sourcefile~~hvacevapcomponent.f90~~EfferentGraph sourcefile~hvacevapcomponent.f90 HVACEvapComponent.f90 sourcefile~datahvacglobals.f90 DataHVACGlobals.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacevapcomponent.f90 sourcefile~hvacfancomponent.f90 HVACFanComponent.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~datazoneequipment.f90 DataZoneEquipment.f90 sourcefile~datahvacglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~watermanager.f90 WaterManager.f90 sourcefile~datahvacglobals.f90->sourcefile~watermanager.f90 sourcefile~general.f90 General.f90 sourcefile~datahvacglobals.f90->sourcefile~general.f90 sourcefile~runtimelanguageprocessor.f90 RuntimeLanguageProcessor.f90 sourcefile~datahvacglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~branchinputmanager.f90 BranchInputManager.f90 sourcefile~datahvacglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~hvacfancomponent.f90->sourcefile~hvacevapcomponent.f90 sourcefile~datazoneequipment.f90->sourcefile~hvacevapcomponent.f90 sourcefile~datazoneequipment.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataipshortcuts.f90 DataIPShortCuts.f90 sourcefile~dataipshortcuts.f90->sourcefile~hvacevapcomponent.f90 sourcefile~schedulemanager.f90 ScheduleManager.f90 sourcefile~dataipshortcuts.f90->sourcefile~schedulemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90 InputProcessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~inputprocessor.f90 sourcefile~curvemanager.f90 CurveManager.f90 sourcefile~dataipshortcuts.f90->sourcefile~curvemanager.f90 sourcefile~outputprocessor.f90 OutputProcessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~outputprocessor.f90 sourcefile~emsmanager.f90 EMSManager.f90 sourcefile~emsmanager.f90->sourcefile~hvacevapcomponent.f90 sourcefile~emsmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~datasizing.f90 DataSizing.f90 sourcefile~datasizing.f90->sourcefile~hvacevapcomponent.f90 sourcefile~datasizing.f90->sourcefile~hvacfancomponent.f90 sourcefile~datasizing.f90->sourcefile~datazoneequipment.f90 sourcefile~datasizing.f90->sourcefile~inputprocessor.f90 sourcefile~dataplant.f90 DataPlant.f90 sourcefile~datasizing.f90->sourcefile~dataplant.f90 sourcefile~datasizing.f90->sourcefile~branchinputmanager.f90 sourcefile~datainterfaces.f90 DataInterfaces.f90 sourcefile~datainterfaces.f90->sourcefile~hvacevapcomponent.f90 sourcefile~datainterfaces.f90->sourcefile~hvacfancomponent.f90 sourcefile~datainterfaces.f90->sourcefile~datazoneequipment.f90 sourcefile~datainterfaces.f90->sourcefile~emsmanager.f90 sourcefile~reportsizingmanager.f90 ReportSizingManager.f90 sourcefile~datainterfaces.f90->sourcefile~reportsizingmanager.f90 sourcefile~datainterfaces.f90->sourcefile~watermanager.f90 sourcefile~outairnodemanager.f90 OutAirNodeManager.f90 sourcefile~datainterfaces.f90->sourcefile~outairnodemanager.f90 sourcefile~dataenvironment.f90 DataEnvironment.f90 sourcefile~datainterfaces.f90->sourcefile~dataenvironment.f90 sourcefile~psychroutines.f90 PsychRoutines.f90 sourcefile~datainterfaces.f90->sourcefile~psychroutines.f90 sourcefile~branchnodeconnections.f90 BranchNodeConnections.f90 sourcefile~datainterfaces.f90->sourcefile~branchnodeconnections.f90 sourcefile~datainterfaces.f90->sourcefile~schedulemanager.f90 sourcefile~datainterfaces.f90->sourcefile~general.f90 sourcefile~nodeinputmanager.f90 NodeInputManager.f90 sourcefile~datainterfaces.f90->sourcefile~nodeinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~inputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~curvemanager.f90 sourcefile~dataheatbalance.f90 DataHeatBalance.f90 sourcefile~datainterfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datainterfaces.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~outputprocessor.f90 sourcefile~dataruntimelanguage.f90 DataRuntimeLanguage.f90 sourcefile~datainterfaces.f90->sourcefile~dataruntimelanguage.f90 sourcefile~sqlitefortranroutines.f90 SQLiteFortranRoutines.f90 sourcefile~datainterfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datainterfaces.f90->sourcefile~dataplant.f90 sourcefile~datainterfaces.f90->sourcefile~branchinputmanager.f90 sourcefile~fluidproperties.f90 FluidProperties.f90 sourcefile~datainterfaces.f90->sourcefile~fluidproperties.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacevapcomponent.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataloopnode.f90 DataLoopNode.f90 sourcefile~dataloopnode.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataloopnode.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataloopnode.f90->sourcefile~datazoneequipment.f90 sourcefile~dataloopnode.f90->sourcefile~emsmanager.f90 sourcefile~dataloopnode.f90->sourcefile~outairnodemanager.f90 sourcefile~dataloopnode.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataloopnode.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataloopnode.f90->sourcefile~curvemanager.f90 sourcefile~dataloopnode.f90->sourcefile~dataplant.f90 sourcefile~dataloopnode.f90->sourcefile~branchinputmanager.f90 sourcefile~dataairsystems.f90 DataAirSystems.f90 sourcefile~dataairsystems.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataairsystems.f90->sourcefile~emsmanager.f90 sourcefile~watermanager.f90->sourcefile~hvacevapcomponent.f90 sourcefile~outairnodemanager.f90->sourcefile~hvacevapcomponent.f90 sourcefile~outairnodemanager.f90->sourcefile~emsmanager.f90 sourcefile~datawater.f90 DataWater.f90 sourcefile~datawater.f90->sourcefile~hvacevapcomponent.f90 sourcefile~datawater.f90->sourcefile~watermanager.f90 sourcefile~dataheatbalfansys.f90 DataHeatBalFanSys.f90 sourcefile~dataheatbalfansys.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataenvironment.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataenvironment.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataenvironment.f90->sourcefile~watermanager.f90 sourcefile~dataenvironment.f90->sourcefile~outairnodemanager.f90 sourcefile~dataenvironment.f90->sourcefile~psychroutines.f90 sourcefile~dataenvironment.f90->sourcefile~schedulemanager.f90 sourcefile~dataenvironment.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataenvironment.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~outputprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~psychroutines.f90->sourcefile~hvacevapcomponent.f90 sourcefile~psychroutines.f90->sourcefile~hvacfancomponent.f90 sourcefile~psychroutines.f90->sourcefile~outairnodemanager.f90 sourcefile~psychroutines.f90->sourcefile~nodeinputmanager.f90 sourcefile~psychroutines.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datazoneenergydemands.f90 DataZoneEnergyDemands.f90 sourcefile~datazoneenergydemands.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataglobalconstants.f90 DataGlobalConstants.f90 sourcefile~dataglobalconstants.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataglobalconstants.f90->sourcefile~outputprocessor.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacevapcomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacfancomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~datazoneequipment.f90 sourcefile~branchnodeconnections.f90->sourcefile~nodeinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~branchinputmanager.f90 sourcefile~schedulemanager.f90->sourcefile~hvacevapcomponent.f90 sourcefile~schedulemanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~schedulemanager.f90->sourcefile~datazoneequipment.f90 sourcefile~schedulemanager.f90->sourcefile~emsmanager.f90 sourcefile~schedulemanager.f90->sourcefile~watermanager.f90 sourcefile~schedulemanager.f90->sourcefile~nodeinputmanager.f90 sourcefile~schedulemanager.f90->sourcefile~outputprocessor.f90 sourcefile~schedulemanager.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~general.f90->sourcefile~hvacevapcomponent.f90 sourcefile~general.f90->sourcefile~hvacfancomponent.f90 sourcefile~general.f90->sourcefile~datazoneequipment.f90 sourcefile~general.f90->sourcefile~emsmanager.f90 sourcefile~general.f90->sourcefile~reportsizingmanager.f90 sourcefile~general.f90->sourcefile~watermanager.f90 sourcefile~general.f90->sourcefile~dataenvironment.f90 sourcefile~general.f90->sourcefile~psychroutines.f90 sourcefile~general.f90->sourcefile~branchnodeconnections.f90 sourcefile~general.f90->sourcefile~schedulemanager.f90 sourcefile~general.f90->sourcefile~nodeinputmanager.f90 sourcefile~general.f90->sourcefile~curvemanager.f90 sourcefile~general.f90->sourcefile~dataheatbalance.f90 sourcefile~general.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~general.f90->sourcefile~outputprocessor.f90 sourcefile~general.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~general.f90->sourcefile~dataplant.f90 sourcefile~general.f90->sourcefile~branchinputmanager.f90 sourcefile~general.f90->sourcefile~fluidproperties.f90 sourcefile~datacontaminantbalance.f90 DataContaminantBalance.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacevapcomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacfancomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~outairnodemanager.f90 sourcefile~datacontaminantbalance.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataprecisionglobals.f90 DataPrecisionGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~emsmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datainterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataprecisionglobals.f90->sourcefile~watermanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datawater.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalfansys.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataprecisionglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazoneenergydemands.f90 sourcefile~dataprecisionglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~general.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataglobals.f90 DataGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~curvemanager.f90 sourcefile~outputreportpredefined.f90 OutputReportPredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataairloop.f90 DataAirLoop.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairloop.f90 sourcefile~dataairflownetwork.f90 DataAirflowNetwork.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairflownetwork.f90 sourcefile~databranchairloopplant.f90 DataBranchAirLoopPlant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~datasystemvariables.f90 DataSystemVariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90 DataBSDFWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~datasurfaces.f90 DataSurfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90 DataVectorTypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datavectortypes.f90 sourcefile~datacomplexfenestration.f90 DataComplexFenestration.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataequivalentlayerwindow.f90 DataEquivalentLayerWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datazonecontrols.f90 DataZoneControls.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~dataprecisionglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataroomair.f90 DataRoomAir.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataplant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataerrortracking.f90 DataErrorTracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataerrortracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataglobals.f90->sourcefile~hvacevapcomponent.f90 sourcefile~dataglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~dataglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataglobals.f90->sourcefile~emsmanager.f90 sourcefile~dataglobals.f90->sourcefile~datasizing.f90 sourcefile~dataglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataglobals.f90->sourcefile~watermanager.f90 sourcefile~dataglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataglobals.f90->sourcefile~datawater.f90 sourcefile~dataglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90->sourcefile~dataglobalconstants.f90 sourcefile~dataglobals.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataglobals.f90->sourcefile~general.f90 sourcefile~dataglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataglobals.f90->sourcefile~dataairloop.f90 sourcefile~dataglobals.f90->sourcefile~dataairflownetwork.f90 sourcefile~dataglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~sortandstringutilities.f90 SortAndStringUtilities.f90 sourcefile~dataglobals.f90->sourcefile~sortandstringutilities.f90 sourcefile~dataoutputs.f90 DataOutputs.f90 sourcefile~dataglobals.f90->sourcefile~dataoutputs.f90 sourcefile~dataglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataglobals.f90->sourcefile~dataplant.f90 sourcefile~dataglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchnodeconnections.f90 DataBranchNodeConnections.f90 sourcefile~dataglobals.f90->sourcefile~databranchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~fluidproperties.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacevapcomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~datazoneequipment.f90 sourcefile~nodeinputmanager.f90->sourcefile~outairnodemanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~hvacevapcomponent.f90 sourcefile~inputprocessor.f90->sourcefile~hvacfancomponent.f90 sourcefile~inputprocessor.f90->sourcefile~datazoneequipment.f90 sourcefile~inputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~inputprocessor.f90->sourcefile~watermanager.f90 sourcefile~inputprocessor.f90->sourcefile~outairnodemanager.f90 sourcefile~inputprocessor.f90->sourcefile~dataglobalconstants.f90 sourcefile~inputprocessor.f90->sourcefile~branchnodeconnections.f90 sourcefile~inputprocessor.f90->sourcefile~schedulemanager.f90 sourcefile~inputprocessor.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~curvemanager.f90 sourcefile~inputprocessor.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~outputprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~inputprocessor.f90->sourcefile~dataplant.f90 sourcefile~inputprocessor.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~fluidproperties.f90 sourcefile~curvemanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~curvemanager.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~curvemanager.f90->sourcefile~branchinputmanager.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacfancomponent.f90 sourcefile~outputreportpredefined.f90->sourcefile~reportsizingmanager.f90 sourcefile~outputreportpredefined.f90->sourcefile~outputprocessor.f90 sourcefile~dataairloop.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataairloop.f90->sourcefile~emsmanager.f90 sourcefile~dataairflownetwork.f90->sourcefile~hvacfancomponent.f90 sourcefile~databranchairloopplant.f90->sourcefile~curvemanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~branchinputmanager.f90 sourcefile~datasystemvariables.f90->sourcefile~schedulemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~inputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~curvemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datastringglobals.f90 DataStringGlobals.f90 sourcefile~datastringglobals.f90->sourcefile~schedulemanager.f90 sourcefile~datastringglobals.f90->sourcefile~general.f90 sourcefile~datastringglobals.f90->sourcefile~inputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datastringglobals.f90->sourcefile~outputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataheatbalance.f90->sourcefile~datazoneequipment.f90 sourcefile~dataheatbalance.f90->sourcefile~emsmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~watermanager.f90 sourcefile~dataheatbalance.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~outputprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~databsdfwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90->sourcefile~datasurfaces.f90 sourcefile~datasurfaces.f90->sourcefile~emsmanager.f90 sourcefile~datasurfaces.f90->sourcefile~watermanager.f90 sourcefile~datasurfaces.f90->sourcefile~general.f90 sourcefile~datasurfaces.f90->sourcefile~datacontaminantbalance.f90 sourcefile~datasurfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datasurfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datavectortypes.f90->sourcefile~dataheatbalance.f90 sourcefile~datavectortypes.f90->sourcefile~databsdfwindow.f90 sourcefile~datavectortypes.f90->sourcefile~datasurfaces.f90 sourcefile~datacomplexfenestration.f90->sourcefile~dataheatbalance.f90 sourcefile~dataequivalentlayerwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~runtimelanguageprocessor.f90->sourcefile~emsmanager.f90 sourcefile~outputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~outputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~outputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataruntimelanguage.f90->sourcefile~emsmanager.f90 sourcefile~dataruntimelanguage.f90->sourcefile~general.f90 sourcefile~dataruntimelanguage.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datazonecontrols.f90->sourcefile~emsmanager.f90 sourcefile~sortandstringutilities.f90->sourcefile~inputprocessor.f90 sourcefile~sortandstringutilities.f90->sourcefile~outputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~inputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~outputprocessor.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~reportsizingmanager.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~outputprocessor.f90 sourcefile~dataroomair.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataplant.f90->sourcefile~dataairsystems.f90 sourcefile~branchinputmanager.f90->sourcefile~dataplant.f90 sourcefile~dataerrortracking.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchnodeconnections.f90->sourcefile~branchnodeconnections.f90 sourcefile~fluidproperties.f90->sourcefile~nodeinputmanager.f90
Help

Files Dependent On This One

sourcefile~~hvacevapcomponent.f90~~AfferentGraph sourcefile~hvacevapcomponent.f90 HVACEvapComponent.f90 sourcefile~simairservingzones.f90 SimAirServingZones.f90 sourcefile~hvacevapcomponent.f90->sourcefile~simairservingzones.f90 sourcefile~zoneequipmentmanager.f90 Zoneequipmentmanager.f90 sourcefile~hvacevapcomponent.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~mixedair.f90 MixedAir.f90 sourcefile~hvacevapcomponent.f90->sourcefile~mixedair.f90 sourcefile~sizingmanager.f90 SizingManager.f90 sourcefile~simairservingzones.f90->sourcefile~sizingmanager.f90 sourcefile~hvacmanager.f90 HVACManager.f90 sourcefile~simairservingzones.f90->sourcefile~hvacmanager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~sizingmanager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~hvacmanager.f90 sourcefile~mixedair.f90->sourcefile~simairservingzones.f90 sourcefile~simulationmanager.f90 SimulationManager.f90 sourcefile~mixedair.f90->sourcefile~simulationmanager.f90 sourcefile~hvacstandaloneerv.f90 HVACStandAloneERV.f90 sourcefile~mixedair.f90->sourcefile~hvacstandaloneerv.f90 sourcefile~hvaccontrollers.f90 HVACControllers.f90 sourcefile~mixedair.f90->sourcefile~hvaccontrollers.f90 sourcefile~packagedterminalheatpump.f90 PackagedTerminalHeatPump.f90 sourcefile~mixedair.f90->sourcefile~packagedterminalheatpump.f90 sourcefile~airflownetworkbalancemanager.f90 AirflowNetworkBalanceManager.f90 sourcefile~mixedair.f90->sourcefile~airflownetworkbalancemanager.f90 sourcefile~hvacvariablerefrigerantflow.f90 HVACVariableRefrigerantFlow.f90 sourcefile~mixedair.f90->sourcefile~hvacvariablerefrigerantflow.f90 sourcefile~hvacunitarybypassvav.f90 HVACUnitaryBypassVAV.f90 sourcefile~mixedair.f90->sourcefile~hvacunitarybypassvav.f90 sourcefile~fancoilunits.f90 FanCoilUnits.f90 sourcefile~mixedair.f90->sourcefile~fancoilunits.f90 sourcefile~windowac.f90 WindowAC.f90 sourcefile~mixedair.f90->sourcefile~windowac.f90 sourcefile~sizingmanager.f90->sourcefile~simulationmanager.f90 sourcefile~hvacmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90 HeatBalanceAirManager.f90 sourcefile~hvacmanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~energyplus.f90 EnergyPlus.f90 sourcefile~simulationmanager.f90->sourcefile~energyplus.f90 sourcefile~utilityroutines.f90 UtilityRoutines.f90 sourcefile~simulationmanager.f90->sourcefile~utilityroutines.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancesurfacemanager.f90 HeatBalanceSurfaceManager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancemanager.f90 HeatBalanceManager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~sizingmanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~simulationmanager.f90 sourcefile~hvacstandaloneerv.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~hvacstandaloneerv.f90->sourcefile~hvacmanager.f90 sourcefile~systemreports.f90 SystemReports.f90 sourcefile~hvacstandaloneerv.f90->sourcefile~systemreports.f90 sourcefile~hvaccontrollers.f90->sourcefile~simairservingzones.f90 sourcefile~hvaccontrollers.f90->sourcefile~simulationmanager.f90 sourcefile~hvacfurnace.f90 HVACFurnace.f90 sourcefile~hvaccontrollers.f90->sourcefile~hvacfurnace.f90 sourcefile~packagedterminalheatpump.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~packagedterminalheatpump.f90->sourcefile~systemreports.f90 sourcefile~airflownetworkbalancemanager.f90->sourcefile~hvacmanager.f90 sourcefile~systemavailabilitymanager.f90 SystemAvailabilityManager.f90 sourcefile~airflownetworkbalancemanager.f90->sourcefile~systemavailabilitymanager.f90 sourcefile~hvacvariablerefrigerantflow.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~plantloopequipment.f90 PlantLoopEquipment.f90 sourcefile~hvacvariablerefrigerantflow.f90->sourcefile~plantloopequipment.f90 sourcefile~hvacunitarybypassvav.f90->sourcefile~simairservingzones.f90 sourcefile~fancoilunits.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~fancoilunits.f90->sourcefile~systemreports.f90 sourcefile~generalroutines.f90 GeneralRoutines.f90 sourcefile~fancoilunits.f90->sourcefile~generalroutines.f90 sourcefile~windowac.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~windowac.f90->sourcefile~systemreports.f90 sourcefile~systemreports.f90->sourcefile~hvacmanager.f90 sourcefile~systemreports.f90->sourcefile~simulationmanager.f90 sourcefile~systemreports.f90->sourcefile~utilityroutines.f90 sourcefile~hvacfurnace.f90->sourcefile~simairservingzones.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~simairservingzones.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~hvacmanager.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~plantmanager.f90 PlantManager.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~plantmanager.f90 sourcefile~plantmanager.f90->sourcefile~hvacmanager.f90 sourcefile~plantmanager.f90->sourcefile~simulationmanager.f90 sourcefile~plantmanager.f90->sourcefile~utilityroutines.f90 sourcefile~plantloopequipment.f90->sourcefile~plantmanager.f90 sourcefile~plantloopsolver.f90 PlantLoopSolver.f90 sourcefile~plantloopequipment.f90->sourcefile~plantloopsolver.f90 sourcefile~plantloopsolver.f90->sourcefile~plantmanager.f90
Help

Source Code


Source Code

Module EvaporativeCoolers
  ! Module containing the EvaporativeCoolers simulation routines

  ! MODULE INFORMATION:
  !       AUTHOR         Richard J. Liesen
  !       DATE WRITTEN   Oct 2000
  !       MODIFIED       BG July 2003 ResearchSpecial Indirect
  !                      BG Febraury 2007 outside air nodes
  !                      BG March 2009 ResearchSpecial Direct
  !       RE-ENGINEERED  na

  ! PURPOSE OF THIS MODULE:
  ! To encapsulate the data and algorithms required for
  ! Evaporative Coolers Components for use in mechanical air systems

  ! provide models for evaporative coolers as zone forced air units.

  ! METHODOLOGY EMPLOYED:
  ! various evaporative component models in this module
  !   different models share common module level data structure.
  !

