2 + SumNonAirSystem**2 + CzdTdt**2)
    IF ((ABS(ImBalance) > Threshold) .AND. (.NOT. WarmUpFlag) &
        .AND. (.NOT. DoingSizing) ) THEN ! air balance is out by more than threshold
      IF (Zone(ZoneNum)%AirHBimBalanceErrIndex == 0) THEN
        Call ShowWarningMessage('Zone Air Heat Balance is out of balance for zone named ' &
                             //trim(Zone(ZoneNum)%Name))
        Call ShowContinueError('Zone Air Heat Balance Deviation Rate is more than ' &
            // Trim(RoundSigDigits(Threshold,1)) //' {W}')
        If (TurnFansOn) then
          Call ShowContinueError('Night cycle fan operation may be causing above error')
        ENDIF

        Call ShowContinueErrorTimeStamp(' Occurance info:  ')
      ENDIF
      Call ShowRecurringWarningErrorAtEnd('Zone Air Heat Balance is out of balance ... zone named ' // &
          trim(Zone(ZoneNum)%Name) , Zone(ZoneNum)%AirHBimBalanceErrIndex, &
          ReportMinOf=ABS(ImBalance)-Threshold,ReportMaxOf=ABS(ImBalance)-Threshold,ReportMinUnits='{W}',ReportMaxUnits='{W}')
    ENDIF
  ENDIF

  RETURN

END SUBROUTINE CalcZoneComponentLoadSums

FUNCTION VerifyThermostatInZone(ZoneName) RESULT (HasThermostat)

          ! FUNCTION INFORMATION:
          !       AUTHOR         Linda Lawrie
          !       DATE WRITTEN   Feb 2005
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          ! This function verifies that a zone (by name) has a Zone Control:Thermostatic
          ! object entered.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor, ONLY: FindItemInList

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! FUNCTION ARGUMENT DEFINITIONS:
  CHARACTER(len=*), INTENT(IN) :: ZoneName  ! Zone to verify
  LOGICAL :: HasThermostat   ! True if does, false if not.

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
          ! na

  IF (GetZoneAirStatsInputFlag) THEN
    CALL GetZoneAirSetpoints
    GetZoneAirStatsInputFlag = .FALSE.
  END IF
  IF (NumTempControlledZones > 0) THEN
    IF (FindItemInList(ZoneName,TempControlledZone%ZoneName,NumTempControlledZones) > 0) THEN
      HasThermostat=.true.
    ELSE
      HasThermostat=.false.
    ENDIF
  ELSE
    HasThermostat=.false.
  ENDIF
  RETURN

END FUNCTION VerifyThermostatInZone

FUNCTION VerifyControlledZoneForThermostat(ZoneName) RESULT (IsControlled)

          ! FUNCTION INFORMATION:
          !       AUTHOR         Linda Lawrie
          !       DATE WRITTEN   Mar 2007
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          ! This function verifies that a zone (by name) has a ZoneHVAC:EquipmentConnections
          ! object entered.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor, ONLY: FindItemInList
  USE DataZoneEquipment, ONLY: ZoneEquipConfig

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! FUNCTION ARGUMENT DEFINITIONS:
  CHARACTER(len=*), INTENT(IN) :: ZoneName  ! Zone to verify
  LOGICAL :: IsControlled   ! True if does, false if not.

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
          ! na

  IF (FindItemInList(ZoneName,ZoneEquipConfig%ZoneName,NumOfZones) > 0) THEN
    IsControlled=.true.
  ELSE
    IsControlled=.false.
  ENDIF
  RETURN

END FUNCTION VerifyControlledZoneForThermostat

SUBROUTINE DetectOscillatingZoneTemp
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Jason Glazer
          !       DATE WRITTEN   August 2005
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Oscillating temperatures between HVAC timesteps indicate that the
          ! simulation may be poor. Code is trying to be fast since the purpose
          ! is to see the impact on oscillating by trying longer time steps in
          ! an attempt to speed up the simulation.
          !
          ! Note that the OscillateMagnitude threshold must be less than
          ! MaxZoneTempDiff since ManageHVAC keeps shortening the timestep
          ! until that is reached unless it goes to less than the
          ! MinTimeStepSys.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
INTEGER :: iZone
REAL(r64)    :: NegOscillateMagnitude
LOGICAL :: isOscillate
REAL(r64)    :: Diff12
REAL(r64)    :: Diff23
REAL(r64)    :: Diff34
LOGICAL,SAVE :: SetupOscillationOutputFlag = .TRUE.
LOGICAL :: isAnyZoneOscillating