  ! REFERENCES: none

  ! OTHER NOTES: none

  ! USE STATEMENTS:
  ! Use statements for data only modules
USE DataPrecisionGlobals
USE DataGlobals, ONLY: BeginEnvrnFlag,BeginDayFlag, SysSizingCalc, SecInHour, ScheduleAlwaysOn, MaxNameLength
USE DataInterfaces, ONLY: ShowContinueError, ShowSevereError,ShowFatalError, SetupOutputVariable, &
                          ShowWarningError, ShowContinueErrorTimeStamp,ShowRecurringWarningErrorAtEnd
USE DataLoopNode
Use DataEnvironment, ONLY: OUTBAROPRESS
USE ScheduleManager
Use Psychrometrics
USE DataGlobalConstants
USE DataZoneEquipment, ONLY: ZoneEvaporativeCoolerUnit_Num
  ! Use statements for access to subroutines in other modules

IMPLICIT NONE         ! Enforce explicit typing of all variables

PRIVATE ! Everything private unless explicitly made public

  ! MODULE PARAMETER DEFINITIONS
INTEGER, PARAMETER :: WaterSupplyFromMains = 101
INTEGER, PARAMETER :: WaterSupplyFromTank  = 102

INTEGER, PARAMETER :: BlowThruFan = 50
INTEGER, PARAMETER :: DrawThruFan = 51

INTEGER, PARAMETER :: ZoneTemperatureDeadbandOnOffCycling     = 20
INTEGER, PARAMETER :: ZoneCoolingLoadOnOffCycling             = 21
INTEGER, PARAMETER :: ZoneCoolingLoadVariableSpeedFan         = 22

  ! DERIVED TYPE DEFINITIONS
TYPE EvapConditions
  CHARACTER(len=MaxNameLength) :: EvapCoolerName  = ' ' ! Name of the EvapCooler
  INTEGER                      :: EquipIndex      = 0
  INTEGER                      :: EvapCoolerType  = 0 ! Type of the EvapCooler (parameters in DataGlobalConstants.f90
  CHARACTER(len=MaxNameLength) :: EvapControlType = ' ' ! Type of Control for the EvapCooler
  CHARACTER(len=MaxNameLength) :: Schedule        = ' ' ! HeatingCoil Operation Schedule
  Integer      :: SchedPtr                        = 0   ! Pointer to the correct schedule
  REAL(r64)    :: VolFlowRate                     = 0.0D0 !Volume Flow Rate in Evap Cooler needed for calculating SatEff
  REAL(r64)    :: OutletTemp                      = 0.0D0 !
  REAL(r64)    :: OuletWetBulbTemp                = 0.0D0 !
  REAL(r64)    :: OutletHumRat                    = 0.0D0 !
  REAL(r64)    :: OutletEnthalpy                  = 0.0D0 !
  REAL(r64)    :: OutletPressure                  = 0.0D0 !
  REAL(r64)    :: OutletMassFlowRate              = 0.0D0 !MassFlow through the EvapCooler being Simulated [kg/Sec]
  REAL(r64)    :: OutletMassFlowRateMaxAvail      = 0.0D0 ! [kg/Sec]
  REAL(r64)    :: OutletMassFlowRateMinAvail      = 0.0D0 ! [kg/Sec]
  LOGICAL      :: InitFlag                        = .FALSE. !
  INTEGER      :: InletNode                       = 0   !
  INTEGER      :: OutletNode                      = 0   !
  INTEGER      :: SecondaryInletNode              = 0   ! This is usually OA node feeding into the purge/secondary side
  INTEGER      :: TertiaryInletNode               = 0   ! This node is used to run building exhaust into purge side.
  REAL(r64)    :: InletMassFlowRate               = 0.0D0 ! Inlet is primary process air node at inlet to cooler
  REAL(r64)    :: InletMassFlowRateMaxAvail       = 0.0D0 !
  REAL(r64)    :: InletMassFlowRateMinAvail       = 0.0D0 !
  REAL(r64)    :: InletTemp                       = 0.0D0 !
  REAL(r64)    :: InletWetBulbTemp                = 0.0D0 !
  REAL(r64)    :: InletHumRat                     = 0.0D0 !
  REAL(r64)    :: InletEnthalpy                   = 0.0D0 !
  REAL(r64)    :: InletPressure                   = 0.0D0 !
  REAL(r64)    :: SecInletMassFlowRate            = 0.0D0 ! Secondary inlet is for indirect coolers
  REAL(r64)    :: SecInletMassFlowRateMaxAvail    = 0.0D0 !
  REAL(r64)    :: SecInletMassFlowRateMinAvail    = 0.0D0 !
  REAL(r64)    :: SecInletTemp                    = 0.0D0 !
  REAL(r64)    :: SecInletWetBulbTemp             = 0.0D0 !
  REAL(r64)    :: SecInletHumRat                  = 0.0D0 !
  REAL(r64)    :: SecInletEnthalpy                = 0.0D0 !
  REAL(r64)    :: SecInletPressure                = 0.0D0 !
  REAL(r64)    :: PadDepth                        = 0.0D0 !
  REAL(r64)    :: PadArea                         = 0.0D0 !
  REAL(r64)    :: RecircPumpPower                 = 0.0D0 !
  REAL(r64)    :: IndirectRecircPumpPower         = 0.0D0 !
  REAL(r64)    :: IndirectPadDepth                = 0.0D0 !
  REAL(r64)    :: IndirectPadArea                 = 0.0D0 !
  REAL(r64)    :: IndirectVolFlowRate             = 0.0D0 !
  REAL(r64)    :: IndirectFanEff                  = 0.0D0 !
  REAL(r64)    :: IndirectFanDeltaPress           = 0.0D0 !
  REAL(r64)    :: IndirectHXEffectiveness         = 0.0D0 !
  REAL(r64)    :: DirectEffectiveness             = 0.0D0 ! input saturation effectiveness for constant effectiveness model
  REAL(r64)    :: WetCoilMaxEfficiency            = 0.0D0 !
  REAL(r64)    :: WetCoilFlowRatio                = 0.0D0 !
  REAL(r64)    :: EvapCoolerEnergy                = 0.0D0 !
  REAL(r64)    :: EvapCoolerPower                 = 0.0D0 !

  INTEGER      :: EvapWaterSupplyMode             = WaterSupplyFromMains !  where does water come from
  CHARACTER(len=MaxNameLength) :: EvapWaterSupplyName = ' ' ! name of water source e.g. water storage tank
  INTEGER      :: EvapWaterSupTankID              = 0 !
  INTEGER      :: EvapWaterTankDemandARRID        = 0 !
  REAL(r64)    :: DriftFraction                   = 0.0D0 ! excess water from drift as fraction of Evap Water Consumption rate
  REAL(r64)    :: BlowDownRatio                   = 0.0D0 ! excess water use for blowdown as solids ratio to be maintained

  REAL(r64)    :: EvapWaterConsumpRate            = 0.0D0 ! Evap Water Consumption rate in m3/sec
  REAL(r64)    :: EvapWaterConsump                = 0.0D0 ! Evap Water Consumption in m3
  REAL(r64)    :: EvapWaterStarvMakupRate         = 0.0D0 ! Evap water consumed but not really available from tank m3/s
  REAL(r64)    :: EvapWaterStarvMakup             = 0.0D0 ! Evap water consumed but not really available from tank m3
  REAL(r64)    :: SatEff                          = 0.0D0 !Reporting for Direct Stage and Ind Dry Saturation Efficiency
  REAL(r64)    :: StageEff                        = 0.0D0 !Reporting for Indirect Total Stage Efficiency
  REAL(r64)    :: DPBoundFactor                   = 0.0D0 ! in RDDSpecial efficency w.r.t. dewpoint
  Integer      :: EvapControlNodeNum              = 0   ! need to control to avoid over cooling
  REAL(r64)    :: DesiredOutletTemp               = 0.0D0 ! setpoint manager should set this
  REAL(r64)    :: PartLoadFract                   = 0.0D0 ! reduces cooling performance and associated fan power
  Integer      :: DewPointBoundFlag               = 0   ! report when indirect research special cooler is bound by dewpoint
                                                        ! rather than wetbulb-depression approach
END TYPE EvapConditions


  TYPE ZoneEvapCoolerUnitStruct
    CHARACTER(len=MaxNameLength) :: Name   =' '    ! user identifier
    INTEGER        :: ZoneEquipType        = ZoneEvaporativeCoolerUnit_Num
    INTEGER        :: ZoneNodeNum          = 0
    INTEGER        :: AvailSchedIndex      = 0     ! pointer to local availability schedule
    CHARACTER(len=MaxNameLength) :: AvailManagerListName = ' ' ! Name of an availability manager list object
    Logical        :: UnitIsAvailable = .FALSE.
    INTEGER        :: FanAvailStatus  = 0
    INTEGER        :: OAInletNodeNum       = 0     ! outdoor air inlet node index
    INTEGER        :: UnitOutletNodeNum    = 0     ! Unit air outlet (to zone) node index
    INTEGER        :: UnitReliefNodeNum    = 0     ! Unit relief air (from zone) node index (optional)
    CHARACTER(len=MaxNameLength) :: FanObjectClassName = ' '
    INTEGER        :: FanType_Num          = 0     !
    CHARACTER(len=MaxNameLength) :: FanName = ' '
    INTEGER        :: FanIndex             = 0
    REAL(r64)      :: ActualFanVolFlowRate = 0.0d0
    INTEGER        :: FanAvailSchedPtr     = 0
    INTEGER        :: FanInletNodeNum      = 0
    INTEGER        :: FanOutletNodeNum     = 0
    REAL(r64)      :: DesignAirVolumeFlowRate = 0.0d0 !
    REAL(r64)      :: DesignAirMassFlowRate = 0.0d0
    REAL(r64)      :: DesignFanSpeedRatio   = 0.0d0 !
    REAL(r64)      :: FanSpeedRatio        = 0.0d0 !

    INTEGER        :: FanLocation          = 0
    INTEGER        :: ControlSchemeType    = 0
    REAL(r64)      :: TimeElapsed          = 0.0d0
    REAL(r64)      :: ThrottlingRange      = 0.0d0  ! temperature range for hystersis type tstat contorl [Delta C]
    LOGICAL        :: IsOnThisTimestep     = .FALSE.
    LOGICAL        :: WasOnLastTimestep    = .FALSE.
    REAL(r64)      :: ThresholdCoolingLoad = 0.0d0
    CHARACTER(len=MaxNameLength) :: EvapCooler_1_ObjectClassName = ' '
    CHARACTER(len=MaxNameLength) :: EvapCooler_1_Name = ' '
    INTEGER        :: EvapCooler_1_Type_Num  = 0     !
    INTEGER        :: EvapCooler_1_Index     = 0
    LOGICAL        :: EvapCooler_1_AvailStatus = .FALSE.
    CHARACTER(len=MaxNameLength) :: EvapCooler_2_ObjectClassName = ' '
    CHARACTER(len=MaxNameLength) :: EvapCooler_2_Name = ' '
    INTEGER        :: EvapCooler_2_Type_Num  = 0     !
    INTEGER        :: EvapCooler_2_Index     = 0
    LOGICAL        :: EvapCooler_2_AvailStatus = .FALSE.
    REAL(r64)      :: OAInletRho           = 0.d0  ! fills internal variable, current inlet air density [kg/m3]
    REAL(r64)      :: OAInletCp            = 0.d0  ! fills internal variable, current inlet air specific heat [J/kg-c]
    REAL(r64)      :: OAInletTemp          = 0.d0  ! fills internal variable, current inlet air temperature [C]
    REAL(r64)      :: OAInletHumRat        = 0.d0  ! fills internal variable, current inlet air humidity ratio [kg/kg]
    REAL(r64)      :: OAInletMassFlowRate  = 0.d0  ! fills internal variable, current inlet air mass flow rate [kg/s]
    REAL(r64)      :: UnitOutletTemp         = 0.d0  ! filled by actuator, component outlet temperature [C]
    REAL(r64)      :: UnitOutletHumRat       = 0.d0  ! filled by actuator, component outlet humidity ratio [kg/kg]
    REAL(r64)      :: UnitOutletMassFlowRate = 0.d0  ! filled by actuator, component outlet mass flow rate [kg/s]
    REAL(r64)      :: UnitReliefTemp         = 0.d0  ! filled by actuator, component outlet temperature [C]
    REAL(r64)      :: UnitReliefHumRat       = 0.d0  ! filled by actuator, component outlet humidity ratio [kg/kg]
    REAL(r64)      :: UnitReliefMassFlowRate = 0.d0  ! filled by actuator, component outlet mass flow rate [kg/s]
    REAL(r64)      :: UnitTotalCoolingRate   = 0.0d0 ! unit output to zone, total cooling rate [W]
    REAL(r64)      :: UnitTotalCoolingEnergy = 0.0d0 ! unit output to zone, total cooling energy [J]
    REAL(r64)      :: UnitSensibleCoolingRate= 0.0d0 ! unit output to zone, sensible cooling rate [W]
    REAL(r64)      :: UnitSensibleCoolingEnergy = 0.0d0 ! unit output to zone, sensible cooling energy [J]
    REAL(r64)      :: UnitLatentHeatingRate  = 0.0d0 ! unit output to zone, latent heating rate [W]
    REAL(r64)      :: UnitLatentHeatingEnergy = 0.0d0 ! unit output to zone, latent heating energy [J]
    REAL(r64)      :: UnitLatentCoolingRate = 0.0d0 ! unit output to zone, latent cooling rate [W]
    REAL(r64)      :: UnitLatentCoolingEnergy = 0.0d0 ! unit output to zone, latent cooling energy [J]
    REAL(r64)      :: UnitFanSpeedRatio = 0.d0 ! unit fan speed ratio, dimensionless [ ]

    INTEGER        :: UnitVSControlMaxIterErrorIndex = 0 ! regula falsi errors, fan speed iteration limits
    INTEGER        :: UnitVSControlLimitsErrorIndex  = 0 ! regula falsi errors, limits exceeded.

  END TYPE

  ! MODULE VARIABLE DECLARATIONS:
  LOGICAL,SAVE      :: GetInputEvapComponentsFlag = .TRUE. ! Flag set to make sure you get input once
  INTEGER     :: NumEvapCool=0             ! The Number of Evap Coolers found in the Input
  TYPE (EvapConditions), ALLOCATABLE, DIMENSION(:) :: EvapCond
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: MySizeFlag
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckEquipName

  INTEGER     :: NumZoneEvapUnits = 0
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckZoneEvapUnitName
  TYPE (ZoneEvapCoolerUnitStruct), Allocatable, Dimension(:) :: ZoneEvapUnit
  LOGICAL :: GetInputZoneEvapUnit = .TRUE.


  ! SUBROUTINE SPECIFICATIONS FOR MODULE EvapCoolers


! component model routines
PUBLIC  SimEvapCooler
PRIVATE GetEvapInput
PRIVATE InitEvapCooler
PRIVATE SizeEvapCooler
PRIVATE CalcDirectEvapCooler
PRIVATE CalcDryIndirectEvapCooler
PRIVATE CalcWetIndirectEvapCooler
PRIVATE CalcResearchSpecialPartLoad
PRIVATE CalcIndirectResearchSpecialEvapCooler
PRIVATE CalcDirectResearchSpecialEvapCooler
PRIVATE UpdateEvapCooler
PRIVATE ReportEvapCooler

! zone unit routines
PUBLIC  SimZoneEvaporativeCoolerUnit
PRIVATE GetInputZoneEvaporativeCoolerUnit
PRIVATE InitZoneEvaporativeCoolerUnit
PRIVATE SizeZoneEvaporativeCoolerUnit
PRIVATE CalcZoneEvaporativeCoolerUnit
PRIVATE ReportZoneEvaporativeCoolerUnit

CONTAINS

! MODULE SUBROUTINES:
!*************************************************************************
SUBROUTINE SimEvapCooler(CompName,CompIndex)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine manages EvapCooler component simulation.
          ! It is called from the SimAirLoopComponent
          ! at the system time step.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor, ONLY: FindItemInList
  USE General, ONLY: TrimSigDigits

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  CHARACTER(len=*), INTENT(IN) :: CompName
  INTEGER, INTENT(INOUT)       :: CompIndex

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER           :: EvapCoolNum     ! The EvapCooler that you are currently loading input into


          ! FLOW:

  ! Obtains and Allocates EvapCooler related parameters from input file
  IF (GetInputEvapComponentsFlag) THEN  !First time subroutine has been entered
    CALL GetEvapInput
    GetInputEvapComponentsFlag=.false.
  End If


  ! Find the correct EvapCoolNumber
  IF (CompIndex == 0) THEN
    EvapCoolNum=FindItemInList(CompName,EvapCond%EvapCoolerName,NumEvapCool)
    IF (EvapCoolNum == 0) THEN
      CALL ShowFatalError('SimEvapCooler: Unit not found='//TRIM(CompName))
    ENDIF
    CompIndex=EvapCoolNum
  ELSE
    EvapCoolNum=CompIndex
    IF (EvapCoolNum > NumEvapCool .or. EvapCoolNum < 1) THEN
      CALL ShowFatalError('SimEvapCooler:  Invalid CompIndex passed='//  &
                          TRIM(TrimSigDigits(EvapCoolNum))// &
                          ', Number of Units='//TRIM(TrimSigDigits(NumEvapCool))//  &
                          ', Entered Unit name='//TRIM(CompName))
    ENDIF
    IF (CheckEquipName(EvapCoolNum)) THEN
      IF (CompName /= EvapCond(EvapCoolNum)%EvapCoolerName) THEN
        CALL ShowFatalError('SimEvapCooler: Invalid CompIndex passed='//  &
                            TRIM(TrimSigDigits(EvapCoolNum))// &
                            ', Unit name='//TRIM(CompName)//', stored Unit Name for that index='//  &
                            TRIM(EvapCond(EvapCoolNum)%EvapCoolerName))
      ENDIF
      CheckEquipName(EvapCoolNum)=.false.
    ENDIF
  ENDIF

  ! With the correct EvapCoolNum Initialize
  CALL InitEvapCooler(EvapCoolNum)  ! Initialize all related parameters

  SELECT CASE (EvapCond(EvapCoolNum)%EvapCoolerType)

  CASE (iEvapCoolerDirectCELDEKPAD)
    CALL CalcDirectEvapCooler(EvapCoolNum)
  CASE (iEvapCoolerInDirectCELDEKPAD)
    CALL CalcDryIndirectEvapCooler(EvapCoolNum)
  CASE ( iEvapCoolerInDirectWETCOIL)
    CALL CalcWetIndirectEvapCooler(EvapCoolNum)
  CASE (iEvapCoolerInDirectRDDSpecial)
    CALL CalcResearchSpecialPartLoad(EvapCoolNum)
    CALL CalcIndirectResearchSpecialEvapCooler(EvapCoolNum)
  CASE (iEvapCoolerDirectResearchSpecial)
    CALL CalcResearchSpecialPartLoad(EvapCoolNum)
    CALL CalcDirectResearchSpecialEvapCooler(EvapCoolNum)
  END SELECT
  ! Update the current Evap Cooler to the outlet nodes
  CALL UpdateEvapCooler(EvapCoolNum)

  ! Report the current Evap Cooler
  CALL ReportEvapCooler(EvapCoolNum)

  RETURN

END SUBROUTINE SimEvapCooler


! Get Input Section of the Module
!******************************************************************************
SUBROUTINE GetEvapInput

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   Oct 2000
          !       MODIFIED       BTG,  adding in EVAPCOOLER:INDIRECT:RDDSPECIAL
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine is the main routine to call other input routines and Get routines

          ! METHODOLOGY EMPLOYED:
          ! Uses the status flags to trigger events.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
    USE InputProcessor, ONLY: GetNumObjectsFound,GetObjectItem,VerifyName
    USE DataIPShortCuts  ! Data for field names, blank numerics
    USE NodeInputManager, ONLY: GetOnlySingleNode
    USE BranchNodeConnections, ONLY: TestCompSet
    USE WaterManager, ONLY: SetupTankDemandComponent
    USE OutAirNodeManager,  ONLY: CheckOutAirNodeNumber

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
    CHARACTER(len=*), PARAMETER :: Blank = ' '

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
    INTEGER :: EvapCoolNum       ! The EvapCooler that you are currently loading input into
    INTEGER :: NumDirectEvapCool ! The number of Direct CelDek EvapCooler in this simulation
    INTEGER :: NumDryInDirectEvapCool ! The number of dry indirect evap coolers
    INTEGER :: NumWetInDirectEvapCool ! The number of wet indirect evap coolers
    INTEGER :: NumRDDEvapCool   ! the number of special research indirect evap coolers
    INTEGER :: NumDirectResearchSpecialEvapCool ! the number of special research direct evap coolers

    INTEGER :: IndEvapCoolNum    !Do Loop Counter for indirect evap coolers
    INTEGER :: DirectEvapCoolNum ! Do loop counter for direct evap cooler
    INTEGER :: NumAlphas
    INTEGER :: NumNums
    INTEGER :: IOSTAT
    LOGICAL :: ErrorsFound=.false.
    LOGICAL :: IsNotOK               ! Flag to verify name
    LOGICAL :: IsBlank               ! Flag for blank name

   ! Start getting the input data
    NumDirectEvapCool      = GetNumObjectsFound('EvaporativeCooler:Direct:CelDekPad')
    NumDryInDirectEvapCool = GetNumObjectsFound('EvaporativeCooler:Indirect:CelDekPad')
    NumWetInDirectEvapCool = GetNumObjectsFound('EvaporativeCooler:Indirect:WetCoil')
    NumRDDEvapCool         = GetNumObjectsFound('EvaporativeCooler:Indirect:ResearchSpecial')
    NumDirectResearchSpecialEvapCool = GetNumObjectsFound('EvaporativeCooler:Direct:ResearchSpecial')

    !Sum up all of the Evap Cooler Types
    NumEvapCool = NumDirectEvapCool + NumDryInDirectEvapCool + NumWetInDirectEvapCool + NumRDDEvapCool &
                  + NumDirectResearchSpecialEvapCool

    IF (NumEvapCool.GT.0) ALLOCATE(EvapCond(NumEvapCool))
    ALLOCATE(CheckEquipName(NumEvapCool))
    CheckEquipName=.true.

    cCurrentModuleObject = 'EvaporativeCooler:Direct:CelDekPad'

    DO EvapCoolNum = 1,  NumDirectEvapCool
      CALL GetObjectItem(cCurrentModuleObject,EvapCoolNum,cAlphaArgs,NumAlphas, &
                      rNumericArgs,NumNums,IOSTAT, AlphaBlank=lAlphaFieldBlanks, &
                      AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      IsNotOK=.false.
      IsBlank=.false.
      CALL VerifyName(cAlphaArgs(1),EvapCond%EvapCoolerName,EvapCoolNum-1,IsNotOK,IsBlank,TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound=.true.
        IF (IsBlank) cAlphaArgs(1)='xxxxx'
      ENDIF
      EvapCond(EvapCoolNum)%EvapCoolerName = Trim(cAlphaArgs(1))
      EvapCond(EvapCoolNum)%EvapCoolerType = iEvapCoolerDirectCELDEKPAD

      EvapCond(EvapCoolNum)%Schedule = cAlphaArgs(2)
      IF (lAlphaFieldBlanks(2)) THEN
        EvapCond(EvapCoolNum)%SchedPtr = ScheduleAlwaysOn
      ELSE
        EvapCond(EvapCoolNum)%SchedPtr = GetScheduleIndex(cAlphaArgs(2))
        IF (EvapCond(EvapCoolNum)%SchedPtr == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(2))//'='//TRIM(cAlphaArgs(2)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound=.true.
        ENDIF
      ENDIF

      EvapCond(EvapCoolNum)%InletNode  = &
               GetOnlySingleNode(cAlphaArgs(3),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%OutletNode  = &
               GetOnlySingleNode(cAlphaArgs(4),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)

      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(3),cAlphaArgs(4), &
                       'Evap Air Nodes')

      EvapCond(EvapCoolNum)%EvapControlType = TRIM(cAlphaArgs(5))

      !input the numerical data
      EvapCond(EvapCoolNum)%PadArea         = rNumericArgs(1)
      EvapCond(EvapCoolNum)%PadDepth        = rNumericArgs(2)
      EvapCond(EvapCoolNum)%RecircPumpPower = rNumericArgs(3)

      CALL SetupOutputVariable('Evaporative Cooler Wet Bulb Effectiveness []',EvapCond(EvapCoolNum)%Sateff, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)

           ! A6 ; \Field Name of Water Supply Storage Tank
      EvapCond(EvapCoolNum)%EvapWaterSupplyName = cAlphaArgs(6)
      IF (lAlphaFieldBlanks(6)) THEN
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromMains
      ELSE
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromTank
         CALL SetupTankDemandComponent(EvapCond(EvapCoolNum)%EvapCoolerName, TRIM(cCurrentModuleObject), &
                    EvapCond(EvapCoolNum)%EvapWaterSupplyName, ErrorsFound, EvapCond(EvapCoolNum)%EvapWaterSupTankID, &
                    EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID )

      ENDIF

    END DO   ! end Number of EvapCooler Loop

    !**************************************************************
    !This is the start of the Dry Indirect Evap Cooler Loop
    cCurrentModuleObject = 'EvaporativeCooler:Indirect:CelDekPad'

    DO IndEvapCoolNum = 1,  NumDryInDirectEvapCool
      EvapCoolNum = NumDirectEvapCool + IndEvapCoolNum

      CALL GetObjectItem(cCurrentModuleObject,IndEvapCoolNum,cAlphaArgs,NumAlphas, &
                      rNumericArgs,NumNums,IOSTAT, AlphaBlank=lAlphaFieldBlanks, &
                      AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      IsNotOK=.false.
      IsBlank=.false.
      CALL VerifyName(cAlphaArgs(1),EvapCond%EvapCoolerName,EvapCoolNum-1,IsNotOK,IsBlank,TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound=.true.
        IF (IsBlank) cAlphaArgs(1)='xxxxx'
      ENDIF
      EvapCond(EvapCoolNum)%EvapCoolerName = Trim(cAlphaArgs(1))
      EvapCond(EvapCoolNum)%EvapCoolerType = iEvapCoolerInDirectCELDEKPAD !'EvaporativeCooler:Indirect:CelDekPad'

      EvapCond(EvapCoolNum)%Schedule = cAlphaArgs(2)
      IF (lAlphaFieldBlanks(2)) THEN
        EvapCond(EvapCoolNum)%SchedPtr = ScheduleAlwaysOn
      ELSE
        EvapCond(EvapCoolNum)%SchedPtr = GetScheduleIndex(cAlphaArgs(2))
        IF (EvapCond(EvapCoolNum)%SchedPtr == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(2))//'='//TRIM(cAlphaArgs(2)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound=.true.
        ENDIF
      ENDIF

      EvapCond(EvapCoolNum)%InletNode  = &
               GetOnlySingleNode(cAlphaArgs(3),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%OutletNode  = &
               GetOnlySingleNode(cAlphaArgs(4),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)

      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(3),cAlphaArgs(4), &
                       'Evap Air Nodes')

      EvapCond(EvapCoolNum)%EvapControlType = TRIM(cAlphaArgs(5))

      !input the numerical data
      EvapCond(EvapCoolNum)%IndirectPadArea         = rNumericArgs(1)
      EvapCond(EvapCoolNum)%IndirectPadDepth        = rNumericArgs(2)
      EvapCond(EvapCoolNum)%IndirectRecircPumpPower = rNumericArgs(3)
      EvapCond(EvapCoolNum)%IndirectVolFlowRate     = rNumericArgs(4)
      EvapCond(EvapCoolNum)%IndirectFanEff          = rNumericArgs(5)
      EvapCond(EvapCoolNum)%IndirectFanDeltaPress   = rNumericArgs(6)
      EvapCond(EvapCoolNum)%IndirectHXEffectiveness = rNumericArgs(7)

      CALL SetupOutputVariable('Evaporative Cooler Wetbulb Effectiveness []',EvapCond(EvapCoolNum)%Sateff, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)
      CALL SetupOutputVariable('Evaporative Cooler Total Stage Effectiveness []',EvapCond(EvapCoolNum)%StageEff, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)

      ! A6 ; \Field Name of Water Supply Storage Tank
      EvapCond(EvapCoolNum)%EvapWaterSupplyName = cAlphaArgs(6)
      IF ( lAlphaFieldBlanks(6) ) THEN
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromMains
      ELSE
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromTank
         CALL SetupTankDemandComponent(EvapCond(EvapCoolNum)%EvapCoolerName, TRIM(cCurrentModuleObject), &
                    EvapCond(EvapCoolNum)%EvapWaterSupplyName, ErrorsFound, EvapCond(EvapCoolNum)%EvapWaterSupTankID, &
                    EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID )

      ENDIF

      !A7 ; \field Secondary Outside Air Inlet node.
      IF ( lAlphaFieldBlanks(7) ) THEN
         EvapCond(EvapCoolNum)%SecondaryInletNode  =  0
      ELSE
         EvapCond(EvapCoolNum)%SecondaryInletNode  = &
               GetOnlySingleNode(cAlphaArgs(7),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_OutsideAirReference,1,ObjectIsNotParent)
         IF ( .not. CheckOutAirNodeNumber(EvapCond(EvapCoolNum)%SecondaryInletNode)) THEN
           CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(7))//'='//TRIM(cAlphaArgs(7)))
           CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
            !TODO rename point
           CALL ShowContinueError('Node does not appear in an OutdoorAir:NodeList or as an OutdoorAir:Node.')
           ErrorsFound=.true.
         ENDIF

      ENDIF

    END DO   ! end Number of Dry Indirect EvapCooler Loop

    !**************************************************************
    !This is the start of the WetIndirect Evap Cooler Loop
    cCurrentModuleObject = 'EvaporativeCooler:Indirect:WetCoil'
    DO IndEvapCoolNum = 1,  NumWetInDirectEvapCool
      EvapCoolNum = NumDirectEvapCool + NumDryInDirectEvapCool + IndEvapCoolNum

      CALL GetObjectItem(cCurrentModuleObject,IndEvapCoolNum,cAlphaArgs,NumAlphas, &
                      rNumericArgs,NumNums,IOSTAT, AlphaBlank=lAlphaFieldBlanks, &
                      AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      IsNotOK=.false.
      IsBlank=.false.
      CALL VerifyName(cAlphaArgs(1),EvapCond%EvapCoolerName,EvapCoolNum-1,IsNotOK,IsBlank,TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound=.true.
        IF (IsBlank) cAlphaArgs(1)='xxxxx'
      ENDIF
      EvapCond(EvapCoolNum)%EvapCoolerName = Trim(cAlphaArgs(1))
      EvapCond(EvapCoolNum)%EvapCoolerType = iEvapCoolerInDirectWETCOIL !'EvaporativeCooler:Indirect:WetCoil'

      EvapCond(EvapCoolNum)%Schedule = cAlphaArgs(2)
      IF (lAlphaFieldBlanks(2)) THEN
        EvapCond(EvapCoolNum)%SchedPtr = ScheduleAlwaysOn
      ELSE
        EvapCond(EvapCoolNum)%SchedPtr = GetScheduleIndex(cAlphaArgs(2))
        IF (EvapCond(EvapCoolNum)%SchedPtr == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(2))//'='//TRIM(cAlphaArgs(2)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound=.true.
        ENDIF
      ENDIF

      EvapCond(EvapCoolNum)%InletNode  = &
               GetOnlySingleNode(cAlphaArgs(3),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%OutletNode  = &
               GetOnlySingleNode(cAlphaArgs(4),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)

      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(3),cAlphaArgs(4), &
                       'Evap Air Nodes')

      EvapCond(EvapCoolNum)%EvapControlType = TRIM(cAlphaArgs(5))

      !input the numerical data
      EvapCond(EvapCoolNum)%WetCoilMaxEfficiency    = rNumericArgs(1)
      EvapCond(EvapCoolNum)%WetCoilFlowRatio        = rNumericArgs(2)
      EvapCond(EvapCoolNum)%IndirectRecircPumpPower = rNumericArgs(3)
      EvapCond(EvapCoolNum)%IndirectVolFlowRate     = rNumericArgs(4)
      EvapCond(EvapCoolNum)%IndirectFanEff          = rNumericArgs(5)
      EvapCond(EvapCoolNum)%IndirectFanDeltaPress   = rNumericArgs(6)

      CALL SetupOutputVariable('Evaporative Cooler Total Stage Effectiveness []',EvapCond(EvapCoolNum)%StageEff, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)

     !  A6 ; \Field Name of Water Supply Storage Tank
      EvapCond(EvapCoolNum)%EvapWaterSupplyName = cAlphaArgs(6)
      IF (lAlphaFieldBlanks(6)) THEN
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromMains
      ELSE
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromTank
         CALL SetupTankDemandComponent(EvapCond(EvapCoolNum)%EvapCoolerName, TRIM(cCurrentModuleObject), &
                    EvapCond(EvapCoolNum)%EvapWaterSupplyName, ErrorsFound, EvapCond(EvapCoolNum)%EvapWaterSupTankID, &
                    EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID )

      ENDIF

     ! A7 ; \field Secondary Outside Air Inlet node.
      IF (lAlphaFieldBlanks(7)) THEN
         EvapCond(EvapCoolNum)%SecondaryInletNode  =  0
      ELSE
         EvapCond(EvapCoolNum)%SecondaryInletNode  = &
               GetOnlySingleNode(cAlphaArgs(7),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_OutsideAirReference,1,ObjectIsNotParent)
         IF ( .not. CheckOutAirNodeNumber(EvapCond(EvapCoolNum)%SecondaryInletNode)) THEN
           CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(7))//'='//TRIM(cAlphaArgs(7)))
           CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
            !TODO rename point
           CALL ShowContinueError('Node does not appear in an OutdoorAir:NodeList or as an OutdoorAir:Node.')
           ErrorsFound=.true.
         ENDIF

      ENDIF

    END DO   ! end Number of Wet Coil Indirect EvapCooler Loop
    !**************************************************************
    !This is the start of the Indirect Research Special Evap Cooler
    cCurrentModuleObject = 'EvaporativeCooler:Indirect:ResearchSpecial'
    DO IndEvapCoolNum = 1,  NumRDDEvapCool
      EvapCoolNum = NumDirectEvapCool + NumDryInDirectEvapCool + &
                    NumWetInDirectEvapCool + IndEvapCoolNum
     CALL GetObjectItem(cCurrentModuleObject,IndEvapCoolNum,cAlphaArgs,NumAlphas, &
                      rNumericArgs,NumNums,IOSTAT, AlphaBlank=lAlphaFieldBlanks, &
                      AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      IsNotOK=.false.
      IsBlank=.false.
      CALL VerifyName(cAlphaArgs(1),EvapCond%EvapCoolerName,EvapCoolNum-1,IsNotOK,IsBlank,TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound=.true.
        IF (IsBlank) cAlphaArgs(1)='xxxxx'
      ENDIF
      EvapCond(EvapCoolNum)%EvapCoolerName = Trim(cAlphaArgs(1))
      EvapCond(EvapCoolNum)%EvapCoolerType = iEvapCoolerInDirectRDDSpecial !'EvaporativeCooler:Indirect:ResearchSpecial'

      EvapCond(EvapCoolNum)%Schedule = cAlphaArgs(2)
      IF (lAlphaFieldBlanks(2)) THEN
        EvapCond(EvapCoolNum)%SchedPtr = ScheduleAlwaysOn
      ELSE
        EvapCond(EvapCoolNum)%SchedPtr = GetScheduleIndex(cAlphaArgs(2))
        IF (EvapCond(EvapCoolNum)%SchedPtr == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(2))//'='//TRIM(cAlphaArgs(2)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound=.true.
        ENDIF
      ENDIF

      EvapCond(EvapCoolNum)%InletNode  = &
               GetOnlySingleNode(cAlphaArgs(3),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%OutletNode  = &
               GetOnlySingleNode(cAlphaArgs(4),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)

      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(3),cAlphaArgs(4), &
                       'Evap Air Nodes')

      EvapCond(EvapCoolNum)%EvapControlType = TRIM(cAlphaArgs(5))

     ! A6 ; \field Secondary Air Inlet Node Name
      IF (lAlphaFieldBlanks(6)) THEN
         EvapCond(EvapCoolNum)%SecondaryInletNode  =  0
      ELSE
      EvapCond(EvapCoolNum)%SecondaryInletNode = &
        GetOnlySingleNode(cAlphaArgs(6),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,2,ObjectIsNotParent)
      END IF

      EvapCond(EvapCoolNum)%EvapControlNodeNum = &
      GetOnlySingleNode(cAlphaArgs(7),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Sensor,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%TertiaryInletNode  = &
      GetOnlySingleNode(cAlphaArgs(8),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,3,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%EvapWaterSupplyName = cAlphaArgs(9)
      IF (lAlphaFieldBlanks(9)) THEN
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromMains
      ELSE
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromTank
         CALL SetupTankDemandComponent(EvapCond(EvapCoolNum)%EvapCoolerName, TRIM(cCurrentModuleObject), &
                    EvapCond(EvapCoolNum)%EvapWaterSupplyName, ErrorsFound, EvapCond(EvapCoolNum)%EvapWaterSupTankID, &
                    EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID )

      ENDIF

      !input the numerical data
      EvapCond(EvapCoolNum)%WetCoilMaxEfficiency    = rNumericArgs(1)
      EvapCond(EvapCoolNum)%WetCoilFlowRatio        = rNumericArgs(2)
      EvapCond(EvapCoolNum)%IndirectRecircPumpPower = rNumericArgs(3)
      EvapCond(EvapCoolNum)%IndirectVolFlowRate     = rNumericArgs(4)
      EvapCond(EvapCoolNum)%IndirectFanEff          = rNumericArgs(5)
      EvapCond(EvapCoolNum)%IndirectFanDeltaPress   = rNumericArgs(6)
      EvapCond(EvapCoolNum)%DPBoundFactor           = rNumericArgs(7)
      IF (lNumericFieldBlanks(8)) THEN
        EvapCond(EvapCoolNum)%DriftFraction   = 0.0D0
      ELSE
        EvapCond(EvapCoolNum)%DriftFraction   = rNumericArgs(8)
      ENDIF

      IF (lNumericFieldBlanks(9)) THEN
        EvapCond(EvapCoolNum)%BlowDownRatio   = 0.0D0
      ELSE
        EvapCond(EvapCoolNum)%BlowDownRatio   = rNumericArgs(9)
      ENDIF


      CALL SetupOutputVariable('Evaporative Cooler Total Stage Effectiveness []',EvapCond(EvapCoolNum)%StageEff, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)
      CALL SetupOutputVariable('Evaporative Cooler Part Load Ratio []',EvapCond(EvapCoolNum)%PartLoadFract, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)

      CALL SetupOutputVariable('Evaporative Cooler Dewpoint Bound Status []', EvapCond(EvapCoolNum)%DewPointBoundFlag, &
                               'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)

    END Do  ! end of Indirect Research Special cooler input loop

    cCurrentModuleObject = 'EvaporativeCooler:Direct:ResearchSpecial'
    Do DirectEvapCoolNum =  1, NumDirectResearchSpecialEvapCool
      EvapCoolNum = NumDirectEvapCool + NumDryInDirectEvapCool + &
                    NumWetInDirectEvapCool + NumRDDEvapCool + DirectEvapCoolNum
      CALL GetObjectItem(cCurrentModuleObject,DirectEvapCoolNum,cAlphaArgs,NumAlphas, &
                      rNumericArgs,NumNums,IOSTAT, AlphaBlank=lAlphaFieldBlanks, NumBlank=lNumericFieldBlanks,&
                      AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)
      IsNotOK=.false.
      IsBlank=.false.
      CALL VerifyName(cAlphaArgs(1),EvapCond%EvapCoolerName,EvapCoolNum-1,IsNotOK,IsBlank,TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound=.TRUE.
        IF (IsBlank) cAlphaArgs(1)='xxxxx'
      ENDIF
      EvapCond(EvapCoolNum)%EvapCoolerName = Trim(cAlphaArgs(1))
      EvapCond(EvapCoolNum)%EvapCoolerType = iEvapCoolerDirectResearchSpecial

      EvapCond(EvapCoolNum)%Schedule       = cAlphaArgs(2)
      IF (lAlphaFieldBlanks(2)) THEN
        EvapCond(EvapCoolNum)%SchedPtr = ScheduleAlwaysOn
      ELSE
        EvapCond(EvapCoolNum)%SchedPtr = GetScheduleIndex(cAlphaArgs(2))
        IF (EvapCond(EvapCoolNum)%SchedPtr == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(2))//'='//TRIM(cAlphaArgs(2)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound=.true.
        ENDIF
      ENDIF

      EvapCond(EvapCoolNum)%InletNode  = &
               GetOnlySingleNode(cAlphaArgs(3),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%OutletNode  = &
               GetOnlySingleNode(cAlphaArgs(4),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)

      CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1),cAlphaArgs(3),cAlphaArgs(4), &
                       'Evap Air Nodes')

      EvapCond(EvapCoolNum)%EvapControlNodeNum = &
         GetOnlySingleNode(cAlphaArgs(5),ErrorsFound,TRIM(cCurrentModuleObject),cAlphaArgs(1),  &
                            NodeType_Air,NodeConnectionType_Sensor,1,ObjectIsNotParent)

      EvapCond(EvapCoolNum)%EvapWaterSupplyName = cAlphaArgs(6)

      IF (lAlphaFieldBlanks(6)) THEN
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromMains
      ELSE
         EvapCond(EvapCoolNum)%EvapWaterSupplyMode = WaterSupplyFromTank
         CALL SetupTankDemandComponent(EvapCond(EvapCoolNum)%EvapCoolerName, TRIM(cCurrentModuleObject), &
                    EvapCond(EvapCoolNum)%EvapWaterSupplyName, ErrorsFound, EvapCond(EvapCoolNum)%EvapWaterSupTankID, &
                    EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID )
      ENDIF
      EvapCond(EvapCoolNum)%DirectEffectiveness = rNumericArgs(1)
      EvapCond(EvapCoolNum)%RecircPumpPower     = rNumericArgs(2)

      IF (lNumericFieldBlanks(3)) THEN
        EvapCond(EvapCoolNum)%DriftFraction   = 0.0D0
      ELSE
        EvapCond(EvapCoolNum)%DriftFraction   = rNumericArgs(3)
      ENDIF

      IF (lNumericFieldBlanks(4)) THEN
        EvapCond(EvapCoolNum)%BlowDownRatio   = 0.0D0
      ELSE
        EvapCond(EvapCoolNum)%BlowDownRatio   = rNumericArgs(4)
      ENDIF

    ENDDO


    IF (ErrorsFound) THEN
      CALL ShowFatalError('Errors found in processing input for evaporative coolers')
    ENDIF



    DO EvapCoolNum=1,NumEvapCool
      ! Setup Report variables for the Evap Coolers
      CALL SetupOutputVariable('Evaporative Cooler Electric Energy [J]',EvapCond(EvapCoolNum)%EvapCoolerEnergy, &
                            'System','Sum',EvapCond(EvapCoolNum)%EvapCoolerName, &
                             ResourceTypeKey='Electric',EndUseKey='Cooling',GroupKey='System')
      CALL SetupOutputVariable('Evaporative Cooler Electric Power [W]',EvapCond(EvapCoolNum)%EvapCoolerPower, &
                            'System','Average',EvapCond(EvapCoolNum)%EvapCoolerName)
      ! this next report variable is setup differently depending on how the water should be metered here.
      IF (EvapCond(EvapCoolNum)%EvapWaterSupplyMode == WaterSupplyFromMains) Then
        CALL SetupOutputVariable('Evaporative Cooler Water Volume [m3]',EvapCond(EvapCoolNum)%EvapWaterConsump, &
                            'System','Sum',EvapCond(EvapCoolNum)%EvapCoolerName, &
                             ResourceTypeKey='Water',EndUseKey='Cooling',GroupKey='System')
        CALL SetupOutputVariable('Evaporative Cooler Mains Water Volume [m3]',EvapCond(EvapCoolNum)%EvapWaterConsump, &
                            'System','Sum',EvapCond(EvapCoolNum)%EvapCoolerName, &
                             ResourceTypeKey='MainsWater',EndUseKey='Cooling',GroupKey='System')

      ELSEIF  (EvapCond(EvapCoolNum)%EvapWaterSupplyMode == WaterSupplyFromTank) THEN
        CALL SetupOutputVariable('Evaporative Cooler Storage Tank Water Volume [m3]',EvapCond(EvapCoolNum)%EvapWaterConsump, &
                            'System','Sum',EvapCond(EvapCoolNum)%EvapCoolerName, &
                             ResourceTypeKey='Water',EndUseKey='Cooling' , GroupKey='System')
        CALL SetupOutputVariable('Evaporative Cooler Starved Water Volume [m3]',EvapCond(EvapCoolNum)%EvapWaterStarvMakup, &
                            'System','Sum',EvapCond(EvapCoolNum)%EvapCoolerName, &
                             ResourceTypeKey='Water',EndUseKey='Cooling', GroupKey='System')
        CALL SetupOutputVariable('Evaporative Cooler Starved Mains Water Volume [m3]',EvapCond(EvapCoolNum)%EvapWaterStarvMakup, &
                            'System','Sum',EvapCond(EvapCoolNum)%EvapCoolerName, &
                             ResourceTypeKey='MainsWater',EndUseKey='Cooling', GroupKey='System')
      ENDIF

    END DO



  RETURN

END SUBROUTINE GetEvapInput

! End of Get Input subroutines for the HB Module
!******************************************************************************



 ! Beginning Initialization Section of the Module
!******************************************************************************

SUBROUTINE InitEvapCooler(EvapCoolNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       B. Griffith, May 2009, added EMS setpoint check
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine is for  initializations of the EvapCooler Components.