!first time run allocate arrays and setup output variable
IF (SetupOscillationOutputFlag) THEN
  ALLOCATE (ZoneTempHist(NumOfZones,4))
  ZoneTempHist = 0.0d0
  ALLOCATE (ZoneTempOscillate(NumOfZones))
  ZoneTempOscillate = 0.0d0
  !set up zone by zone variables
  ! CurrentModuleObject='Zone'
  DO iZone = 1, NumOfZones
    CALL SetupOutputVariable('Zone Oscillating Temperatures Time [hr]',ZoneTempOscillate(iZone), &
                              'System','Sum',Zone(iZone)%Name)
  END DO
  !set up a variable covering all zones
  CALL SetupOutputVariable('Facility Any Zone Oscillating Temperatures Time [hr]',AnyZoneTempOscillate, &
                              'System','Sum','Facility')
  SetupOscillationOutputFlag = .FALSE.
END IF
!precalc the negative value for performance
NegOscillateMagnitude = -OscillateMagnitude
!assume no zone is oscillating
isAnyZoneOscillating = .FALSE.
DO iZone = 1, NumOfZones
  isOscillate = .FALSE.
  ZoneTempHist(iZone,4) = ZoneTempHist(iZone,3)
  ZoneTempHist(iZone,3) = ZoneTempHist(iZone,2)
  ZoneTempHist(iZone,2) = ZoneTempHist(iZone,1)
  ZoneTempHist(iZone,1) = ZT(iZone)
  Diff34 = ZoneTempHist(iZone,3) - ZoneTempHist(iZone,4)
  Diff23 = ZoneTempHist(iZone,2) - ZoneTempHist(iZone,3)
  Diff12 = ZoneTempHist(iZone,1) - ZoneTempHist(iZone,2)
  ! roll out the conditionals for increased performance
  IF (Diff12 .GT. OscillateMagnitude) THEN
    IF (Diff23 .LT. NegOscillateMagnitude) THEN
      IF (Diff34 .GT. OscillateMagnitude) THEN
        isOscillate = .TRUE.
      END IF
    END IF
  END IF
  ! now try the opposite sequence of swings
  IF (Diff12 .LT. NegOscillateMagnitude) THEN
    IF (Diff23 .GT. OscillateMagnitude) THEN
      IF (Diff34 .LT. NegOscillateMagnitude) THEN
        isOscillate = .TRUE.
      END IF
    END IF
  END IF
  IF (isOscillate) THEN
    ZoneTempOscillate(iZone) = TimeStepSys
    isAnyZoneOscillating = .TRUE.
  ELSE
    ZoneTempOscillate(iZone) = 0.0d0
  END IF
END DO
!any zone variable
IF (isAnyZoneOscillating) THEN
  AnyZoneTempOscillate = TimeStepSys
ELSE
  AnyZoneTempOscillate = 0.0d0
END IF
END SUBROUTINE DetectOscillatingZoneTemp

SUBROUTINE AdjustAirSetpointsforOpTempCntrl(TempControlledZoneID, ActualZoneNum, ZoneAirSetpoint)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   June 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine modifies the air temperature setpoint to effect operative temperature control

          ! METHODOLOGY EMPLOYED:
          ! pass in data and alter setpoint if needed

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHeatBalance,   ONLY: MRT
  USE ScheduleManager, ONLY: GetCurrentScheduleValue

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: TempControlledZoneID
  INTEGER, INTENT(IN) :: ActualZoneNum
  REAL(r64),    INTENT(INOUT) :: ZoneAirSetpoint

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: thisMRT  ! local variable for mean radiant temperature in this zone
  REAL(r64) :: thisMRTFraction ! local variable for fraction that MRT is in Op Temp definition

  IF (.NOT.(AnyOpTempControl)) RETURN  ! do nothing to setpoint

  IF (.NOT. (TempControlledZone(TempControlledZoneID)%OperativeTempControl)) RETURN ! do nothing to setpoint

  ! is operative temp radiative fraction scheduled or fixed?
  If (TempControlledZone(TempControlledZoneID)%OpTempCntrlModeScheduled) then
    thisMRTFraction = GetCurrentScheduleValue(TempControlledZone(TempControlledZoneID)%OpTempRadiativeFractionSched)
  ELSE
    thisMRTFraction = TempControlledZone(TempControlledZoneID)%FixedRadiativeFraction
  ENDIF

  ! get mean radiant temperature for zone
  thisMRT = MRT(ActualZoneNum)

  ! modify setpoint for operative temperature control
  !  traping for MRT fractions between 0.0 and 0.9 during get input, so shouldn't be able to divide by zero here.
  ZoneAirSetpoint = (ZoneAirSetpoint - thisMRTFraction * thisMRT) / (1.d0 - thisMRTFraction)

  RETURN

END SUBROUTINE AdjustAirSetpointsforOpTempCntrl


SUBROUTINE CalcZoneAirComfortSetpoints

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Lixing Gu
          !       DATE WRITTEN   May 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This routine sets the thermal comfort setpoints for each controlled zone based on air tempeature
          ! obtained from thermal comfort models.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE General, ONLY: TrimSigDigits
  USE ThermalComfort, ONLY: ManageThermalComfort
  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: RelativeZoneNum
  INTEGER :: ActualZoneNum
  INTEGER :: ComfortControlSchedIndex
  INTEGER :: SetPointComfortSchedIndex
  INTEGER :: SetPointComfortSchedIndexHot
  INTEGER :: SetPointComfortSchedIndexCold
  INTEGER :: SchedNameIndex
  INTEGER :: SchedTypeIndex
  INTEGER :: PeopleNum
  INTEGER :: ObjectCount
  REAL(r64)    :: PeopleCount
  REAL(r64)    :: SetPointLo
  REAL(r64)    :: SetPointHi
  REAL(r64)    :: NumberOccupants
  REAL(r64)    :: Tset

  LOGICAL,SAVE :: FirstTimeFlag = .TRUE. ! Flag set to make sure you get input once

          ! FLOW:
   ! Call thermal comfort module to read zone control comfort object
   IF (FirstTimeFlag) THEN
     CALL ManageThermalComfort(InitializeOnly=.true.)
     FirstTimeFlag = .FALSE.
   END IF

   ComfortControlType = 0 ! Default

   DO RelativeZoneNum = 1, NumComfortControlledZones

    ActualZoneNum = ComfortControlledZone(RelativeZoneNum)%ActualZoneNum
    ComfortControlSchedIndex = ComfortControlledZone(RelativeZoneNum)%ComfortSchedIndex
    ComfortControlType(ActualZoneNum) = GetCurrentScheduleValue(ComfortControlSchedIndex)

    ! Get PMV values

    SELECT CASE (ComfortControlType(ActualZoneNum)) ! Is this missing the possibility of sometimes having no control on a zone
                                                 ! during the simulation?
      CASE (0) ! Uncontrolled for thermal comfort
        ZoneComfortControlsFanger(ActualZoneNum)%LowPMV = -999.0d0
        ZoneComfortControlsFanger(ActualZoneNum)%HighPMV = -999.0d0

      CASE (SglHeatSetPointFanger)

        SchedNameIndex = ComfortControlledZone(RelativeZoneNum)%SchIndx_SglHeatSetPointFanger
        SchedTypeIndex = ComfortControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)
        SetPointComfortSchedIndex = SetPointSingleHeatingFanger(SchedTypeIndex)%PMVSchedIndex
        ZoneComfortControlsFanger(ActualZoneNum)%FangerType = SglHeatSetPointFanger
        ZoneComfortControlsFanger(ActualZoneNum)%LowPMV = GetCurrentScheduleValue(SetPointComfortSchedIndex)
        ZoneComfortControlsFanger(ActualZoneNum)%HighPMV = -999.0d0

      CASE (SglCoolSetPointFanger)

        SchedNameIndex = ComfortControlledZone(RelativeZoneNum)%SchIndx_SglCoolSetPointFanger
        SchedTypeIndex = ComfortControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)
        SetPointComfortSchedIndex = SetPointSingleCoolingFanger(SchedTypeIndex)%PMVSchedIndex
        ZoneComfortControlsFanger(ActualZoneNum)%FangerType = SglCoolSetPointFanger
        ZoneComfortControlsFanger(ActualZoneNum)%LowPMV = -999.0d0
        ZoneComfortControlsFanger(ActualZoneNum)%HighPMV = GetCurrentScheduleValue(SetPointComfortSchedIndex)

      CASE (SglHCSetPointFanger)

        SchedNameIndex = ComfortControlledZone(RelativeZoneNum)%SchIndx_SglHCSetPointFanger
        SchedTypeIndex = ComfortControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)
        SetPointComfortSchedIndex = SetPointSingleHeatCoolFanger(SchedTypeIndex)%PMVSchedIndex
        ZoneComfortControlsFanger(ActualZoneNum)%FangerType = SglHCSetPointFanger
        ZoneComfortControlsFanger(ActualZoneNum)%LowPMV = GetCurrentScheduleValue(SetPointComfortSchedIndex)
        ZoneComfortControlsFanger(ActualZoneNum)%HighPMV = GetCurrentScheduleValue(SetPointComfortSchedIndex)

      CASE (DualSetPointFanger)

        SchedNameIndex = ComfortControlledZone(RelativeZoneNum)%SchIndx_DualSetPointFanger
        SchedTypeIndex = ComfortControlledZone(RelativeZoneNum)%ControlTypeSchIndx(SchedNameIndex)
        SetPointComfortSchedIndexHot = SetPointDualHeatCoolFanger(SchedTypeIndex)%HeatPMVSchedIndex
        SetPointComfortSchedIndexCold = SetPointDualHeatCoolFanger(SchedTypeIndex)%CoolPMVSchedIndex
        ZoneComfortControlsFanger(ActualZoneNum)%FangerType = DualSetPointFanger
        ZoneComfortControlsFanger(ActualZoneNum)%LowPMV = GetCurrentScheduleValue(SetPointComfortSchedIndexHot)
        ZoneComfortControlsFanger(ActualZoneNum)%HighPMV = GetCurrentScheduleValue(SetPointComfortSchedIndexCold)
        If (ZoneComfortControlsFanger(ActualZoneNum)%LowPMV > ZoneComfortControlsFanger(ActualZoneNum)%HighPMV) then
          ZoneComfortControlsFanger(ActualZoneNum)%DualPMVErrCount = ZoneComfortControlsFanger(ActualZoneNum)%DualPMVErrCount + 1
          if (ZoneComfortControlsFanger(ActualZoneNum)%DualPMVErrCount < 2) then
            CALL ShowWarningError('ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint: The heating PMV setpoint is above '// &
                'the cooling PMV setpoint in '//TRIM(SetPointDualHeatCoolFanger(SchedTypeIndex)%Name))
            CALL ShowContinueError('The zone dual heating PMV setpoint is set to the dual cooling PMV setpoint.')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          else
            CALL ShowRecurringWarningErrorAtEnd('The heating PMV setpoint is still above '// &
                'the cooling PMV setpoint',ZoneComfortControlsFanger(ActualZoneNum)%DualPMVErrIndex, &
                 ZoneComfortControlsFanger(ActualZoneNum)%LowPMV, ZoneComfortControlsFanger(ActualZoneNum)%LowPMV)
          end if
          ZoneComfortControlsFanger(ActualZoneNum)%LowPMV = ZoneComfortControlsFanger(ActualZoneNum)%HighPMV
        End If

      CASE DEFAULT
        CALL ShowSevereError('CalcZoneAirTempSetpoints: Illegal thermal control control type for Zone='//  &
                               TRIM(Zone(ActualZoneNum)%Name)//  &
                               ', Found value='//TRIM(TrimSigDigits(ComfortControlType(ActualZoneNum)))//  &
                               ', in Schedule='//TRIM(COmfortControlledZone(RelativeZoneNum)%ControlTypeSchedName))