          ! METHODOLOGY EMPLOYED:
          ! Uses the status flags to trigger events.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHVACGlobals, ONLY: DoSetPointTest, SetPointErrorFlag
  USE DataEnvironment, ONLY: OutAirDensity, OutDryBulbTemp, OutEnthalpy, OutWetBulbTemp
  USE DataGlobals,     ONLY: AnyEnergyManagementSystemInModel
  USE EMSManager,      ONLY: iTemperatureSetpoint, CheckIfNodeSetpointManagedByEMS

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  Integer, Intent(IN) :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  Integer             :: InletNode
  Integer             :: SecInletNode   ! local index for secondary inlet node.
  REAL(r64)           :: RhoAir !Air Density
  Integer             :: ControlNode
  Integer             :: OutNode
  Integer             :: EvapUnitNum
  LOGICAL,SAVE        :: MySetPointCheckFlag = .TRUE.
  LOGICAL,SAVE        :: MyOneTimeFlag = .true.
  LOGICAL             :: localSetpointCheck = .FALSE.

  IF (MyOneTimeFlag) THEN
    ALLOCATE(MySizeFlag(NumEvapCool))
    MySizeFlag = .TRUE.
    MyOneTimeFlag = .false.
  ENDIF

  ! FLOW:
  !Check that setpoint is active
  IF ( .NOT. SysSizingCalc .AND. MySetPointCheckFlag .AND. DoSetPointTest) THEN
    DO EvapUnitNum = 1, NumEvapCool

      !only check evap coolers that are supposed to have a control node
      IF (( EvapCond(EvapCoolNum)%EvapCoolerType /= iEvapCoolerInDirectRDDSpecial) &
          .AND.  (EvapCond(EvapCoolNum)%EvapCoolerType /= iEvapCoolerDirectResearchSpecial) ) CYCLE

      ControlNode = EvapCond(EvapUnitNum)%EvapControlNodeNum
      IF (ControlNode > 0) THEN
        IF (Node(ControlNode)%TempSetPoint == SensedNodeFlagValue) THEN
          IF (.NOT. AnyEnergyManagementSystemInModel) THEN
            CALL ShowSevereError('Missing temperature setpoint for Evap Cooler unit ' // &
                                  TRIM(EvapCond(EvapCoolNum)%EvapCoolerName))
            CALL ShowContinueError(' use a Setpoint Manager to establish a setpoint at the unit control node.')
          ELSE
            localSetpointCheck = .FALSE.
            CALL CheckIfNodeSetpointManagedByEMS(ControlNode, iTemperatureSetpoint, localSetpointCheck)
            IF (localSetpointCheck) THEN
              CALL ShowSevereError('Missing temperature setpoint for Evap Cooler unit ' // &
                                    TRIM(EvapCond(EvapCoolNum)%EvapCoolerName))
              CALL ShowContinueError(' use a Setpoint Manager to establish a setpoint at the unit control node.')
              CALL ShowContinueError(' or use an EMS actuator to establish a setpoint at the unit control node.')
            ENDIF
          ENDIF
        END IF
      END IF
    END DO
    MySetPointCheckFlag = .FALSE.
  END IF

  IF ( .NOT. SysSizingCalc .AND. MySizeFlag(EvapCoolNum)) THEN
    ! for each cooler, do the sizing once.
    CALL SizeEvapCooler(EvapCoolNum)

    MySizeFlag(EvapCoolNum) = .FALSE.
  END IF

  ! Do the following initializations (every time step): This should be the info from
  ! the previous components outlets or the node data in this section.

  !Transfer the node data to EvapCond data structure
  InletNode = EvapCond(EvapCoolNum)%InletNode

  RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,Node(InletNode)%Temp,Node(InletNode)%HumRat)

   ! set the volume flow rates from the input mass flow rates
  EvapCond(EvapCoolNum)%VolFlowRate = Node(InletNode)%MassFlowRate/RhoAir

   ! Calculate the entering wet bulb temperature for inlet conditions
  EvapCond(EvapCoolNum)%InletWetBulbTemp=PsyTwbFnTdbWPb(Node(InletNode)%Temp,Node(InletNode)%HumRat,OutBaroPress)

    !Set all of the inlet mass flow variables from the nodes
  EvapCond(EvapCoolNum)%InletMassFlowRate         = Node(InletNode)%MassFlowRate
  EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail = Node(InletNode)%MassFlowRateMaxAvail
  EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail = Node(InletNode)%MassFlowRateMinAvail
    !Set all of the inlet state variables from the inlet nodes
  EvapCond(EvapCoolNum)%InletTemp        = Node(InletNode)%Temp
  EvapCond(EvapCoolNum)%InletHumRat      = Node(InletNode)%HumRat
  EvapCond(EvapCoolNum)%InletEnthalpy    = Node(InletNode)%Enthalpy
  EvapCond(EvapCoolNum)%InletPressure    = Node(InletNode)%Press
    !Set default outlet state to inlet states(?)
  EvapCond(EvapCoolNum)%OutletTemp       = EvapCond(EvapCoolNum)%InletTemp
  EvapCond(EvapCoolNum)%OutletHumRat     = EvapCond(EvapCoolNum)%InletHumRat
  EvapCond(EvapCoolNum)%OutletEnthalpy   = EvapCond(EvapCoolNum)%InletEnthalpy
  EvapCond(EvapCoolNum)%OutletPressure   = EvapCond(EvapCoolNum)%InletPressure

  EvapCond(EvapCoolNum)%OutletMassFlowRate         = EvapCond(EvapCoolNum)%InletMassFlowRate
  EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail
  EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail

    !Set all of the secondary inlet mass flow variables from the nodes
  SecInletNode = EvapCond(EvapCoolNum)%SecondaryInletNode
  IF (SecInletNode /= 0) THEN
    EvapCond(EvapCoolNum)%SecInletMassFlowRate         = Node(SecInletNode)%MassFlowRate
    EvapCond(EvapCoolNum)%SecInletMassFlowRateMaxAvail = Node(SecInletNode)%MassFlowRateMaxAvail
    EvapCond(EvapCoolNum)%SecInletMassFlowRateMinAvail = Node(SecInletNode)%MassFlowRateMinAvail
    EvapCond(EvapCoolNum)%SecInletTemp                 = Node(SecInletNode)%Temp
    EvapCond(EvapCoolNum)%SecInletHumRat               = Node(SecInletNode)%HumRat
    EvapCond(EvapCoolNum)%SecInletEnthalpy             = Node(SecInletNode)%Enthalpy
    EvapCond(EvapCoolNum)%SecInletPressure             = Node(SecInletNode)%Press
  ELSE
    EvapCond(EvapCoolNum)%SecInletMassFlowRate         = EvapCond(EvapCoolNum)%IndirectVolFlowRate * OutAirDensity
    EvapCond(EvapCoolNum)%SecInletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%IndirectVolFlowRate * OutAirDensity
    EvapCond(EvapCoolNum)%SecInletMassFlowRateMinAvail = 0.0d0
    EvapCond(EvapCoolNum)%SecInletTemp                 = OutDryBulbTemp
    EvapCond(EvapCoolNum)%SecInletHumRat               = PsyWFnTdbTwbPb(OutDryBulbTemp,OutWetBulbTemp,OutBaroPress)
    EvapCond(EvapCoolNum)%SecInletEnthalpy             = OutEnthalpy
    EvapCond(EvapCoolNum)%SecInletPressure             = OutBaroPress
  ENDIF
!Set the energy consumption to zero each time through for reporting
  EvapCond(EvapCoolNum)%EvapCoolerEnergy = 0.0d0
  EvapCond(EvapCoolNum)%EvapCoolerPower  = 0.0d0
  EvapCond(EvapCoolNum)%DewPointBoundFlag = 0
!Set the water consumption to zero each time through for reporting
  EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0
  EvapCond(EvapCoolNum)%EvapWaterConsump     = 0.0d0
  EvapCond(EvapCoolNum)%EvapWaterStarvMakup  = 0.0d0

!Set the Saturation and Stage Efficiency to zero each time through for reporting
  EvapCond(EvapCoolNum)%StageEff  = 0.0d0
  EvapCond(EvapCoolNum)%SatEff    = 0.0d0

! These initializations are done every iteration
  OutNode = EvapCond(EvapCoolNum)%OutletNode
  ControlNode = EvapCond(EvapCoolNum)%EvapControlNodeNum

  IF (ControlNode.EQ.0) THEN
    EvapCond(EvapCoolNum)%DesiredOutletTemp = 0.0d0
  ELSE IF (ControlNode.EQ.OutNode) THEN
    EvapCond(EvapCoolNum)%DesiredOutletTemp = Node(ControlNode)%TempSetPoint
  ELSE
    EvapCond(EvapCoolNum)%DesiredOutletTemp = Node(ControlNode)%TempSetPoint - &
      (Node(ControlNode)%Temp - Node(OutNode)%Temp)
  END IF

  RETURN

END SUBROUTINE InitEvapCooler

SUBROUTINE SizeEvapCooler(EvapCoolNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   March 2009
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Size calculations for Evap coolers
          !  currently just for secondary side of Research Special Indirect evap cooler

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataSizing
  USE DataAirSystems, ONLY: PrimaryAirSystem
  USE InputProcessor, ONLY: SameString
  USE ReportSizingManager, ONLY: ReportSizingOutput

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  LOGICAL :: CoolerOnOApath      = .FALSE.
  LOGICAL :: CoolerOnMainAirLoop = .FALSE.
!unused0509  INTEGER :: OAsysIndex = 0
  INTEGER :: AirSysBranchLoop = 0
!unused0509  INTEGER :: OAsysLoop = 0
!unuse0509  INTEGER :: OAcompLoop = 0
  INTEGER :: BranchComp = 0

  !inits
  CoolerOnOApath      = .FALSE.
  CoolerOnMainAirLoop = .FALSE.

  IF (EvapCond(EvapCoolNum)%IndirectVolFlowRate == Autosize) Then
    IF (CurSysNum > 0) THEN !central system
      !where is this cooler located, is it on OA system or main loop?
      ! search for this component in Air loop branches.
      DO AirSysBranchLoop =1,  PrimaryAirSystem(CurSysNum)%NumBranches
        DO BranchComp  =1, PrimaryAirSystem(CurSysNum)%Branch(AirSysBranchLoop)%TotalComponents

          IF (SameString(PrimaryAirSystem(CurSysNum)%Branch(AirSysBranchLoop)%comp(BranchComp)%Name, &
                          EvapCond(EvapCoolNum)%EvapCoolerName )) THEN
            CoolerOnMainAirLoop = .TRUE.
          ENDIF

        ENDDO
      ENDDO

      ! would like search for this componenent in some OutsideAirSys structure
       ! but thats not so easy becuase of circular USE with MixedAir.f90
       !  So assume if its not on main air path, its on OA path (for now)
      IF (.NOT. CoolerOnMainAirLoop) CoolerOnOApath = .TRUE.

      IF (CoolerOnMainAirLoop) THEN
        EvapCond(EvapCoolNum)%IndirectVolFlowRate =FinalSysSizing(CurSysNum)%DesMainVolFlow
      ELSEIF (CoolerOnOApath) THEN
        EvapCond(EvapCoolNum)%IndirectVolFlowRate =MAX(FinalSysSizing(CurSysNum)%DesOutAirVolFlow, &
                                                      0.5D0*FinalSysSizing(CurSysNum)%DesMainVolFlow)
      ENDIF

    ELSE !zone equipment
      ! we have no zone equipment evap coolers yet

    ENDIF

    CALL ReportSizingOutput('EvaporativeCooler:Indirect:ResearchSpecial', EvapCond(EvapCoolNum)%EvapCoolerName, &
                              'Secondary Fan Flow Rate [m3/s]', EvapCond(EvapCoolNum)%IndirectVolFlowRate)
  ENDIF

  RETURN

END SUBROUTINE SizeEvapCooler


 ! End Initialization Section of the Module
!******************************************************************************


 ! Begin Algorithm Section of the Module
!******************************************************************************
SUBROUTINE CalcDirectEvapCooler(EvapCoolNum)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE General,         ONLY : RoundSigDigits

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
      Integer :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
      !REAL(r64) Variables
      REAL(r64)  :: PadDepth    ! EvapCooler Pad Depth in Meters as input by the User
      REAL(r64)  :: SatEff      ! Saturation Efficiency of the CelDek Pad
      REAL(r64)  :: AirVel      ! The Calculated Air Velocity through the Pad
      REAL(r64)  :: TEDB        ! Entering Dry Bulb Temperature
      REAL(r64)  :: TEWB        ! Entering Wet Bulb Temperature
      REAL(r64)  :: RhoWater


  ! If the Evaporative Cooler  is operating there should be some mass flow rate
  !  Also the evap cooler has to be scheduled to be available
  IF((EvapCond(EvapCoolNum)%InletMassFlowRate .GT. 0.0d0) .and. &
     (GetCurrentScheduleValue(EvapCond(EvapCoolNum)%SchedPtr) .gt. 0.0d0)) THEN


   PadDepth = EvapCond(EvapCoolNum)%PadDepth
!******************************************************************************
!   THIS SUBROUTINE WILL CACULATE THE TEMPERATURE OF THE LEAVING AIR DRY BULB
!   FOR A DIRECT EVAPORATIVE AIR COOLER SUPPLIED WITH CFMAIR,DIRPAD,TEWB,TEDB,
!   AND PB (ATM. PRESS.) FOR AIR DENSITY CALCULATIONS.
!******************************************************************************


  AirVel=EvapCond(EvapCoolNum)%VolFlowRate/EvapCond(EvapCoolNum)%PadArea

!******************************************************************************
!   SAT EFF IS FOR DIFFERENT THICKNESS CELDEK PAD (CURVE FIT FROM DATA)
!******************************************************************************
  SatEff=0.792714d0+0.958569d0*PadDepth - 0.25193d0*AirVel                           &
         - 1.03215d0*PadDepth**2 + 2.62659d-2*AirVel**2 + 0.914869d0*PadDepth*AirVel &
         - 1.48241d0*AirVel*PadDepth**2 - 1.89919d-2*AirVel**3*PadDepth              &
         + 1.13137d0*PadDepth**3*AirVel + 3.27622d-2*AirVel**3*PadDepth**2           &
         - 0.145384d0*PadDepth**3*AirVel**2

  IF(SatEff.GE.1.0d0) SatEff=1.0d0
  IF(SatEff < 0.0d0) THEN ! we have a serious problem.  Pad Area and/or depth not suitable for system air flow rates
    Call ShowSevereError('EVAPCOOLER:DIRECT:CELDEKPAD: '//trim(EvapCond(EvapCoolNum)%EvapCoolerName)//' has a problem')
    Call ShowContinueError('Check size of Pad Area and/or Pad Depth in input')
    Call ShowContinueError('Cooler Effectiveness calculated as: '//trim(RoundSigDigits(SatEff,2)) )
    Call ShowContinueError('Air velocity (m/s) through pads calculated as: '//trim(RoundSigDigits(AirVel,2)) )
    CALL showFatalError('Program Terminates due to previous error condition')

  ENDIF
  EvapCond(EvapCoolNum)%SatEff = SatEff
!***************************************************************************
!   TEMP LEAVING DRY BULB IS CALCULATED FROM SATURATION EFFICIENCY AS THE
!   DRY BULB TEMP APPROACHES THE WET BULB TEMP. WET BULB TEMP IS CONSTANT
!   ACROSS A DIRECT EVAPORATION COOLER.
      TEWB = EvapCond(EvapCoolNum)%InletWetBulbTemp
      TEDB = EvapCond(EvapCoolNum)%InletTemp

      EvapCond(EvapCoolNum)%OutletTemp = TEDB-((TEDB-TEWB)*SatEff)

      EvapCond(EvapCoolNum)%OuletWetBulbTemp = EvapCond(EvapCoolNum)%InletWetBulbTemp


      EvapCond(EvapCoolNum)%OutletHumRat = PsyWFnTdbTwbPb(EvapCond(EvapCoolNum)%OutletTemp,TEWB,OutBaroPress)

      EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                             EvapCond(EvapCoolNum)%OutletHumRat)

!***************************************************************************
!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!Add the pump energy to the total Evap Cooler energy comsumption
      EvapCond(EvapCoolNum)%EvapCoolerPower = EvapCond(EvapCoolNum)%EvapCoolerPower +  &
                                              EvapCond(EvapCoolNum)%RecircPumpPower


!******************
!             WATER CONSUMPTION IN m3 OF WATER FOR DIRECT
!             H2O [m3/sec] = Delta W[KgH2O/Kg air]*Mass Flow Air[Kg air]
!                                /RhoWater [kg H2O/m3 H2O]
!******************
      RhoWater = RhoH2O(EvapCond(EvapCoolNum)%OutletTemp)
      EvapCond(EvapCoolNum)%EvapWaterConsumpRate =  &
                 (EvapCond(EvapCoolNum)%OutletHumRat - EvapCond(EvapCoolNum)%InletHumRat) *  &
                  EvapCond(EvapCoolNum)%InletMassFlowRate/Rhowater
      ! A numerical check to keep from having very tiny negative water consumption values being reported
      If(EvapCond(EvapCoolNum)%EvapWaterConsumpRate < 0.0d0) EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0


 Else
     ! The evap cooler is not running and does not change conditions from inlet to outlet
      EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%InletTemp

      EvapCond(EvapCoolNum)%OuletWetBulbTemp = EvapCond(EvapCoolNum)%InletWetBulbTemp

      EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

      EvapCond(EvapCoolNum)%OutletEnthalpy = EvapCond(EvapCoolNum)%InletEnthalpy

      EvapCond(EvapCoolNum)%EvapCoolerEnergy = 0.0d0

      EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0

 End IF
 ! all of the mass flowrates are not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletMassFlowRate         = EvapCond(EvapCoolNum)%InletMassFlowRate
 EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail
 EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail

 ! the pressure is not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletPressure = EvapCond(EvapCoolNum)%InletPressure

 RETURN

END SUBROUTINE CalcDirectEvapCooler


SUBROUTINE CalcDryIndirectEvapCooler(EvapCoolNum)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       BG Feb. 2007 secondary air inlet node
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:

      IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
      Integer :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
      !REAL(r64) Variables
      REAL(r64)  :: PadDepth    ! EvapCooler Pad Depth in Meters as input by the User
      REAL(r64)  :: SatEff      ! Saturation Efficiency of the CelDek Pad
      REAL(r64)  :: AirVel      ! The Calculated Air Velocity through the Pad
      REAL(r64)  :: TDBSec      ! Secondary leaving dry bulb
      REAL(r64)  :: TWBSec      ! Secondary Leaving Wet Bulb
      REAL(r64)  :: HumRatSec   ! Secondary leaving Humidity Ratio
      REAL(r64)  :: EffHX       ! Effectiveness of Secondary Heat Exchanger
      REAL(r64)  :: QHX         ! Q Across Sec HX
      REAL(r64)  :: RhoWater
      REAL(r64)  :: RhoAir      ! Density of the primary side air
      REAL(r64)  :: CpAir       ! Cp of the primary side air
      REAL(r64)  :: CFMAir
      REAL(r64)  :: CFMSec


  ! If the Evaporative Cooler  is operating there should be some mass flow rate
  !  Also the evap cooler has to be scheduled to be available
  IF((EvapCond(EvapCoolNum)%InletMassFlowRate .GT. 0.0d0) .and. &
     (GetCurrentScheduleValue(EvapCond(EvapCoolNum)%SchedPtr) .gt. 0.0d0)) THEN


   PadDepth = EvapCond(EvapCoolNum)%IndirectPadDepth
!******************************************************************************
!   THIS SUBROUTINE WILL CACULATE THE TEMPERATURE OF THE LEAVING AIR DRY BULB
!   FOR A DIRECT EVAPORATIVE AIR COOLER SUPPLIED WITH CFMAIR,DIRPAD,TEWB,TEDB,
!   AND PB (ATM. PRESS.) FOR AIR DENSITY CALCULATIONS.
!******************************************************************************


  AirVel=EvapCond(EvapCoolNum)%IndirectVolFlowRate/EvapCond(EvapCoolNum)%IndirectPadArea

!******************************************************************************
!   SAT EFF IS FOR DIFFERENT THICKNESS CELDEK PAD (CURVE FIT FROM DATA)
!******************************************************************************
  SatEff=0.792714d0+0.958569d0*PadDepth - 0.25193d0*AirVel                           &
         - 1.03215d0*PadDepth**2 + 2.62659d-2*AirVel**2 + 0.914869d0*PadDepth*AirVel &
         - 1.48241d0*AirVel*PadDepth**2 - 1.89919d-2*AirVel**3*PadDepth              &
         + 1.13137d0*PadDepth**3*AirVel + 3.27622d-2*AirVel**3*PadDepth**2         &
         - 0.145384d0*PadDepth**3*AirVel**2

  IF(SatEff.GE.1.0d0) SatEff=1.0d0
  EvapCond(EvapCoolNum)%SatEff = SatEff
!***************************************************************************
!   TEMP LEAVING DRY BULB IS CALCULATED FROM SATURATION EFFICIENCY AS THE
!   DRY BULB TEMP APPROACHES THE WET BULB TEMP ACROSS THE PAD BEFORE THE HX.
!***************************************************************************
!***** FIRST CHECK IF THIS TEWB IS A FEASIBLE POINT ON PSYCH CHART**********

! BG Feb 2007 mods for oa node (eg. height-dependent outside air model)
      TWBSec =  PsyTwbFnTdbWPb(EvapCond(EvapCoolNum)%SecInletTemp  &
                              ,EvapCond(EvapCoolNum)%SecInletHumRat &
                              ,EvapCond(EvapCoolNum)%SecInletPressure )  !  OutWetBulbTemp
      TDBSec = EvapCond(EvapCoolNum)%SecInletTemp-((EvapCond(EvapCoolNum)%SecInletTemp-TWBSec)*SatEff)

      HumratSec = PsyWFnTdbTwbPb(TDBSec,TWBSec,EvapCond(EvapCoolNum)%SecInletPressure)

!***************************************************************************
!                  CALCULATE THE TLDB FROM HX EQUATIONS GIVEN AN EFFICIENCY
!***************************************************************************
      EffHX  = EvapCond(EvapCoolNum)%IndirectHXEffectiveness
      CpAir  = PsyCpAirFnWTdb(EvapCond(EvapCoolNum)%InletHumRat,EvapCond(EvapCoolNum)%InletTemp)
      RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,EvapCond(EvapCoolNum)%InletTemp,EvapCond(EvapCoolNum)%InletHumRat)
      CFMAir = EvapCond(EvapCoolNum)%VolFlowRate            !Volume Flow Rate Primary Side
      CFMSec = EvapCond(EvapCoolNum)%IndirectVolFlowRate    !Volume Flolw Rate Secondary Side

      QHX=EFFHX*MIN(CFMSEC,CFMAIR)*RhoAir*CpAir*(EvapCond(EvapCoolNum)%InletTemp-TDBSec)
      EvapCond(EvapCoolNum)%OutletTemp=EvapCond(EvapCoolNum)%InletTemp-QHX/(RhoAir*CFMAIR*CpAir)
! This is a rough approximation of the Total Indirect Stage Efficiency for the Dry stage which
!   is a 2 step process the first being teh pad efficiency and then the HX Effectiveness.  I think that
!   this would mainly be used for evap sizing purposes.
      EvapCond(EvapCoolNum)%StageEff = SatEff * EFFHX
!***************************************************************************
!                  CALCULATE THE WET BULB TEMP in the primary system air USING PSYCH ROUTINES
! There is a constant humidity ratio across the primary side but a reduction in the dry bulb temp
      EvapCond(EvapCoolNum)%OuletWetBulbTemp=PsyTwbFnTdbWPb(EvapCond(EvapCoolNum)%OutletTemp, &
                                             EvapCond(EvapCoolNum)%InletHumRat,OutBaroPress)
!***************************************************************************
!   TEMP LEAVING DRY BULB IS CALCULATED FROM SATURATION EFFICIENCY AS THE
!   DRY BULB TEMP APPROACHES THE WET BULB TEMP. WET BULB TEMP IS CONSTANT
!   ACROSS A DIRECT EVAPORATION COOLER.

      EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

      EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                             EvapCond(EvapCoolNum)%OutletHumRat)

!***************************************************************************
!                  POWER OF THE SECONDARY AIR FAN
      IF (EvapCond(EvapCoolNum)%IndirectFanEff > 0.0D0) THEN
        EvapCond(EvapCoolNum)%EvapCoolerPower=EvapCond(EvapCoolNum)%EvapCoolerPower +      &
                                              EvapCond(EvapCoolNum)%IndirectFanDeltaPress* &
                                              EvapCond(EvapCoolNum)%IndirectVolFlowRate/   &
                                              EvapCond(EvapCoolNum)%IndirectFanEff
      ENDIF

!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!Add the pump energy to the total Evap Cooler energy comsumption
      EvapCond(EvapCoolNum)%EvapCoolerPower = EvapCond(EvapCoolNum)%EvapCoolerPower +  &
                                              EvapCond(EvapCoolNum)%IndirectRecircPumpPower


!******************
!             WATER CONSUMPTION IN LITERS OF WATER FOR DIRECT
!             H2O [m3/sec] = Delta W[KgH2O/Kg air]*Mass Flow Air[Kg air]
!                                /RhoWater [kg H2O/m3 H2O]
!******************
      RhoWater = RhoH2O(TDBSec)
      RhoAir = ( PsyRhoAirFnPbTdbW(EvapCond(EvapCoolNum)%SecInletPressure  &
                                  , EvapCond(EvapCoolNum)%SecInletTemp     &
                                  , EvapCond(EvapCoolNum)%SecInletHumRat ) &
                + PsyRhoAirFnPbTdbW(EvapCond(EvapCoolNum)%SecInletPressure  &
                                  , TDBSec     &
                                  , HumratSec ) ) / 2.0d0
      EvapCond(EvapCoolNum)%EvapWaterConsumpRate =  &
                 (HumratSec - EvapCond(EvapCoolNum)%SecInletHumRat) *  &
                 EvapCond(EvapCoolNum)%IndirectVolFlowRate*RhoAir/RhoWater
      ! A numerical check to keep from having very tiny negative water consumption values being reported
      If(EvapCond(EvapCoolNum)%EvapWaterConsumpRate < 0.0d0) EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0

 Else
     ! The evap cooler is not running and does not change conditions from inlet to outlet
      EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%InletTemp

      EvapCond(EvapCoolNum)%OuletWetBulbTemp = EvapCond(EvapCoolNum)%InletWetBulbTemp

      EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

      EvapCond(EvapCoolNum)%OutletEnthalpy = EvapCond(EvapCoolNum)%InletEnthalpy

      EvapCond(EvapCoolNum)%EvapCoolerEnergy = 0.0d0

      EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0

 End IF
 ! all of the mass flowrates are not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletMassFlowRate         = EvapCond(EvapCoolNum)%InletMassFlowRate
 EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail
 EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail

 ! the pressure is not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletPressure = EvapCond(EvapCoolNum)%InletPressure

 RETURN

END SUBROUTINE CalcDryIndirectEvapCooler


SUBROUTINE CalcWetIndirectEvapCooler(EvapCoolNum)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
 !     Use DataEnvironment, ONLY: OutDryBulbTemp, OutWetBulbTemp, OutHumRat, OutBaroPress


      IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
      Integer :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
      !REAL(r64) Variables
      REAL(r64)  :: StageEff    ! Stage Efficiency of the Heat Exchanger
      REAL(r64)  :: TEDB        ! Entering Dry Bulb Temperature
      REAL(r64)  :: TEWB        ! Entering Wet Bulb Temperature
      REAL(r64)  :: QHX         ! Q Across Sec HX in Watts or J/sec
      REAL(r64)  :: RhoWater
      REAL(r64)  :: RhoAir      ! Density of the primary side air
      REAL(r64)  :: CFMAir
      REAL(r64)  :: CFMSec
      REAL(r64)  :: TWBSec  ! wet bulb of secondary air


  ! If the Evaporative Cooler  is operating there should be some mass flow rate
  !  Also the evap cooler has to be scheduled to be available
  IF((EvapCond(EvapCoolNum)%InletMassFlowRate .GT. 0.0d0) .and. &
     (GetCurrentScheduleValue(EvapCond(EvapCoolNum)%SchedPtr) .gt. 0.0d0)) THEN


!******************************************************************************
!   THIS SUBROUTINE WILL CACULATE THE TEMPERATURE OF THE LEAVING AIR DRY BULB
!   FOR A WET COIL EVAPORATIVE COOLER
!******************************************************************************
!  INDIRECT STAGE EFFICIENCY FOR WET COIL INDIRECT EVAP COOLERS
      CFMAir = EvapCond(EvapCoolNum)%VolFlowRate            !Volume Flow Rate Primary Side
      CFMSec = EvapCond(EvapCoolNum)%IndirectVolFlowRate    !Volume Flolw Rate Secondary Side

      StageEff = EvapCond(EvapCoolNum)%WetCoilMaxEfficiency - &
              MIN(EvapCond(EvapCoolNum)%WetCoilFlowRatio*CFMAIR/CFMSEC, &
                  EvapCond(EvapCoolNum)%WetCoilMaxEfficiency)

      IF(StageEff.GE.1.0d0) StageEff=1.0d0
! This is a rough approximation of the Total Indirect Stage Efficiency.  I think that
!   this would mainly be used for evap sizing purposes.
      EvapCond(EvapCoolNum)%StageEff = StageEff
!***************************************************************************
!   TEMP LEAVING DRY BULB IS CALCULATED FROM A SIMPLE WET BULB APPROACH
!   MODEL GIVEN THE INDIRECT STAGE EFFICIENCY.
!   DRY BULB TEMP APPROACHES THE WET BULB TEMP ACROSS THE INDIRECT STAGE.
!***************************************************************************
!                  CALCULATE THE TLDB
      TEWB = EvapCond(EvapCoolNum)%InletWetBulbTemp
      TEDB = EvapCond(EvapCoolNum)%InletTemp
      TWBSec =  PsyTwbFnTdbWPb(EvapCond(EvapCoolNum)%SecInletTemp  &
                              ,EvapCond(EvapCoolNum)%SecInletHumRat &
                              ,EvapCond(EvapCoolNum)%SecInletPressure )
      EvapCond(EvapCoolNum)%OutletTemp = TEDB - StageEff*(TEDB-TWBSec)

!***************************************************************************
!                  CALCULATE THE WET BULB TEMP in the primary system air using PSYCH ROUTINES
! There is a constant humidity ratio across the primary side but a reduction in the dry bulb temp
      EvapCond(EvapCoolNum)%OuletWetBulbTemp = PsyTwbFnTdbWPb(EvapCond(EvapCoolNum)%OutletTemp, &
                                               EvapCond(EvapCoolNum)%InletHumRat,OutBaroPress)
!***************************************************************************
!                  CALCULATE other outlet properties using PSYCH ROUTINES
      EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

      EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                             EvapCond(EvapCoolNum)%OutletHumRat)

!***************************************************************************
!                  POWER OF THE SECONDARY AIR FAN
      IF (EvapCond(EvapCoolNum)%IndirectFanEff > 0.0D0) THEN
        EvapCond(EvapCoolNum)%EvapCoolerPower=EvapCond(EvapCoolNum)%EvapCoolerPower +      &
                                              EvapCond(EvapCoolNum)%IndirectFanDeltaPress* &
                                              EvapCond(EvapCoolNum)%IndirectVolFlowRate/   &
                                              EvapCond(EvapCoolNum)%IndirectFanEff
      ENDIF

!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!Add the pump energy to the total Evap Cooler energy comsumption
      EvapCond(EvapCoolNum)%EvapCoolerPower = EvapCond(EvapCoolNum)%EvapCoolerPower +  &
                                              EvapCond(EvapCoolNum)%IndirectRecircPumpPower


!******************
!             WATER CONSUMPTION IN LITERS OF WATER FOR Wet InDIRECT
!             H2O [m3/sec] = (QHx [J/s])/(2,500,000 [J/kg H2O] * RhoWater [kg H2O/m3 H2O])
!******************
!***** FIRST calculate the heat exchange on the primary air side**********
      RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,EvapCond(EvapCoolNum)%InletTemp,EvapCond(EvapCoolNum)%InletHumRat)
      QHX = CFMAir*RhoAir*(EvapCond(EvapCoolNum)%InletEnthalpy - EvapCond(EvapCoolNum)%OutletEnthalpy)

      RhoWater = RhoH2O(EvapCond(EvapCoolNum)%SecInletTemp)
      EvapCond(EvapCoolNum)%EvapWaterConsumpRate =  (QHx/StageEff)/(2500000.0d0 * RhoWater)
      ! A numerical check to keep from having very tiny negative water consumption values being reported
      If(EvapCond(EvapCoolNum)%EvapWaterConsumpRate < 0.0d0) EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0

 Else
     ! The evap cooler is not running and does not change conditions from inlet to outlet
      EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%InletTemp

      EvapCond(EvapCoolNum)%OuletWetBulbTemp = EvapCond(EvapCoolNum)%InletWetBulbTemp

      EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

      EvapCond(EvapCoolNum)%OutletEnthalpy = EvapCond(EvapCoolNum)%InletEnthalpy

      EvapCond(EvapCoolNum)%EvapCoolerEnergy = 0.0d0

      EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0

 End IF
 ! all of the mass flowrates are not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletMassFlowRate         = EvapCond(EvapCoolNum)%InletMassFlowRate
 EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail
 EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail

 ! the pressure is not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletPressure = EvapCond(EvapCoolNum)%InletPressure

 RETURN

END SUBROUTINE CalcWetIndirectEvapCooler

Subroutine CalcResearchSpecialPartLoad(EvapCoolNum)
      ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2003
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Subroutine models a "special" cooler.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! copied CalcWetIndirectEvapCooler as template for new cooler

                   ! USE STATEMENTS:
      USE DataHVACGlobals, only:  TempControlTol

      IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
      Integer :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na
  REAL(r64), PARAMETER :: MinAirMassFlow = 0.001d0
          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:

  CHARACTER(len=MaxNameLength)  :: CompName
  REAL(r64)           :: FullOutput
  REAL(r64)           :: ReqOutput
  Integer             :: InletNode
  Integer             :: OutletNode
  Integer             :: ControlNode
  REAL(r64)           :: PartLoadFrac
  REAL(r64)           :: DesOutTemp
      ! Set local variables
      ! Retrieve the load on the controlled zone
  OutletNode = EvapCond(EvapCoolNum)%OutletNode
  InletNode = EvapCond(EvapCoolNum)%InletNode
  ControlNode = EvapCond(EvapCoolNum)%EvapControlNodeNum
  DesOutTemp = EvapCond(EvapCoolNum)%DesiredOutletTemp
  PartLoadFrac = 0.0d0
  CompName=EvapCond(EvapCoolNum)%EvapCoolerName

  ! If Evap Cooler runs with a cooling load then set PartLoadFrac on Cooling System and the Mass Flow
  If((GetCurrentScheduleValue(EvapCond(EvapCoolNum)%SchedPtr) .gt. 0.0d0) .and. &
       (Node(InletNode)%MassFlowRate .gt. MinAirMassFlow) .and. &
       (Node(InletNode)%Temp > Node(ControlNode)%TempSetPoint) .and. &
       (ABS(Node(InletNode)%Temp - DesOutTemp) .gt. TempControlTol) ) Then

        ! Get full load result, depending on model
        EvapCond(EvapCoolNum)%PartLoadFract = 1.0d0
        SELECT CASE (EvapCond(EvapCoolNum)%EvapCoolerType)
        CASE (iEvapCoolerInDirectRDDSpecial)
          CALL CalcIndirectResearchSpecialEvapCooler(EvapCoolNum)
          CALL UpdateEvapCooler(EvapCoolNum)
          FullOutput = Node(InletNode)%MassFlowRate *  &
                     (PsyHFnTdbW(Node(OutletNode)%Temp,Node(InletNode)%HumRat)  &
                      - PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                     (PsyHFnTdbW(EvapCond(EvapCoolNum)%DesiredOutletTemp,Node(InletNode)%HumRat) - &
                      PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

          ! now reinit after test call
          CALL InitEvapCooler(EvapCoolNum)

        CASE (iEvapCoolerDirectResearchSpecial)
          CALL CalcDirectResearchSpecialEvapCooler(EvapCoolNum)
          CALL UpdateEvapCooler(EvapCoolNum)
          FullOutput = Node(OutletNode)%Temp - Node(InletNode)%Temp
          ReqOutput = EvapCond(EvapCoolNum)%DesiredOutletTemp - Node(InletNode)%Temp

          ! now reinit after test call
          CALL InitEvapCooler(EvapCoolNum)

        END SELECT

        ! Since we are cooling, we expect FullOutput to be < 0 and FullOutput < NoCoolOutput
        ! Check that this is the case; if not set PartLoadFrac = 0.0 (off) and return
        ! Calculate the part load fraction
        If (FullOutput .EQ. 0.0D0) then
          FullOutput = 0.00001D0
        ENDIF
          PartLoadFrac = ReqOutput/FullOutput
        IF(PartLoadFrac.GT.1.0D0) THEN
          PartLoadFrac = 1.0D0
        ELSEIF(PartLoadFrac < 0.0D0) THEN
          PartLoadFrac = 0.0D0
        END IF

  ELSE ! No cooling
    PartLoadFrac = 0.0D0

  ENDIF   ! End of the cooler running If block
  !Set the final results
  EvapCond(EvapCoolNum)%PartLoadFract = PartLoadFrac

  RETURN
END SUBROUTINE CalcResearchSpecialPartLoad

SUBROUTINE CalcIndirectResearchSpecialEvapCooler(EvapCoolNum)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2003
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Subroutine models a "special" cooler that allows high effectiveness and controls

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! copied CalcWetIndirectEvapCooler as template for new cooler

          ! USE STATEMENTS:
      Use DataEnvironment, ONLY: OutDryBulbTemp, OutWetBulbTemp, OutHumRat, OutBaroPress
      USE DataWater ,      ONLY: WaterStorage
      IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
      INTEGER, INTENT(IN) :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  !REAL(r64) Variables
  REAL(r64)  :: SecondaryInletWetBulbTemp ! entering wet bulb for secondary/purge side
  REAL(r64)  :: SecondaryInletDewpointTemp ! entering dewpoint for secondary/purge side
  REAL(r64)  :: StageEff    ! Stage Efficiency of the Heat Exchanger
  REAL(r64)  :: TEDB        ! Entering Dry Bulb Temperature
  REAL(r64)  :: TEWB        ! Entering Wet Bulb Temperature
  REAL(r64)  :: QHX         ! Q Across Sec HX in Watts or J/sec
  REAL(r64)  :: RhoWater
  REAL(r64)  :: RhoAir      ! Density of the primary side air
  REAL(r64)  :: CFMAir
  Integer    :: TertNode  ! inlet node for relief (from bulding) to mix for purge
  REAL(r64)  :: BoundTemp   ! temperature limit for outlet
  REAL(r64)  :: PartLoad
  REAL(r64)  :: TotalVolFlow
  REAL(r64)  :: TertMdot
  REAL(r64)  :: TertHumRate
  REAL(r64)  :: TertTemp
  REAL(r64)  :: TertRho
  REAL(r64)  :: TertVdot
  REAL(r64)  :: SecVdot
  REAL(r64)  :: SecRho
  REAL(r64)  :: SecMdot
  REAL(r64)  :: PurgeMdot
  REAL(r64)  :: PurgeHumRat
  REAL(r64)  :: PurgeEnthalpy
  REAL(r64)  :: PurgeTemp
  REAL(r64)  :: BlowDownVdot      =0.0d0
  REAL(r64)  :: DriftVdot         =0.0d0
  REAL(r64)  :: EvapVdot          =0.0d0

  ! If the Evaporative Cooler  is operating there should be some mass flow rate
  !  Also the evap cooler has to be scheduled to be available
  IF((EvapCond(EvapCoolNum)%InletMassFlowRate .GT. 0.0d0) .and. &
     (GetCurrentScheduleValue(EvapCond(EvapCoolNum)%SchedPtr) .gt. 0.0d0)) THEN


!******************************************************************************
!   THIS SUBROUTINE WILL CACULATE THE TEMPERATURE OF THE LEAVING AIR DRY BULB
!   FOR A WET COIL EVAPORATIVE COOLER
!******************************************************************************
!  INDIRECT STAGE EFFICIENCY FOR WET COIL INDIRECT EVAP COOLERS
      CFMAir = EvapCond(EvapCoolNum)%VolFlowRate            !Volume Flow Rate Primary Side
!      CFMSec = EvapCond(EvapCoolNum)%IndirectVolFlowRate    !Volume Flolw Rate Secondary Side

      StageEff = EvapCond(EvapCoolNum)%WetCoilMaxEfficiency

! This is model is for special indirect cooler with efficiency greater than 1.0

      IF(StageEff.GE.1.5d0) StageEff=1.5d0

      EvapCond(EvapCoolNum)%StageEff = StageEff

!***********************************************
!  Unit is allowed to mix relief air that would otherwise be exhausted outdoors for ventilation
!  If tertiary node is set >0 then it assumed that this node is the exhaust out of the building
!  and the remainder will be made up with outside air from the secondary node
!*********************************************

  TertNode = EvapCond(EvapCoolNum)%TertiaryInletNode
  If (tertNode .EQ. 0) then

    SecondaryInletWetBulbTemp  = PsyTwbFnTdbWPb(EvapCond(EvapCoolNum)%SecInletTemp, &
                                                EvapCond(EvapCoolNum)%SecInletHumRat,OutBaroPress)
    SecondaryInletDewpointTemp = PsyTdpFnTdbTwbPb(EvapCond(EvapCoolNum)%SecInletTemp, SecondaryInletWetBulbTemp, OutBaroPress)