    END SELECT

    ! Check Average method
    SELECT CASE (ComfortControlledZone(RelativeZoneNum)%AverageMethodNum)
      CASE (AverageMethodNum_NO)
        PeopleNum = ComfortControlledZone(RelativeZoneNum)%SpecificObjectNum
        If (ComfortControlType(ActualZoneNum) == SglCoolSetPointFanger) then
          CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,SetPointLo)
        Else
          CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%LowPMV,SetPointLo)
        End If
        If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) &
        CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,SetPointHi)
      CASE (AverageMethodNum_SPE)
        PeopleNum = ComfortControlledZone(RelativeZoneNum)%SpecificObjectNum
        If (ComfortControlType(ActualZoneNum) == SglCoolSetPointFanger) then
          CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,SetPointLo)
        Else
          CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%LowPMV,SetPointLo)
        End If
        If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) &
        CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,SetPointHi)
      CASE (AverageMethodNum_OBJ)
        ObjectCount = 0
        SetPointLo = 0.0d0
        SetPointHi = 0.0d0
        Do PeopleNum=1,TotPeople
          If (ActualZoneNum == People(PeopleNum)%ZonePtr) then
            ObjectCount=ObjectCount+1
            CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%LowPMV,Tset)
            SetPointLo = SetPointLo + Tset
            If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) then
              CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,Tset)
              SetPointHi = SetPointHi + Tset
            End If
          End IF
        End Do
        SetPointLo = SetPointLo/ObjectCount
        If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) SetPointHi = SetPointHi/ObjectCount
      CASE (AverageMethodNum_PEO)
        PeopleCount = 0.0d0
        SetPointLo = 0.0d0
        SetPointHi = 0.0d0
        Do PeopleNum=1,TotPeople
          If (ActualZoneNum == People(PeopleNum)%ZonePtr) then
            NumberOccupants = People(PeopleNum)%NumberOfPeople * GetCurrentScheduleValue(People(PeopleNum)%NumberOfPeoplePtr)
            PeopleCount=PeopleCount+NumberOccupants
            CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%LowPMV,Tset)
            SetPointLo = SetPointLo + Tset*NumberOccupants
            If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) then
              CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,Tset)
              SetPointHi = SetPointHi+ Tset*NumberOccupants
            End If
          End If
        End Do
        If (PeopleCount > 0) then
          SetPointLo = SetPointLo/PeopleCount
          If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) SetPointHi = SetPointHi/PeopleCount
        Else
          ! reccurring warnings
!          ComfortControlledZone(RelativeZoneNum)%PeopleAverageErrCount = &
!                                           ComfortControlledZone(RelativeZoneNum)%PeopleAverageErrCount + 1
          if (ComfortControlledZone(RelativeZoneNum)%PeopleAverageErrIndex == 0) then
            Call ShowWarningMessage('ZoneControl:Thermostat:ThermalComfort: The total number of people in Zone = '// &
                 Trim(Zone(ActualZoneNum)%Name)//' is zero. The People Average option is not used.')
            Call ShowContinueError('The Object Average option is used instead. Simulation continues .....')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          end if
          Call ShowRecurringWarningErrorAtEnd('ZoneControl:Thermostat:ThermalComfort: The total number of people in Zone = '// &
                 Trim(Zone(ActualZoneNum)%Name)//' is still zero. The People Average option is not used', &
                 ComfortControlledZone(RelativeZoneNum)%PeopleAverageErrIndex, PeopleCount, PeopleCount)
          ObjectCount = 0
          SetPointLo = 0.0d0
          SetPointHi = 0.0d0
          Do PeopleNum=1,TotPeople
            If (ActualZoneNum == People(PeopleNum)%ZonePtr) then
              ObjectCount=ObjectCount+1
              CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%LowPMV,Tset)
              SetPointLo = SetPointLo + Tset
              If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) then
                CALL GetComfortSetpoints(PeopleNum, RelativeZoneNum, ZoneComfortControlsFanger(ActualZoneNum)%HighPMV,Tset)
                SetPointHi = SetPointHi + Tset
              End If
            End IF
          End Do
          SetPointLo = SetPointLo/ObjectCount
          If (ComfortControlType(ActualZoneNum) == DualSetPointFanger) SetPointHi = SetPointHi/ObjectCount
        End If
    END SELECT

    ! Assign setpoint
    SELECT CASE (ComfortControlType(ActualZoneNum)) ! Is this missing the possibility of sometimes having no control on a zone
                                                 ! during the simulation?
      CASE (0) ! Uncontrolled for thermal comfort
        SELECT CASE (TempControlType(ActualZoneNum))
          CASE (SingleHeatingSetPoint)
            ZoneThermostatSetPointHi(ActualZoneNum) = 0.0d0
          CASE (SingleCoolingSetPoint)
            ZoneThermostatSetPointLo(ActualZoneNum) = 0.0d0
        END SELECT

      CASE (SglHeatSetPointFanger)
        If (SetPointLo < ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint) then
          SetPointLo = ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint
!          ComfortControlledZone(RelativeZoneNum)%TdbMinErrCount = ComfortControlledZone(RelativeZoneNum)%TdbMinErrCount + 1
          if (ComfortControlledZone(RelativeZoneNum)%TdbMinErrIndex < 2) then
            CALL ShowWarningMessage('ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating temperature is below '// &
                'the Minimum dry-bulb temperature setpoint '//TRIM(ComfortControlledZone(RelativeZoneNum)%Name))
            CALL ShowContinueError('The zone heating setpoint is set to the Minimum dry-bulb temperature setpoint')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          end if
          CALL ShowRecurringWarningErrorAtEnd('ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating temperature is still'// &
                ' below the Minimum dry-bulb temperature setpoint ...', &
                ComfortControlledZone(RelativeZoneNum)%TdbMinErrIndex, SetPointLo, SetPointLo)
        End If
        TempZoneThermostatSetPoint(ActualZoneNum) = SetPointLo
        ZoneThermostatSetPointLo(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
        TempControlType(ActualZoneNum) = SingleHeatingSetPoint

      CASE (SglCoolSetPointFanger)