  Else

    TotalVolFlow = EvapCond(EvapCoolNum)%IndirectVolFlowRate
    TertMdot    = node(TertNode)%MassFlowRate
    TertHumRate = node(TertNode)%HumRat
    TertTemp    = node(TertNode)%Temp
    ! is Node pressure available or better? using outdoor pressure for now
    TertRho     = PsyRhoAirFnPbTdbW(OutBaroPress, TertTemp , TertHumRate)
    TertVdot    = TertMdot/TertRho

    SecVdot     = TotalVolFlow - TertVdot

    IF (SecVdot .LT. 0.0d0) then ! all tertiary/releif air e.g. econonizer wide open
      SecVdot =  0.0d0
      SecondaryInletWetBulbTemp  = PsyTwbFnTdbWPb(TertTemp, TertHumRate , OutBaroPress)
      SecondaryInletDewpointTemp = PsyTdpFnTdbTwbPb(TertTemp, SecondaryInletWetBulbTemp, OutBaroPress)

    Else

      ! First determine mass flow of OA,  in secondary
      SecRho = PsyRhoAirFnPbTdbW(OutBaroPress, EvapCond(EvapCoolNum)%SecInletTemp,EvapCond(EvapCoolNum)%SecInletHumRat)
      SecMdot = SecRho * SecVdot
      ! Mass balance on moisture to get outlet air humidity ratio
      ! this mixing takes place before wet media.
      PurgeMdot   = SecMdot + TertMdot
      PurgeHumRat = (SecMdot * EvapCond(EvapCoolNum)%SecInletHumRat + TertMdot * TertHumRate) / PurgeMdot

      ! Energy balance to get outlet air enthalpy

      PurgeEnthalpy = (SecMdot * PsyHFnTdbW(EvapCond(EvapCoolNum)%SecInletTemp,EvapCond(EvapCoolNum)%SecInletHumRat) &
                 +   TertMdot * PsyHFnTdbW(TertTemp, TertHumRate)) / PurgeMdot

      ! Use Enthalpy and humidity ratio to get outlet temperature from psych chart

      PurgeTemp = PsyTdbFnHW(PurgeEnthalpy, PurgeHumRat)
      SecondaryInletWetBulbTemp  = PsyTwbFnTdbWPb(PurgeTemp, PurgeHumRat, OutBaroPress)
      SecondaryInletDewpointTemp = PsyTdpFnTdbTwbPb(PurgeTemp,SecondaryInletWetBulbTemp, OutBaroPress)
    Endif
 endif
 !***************************************************************************
!   TEMP LEAVING DRY BULB IS CALCULATED FROM A SIMPLE WET BULB APPROACH
!   MODEL GIVEN THE INDIRECT STAGE EFFICIENCY.
!   DRY BULB TEMP APPROACHES THE WET BULB TEMP ACROSS THE INDIRECT STAGE.
!***************************************************************************
      TEWB = EvapCond(EvapCoolNum)%InletWetBulbTemp
      TEDB = EvapCond(EvapCoolNum)%InletTemp
      PartLoad = EvapCond(EvapCoolNum)%PartLoadFract

  IF (PartLoad .EQ. 1.0D0) THEN
  !                                 Tout = Tin -  (   0.7    (Tin  - Tpurge,wb,in)
        EvapCond(EvapCoolNum)%OutletTemp = TEDB - StageEff*(TEDB - SecondaryInletWetBulbTemp )
  !  now bound with secondary dewpoint.
  ! unless the resulting Tout<=Tpurge,dp,in ; in which case Tout = Tin - 0.9(Tin-Tpurge,dp,in)

     BoundTemp = TEDB - EvapCond(EvapCoolNum)%DPBoundFactor *(TEDB - SecondaryInletDewpointTemp )
     IF (EvapCond(EvapCoolNum)%OutletTemp .LT. BoundTemp) THEN
       EvapCond(EvapCoolNum)%OutletTemp = BoundTemp
       EvapCond(EvapCoolNum)%DewPointBoundFlag = 1
     ENDIF
  ELSEIF ((partLoad .LT. 1.0D0) .AND. (partLoad .GT. 0.0D0)) THEN
    ! assume perfect control Use PLF for energy consumption
    IF (EvapCond(EvapCoolNum)%DesiredOutletTemp .LT. TEDB ) THEN
      EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%DesiredOutletTemp
    ENDIF
  ELSE
    !part load set to zero so no cooling
    EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%InletTemp
  ENDIF


!***************************************************************************
!                  CALCULATE THE WET BULB TEMP in the primary system air using PSYCH ROUTINES
! There is a constant humidity ratio across the primary side but a reduction in the dry bulb temp
      EvapCond(EvapCoolNum)%OuletWetBulbTemp = PsyTwbFnTdbWPb(EvapCond(EvapCoolNum)%OutletTemp, &
                                               EvapCond(EvapCoolNum)%InletHumRat,OutBaroPress)
!***************************************************************************
!                  CALCULATE other outlet propertiesusing PSYCH ROUTINES
      EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

      EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                             EvapCond(EvapCoolNum)%OutletHumRat)

!***************************************************************************
!                  POWER OF THE SECONDARY AIR FAN with part load factor applied (assumes const efficiency)
      IF (EvapCond(EvapCoolNum)%IndirectFanEff > 0.0D0) THEN
        EvapCond(EvapCoolNum)%EvapCoolerPower=EvapCond(EvapCoolNum)%EvapCoolerPower +      &
                                              EvapCond(EvapCoolNum)%IndirectFanDeltaPress* &
                                              EvapCond(EvapCoolNum)%IndirectVolFlowRate/   &
                                              EvapCond(EvapCoolNum)%IndirectFanEff* PartLoad
      ENDIF
!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!Add the pump energy to the total Evap Cooler energy comsumption
      EvapCond(EvapCoolNum)%EvapCoolerPower = EvapCond(EvapCoolNum)%EvapCoolerPower +  &
                                              EvapCond(EvapCoolNum)%IndirectRecircPumpPower* PartLoad


!******************
!             WATER CONSUMPTION IN LITERS OF WATER FOR Wet InDIRECT
!             H2O [m3/sec] = (QHx [J/s])/(2,500,000 [J/kg H2O] * RhoWater [kg H2O/m3 H2O])
!******************
!***** FIRST calculate the heat exchange on the primary air side**********
      RhoAir = PsyRhoAirFnPbTdbW(OutBaroPress,EvapCond(EvapCoolNum)%InletTemp,EvapCond(EvapCoolNum)%InletHumRat)
      QHX = CFMAir*RhoAir*(EvapCond(EvapCoolNum)%InletEnthalpy - EvapCond(EvapCoolNum)%OutletEnthalpy)

      RhoWater = RhoH2O(OutDryBulbTemp)
      EvapVdot=  (QHx)/(2500000.0d0 * RhoWater)
      DriftVdot = EvapVdot * EvapCond(EvapCoolNum)%DriftFraction
      IF (EvapCond(EvapCoolNum)%BlowDownRatio > 0.0D0) THEN
        BlowDownVdot =  EvapVdot / (EvapCond(EvapCoolNum)%BlowDownRatio - 1) - DriftVdot
        IF ( BlowDownVdot < 0.0d0 ) BlowDownVdot = 0.0d0
      ELSE
        BlowDownVdot = 0.0D0
      ENDIF
      EvapCond(EvapCoolNum)%EvapWaterConsumpRate =  EvapVdot + DriftVdot + BlowDownVdot
      ! A numerical check to keep from having very tiny negative water consumption values being reported
      IF(EvapCond(EvapCoolNum)%EvapWaterConsumpRate < 0.0d0) EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0

 ELSE
   ! The evap cooler is not running and does not change conditions from inlet to outlet
    EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%InletTemp

    EvapCond(EvapCoolNum)%OuletWetBulbTemp = EvapCond(EvapCoolNum)%InletWetBulbTemp

    EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

    EvapCond(EvapCoolNum)%OutletEnthalpy = EvapCond(EvapCoolNum)%InletEnthalpy

    EvapCond(EvapCoolNum)%EvapCoolerEnergy     = 0.0D0
    EvapCond(EvapCoolNum)%EvapCoolerPower      = 0.0D0
    EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0D0

 End IF

 ! all of the mass flowrates are not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletMassFlowRate         = EvapCond(EvapCoolNum)%InletMassFlowRate
 EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail
 EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail

 ! the pressure is not changed across the evap cooler
 EvapCond(EvapCoolNum)%OutletPressure = EvapCond(EvapCoolNum)%InletPressure

 RETURN

END SUBROUTINE CalcIndirectResearchSpecialEvapCooler

SUBROUTINE CalcDirectResearchSpecialEvapCooler(EvapCoolNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   March 2009
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! calculate model for direct evaporative cooler that is simple and controllable

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
          ! na

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)  :: SatEff      ! Saturation Efficiency of the CelDek Pad
  REAL(r64)  :: TEDB        ! Entering Dry Bulb Temperature
  REAL(r64)  :: TEWB        ! Entering Wet Bulb Temperature
  REAL(r64)  :: RhoWater
  REAL(r64)  :: PartLoad
  REAL(r64)  :: BlowDownVdot      =0.0d0
  REAL(r64)  :: DriftVdot         =0.0d0
  REAL(r64)  :: EvapVdot          =0.0d0

  ! If the Evaporative Cooler  is operating there should be some mass flow rate
  !  Also the evap cooler has to be scheduled to be available
  IF((EvapCond(EvapCoolNum)%InletMassFlowRate .GT. 0.0d0) .and. &
     (GetCurrentScheduleValue(EvapCond(EvapCoolNum)%SchedPtr) .gt. 0.0d0)) THEN

!***************************************************************************
!   TEMP LEAVING DRY BULB IS CALCULATED FROM SATURATION EFFICIENCY AS THE
!   DRY BULB TEMP APPROACHES THE WET BULB TEMP. WET BULB TEMP IS CONSTANT
!   ACROSS A DIRECT EVAPORATION COOLER.
      TEWB   = EvapCond(EvapCoolNum)%InletWetBulbTemp
      TEDB   = EvapCond(EvapCoolNum)%InletTemp
      SatEff = EvapCond(EvapCoolNum)%DirectEffectiveness
      PartLoad = EvapCond(EvapCoolNum)%PartLoadFract
      IF (PartLoad .EQ. 1.0d0) THEN
        EvapCond(EvapCoolNum)%OutletTemp = TEDB-((TEDB-TEWB)*SatEff)
        EvapCond(EvapCoolNum)%OuletWetBulbTemp = TEWB
        EvapCond(EvapCoolNum)%OutletHumRat = PsyWFnTdbTwbPb(EvapCond(EvapCoolNum)%OutletTemp,TEWB,OutBaroPress)
        EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                               EvapCond(EvapCoolNum)%OutletHumRat)
      ELSEIF ((partLoad .LT. 1.0D0) .AND. (partLoad .GT. 0.0D0)) THEN
        ! assume perfect control Use PLF for energy consumption
        IF (EvapCond(EvapCoolNum)%DesiredOutletTemp .LT. TEDB ) THEN
          EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%DesiredOutletTemp
          EvapCond(EvapCoolNum)%OuletWetBulbTemp = TEWB
          EvapCond(EvapCoolNum)%OutletHumRat = PsyWFnTdbTwbPb(EvapCond(EvapCoolNum)%OutletTemp,TEWB,OutBaroPress)

          EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                               EvapCond(EvapCoolNum)%OutletHumRat)
        ELSE !do no cooling
          EvapCond(EvapCoolNum)%OutletTemp = TEDB
          EvapCond(EvapCoolNum)%OuletWetBulbTemp = TEWB
          EvapCond(EvapCoolNum)%OutletHumRat = PsyWFnTdbTwbPb(EvapCond(EvapCoolNum)%OutletTemp,TEWB,OutBaroPress)
          EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                               EvapCond(EvapCoolNum)%OutletHumRat)
        ENDIF
      ELSE
        !part load set to zero so no cooling
        EvapCond(EvapCoolNum)%OutletTemp = TEDB
        EvapCond(EvapCoolNum)%OuletWetBulbTemp = TEWB
        EvapCond(EvapCoolNum)%OutletHumRat = PsyWFnTdbTwbPb(EvapCond(EvapCoolNum)%OutletTemp,TEWB,OutBaroPress)
        EvapCond(EvapCoolNum)%OutletEnthalpy = PsyHFnTdbW(EvapCond(EvapCoolNum)%OutletTemp,  &
                                             EvapCond(EvapCoolNum)%OutletHumRat)
      ENDIF

!***************************************************************************
!                  ENERGY CONSUMED BY THE RECIRCULATING PUMP
!Add the pump energy to the total Evap Cooler energy comsumption
      EvapCond(EvapCoolNum)%EvapCoolerPower = EvapCond(EvapCoolNum)%RecircPumpPower * PartLoad

!******************
!             WATER CONSUMPTION IN m3 OF WATER FOR DIRECT
!             H2O [m3/sec] = Delta W[KgH2O/Kg air]*Mass Flow Air[Kg air]
!                                /RhoWater [kg H2O/m3 H2O]
!******************
      RhoWater = RhoH2O(EvapCond(EvapCoolNum)%OutletTemp)
      EvapVdot =  (EvapCond(EvapCoolNum)%OutletHumRat - EvapCond(EvapCoolNum)%InletHumRat) *  &
                  EvapCond(EvapCoolNum)%InletMassFlowRate/Rhowater
      DriftVdot = EvapVdot * EvapCond(EvapCoolNum)%DriftFraction

      IF (EvapCond(EvapCoolNum)%BlowDownRatio > 0.0D0) THEN
        BlowDownVdot =  EvapVdot / (EvapCond(EvapCoolNum)%BlowDownRatio - 1.0D0) - DriftVdot
        IF ( BlowDownVdot < 0.0D0 ) BlowDownVdot = 0.0D0
      ELSE
        BlowDownVdot = 0.0D0
      ENDIF

      EvapCond(EvapCoolNum)%EvapWaterConsumpRate =  EvapVdot + DriftVdot + BlowDownVdot

      ! A numerical check to keep from having very tiny negative water consumption values being reported
      If(EvapCond(EvapCoolNum)%EvapWaterConsumpRate < 0.0d0) EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0d0


  Else
   ! The evap cooler is not running and does not change conditions from inlet to outlet
    EvapCond(EvapCoolNum)%OutletTemp = EvapCond(EvapCoolNum)%InletTemp

    EvapCond(EvapCoolNum)%OuletWetBulbTemp = EvapCond(EvapCoolNum)%InletWetBulbTemp

    EvapCond(EvapCoolNum)%OutletHumRat = EvapCond(EvapCoolNum)%InletHumRat

    EvapCond(EvapCoolNum)%OutletEnthalpy = EvapCond(EvapCoolNum)%InletEnthalpy
    EvapCond(EvapCoolNum)%EvapCoolerPower  = 0.0D0
    EvapCond(EvapCoolNum)%EvapCoolerEnergy = 0.0D0

    EvapCond(EvapCoolNum)%EvapWaterConsumpRate = 0.0D0

  End IF
 ! all of the mass flowrates are not changed across the evap cooler
  EvapCond(EvapCoolNum)%OutletMassFlowRate         = EvapCond(EvapCoolNum)%InletMassFlowRate
  EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMaxAvail
  EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail = EvapCond(EvapCoolNum)%InletMassFlowRateMinAvail

  ! the pressure is not changed across the evap cooler
  EvapCond(EvapCoolNum)%OutletPressure = EvapCond(EvapCoolNum)%InletPressure

  RETURN

END SUBROUTINE CalcDirectResearchSpecialEvapCooler


! End Algorithm Section of the Module
! *****************************************************************************

! Beginning of Update subroutines for the EvapCooler Module
! *****************************************************************************

SUBROUTINE UpdateEvapCooler(EvapCoolNum)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   October 2000
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  Use DataWater
  USE DataContaminantBalance, ONLY: Contaminant

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  Integer, Intent(IN) :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  Integer             :: OutletNode
  Integer             :: InletNode
  REAL(r64)           :: AvailWaterRate = 0.0d0

   OutletNode = EvapCond(EvapCoolNum)%OutletNode
   InletNode  = EvapCond(EvapCoolNum)%InletNode

   ! Set the outlet air nodes of the EvapCooler
   Node(OutletNode)%MassFlowRate  = EvapCond(EvapCoolNum)%OutletMassFlowRate
   Node(OutletNode)%MassFlowRateMaxAvail  = EvapCond(EvapCoolNum)%OutletMassFlowRateMaxAvail
   Node(OutletNode)%MassFlowRateMinAvail  = EvapCond(EvapCoolNum)%OutletMassFlowRateMinAvail
   Node(OutletNode)%Temp          = EvapCond(EvapCoolNum)%OutletTemp
   Node(OutletNode)%HumRat        = EvapCond(EvapCoolNum)%OutletHumRat
   Node(OutletNode)%Enthalpy      = EvapCond(EvapCoolNum)%OutletEnthalpy
   Node(OutletNode)%Press         = EvapCond(EvapCoolNum)%OutletPressure
   ! Set the outlet nodes for properties that just pass through & not used
   Node(OutletNode)%Quality         = Node(InletNode)%Quality

    ! Set the demand request for supply water from water storage tank (if needed)
    If (EvapCond(EvapCoolNum)%EvapWaterSupplyMode == WaterSupplyFromTank) Then
      WaterStorage(EvapCond(EvapCoolNum)%EvapWaterSupTankID)%VdotRequestDemand(EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID) &
       = EvapCond(EvapCoolNum)%EvapWaterConsumpRate
    endif

   !check if should be starved by restricted flow from tank
    IF (EvapCond(EvapCoolNum)%EvapWaterSupplyMode == WaterSupplyFromTank) THEN
      AvailWaterRate = &
      WaterStorage(EvapCond(EvapCoolNum)%EvapWaterSupTankID)%VdotAvailDemand(EvapCond(EvapCoolNum)%EvapWaterTankDemandARRID)
      IF (AvailWaterRate < EvapCond(EvapCoolNum)%EvapWaterConsumpRate) THEN
        EvapCond(EvapCoolNum)%EvapWaterStarvMakupRate = EvapCond(EvapCoolNum)%EvapWaterConsumpRate - AvailWaterRate
        EvapCond(EvapCoolNum)%EvapWaterConsumpRate = AvailWaterRate
      ELSE
        EvapCond(EvapCoolNum)%EvapWaterStarvMakupRate = 0.d0
      ENDIF
    ENDIF

  IF (Contaminant%CO2Simulation) Then
    Node(OutletNode)%CO2 = Node(InletNode)%CO2
  End If

  IF (Contaminant%GenericContamSimulation) Then
    Node(OutletNode)%GenContam = Node(InletNode)%GenContam
  End If

  RETURN
END Subroutine UpdateEvapCooler


!        End of Update subroutines for the EvapCooler Module
! *****************************************************************************


! Beginning of Reporting subroutines for the EvapCooler Module
! *****************************************************************************

SUBROUTINE ReportEvapCooler(EvapCoolNum)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard J. Liesen
          !       DATE WRITTEN   Oct 2000
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine needs a description.