        If (SetPointLo > ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint) then
          SetPointLo = ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint
!          ComfortControlledZone(RelativeZoneNum)%TdbMaxErrCount = ComfortControlledZone(RelativeZoneNum)%TdbMaxErrCount + 1
          if (ComfortControlledZone(RelativeZoneNum)%TdbMaxErrIndex == 0) then
            CALL ShowWarningMessage('ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling temperature is above  '// &
                'the Maximum dry-bulb temperature setpoint '//TRIM(ComfortControlledZone(RelativeZoneNum)%Name))
            CALL ShowContinueError('The zone cooling setpoint is set to the Maximum dry-bulb temperature setpoint')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          end if
          CALL ShowRecurringWarningErrorAtEnd('ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling temperature is still'// &
                ' above the Maximum dry-bulb temperature setpoint ...', &
                ComfortControlledZone(RelativeZoneNum)%TdbMaxErrIndex, SetPointLo, SetPointLo)
        End If
        TempZoneThermostatSetPoint(ActualZoneNum) = SetPointLo
        ZoneThermostatSetPointHi(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
        TempControlType(ActualZoneNum) = SingleCoolingSetPoint

      CASE (SglHCSetPointFanger)

        If (ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint == ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint) then
          SetPointLo = ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint
        End If
        If (SetPointLo > ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint) &
          SetPointLo = ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint
        If (SetPointLo < ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint) &
          SetPointLo = ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint
        If (SetPointLo < ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint .or. &
            SetPointLo > ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint) then
!          ComfortControlledZone(RelativeZoneNum)%TdbHCErrCount = ComfortControlledZone(RelativeZoneNum)%TdbHCErrCount + 1
          if (ComfortControlledZone(RelativeZoneNum)%TdbHCErrIndex == 0) then
            CALL ShowWarningMessage('ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling temperature is above  '// &
                'the Maximum or below the Minimum dry-bulb temperature setpoint '//  &
                TRIM(ComfortControlledZone(RelativeZoneNum)%Name))
            CALL ShowContinueError('The zone setpoint is set to the Maximum dry-bulb temperature setpoint if above or ' &
                 //'the Minimum dry-bulb temperature setpoint if below')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          end if
          CALL ShowRecurringWarningErrorAtEnd('ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling '//  &
               'temperature is still beyond the range between Maximum and Minimum dry-bulb temperature setpoint ...', &
                ComfortControlledZone(RelativeZoneNum)%TdbHCErrIndex, SetPointLo, SetPointLo)
        End If
        TempZoneThermostatSetPoint(ActualZoneNum) = SetPointLo
        ZoneThermostatSetPointHi(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
        ZoneThermostatSetPointLo(ActualZoneNum) = TempZoneThermostatSetPoint(ActualZoneNum)
        TempControlType(ActualZoneNum) = SingleHeatCoolSetPoint

      CASE (DualSetPointFanger)

        If (SetPointLo < ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint) then
          SetPointLo = ComfortControlledZone(RelativeZoneNum)%TdbMinSetPoint
!          ComfortControlledZone(RelativeZoneNum)%TdbDualMinErrCount = ComfortControlledZone(RelativeZoneNum)%TdbDualMinErrCount+1
          if (ComfortControlledZone(RelativeZoneNum)%TdbDualMinErrIndex == 0) then
            CALL ShowWarningMessage('ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint temperature is below '// &
                'the Minimum dry-bulb temperature setpoint '//TRIM(ComfortControlledZone(RelativeZoneNum)%Name))
            CALL ShowContinueError('The zone dual heating setpoint is set to the Minimum dry-bulb temperature setpoint')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          end if
          CALL ShowRecurringWarningErrorAtEnd('ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint temperature is still'// &
                ' below the Minimum dry-bulb temperature setpoint ...', &
                ComfortControlledZone(RelativeZoneNum)%TdbDualMinErrIndex, SetPointLo, SetPointLo)
        End If
        If (SetPointHi > ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint) then
          SetPointHi = ComfortControlledZone(RelativeZoneNum)%TdbMaxSetPoint
!          ComfortControlledZone(RelativeZoneNum)%TdbDualMaxErrCount = ComfortControlledZone(RelativeZoneNum)%TdbDualMaxErrCount + 1
          if (ComfortControlledZone(RelativeZoneNum)%TdbDualMaxErrIndex == 0) then
            CALL ShowWarningMessage('ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint temperature is above  '// &
                'the Maximum dry-bulb temperature setpoint '//TRIM(ComfortControlledZone(RelativeZoneNum)%Name))
            CALL ShowContinueError('The zone dual cooling setpoint is set to the Maximum dry-bulb temperature setpoint')
            CALL ShowContinueErrorTimeStamp(' Occurrence info: ')
          end if
          CALL ShowRecurringWarningErrorAtEnd('ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint temperature is still'// &
                ' above the Maximum dry-bulb temperature setpoint ...', &
                ComfortControlledZone(RelativeZoneNum)%TdbDualMaxErrIndex, SetPointLo, SetPointLo)
        End If

        ZoneThermostatSetPointLo(ActualZoneNum) = SetPointLo
        ZoneThermostatSetPointHi(ActualZoneNum) = SetPointHi
        TempControlType(ActualZoneNum) = DualSetPointWithDeadBand

      CASE DEFAULT
        CALL ShowSevereError('CalcZoneAirComfortSetpoints: Illegal thermal control control type for Zone='//  &
                               TRIM(Zone(ActualZoneNum)%Name)//  &
                               ', Found value='//TRIM(TrimSigDigits(ComfortControlType(ActualZoneNum)))//  &
                               ', in Schedule='//TRIM(ComfortControlledZone(ActualZoneNum)%ControlTypeSchedName))