          ! METHODOLOGY EMPLOYED:
          ! Needs description, as appropriate.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  Use DataHVACGlobals, ONLY: TimeStepSys

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  Integer, Intent(IN) :: EvapCoolNum

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
          ! na
 ! report the Evap Cooler energy from this component
   EvapCond(EvapCoolNum)%EvapCoolerPower= EvapCond(EvapCoolNum)%EvapCoolerPower
   EvapCond(EvapCoolNum)%EvapCoolerEnergy= EvapCond(EvapCoolNum)%EvapCoolerPower*TimeStepSys*SecInHour

   ! Report Water comsumption in cubic meters per timestep
   EvapCond(EvapCoolNum)%EvapWaterConsump  = EvapCond(EvapCoolNum)%EvapWaterConsumpRate*TimeStepSys*SecInHour
   EvapCond(EvapCoolNum)%EvapWaterStarvMakup = EvapCond(EvapCoolNum)%EvapWaterStarvMakupRate *TimeStepSys*SecInHour


  RETURN
END Subroutine ReportEvapCooler

!***************
!Begin routines for zone HVAC Evaporative cooler unit
!_______________________________________________________________________________________________________________________
!***************

SUBROUTINE SimZoneEvaporativeCoolerUnit(CompName,ZoneNum,SensibleOutputProvided,LatentOutputProvided,CompIndex)


          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! public simulation routine for managing zone hvac evaporative cooler unit

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE InputProcessor, ONLY : FindItemInList
  USE General, ONLY : TrimSigDigits

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  CHARACTER(len=*), INTENT    (IN) :: CompName            ! name of the packaged terminal heat pump
  INTEGER,          INTENT    (IN) :: ZoneNum             ! number of zone being served
  REAL(r64),        INTENT   (OUT) :: SensibleOutputProvided   ! sensible capacity delivered to zone
  REAL(r64),        INTENT   (OUT) :: LatentOutputProvided   ! Latent add/removal  (kg/s), dehumid = negative
  INTEGER,          INTENT (INOUT) :: CompIndex           ! index to zone hvac unit

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER    :: CompNum

  IF (GetInputZoneEvapUnit) THEN
    CALL GetInputZoneEvaporativeCoolerUnit
    GetInputZoneEvapUnit=.FALSE.
  END IF

  ! Find the correct Equipment
  IF (CompIndex == 0) THEN
    CompNum = FindItemInList(CompName, ZoneEvapUnit%Name, NumZoneEvapUnits)
    IF (CompNum == 0) THEN
      CALL ShowFatalError('SimZoneEvaporativeCoolerUnit: Zone evaporative cooler unit not found.')
    ENDIF
    CompIndex = CompNum
  ELSE
    CompNum = CompIndex
    IF (CompNum < 1 .OR. CompNum > NumZoneEvapUnits) THEN
      CALL ShowFatalError('SimZoneEvaporativeCoolerUnit: Invalid CompIndex passed='//  &
                           TRIM(TrimSigDigits(CompNum))// &
                           ', Number of units ='//TRIM(TrimSigDigits(NumZoneEvapUnits))// &
                           ', Entered Unit name = '//TRIM(CompName) )
    ENDIF
    IF(CheckZoneEvapUnitName(CompNum)) THEN
      IF (CompName /= ZoneEvapUnit(CompNum)%Name) THEN
        CALL ShowFatalError('SimZoneEvaporativeCoolerUnit: Invalid CompIndex passed='//  &
                           TRIM(TrimSigDigits(CompNum))// &
                           ', Unit name='//TRIM(CompName)//', stored unit name for that index='// &
                           TRIM(ZoneEvapUnit(CompNum)%Name) )
      ENDIF
      CheckZoneEvapUnitName(CompNum) = .FALSE.
    ENDIF
  ENDIF

  CALL InitZoneEvaporativeCoolerUnit(CompNum, ZoneNum)

  CALL CalcZoneEvaporativeCoolerUnit(CompNum, ZoneNum, SensibleOutputProvided, LatentOutputProvided )

  CALL ReportZoneEvaporativeCoolerUnit(CompNum)

  RETURN

END SUBROUTINE SimZoneEvaporativeCoolerUnit

SUBROUTINE GetInputZoneEvaporativeCoolerUnit

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! get input for zone evap cooler unit

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE Fans,              ONLY: GetFanType, GetFanIndex, GetFanVolFlow, GetFanInletNode, GetFanOutletNode, GetFanAvailSchPtr
  USE General,           ONLY: TrimSigDigits
  USE InputProcessor,    ONLY: GetNumObjectsFound, GetObjectDefMaxArgs, GetObjectItem, &
                                   FindItemInList, VerifyName
  USE NodeInputManager,  ONLY: GetOnlySingleNode
  USE DataHVACGlobals,   ONLY: ZoneComp, FanType_SimpleConstVolume, FanType_SimpleOnOff
  USE DataZoneEquipment, ONLY: ZoneEvaporativeCoolerUnit_Num
  USE BranchNodeConnections, ONLY: SetUpCompSets

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
  CHARACTER(len=*), PARAMETER :: RoutineName='GetInputZoneEvaporativeCoolerUnit: '

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  CHARACTER(len=MaxNameLength)   :: CurrentModuleObject ! Object type for getting and error messages
  CHARACTER(len=MaxNameLength), &
                   ALLOCATABLE, DIMENSION(:) :: Alphas     ! Alpha items for object
  REAL(r64), ALLOCATABLE, DIMENSION(:)       :: Numbers    ! Numeric items for object
  CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cAlphaFields   ! Alpha field names
  CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cNumericFields ! Numeric field names
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: lAlphaBlanks     ! Logical array, alpha field input BLANK = .true.
  LOGICAL, ALLOCATABLE, DIMENSION(:) :: lNumericBlanks   ! Logical array, numeric field input BLANK = .true.
  INTEGER                        :: NumAlphas  ! Number of Alphas for each GetObjectItem call
  INTEGER                        :: NumNumbers ! Number of Numbers for each GetObjectItem call
  INTEGER                        :: MaxAlphas     ! Maximum number of alpha fields in all objects
  INTEGER                        :: MaxNumbers    ! Maximum number of numeric fields in all objects
  INTEGER                        :: NumFields     ! Total number of fields in object
  INTEGER                        :: IOStatus   ! Used in GetObjectItem
  LOGICAL                        :: ErrorsFound=.FALSE.  ! Set to true if errors in input, fatal at end of routine
  LOGICAL                        :: IsNotOK    ! Flag to verify name
  LOGICAL                        :: IsBlank    ! Flag for blank name
  LOGICAL                        :: ErrFlag
  REAL(r64)                      :: FanVolFlow
  INTEGER                        :: UnitLoop

  IF (GetInputEvapComponentsFlag) THEN
    CALL GetEvapInput
    GetInputEvapComponentsFlag=.false.
  End If

  MaxNumbers = 0
  MaxAlphas  = 0

  CurrentModuleObject = 'ZoneHVAC:EvaporativeCoolerUnit'
  NumZoneEvapUnits    = GetNumObjectsFound(CurrentModuleObject)
  CALL GetObjectDefMaxArgs(CurrentModuleObject,NumFields,NumAlphas,NumNumbers)
  MaxNumbers=MAX(MaxNumbers,NumNumbers)
  MaxAlphas=MAX(MaxAlphas,NumAlphas)
  ALLOCATE(Alphas(MaxAlphas))
  Alphas=' '
  ALLOCATE(Numbers(MaxNumbers))
  Numbers=0.0d0
  ALLOCATE(cAlphaFields(MaxAlphas))
  cAlphaFields=' '
  ALLOCATE(cNumericFields(MaxNumbers))
  cNumericFields=' '
  ALLOCATE(lAlphaBlanks(MaxAlphas))
  lAlphaBlanks=.TRUE.
  ALLOCATE(lNumericBlanks(MaxNumbers))
  lNumericBlanks=.TRUE.

  IF (NumZoneEvapUnits > 0) THEN
    ALLOCATE (CheckZoneEvapUnitName(NumZoneEvapUnits))
    CheckZoneEvapUnitName = .TRUE.
    ALLOCATE (ZoneEvapUnit(NumZoneEvapUnits))

    DO UnitLoop = 1, NumZoneEvapUnits
      CALL GetObjectItem(CurrentModuleObject,UnitLoop,Alphas,NumAlphas,Numbers,NumNumbers,IOStatus, &
                       NumBlank=lNumericBlanks,AlphaBlank=lAlphaBlanks, &
                       AlphaFieldNames=cAlphaFields,NumericFieldNames=cNumericFields)
      IsNotOK=.FALSE.
      IsBlank=.FALSE.
      CALL VerifyName(Alphas(1),ZoneEvapUnit%Name,UnitLoop-1,IsNotOK,IsBlank,TRIM(CurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound=.TRUE.
        IF (IsBlank) Alphas(1)='xxxxx'
      ENDIF
      ZoneEvapUnit(UnitLoop)%Name = Alphas(1)
      IF (lAlphaBlanks(2)) THEN
        ZoneEvapUnit(UnitLoop)%AvailSchedIndex = ScheduleAlwaysOn
      ELSE
        ZoneEvapUnit(UnitLoop)%AvailSchedIndex  = GetScheduleIndex(Alphas(2))  ! convert schedule name to pointer (index number)
        IF (ZoneEvapUnit(UnitLoop)%AvailSchedIndex  .EQ. 0) THEN
          CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
          CALL ShowContinueError('invalid-not found '//TRIM(cAlphaFields(2))//'="'//TRIM(Alphas(2))//'".')
          ErrorsFound=.TRUE.
        ENDIF
      END IF

      IF (.NOT. lAlphaBlanks(3)) THEN
        ZoneEvapUnit(UnitLoop)%AvailManagerListName = Alphas(3)
        ZoneComp(ZoneEvaporativeCoolerUnit_Num)%ZoneCompAvailMgrs(UnitLoop)%AvailManagerListName = Alphas(3)
      ENDIF

      ZoneEvapUnit(UnitLoop)%OAInletNodeNum = &
               GetOnlySingleNode(Alphas(4),ErrorsFound,TRIM(CurrentModuleObject),Alphas(1), &
                            NodeType_Air,NodeConnectionType_OutsideAir,1,ObjectIsParent)

      ZoneEvapUnit(UnitLoop)%UnitOutletNodeNum = &
               GetOnlySingleNode(Alphas(5),ErrorsFound,TRIM(CurrentModuleObject),Alphas(1), &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsParent)

      IF (.NOT. lAlphaBlanks(6)) THEN
        ZoneEvapUnit(UnitLoop)%UnitReliefNodeNum = &
               GetOnlySingleNode(Alphas(6),ErrorsFound,TRIM(CurrentModuleObject),Alphas(1), &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsParent)
      ENDIF

      ZoneEvapUnit(UnitLoop)%FanObjectClassName = Alphas(7)
      ZoneEvapUnit(UnitLoop)%FanName            = Alphas(8)
      ErrFlag = .FALSE.
      CALL GetFanType(ZoneEvapUnit(UnitLoop)%FanName,ZoneEvapUnit(UnitLoop)%FanType_Num,ErrFlag,&
                     CurrentModuleObject,ZoneEvapUnit(UnitLoop)%Name)
      FanVolFlow = 0.d0
      IF(ErrFlag)THEN
        CALL ShowContinueError('specified in '//TRIM(CurrentModuleObject)//' = '//TRIM(ZoneEvapUnit(UnitLoop)%Name))
        ErrorsFound = .TRUE.
      ELSE
        CALL GetFanIndex(ZoneEvapUnit(UnitLoop)%FanName,ZoneEvapUnit(UnitLoop)%FanIndex,ErrFlag,CurrentModuleObject)
        ZoneEvapUnit(UnitLoop)%FanInletNodeNum = &
            GetFanInletNode(ZoneEvapUnit(UnitLoop)%FanObjectClassName,ZoneEvapUnit(UnitLoop)%FanName,ErrFlag)
        ZoneEvapUnit(UnitLoop)%FanOutletNodeNum = &
            GetFanOutletNode(ZoneEvapUnit(UnitLoop)%FanObjectClassName,ZoneEvapUnit(UnitLoop)%FanName,ErrFlag)
        CALL GetFanVolFlow(ZoneEvapUnit(UnitLoop)%FanIndex,FanVolFlow)
        ZoneEvapUnit(UnitLoop)%ActualFanVolFlowRate = FanVolFlow
        ! Get the fan's availability schedule
        ZoneEvapUnit(UnitLoop)%FanAvailSchedPtr = GetFanAvailSchPtr(ZoneEvapUnit(UnitLoop)%FanObjectClassName, &
                                                                      ZoneEvapUnit(UnitLoop)%FanName,ErrFlag)
        IF (ErrFlag) THEN
          CALL ShowContinueError('...specified in '//TRIM(CurrentModuleObject)//' = '//TRIM(ZoneEvapUnit(UnitLoop)%Name))
          ErrorsFound=.TRUE.
        ENDIF
      ENDIF

      ZoneEvapUnit(UnitLoop)%DesignAirVolumeFlowRate = Numbers(1)

      SELECT CASE (TRIM(Alphas(9)))
      CASE ( 'BLOWTHROUGH' )
        ZoneEvapUnit(UnitLoop)%FanLocation = BlowThruFan
      CASE ( 'DRAWTHROUGH' )
        ZoneEvapUnit(UnitLoop)%FanLocation = DrawThruFan
      CASE DEFAULT
        CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
        CALL ShowContinueError('invalid choice found '//TRIM(cAlphaFields(9))//'="'//TRIM(Alphas(9))//'".')
        ErrorsFound=.TRUE.
      END SELECT

      SELECT CASE ( TRIM(Alphas(10)) )
      CASE ( 'ZONETEMPERATUREDEADBANDONOFFCYCLING' )
        ZoneEvapUnit(UnitLoop)%ControlSchemeType = ZoneTemperatureDeadbandOnOffCycling
      CASE ( 'ZONECOOLINGLOADONOFFCYCLING' )
        ZoneEvapUnit(UnitLoop)%ControlSchemeType = ZoneCoolingLoadOnOffCycling
      CASE ( 'ZONECOOLINGLOADVARIABLESPEEDFAN' )
        ZoneEvapUnit(UnitLoop)%ControlSchemeType = ZoneCoolingLoadVariableSpeedFan
      CASE DEFAULT
        CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
        CALL ShowContinueError('invalid choice found '//TRIM(cAlphaFields(10))//'="'//TRIM(Alphas(10))//'".')
        ErrorsFound=.TRUE.
      END SELECT

      ZoneEvapUnit(UnitLoop)%ThrottlingRange = Numbers(2)
      ZoneEvapUnit(UnitLoop)%ThresholdCoolingLoad = Numbers(3)

      SELECT CASE (TRIM(Alphas(11)))

      CASE ( 'EVAPORATIVECOOLER:DIRECT:CELDEKPAD')
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_ObjectClassName = 'EvaporativeCooler:Direct:CelDekPad'
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_Type_Num = iEvapCoolerDirectCELDEKPAD
      CASE ( 'EVAPORATIVECOOLER:DIRECT:RESEARCHSPECIAL')
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_ObjectClassName = 'EvaporativeCooler:Direct:ResearchSpecial'
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_Type_Num = iEvapCoolerDirectResearchSpecial
      CASE ( 'EVAPORATIVECOOLER:INDIRECT:CELDEKPAD' )
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_ObjectClassName = 'EvaporativeCooler:Indirect:CelDekPad'
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_Type_Num = iEvapCoolerInDirectCELDEKPAD
      CASE ( 'EVAPORATIVECOOLER:INDIRECT:WETCOIL' )
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_ObjectClassName = 'EvaporativeCooler:Indirect:WetCoil'
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_Type_Num = iEvapCoolerInDirectWETCOIL
      CASE ( 'EVAPORATIVECOOLER:INDIRECT:RESEARCHSPECIAL')
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_ObjectClassName = 'EvaporativeCooler:Indirect:ResearchSpecial'
        ZoneEvapUnit(UnitLoop)%EvapCooler_1_Type_Num = iEvapCoolerInDirectRDDSpecial
      CASE DEFAULT
        CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
        CALL ShowContinueError('invalid choice found '//TRIM(cAlphaFields(11))//'="'//TRIM(Alphas(11))//'".')
        ErrorsFound=.TRUE.
      END SELECT

      ZoneEvapUnit(UnitLoop)%EvapCooler_1_Name  =  Alphas(12)
      ZoneEvapUnit(UnitLoop)%EvapCooler_1_Index =  FindItemInList(Alphas(12), EvapCond%EvapCoolerName, NumEvapCool)
      IF (ZoneEvapUnit(UnitLoop)%EvapCooler_1_Index == 0 ) THEN
        CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
        CALL ShowContinueError('invalid, not found '//TRIM(cAlphaFields(12))//'="'//TRIM(Alphas(12))//'".')
        ErrorsFound=.TRUE.
      ENDIF

      IF (.NOT. lAlphaBlanks(13)) THEN
        SELECT CASE (TRIM(Alphas(13)))

        CASE ( 'EVAPORATIVECOOLER:DIRECT:CELDEKPAD')
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_ObjectClassName = 'EvaporativeCooler:Direct:CelDekPad'
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Type_Num = iEvapCoolerDirectCELDEKPAD
        CASE ( 'EVAPORATIVECOOLER:DIRECT:RESEARCHSPECIAL')
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_ObjectClassName = 'EvaporativeCooler:Direct:ResearchSpecial'
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Type_Num = iEvapCoolerDirectResearchSpecial
        CASE ( 'EVAPORATIVECOOLER:INDIRECT:CELDEKPAD' )
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_ObjectClassName = 'EvaporativeCooler:Indirect:CelDekPad'
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Type_Num = iEvapCoolerInDirectCELDEKPAD
        CASE ( 'EVAPORATIVECOOLER:INDIRECT:WETCOIL' )
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_ObjectClassName = 'EvaporativeCooler:Indirect:WetCoil'
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Type_Num = iEvapCoolerInDirectWETCOIL
        CASE ( 'EVAPORATIVECOOLER:INDIRECT:RESEARCHSPECIAL')
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_ObjectClassName = 'EvaporativeCooler:Indirect:ResearchSpecial'
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Type_Num = iEvapCoolerInDirectRDDSpecial
        CASE DEFAULT
          CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
          CALL ShowContinueError('invalid choice found '//TRIM(cAlphaFields(13))//'="'//TRIM(Alphas(13))//'".')
          ErrorsFound=.TRUE.
        END SELECT
        IF (.NOT. lAlphaBlanks(14)) THEN
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Name  =  Alphas(14)
          ZoneEvapUnit(UnitLoop)%EvapCooler_2_Index =  FindItemInList(Alphas(14), EvapCond%EvapCoolerName, NumEvapCool)
          IF (ZoneEvapUnit(UnitLoop)%EvapCooler_2_Index == 0 ) THEN
            CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
            CALL ShowContinueError('invalid, not found '//TRIM(cAlphaFields(14))//'="'//TRIM(Alphas(14))//'".')
            ErrorsFound=.TRUE.
          ENDIF
        ELSE
          CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
          CALL ShowContinueError('missing input for '//TRIM(cAlphaFields(14)))
          ErrorsFound=.TRUE.
        ENDIF
      ENDIF

      !Add fan to component sets array
      CALL SetUpCompSets(CurrentModuleObject, ZoneEvapUnit(UnitLoop)%Name, &
                          ZoneEvapUnit(UnitLoop)%FanObjectClassName, ZoneEvapUnit(UnitLoop)%FanName, &
                          NodeID(ZoneEvapUnit(UnitLoop)%FanInletNodeNum), NodeID(ZoneEvapUnit(UnitLoop)%FanOutletNodeNum ) )

      !Add first evap cooler to component sets array
      CALL SetUpCompSets(CurrentModuleObject, ZoneEvapUnit(UnitLoop)%Name, &
                          ZoneEvapUnit(UnitLoop)%EvapCooler_1_ObjectClassName, ZoneEvapUnit(UnitLoop)%EvapCooler_1_Name, &
                          NodeID(EvapCond(ZoneEvapUnit(UnitLoop)%EvapCooler_1_Index)%InletNode), &
                          NodeID(EvapCond(ZoneEvapUnit(UnitLoop)%EvapCooler_1_Index)%OutletNode ) )

      IF (ZoneEvapUnit(UnitLoop)%EvapCooler_2_Index > 0) THEN
        !Add second evap cooler to component sets array
        CALL SetUpCompSets(CurrentModuleObject, ZoneEvapUnit(UnitLoop)%Name, &
                            ZoneEvapUnit(UnitLoop)%EvapCooler_2_ObjectClassName, ZoneEvapUnit(UnitLoop)%EvapCooler_2_Name, &
                            NodeID(EvapCond(ZoneEvapUnit(UnitLoop)%EvapCooler_2_Index)%InletNode), &
                            NodeID(EvapCond(ZoneEvapUnit(UnitLoop)%EvapCooler_2_Index)%OutletNode ) )

      ENDIF

      ! check that fan type is consistent with control method
      IF (ZoneEvapUnit(UnitLoop)%ControlSchemeType == ZoneCoolingLoadVariableSpeedFan) THEN ! must have a VS fan type
        IF (ZoneEvapUnit(UnitLoop)%FanType_Num == FanType_SimpleConstVolume) THEN
          CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
          CALL ShowContinueError('Fan:ConstantVolume is not consistent with control method ZoneCoolingLoadVariableSpeedFan.')
          CALL ShowContinueError('Change to a variable speed fan object type')
          ErrorsFound=.TRUE.
        ELSEIF (ZoneEvapUnit(UnitLoop)%FanType_Num == FanType_SimpleOnOff ) THEN
          CALL ShowSevereError(TRIM(CurrentModuleObject)//'="'//TRIM(ZoneEvapUnit(UnitLoop)%Name)//'" invalid data.')
          CALL ShowContinueError('Fan:OnOff is not consistent with control method ZoneCoolingLoadVariableSpeedFan.')
          CALL ShowContinueError('Change to a variable speed fan object type')
          ErrorsFound=.TRUE.
        ENDIF

      ENDIF

    ENDDO ! unit loop

  ENDIF


!***********************************************************************************


  DEALLOCATE(Alphas)
  DEALLOCATE(Numbers)
  DEALLOCATE(cAlphaFields)
  DEALLOCATE(cNumericFields)
  DEALLOCATE(lAlphaBlanks)
  DEALLOCATE(lNumericBlanks)

  IF (ErrorsFound) THEN
    CALL ShowFatalError(RoutineName//'Errors found in getting input.')
    CALL ShowContinueError('... Preceding condition causes termination.')
  END IF

  ! setup output variables
  DO UnitLoop = 1, NumZoneEvapUnits

    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Total Cooling Rate [W]', &
                              ZoneEvapUnit(UnitLoop)%UnitTotalCoolingRate, &
                             'System','Average', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Total Cooling Energy [J]', &
                              ZoneEvapUnit(UnitLoop)%UnitTotalCoolingEnergy, &
                             'System','Sum', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Sensible Cooling Rate [W]', &
                              ZoneEvapUnit(UnitLoop)%UnitSensibleCoolingRate, &
                             'System','Average', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Sensible Cooling Energy [J]', &
                              ZoneEvapUnit(UnitLoop)%UnitSensibleCoolingEnergy, &
                             'System','Sum', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Latent Heating Rate [W]', &
                              ZoneEvapUnit(UnitLoop)%UnitLatentHeatingRate, &
                             'System','Average', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Latent Heating Energy [J]', &
                              ZoneEvapUnit(UnitLoop)%UnitLatentHeatingEnergy, &
                             'System','Sum', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Latent Cooling Rate [W]', &
                              ZoneEvapUnit(UnitLoop)%UnitLatentCoolingRate, &
                             'System','Average', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Latent Cooling Energy [J]', &
                              ZoneEvapUnit(UnitLoop)%UnitLatentCoolingEnergy, &
                             'System','Sum', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Fan Speed Ratio []', &
                              ZoneEvapUnit(UnitLoop)%UnitFanSpeedRatio, &
                             'System','Average', ZoneEvapUnit(UnitLoop)%Name)
    CALL SetupOutputVariable('Zone Evaporative Cooler Unit Fan Availability Status []', &
                              ZoneEvapUnit(UnitLoop)%FanAvailStatus, &
                             'System','Average', ZoneEvapUnit(UnitLoop)%Name)
  ENDDO

  RETURN

END SUBROUTINE GetInputZoneEvaporativeCoolerUnit

SUBROUTINE InitZoneEvaporativeCoolerUnit(UnitNum, ZoneNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! <description>

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataGlobals,          ONLY: TimeStep, TimeStepZone, WarmupFlag, HourOfDay
  USE DataZoneEquipment,    ONLY: ZoneEquipInputsFilled,CheckZoneEquipmentList, ZoneEquipConfig
  USE DataHVACGlobals,      ONLY: ZoneComp, SysTimeElapsed
  USE DataSizing,           ONLY: Autosize
  USE DataEnvironment,      ONLY: StdRhoAir
  USE Fans,                 ONLY: GetFanVolFlow