    END SELECT

  END DO

  RETURN

END SUBROUTINE CalcZoneAirComfortSetpoints

SUBROUTINE GetComfortSetpoints(PeopleNum, ComfortControlNum, PMVSet, Tset)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Lixing Gu
          !       DATE WRITTEN   May, 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na
          ! PURPOSE OF THIS SUBROUTINE:

          ! This routine sets what the thermal comfort setpoints for each controlled zone should be based on air tempeature
          ! obtained from thermal comfort models.
          ! This is called each time step.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE General, ONLY: SolveRegulaFalsi
  USE ThermalComfort, ONLY: CalcThermalComfortFanger
  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
       INTEGER, INTENT(IN)    :: PeopleNum                    !
       INTEGER, INTENT(IN)    :: ComfortControlNum                    !
       REAL(r64), INTENT(IN)       :: PMVSet                      !
       REAL(r64), INTENT(OUT)      :: TSet              ! drybulb setpoint temperature for a given PMV value
                                                   ! 0 = Solution; 1 = Set to Min; 2 Set to Max

          ! SUBROUTINE PARAMETER DEFINITIONS:
          REAL(r64),PARAMETER :: Acc = 0.001D0    ! accuracy control for SolveRegulaFalsi
          INTEGER,PARAMETER          :: MaxIter = 500  !iteration control for SolveRegulaFalsi

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
          REAL(r64) :: Tmin ! Minimun drybulb setpoint temperature
          REAL(r64) :: Tmax ! Maximun drybulb setpoint temperature
          REAL(r64) :: PMVResult ! Calculated PMV value
          REAL(r64) :: PMVMin ! Minimum allowed PMV value
          REAL(r64) :: PMVMax ! Calculated PMV value
          REAL(r64) :: Par(2) ! Passed parameter for RegularFalsi function
          INTEGER  :: SolFla !feed back flag from SolveRegulaFalsi
          INTEGER, SAVE :: IterLimitExceededNum1 = 0
          INTEGER, SAVE :: IterLimitErrIndex1 = 0
          INTEGER, SAVE :: IterLimitExceededNum2 = 0
          INTEGER, SAVE :: IterLimitErrIndex2 = 0

    Tmin = ComfortControlledZone(ComfortControlNum)%TdbMinSetPoint
    Tmax = ComfortControlledZone(ComfortControlNum)%TdbMaxSetPoint

    CALL CalcThermalComfortFanger(PeopleNum,Tmin,PMVResult)
    PMVmin = PMVResult
    CALL CalcThermalComfortFanger(PeopleNum,Tmax,PMVResult)
    PMVmax = PMVResult
    If (PMVset > PMVmin .AND. PMVset < PMVmax) then
      Par(1)=PMVset
      Par(2)=REAL(PeopleNum,r64)
      CALL SolveRegulaFalsi(Acc, MaxIter, SolFla, Tset, PMVResidual, Tmin, Tmax, Par)
      IF (SolFla == -1) THEN
        IF(.NOT. WarmupFlag)THEN
          IterLimitExceededNum1 = IterLimitExceededNum1 + 1
          IF (IterLimitExceededNum1 .EQ. 1) THEN
            CALL ShowWarningError(TRIM(ComfortControlledZone(ComfortControlNum)%Name) //  &
            ': Iteration limit exceeded calculating thermal comfort Fanger setpoint and non-converged setpoint is used')
          ELSE
            CALL ShowRecurringWarningErrorAtEnd(TRIM(ComfortControlledZone(ComfortControlNum)%Name)// &
             ':  Iteration limit exceeded calculating thermal comfort setpoint.', &
             IterLimitErrIndex1, Tset, Tset)
          END IF
        END IF
      ELSE IF (SolFla == -2) THEN
        IF(.NOT. WarmupFlag)THEN
          IterLimitExceededNum2 = IterLimitExceededNum2 + 1
          IF (IterLimitExceededNum2 .EQ. 1) THEN
            CALL ShowWarningError(TRIM(ComfortControlledZone(ComfortControlNum)%Name) //  &
            ': Solution is not found in calculating thermal comfort Fanger setpoint and the minimum setpoint is used')
          ELSE
            CALL ShowRecurringWarningErrorAtEnd(TRIM(ComfortControlledZone(ComfortControlNum)%Name)// &
             ':  Solution is not found in  calculating thermal comfort Fanger setpoint.', &
             IterLimitErrIndex2, Tset, Tset)
          END IF
        END IF
      END IF
    else if (PMVset < PMVmin) then
      Tset = Tmin
    else if (PMVset > PMVmax) then
      Tset = Tmax
    End If

  RETURN

END SUBROUTINE GetComfortSetpoints

REAL(r64) FUNCTION PMVResidual(Tset, Par)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad
          !       DATE WRITTEN   May 2006
          !       MODIFIED       L.Gu, May 2006
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (desired PMV value - actual PMV value) for thermal comfort control.

          ! METHODOLOGY EMPLOYED:
          !  Calls CalcThermalComfortFanger to get PMV value at the given zone and people conditions
          !  and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE ThermalComfort, ONLY: CalcThermalComfortFanger

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN)     :: Tset                    !
  REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = PMV set point

          ! FUNCTION PARAMETER DEFINITIONS:
          !  na

          ! INTERFACE BLOCK SPECIFICATIONS
          !  na

          ! DERIVED TYPE DEFINITIONS
          !  na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER :: PeopleNum          ! index of people object
  REAL(r64)    :: PMVresult          ! resulting PMV values

  PeopleNum = INT(Par(2))
  CALL CalcThermalComfortFanger(PeopleNum, Tset, PMVresult)
  PMVResidual = Par(1) - PMVresult
  RETURN

END FUNCTION PMVResidual

SUBROUTINE AdjustCoolingSetPointforTempAndHumidityControl(TempControlledZoneID, ActualZoneNum)
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Bereket A Nigusse, FSEC/UCF
          !       DATE WRITTEN   Nov 2010
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS SUBROUTINE:
          !  This subroutine modifies the air cooling setpoint temperature to effect zone air Temperature
          !  and humidity control
          !
          ! METHODOLOGY EMPLOYED:
          !  Alter the zone air cooling setpoint if the zone air relative humidity value exceeds the
          !  the zone dehumidifying relative humidity setpoint.

          ! REFERENCES:

          ! USE STATEMENTS:
  USE ScheduleManager,   ONLY: GetCurrentScheduleValue

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN)     :: TempControlledZoneID
  INTEGER, INTENT(IN)     :: ActualZoneNum            ! controlled zone actual zone number

          ! SUBROUTINE PARAMETER DEFINITIONS:
          !  na

          ! INTERFACE BLOCK SPECIFICATIONS
          !  na

          ! DERIVED TYPE DEFINITIONS
          !  na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)    :: MaxAllowedOvercoolRange    ! Maximum allowed zone overcool range [DeltaC]
  REAL(r64)    :: RelativeHumidityDiff       ! Difference between zone air relative humidity and dehumidifying setpoint [%RH]
  REAL(r64)    :: ZoneOvercoolRange          !
  REAL(r64)    :: ZoneOvercoolControlRatio   !


  IF (.NOT.(AnyZoneTempAndHumidityControl)) RETURN  ! do nothing to setpoint

  IF (.NOT. (TempControlledZone(TempControlledZoneID)%ZoneOvercoolControl)) RETURN ! do nothing to setpoint

  IF (TempControlledZone(TempControlledZoneID)%OverCoolCntrlModeScheduled)THEN
       ZoneOvercoolRange = &
       GetCurrentScheduleValue(TempControlledZone(TempControlledZoneID)%ZoneOverCoolRangeSchedIndex)
  ELSE
       ZoneOvercoolRange = TempControlledZone(TempControlledZoneID)%ZoneOvercoolConstRange
  ENDIF
  ZoneOvercoolControlRatio = TempControlledZone(TempControlledZoneID)%ZoneOvercoolControlRatio

  ! For Dual Setpoint thermostat the overcool range is limited by the temperature difference between cooling
  ! and heating setpoints
  MaxAllowedOvercoolRange = ZoneThermostatSetPointHi(ActualZoneNum) - ZoneThermostatSetPointLo(ActualZoneNum)
  IF (MaxAllowedOvercoolRange > 0.0d0)THEN
      ZoneOvercoolRange = MIN(ZoneOvercoolRange, MaxAllowedOvercoolRange)
  ENDIF
  ! Calculate difference between zone air relative humidity and the dehumidifying setpoint
  RelativeHumidityDiff = ZoneAirRelHum(ActualZoneNum) &
                 - GetCurrentScheduleValue(TempControlledZone(TempControlledZoneID)%DehumidifyingSchedIndex)
  IF (RelativeHumidityDiff > 0.0d0 .AND. ZoneOvercoolControlRatio > 0.0d0) THEN
    ! proportionally reset the cooling setpoint temperature downward (zone Overcool)
    ZoneOvercoolRange = MIN(ZoneOvercoolRange, RelativeHumidityDiff / ZoneOvercoolControlRatio)
    ZoneThermostatSetPointHi(ActualZoneNum) = ZoneThermostatSetPointHi(ActualZoneNum) - ZoneOvercoolRange
  ENDIF
  RETURN

END SUBROUTINE AdjustCoolingSetPointforTempAndHumidityControl

!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!

END MODULE ZoneTempPredictorCorrector

AirflowNetworkBalanceManager.f90 AirflowNetworkSolver.f90 BaseboardRadiator.f90 BaseboardRadiatorElectric.f90 BaseboardRadiatorSteam.f90 BaseboardRadiatorWater.f90 BranchInputManager.f90 BranchNodeConnections.f90 ConductionTransferFunctionCalc.f90 CoolTower.f90 CostEstimateManager.f90 CurveManager.f90 CVFOnlyRoutines.f90 DataAirflowNetwork.f90 DataAirLoop.f90 DataAirSystems.f90 DataBranchAirLoopPlant.f90 DataBranchNodeConnections.f90 DataBSDFWindow.f90 DataComplexFenestration.f90 DataContaminantBalance.f90 DataConvergParams.f90 DataConversions.f90 DataCostEstimate.f90 DataDaylighting.f90 DataDaylightingDevices.f90 Datadefineequip.f90 DataDElight.f90 DataEnvironment.f90 DataEquivalentLayerWindow.f90 DataErrorTracking.f90 DataGenerators.f90 DataGlobalConstants.f90 DataGlobals.f90 DataHeatBalance.f90 DataHeatBalFanSys.f90 DataHeatBalSurface.f90 DataHVACControllers.f90 DataHVACGlobals.f90 DataInterfaces.f90 DataIPShortCuts.f90 DataLoopNode.f90 DataMoistureBalance.f90 DataMoistureBalanceEMPD.f90 DataOutputs.f90 DataPhotovoltaics.f90 DataPlant.f90 DataPlantPipingSystems.f90 DataPrecisionGlobals.f90 DataReportingFlags.f90 DataRoomAir.f90 DataRootFinder.f90 DataRuntimeLanguage.f90 DataShadowingCombinations.f90 DataSizing.f90 DataStringGlobals.f90 DataSurfaceColors.f90 DataSurfaceLists.f90 DataSurfaces.f90 DataSystemVariables.f90 DataTimings.f90 DataUCSDSharedData.f90 DataVectorTypes.f90 DataViewFactorInformation.f90 DataWater.f90 DataZoneControls.f90 DataZoneEnergyDemands.f90 DataZoneEquipment.f90 DaylightingDevices.f90 DaylightingManager.f90 DElightManagerF.f90 DElightManagerF_NO.f90 DemandManager.f90 DesiccantDehumidifiers.f90 DirectAir.f90 DisplayRoutines.f90 DXCoil.f90 EarthTube.f90 EconomicLifeCycleCost.f90 EconomicTariff.f90 EcoRoof.f90 ElectricPowerGenerators.f90 ElectricPowerManager.f90 EMSManager.f90 EnergyPlus.f90 ExteriorEnergyUseManager.f90 ExternalInterface_NO.f90 FanCoilUnits.f90 FaultsManager.f90 FluidProperties.f90 General.f90 GeneralRoutines.f90 GlobalNames.f90 HeatBalanceAirManager.f90 HeatBalanceConvectionCoeffs.f90 HeatBalanceHAMTManager.f90 HeatBalanceInternalHeatGains.f90 HeatBalanceIntRadExchange.f90 HeatBalanceManager.f90 HeatBalanceMovableInsulation.f90 HeatBalanceSurfaceManager.f90 HeatBalFiniteDifferenceManager.f90 HeatRecovery.f90 Humidifiers.f90 HVACControllers.f90 HVACCooledBeam.f90 HVACDualDuctSystem.f90 HVACDuct.f90 HVACDXSystem.f90 HVACEvapComponent.f90 HVACFanComponent.f90 HVACFurnace.f90 HVACHeatingCoils.f90 HVACHXAssistedCoolingCoil.f90 HVACInterfaceManager.f90 HVACManager.f90 HVACMixerComponent.f90 HVACMultiSpeedHeatPump.f90 HVACSingleDuctInduc.f90 HVACSingleDuctSystem.f90 HVACSplitterComponent.f90 HVACStandAloneERV.f90 HVACSteamCoilComponent.f90 HVACTranspiredCollector.f90 HVACUnitaryBypassVAV.f90 HVACUnitarySystem.f90 HVACVariableRefrigerantFlow.f90 HVACWaterCoilComponent.f90 HVACWatertoAir.f90 HVACWatertoAirMultiSpeedHP.f90 InputProcessor.f90 MatrixDataManager.f90 MixedAir.f90 MoistureBalanceEMPDManager.f90 NodeInputManager.f90 NonZoneEquipmentManager.f90 OutAirNodeManager.f90 OutdoorAirUnit.f90 OutputProcessor.f90 OutputReportPredefined.f90 OutputReports.f90 OutputReportTabular.f90 PackagedTerminalHeatPump.f90 PackagedThermalStorageCoil.f90 Photovoltaics.f90 PhotovoltaicThermalCollectors.f90 PlantAbsorptionChillers.f90 PlantBoilers.f90 PlantBoilersSteam.f90 PlantCentralGSHP.f90 PlantChillers.f90 PlantCondLoopOperation.f90 PlantCondLoopTowers.f90 PlantEIRChillers.f90 PlantEvapFluidCoolers.f90 PlantExhaustAbsorptionChiller.f90 PlantFluidCoolers.f90 PlantGasAbsorptionChiller.f90 PlantGroundHeatExchangers.f90 PlantHeatExchanger.f90 PlantIceThermalStorage.f90 PlantLoadProfile.f90 PlantLoopEquipment.f90 PlantLoopSolver.f90 PlantManager.f90 PlantOutsideEnergySources.f90 PlantPipeHeatTransfer.f90 PlantPipes.f90 PlantPipingSystemManager.f90 PlantPondGroundHeatExchanger.f90 PlantPressureSystem.f90 PlantPumps.f90 PlantSolarCollectors.f90 PlantSurfaceGroundHeatExchanger.f90 PlantUtilities.f90 PlantValves.f90 PlantWaterSources.f90 PlantWaterThermalTank.f90 PlantWatertoWaterGSHP.f90 PlantWaterUse.f90 PollutionAnalysisModule.f90 PoweredInductionUnits.f90 PsychRoutines.f90 Purchasedairmanager.f90 RadiantSystemHighTemp.f90 RadiantSystemLowTemp.f90 RefrigeratedCase.f90 ReportSizingManager.f90 ReturnAirPath.f90 RoomAirManager.f90 RoomAirModelCrossVent.f90 RoomAirModelDisplacementVent.f90 RoomAirModelMundt.f90 RoomAirModelUFAD.f90 RoomAirModelUserTempPattern.f90 RootFinder.f90 RuntimeLanguageProcessor.f90 ScheduleManager.f90 SetPointManager.f90 SimAirServingZones.f90 SimulationManager.f90 SizingManager.f90 SolarReflectionManager.f90 SolarShading.f90 SortAndStringUtilities.f90 sqlite3.c SQLiteCRoutines.c SQLiteFortranRoutines.f90 SQLiteFortranRoutines_NO.f90 StandardRatings.f90 SurfaceGeometry.f90 SystemAvailabilityManager.f90 SystemReports.f90 TarcogComplexFenestration.f90 ThermalChimney.f90 ThermalComfort.f90 UnitHeater.f90 UnitVentilator.f90 UserDefinedComponents.f90 UtilityRoutines.f90 VectorUtilities.f90 VentilatedSlab.f90 WaterManager.f90 WeatherManager.f90 WindowAC.f90 WindowComplexManager.f90 WindowEquivalentLayer.f90 WindowManager.f90 WindTurbine.f90 Zoneairloopequipmentmanager.f90 ZoneContaminantPredictorCorrector.f90 ZoneDehumidifier.f90 Zoneequipmentmanager.f90 ZonePlenumComponent.f90 ZoneTempPredictorCorrector.f90