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,          INTENT    (IN) :: UnitNum             ! unit number
  INTEGER,          INTENT    (IN) :: ZoneNum             ! number of zone being served

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  LOGICAL, SAVE                            :: MyOneTimeFlag = .TRUE. ! one time flag
  LOGICAL, ALLOCATABLE, SAVE, DIMENSION(:) :: MySizeFlag
  LOGICAL, ALLOCATABLE, SAVE, DIMENSION(:) :: MyEnvrnFlag
  LOGICAL, ALLOCATABLE, SAVE, DIMENSION(:) :: MyFanFlag
  LOGICAL  :: errFlag
  INTEGER :: Loop
  LOGICAL,SAVE        :: ZoneEquipmentListChecked = .FALSE.  ! True after the Zone Equipment List has been checked for items
  REAL(r64) :: TimeElapsed

  IF (MyOneTimeFlag) THEN
    ALLOCATE(MySizeFlag(NumZoneEvapUnits))
    MySizeFlag = .TRUE.
    ALLOCATE(MyEnvrnFlag(NumZoneEvapUnits))
    MyEnvrnFlag = .TRUE.
    ALLOCATE(MyFanFlag(NumZoneEvapUnits))
    MyFanFlag = .TRUE.
    MyOneTimeFlag = .FALSE.
  END IF

  IF (ALLOCATED(ZoneComp)) THEN
    ZoneComp(ZoneEvapUnit(UnitNum)%ZoneEquipType)%ZoneCompAvailMgrs(UnitNum)%ZoneNum = ZoneNum
    ZoneEvapUnit(UnitNum)%FanAvailStatus = ZoneComp(ZoneEvapUnit(UnitNum)%ZoneEquipType)%ZoneCompAvailMgrs(UnitNum)%AvailStatus
  ENDIF

  IF (.NOT. ZoneEquipmentListChecked .AND. ZoneEquipInputsFilled) THEN
    ZoneEquipmentListChecked=.TRUE.
    DO Loop=1,NumZoneEvapUnits
      IF (CheckZoneEquipmentList('ZoneHVAC:EvaporativeCoolerUnit',ZoneEvapUnit(Loop)%Name)) THEN
        ZoneEvapUnit(Loop)%ZoneNodeNum = ZoneEquipConfig(ZoneNum)%ZoneNode
      ELSE
        CALL ShowSevereError('InitZoneEvaporativeCoolerUnit: ZoneHVAC:EvaporativeCoolerUnit = '  &
         // TRIM(ZoneEvapUnit(Loop)%Name)//  &
           ', is not on any ZoneHVAC:EquipmentList.  It will not be simulated.')
      ENDIF
    ENDDO
  ENDIF

  IF ( .NOT. SysSizingCalc .AND. MySizeFlag(UnitNum) ) THEN
    CALL SizeZoneEvaporativeCoolerUnit(UnitNum)
    MySizeFlag(UnitNum) = .FALSE.
  END IF

  IF (MyFanFlag(UnitNum)) THEN
    IF (ZoneEvapUnit(UnitNum)%ActualFanVolFlowRate /= Autosize) THEN
      IF (ZoneEvapUnit(UnitNum)%ActualFanVolFlowRate > 0.d0) THEN
        ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio = ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate &
                                              / ZoneEvapUnit(UnitNum)%ActualFanVolFlowRate
      ENDIF
      MyFanFlag(UnitNum) = .FALSE.
    ELSE
      CALL GetFanVolFlow(ZoneEvapUnit(UnitNum)%FanIndex,ZoneEvapUnit(UnitNum)%ActualFanVolFlowRate)
    ENDIF
  ENDIF

  IF (ZoneEvapUnit(UnitNum)%FanAvailSchedPtr > 0 ) THEN
    ! include fan is not available, then unit is not available
    IF ((GetCurrentScheduleValue(ZoneEvapUnit(UnitNum)%FanAvailSchedPtr)  > 0.d0 )     &
       .AND. (GetCurrentScheduleValue(ZoneEvapUnit(UnitNum)%AvailSchedIndex)  > 0.d0 ) ) THEN
      ! .AND. ( ZoneComp(ZoneEvapUnit(UnitNum)%ZoneEquipType)%ZoneCompAvailMgrs(UnitNum)%AvailStatus) ) THEN
      ZoneEvapUnit(UnitNum)%UnitIsAvailable = .TRUE.
    ELSE
      ZoneEvapUnit(UnitNum)%UnitIsAvailable = .FALSE.
    ENDIF
  ELSE
    IF (GetCurrentScheduleValue(ZoneEvapUnit(UnitNum)%AvailSchedIndex)  > 0.d0 )  THEN
       !.AND. ( ZoneComp(ZoneEvapUnit(UnitNum)%ZoneEquipType)%ZoneCompAvailMgrs(UnitNum)%AvailStatus) )THEN
      ZoneEvapUnit(UnitNum)%UnitIsAvailable = .TRUE.
    ELSE
      ZoneEvapUnit(UnitNum)%UnitIsAvailable = .FALSE.
    ENDIF
  ENDIF

  IF (GetCurrentScheduleValue(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%SchedPtr) > 0.d0 ) THEN
    ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus = .TRUE.
  ELSE
    ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus = .FALSE.
  ENDIF

  IF ( ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0 ) THEN
    IF (GetCurrentScheduleValue(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%SchedPtr) > 0.d0 ) THEN
      ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus = .TRUE.
    ELSE
      ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus = .FALSE.
    ENDIF
  ENDIF
! Do the Begin Environment initializations
  IF (BeginEnvrnFlag .and. MyEnvrnFlag(UnitNum)) THEN

    ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate = StdRhoAir * ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate
    Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMax      = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate
    Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMin      = 0.d0
    Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMinAvail = 0.d0

    Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMax      = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate
    Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMin      = 0.d0
    Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMinAvail = 0.d0

    IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
      Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMax      = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMin      = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMinAvail = 0.d0
    ENDIF
    ZoneEvapUnit(UnitNum)%WasOnLastTimestep   = .FALSE.
    ZoneEvapUnit(UnitNum)%IsOnThisTimestep    = .FALSE.
    ZoneEvapUnit(UnitNum)%FanSpeedRatio             = 0.d0
    ZoneEvapUnit(UnitNum)%UnitFanSpeedRatio         = 0.d0
    ZoneEvapUnit(UnitNum)%UnitTotalCoolingRate      = 0.d0
    ZoneEvapUnit(UnitNum)%UnitTotalCoolingEnergy    = 0.d0
    ZoneEvapUnit(UnitNum)%UnitSensibleCoolingRate   = 0.d0
    ZoneEvapUnit(UnitNum)%UnitSensibleCoolingEnergy = 0.d0
    ZoneEvapUnit(UnitNum)%UnitLatentHeatingRate     = 0.d0
    ZoneEvapUnit(UnitNum)%UnitLatentHeatingEnergy   = 0.d0
    ZoneEvapUnit(UnitNum)%UnitLatentCoolingRate     = 0.d0
    ZoneEvapUnit(UnitNum)%UnitLatentCoolingEnergy   = 0.d0
    ZoneEvapUnit(UnitNum)%FanAvailStatus            = 0.d0

    ! place default cold setpoints on control nodes of select evap coolers
    IF ((ZoneEvapUnit(UnitNum)%EvapCooler_1_Type_Num == iEvapCoolerDirectResearchSpecial) &
        .OR. (ZoneEvapUnit(UnitNum)%EvapCooler_1_Type_Num == iEvapCoolerInDirectRDDSpecial)) THEN
      IF ( EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%EvapControlNodeNum > 0 ) THEN
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%EvapControlNodeNum)%TempSetPoint = -20.0d0
      ENDIF
    ENDIF
    IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Type_Num == iEvapCoolerDirectResearchSpecial) &
        .OR. (ZoneEvapUnit(UnitNum)%EvapCooler_2_Type_Num == iEvapCoolerInDirectRDDSpecial)) THEN
      IF ( EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%EvapControlNodeNum > 0 ) THEN
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%EvapControlNodeNum)%TempSetPoint = -20.0d0
      ENDIF
    ENDIF

    MyEnvrnFlag(UnitNum) = .FALSE.
  ENDIF
  IF (.NOT. BeginEnvrnFlag) THEN
    MyEnvrnFlag(UnitNum) = .TRUE.
  END IF


  TimeElapsed = HourOfDay + TimeStep * TimeStepZone + SysTimeElapsed
  IF (ZoneEvapUnit(UnitNum)%TimeElapsed /= TimeElapsed) THEN
    ZoneEvapUnit(UnitNum)%WasOnLastTimestep = ZoneEvapUnit(UnitNum)%IsOnThisTimestep

    ZoneEvapUnit(UnitNum)%TimeElapsed = TimeElapsed
  ENDIF

  RETURN

END SUBROUTINE InitZoneEvaporativeCoolerUnit

SUBROUTINE SizeZoneEvaporativeCoolerUnit(UnitNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! <description>

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE ReportSizingManager, ONLY: ReportSizingOutput
  USE DataSizing,          ONLY: Autosize, CurZoneEqNum, FinalZoneSizing
  USE DataHVACGlobals,     ONLY: SmallAirVolFlow

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,          INTENT    (IN) :: UnitNum             ! unit number

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
          ! na

  IF (ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate == AutoSize) THEN

    IF (CurZoneEqNum > 0) THEN
      CALL CheckZoneSizing('ZoneHVAC:EvaporativeCoolerUnit',ZoneEvapUnit(UnitNum)%Name)
      ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate = FinalZoneSizing(CurZoneEqNum)%DesCoolVolFlow
      IF (ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate < SmallAirVolFlow) THEN
        ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate = 0.d0
      ENDIF
      CALL ReportSizingOutput('ZoneHVAC:EvaporativeCoolerUnit', ZoneEvapUnit(UnitNum)%Name, &
                              'Design Supply Air Flow Rate [m3/s]', ZoneEvapUnit(UnitNum)%DesignAirVolumeFlowRate)
    ENDIF

  ENDIF

  RETURN

END SUBROUTINE SizeZoneEvaporativeCoolerUnit

SUBROUTINE CalcZoneEvaporativeCoolerUnit(UnitNum, ZoneNum, SensibleOutputProvided, LatentOutputProvided )

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! <description>

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHVACGlobals,       ONLY: SmallLoad
  USE DataZoneEnergyDemands, ONLY: ZoneSysEnergyDemand
  USE DataHVACGlobals,       ONLY: ZoneCompTurnFansOn, ZoneCompTurnFansOff
  USE Fans,                  ONLY: SimulateFanComponents
  USE DataHeatBalFanSys,     ONLY: ZoneThermostatSetPointHi

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,          INTENT    (IN) :: UnitNum             ! unit number
  INTEGER,          INTENT    (IN) :: ZoneNum             ! number of zone being served
  REAL(r64),        INTENT   (OUT) :: SensibleOutputProvided   ! sensible capacity delivered to zone
  REAL(r64),        INTENT   (OUT) :: LatentOutputProvided   ! Latent add/removal  (kg/s), dehumid = negative
          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: ZoneCoolingLoad
  REAL(r64) :: MinHumRat
  REAL(r64) :: CoolingLoadThreashold
  REAL(r64) :: ZoneTemp
  REAL(r64) :: CoolSetLowThrottle
  REAL(r64) :: CoolSetHiThrottle

  SELECT CASE (ZoneEvapUnit(UnitNum)%ControlSchemeType)

  CASE (ZoneTemperatureDeadbandOnOffCycling)
    ZoneTemp = Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum)%Temp
    CoolSetLowThrottle  = ZoneThermostatSetPointHi(ZoneNum) - (0.5d0 * ZoneEvapUnit(UnitNum)%ThrottlingRange)
    CoolSetHiThrottle   = ZoneThermostatSetPointHi(ZoneNum) + (0.5d0 * ZoneEvapUnit(UnitNum)%ThrottlingRange)

    IF ((ZoneTemp < CoolSetLowThrottle) .OR. .NOT. ZoneEvapUnit(UnitNum)%UnitIsAvailable) THEN
      ZoneEvapUnit(UnitNum)%IsOnThisTimestep = .FALSE.
    ELSEIF (ZoneTemp > CoolSetHiThrottle) THEN
      ZoneEvapUnit(UnitNum)%IsOnThisTimestep = .TRUE.
    ELSE
      IF (ZoneEvapUnit(UnitNum)%WasOnLastTimestep) THEN
        ZoneEvapUnit(UnitNum)%IsOnThisTimestep = .TRUE.
      ELSE
        ZoneEvapUnit(UnitNum)%IsOnThisTimestep = .FALSE.
      ENDIF
    ENDIF

    IF (ZoneEvapUnit(UnitNum)%IsOnThisTimestep) THEN

      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate &
                                                                * ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail  = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail =  &
                           Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate

      IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = &
                                                                    Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
        Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = &
                                 Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,&
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
      ENDIF

      IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,&
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF
    ELSE ! not running
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanInletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanInletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = 0.d0

      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%InletNode)%MassFlowRate = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%InletNode)%MassFlowRateMaxAvail = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%OutletNode)%MassFlowRate = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%OutletNode)%MassFlowRateMaxAvail = 0.d0

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) THEN
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%InletNode)%MassFlowRate = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%InletNode)%MassFlowRateMaxAvail = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%OutletNode)%MassFlowRate = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%OutletNode)%MassFlowRateMaxAvail = 0.d0
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = 0.d0
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = 0.d0
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
      ENDIF

      IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF
    ENDIF

  CASE (ZoneCoolingLoadOnOffCycling)

    ! get zone loads
    ZoneCoolingLoad = ZoneSysEnergyDemand(ZoneNum)%RemainingOutputReqToCoolSP
    CoolingLoadThreashold = -1.0d0 * ZoneEvapUnit(UnitNum)%ThresholdCoolingLoad

    IF ((ZoneCoolingLoad < CoolingLoadThreashold) .AND. ZoneEvapUnit(UnitNum)%UnitIsAvailable) THEN

      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate &
                                                                * ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail  = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = &
                                    Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate

      IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = &
                                                                    Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
        Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = &
                                           Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
      ENDIF

      IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF
    ELSE
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanInletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanInletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = 0.d0

      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%InletNode)%MassFlowRate = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%InletNode)%MassFlowRateMaxAvail = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%OutletNode)%MassFlowRate = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%OutletNode)%MassFlowRateMaxAvail = 0.d0

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) THEN
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%InletNode)%MassFlowRate = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%InletNode)%MassFlowRateMaxAvail = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%OutletNode)%MassFlowRate = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%OutletNode)%MassFlowRateMaxAvail = 0.d0
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = 0.d0
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = 0.d0
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
      ENDIF

      IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF
    ENDIF

  CASE (ZoneCoolingLoadVariableSpeedFan)
    ! get zone loads
    ZoneCoolingLoad = ZoneSysEnergyDemand(ZoneNum)%RemainingOutputReqToCoolSP
    CoolingLoadThreashold = -1.0d0 * ZoneEvapUnit(UnitNum)%ThresholdCoolingLoad
    IF ((ZoneCoolingLoad < CoolingLoadThreashold) .AND. ZoneEvapUnit(UnitNum)%UnitIsAvailable) THEN

      !determine fan speed to meet load
      CALL ControlVSEvapUnitToMeetLoad(UnitNum, ZoneNum, ZoneCoolingLoad)


      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate &
                                                                * ZoneEvapUnit(UnitNum)%FanSpeedRatio
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail  = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = &
                                                                  Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate

      IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = &
                                                                    Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
        Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = &
                                           Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,&
                                 ZoneEvapUnit(UnitNum)%FanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
      ENDIF

      IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,&
                                 ZoneEvapUnit(UnitNum)%FanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF
    ELSE
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanInletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanInletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = 0.d0
      Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = 0.d0

      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%InletNode)%MassFlowRate = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%InletNode)%MassFlowRateMaxAvail = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%OutletNode)%MassFlowRate = 0.d0
      Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)%OutletNode)%MassFlowRateMaxAvail = 0.d0

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) THEN
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%InletNode)%MassFlowRate = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%InletNode)%MassFlowRateMaxAvail = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%OutletNode)%MassFlowRate = 0.d0
        Node(EvapCond(ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)%OutletNode)%MassFlowRateMaxAvail = 0.d0
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = 0.d0
        Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = 0.d0
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%FanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF

      IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
      ENDIF

      IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
        CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
      ENDIF
      IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
        CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex, &
                                 ZoneEvapUnit(UnitNum)%FanSpeedRatio,&
                                 ZoneCompTurnFansOn,ZoneCompTurnFansOff)
      ENDIF
    ENDIF
  END SELECT

! calculate sensible load met (unit serving Zone) using delta enthalpy at a constant (minimum) humidity ratio)
  MinHumRat = MIN(Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum )%HumRat,Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%HumRat)
  SensibleOutputProvided   = Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate &
                         * (PsyHFnTdbW(Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%Temp,MinHumRat) &
                                - PsyHFnTdbW(Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum)%Temp,MinHumRat))
  LatentOutputProvided = Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate * &
                           (Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%HumRat &
                                - Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum)%HumRat)
  RETURN

END SUBROUTINE CalcZoneEvaporativeCoolerUnit

SUBROUTINE ControlVSEvapUnitToMeetLoad(UnitNum, ZoneNum, ZoneCoolingLoad)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         <author>
          !       DATE WRITTEN   <date_written>
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! <description>

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataGlobals,           ONLY: WarmupFlag
  USE DataHVACGlobals,       ONLY: ZoneCompTurnFansOn, ZoneCompTurnFansOff
  USE Fans,                  ONLY: SimulateFanComponents
  USE General,               ONLY: SolveRegulaFalsi, RoundSigDigits

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,          INTENT(IN)  :: UnitNum             ! unit number
  INTEGER,          INTENT(IN)  :: ZoneNum             ! number of zone being served
  REAL(r64),        INTENT(IN)  :: ZoneCoolingLoad     ! target cooling load

          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER :: MaxIte   = 500          ! maximum number of iterations

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: MinHumRat
  REAL(r64), DIMENSION(5) :: Par           ! Parameters passed to RegulaFalsi
  REAL(r64) :: FanSpeedRatio
  REAL(r64)          :: ErrorToler = 0.001d0   ! error tolerance
  INTEGER            :: SolFla        ! Flag of RegulaFalsi solver
  REAL(r64) :: FullFlowSensibleOutputProvided

  ! first get full load result
  ErrorToler = 0.01d0

  ZoneEvapUnit(UnitNum)%FanSpeedRatio = ZoneEvapUnit(UnitNum)%DesignFanSpeedRatio
  Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate &
                                                            * ZoneEvapUnit(UnitNum)%FanSpeedRatio
  Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail  = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
  Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
  Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = &
                                                       Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate

  IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
    Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
    Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = &
                                                                Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
  ENDIF
  IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
    Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
    Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
    CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,&
                              ZoneEvapUnit(UnitNum)%FanSpeedRatio,&
                              ZoneCompTurnFansOn,ZoneCompTurnFansOff)
  ENDIF

  IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
    CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
  ENDIF

  IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
    CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
  ENDIF
  IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
    CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,&
                              ZoneEvapUnit(UnitNum)%FanSpeedRatio,&
                              ZoneCompTurnFansOn,ZoneCompTurnFansOff)
  ENDIF

! calculate sensible load met using delta enthalpy at a constant (minimum) humidity ratio)
  MinHumRat = MIN(Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum )%HumRat,Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%HumRat)
  FullFlowSensibleOutputProvided   = Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate &
                         * (PsyHFnTdbW(Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%Temp,MinHumRat) &
                                - PsyHFnTdbW(Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum)%Temp,MinHumRat))


  IF (FullFlowSensibleOutputProvided < ZoneCoolingLoad) THEN ! find speed ratio by regula falsi numerical method
    Par(1) = UnitNum
    Par(2) = ZoneNum
    Par(3) = ZoneEvapUnit(UnitNum)%ZoneNodeNum
    Par(5) = ZoneCoolingLoad
    FanSpeedRatio = 1.0d0

    CALL SolveRegulaFalsi(ErrorToler, MaxIte, SolFla, FanSpeedRatio, VSEvapUnitLoadResidual, 0.0d0, 1.0d0, Par)
    IF (SolFla == -1) THEN
      IF (ZoneEvapUnit(UnitNum)%UnitVSControlMaxIterErrorIndex == 0) THEN
        CALL ShowWarningError('Iteration limit exceeded calculating variable speed evap unit fan speed ratio, for unit='// &
                      TRIM(ZoneEvapUnit(UnitNum)%Name))
        CALL ShowContinueErrorTimeStamp(' ')
        CALL ShowContinueError('Fan speed ratio returned='//RoundSigDigits(FanSpeedRatio,2))
        CALL ShowContinueError('Check input for Fan Placement.')
      ENDIF
      CALL ShowRecurringWarningErrorAtEnd('Zone Evaporative Cooler unit control failed (iteration limit ['//  &
                        trim(RoundSigDigits(MaxIte))//']) for ZoneHVAC:EvaporativeCoolerUnit ="'// &
                        TRIM(ZoneEvapUnit(UnitNum)%Name),ZoneEvapUnit(UnitNum)%UnitVSControlMaxIterErrorIndex)

    ELSE IF (SolFla == -2) THEN
      IF (ZoneEvapUnit(UnitNum)%UnitVSControlLimitsErrorIndex == 0) THEN
        CALL ShowWarningError('Variable speed evaporative cooler unit calculation failed: fan speed ratio limits exceeded,' &
                      //' for unit = '//TRIM(ZoneEvapUnit(UnitNum)%Name))
        CALL ShowContinueError('Check input for Fan Placement.')
        CALL ShowContinueErrorTimeStamp(' ')
        IF (WarmupFlag) CALL ShowContinueError ('Error occurred during warmup days.')
      ENDIF
      CALL ShowRecurringWarningErrorAtEnd('Zone Evaporative Cooler unit control failed (limits exceeded) ' &
                        // 'for ZoneHVAC:EvaporativeCoolerUnit ="'// &
                        TRIM(ZoneEvapUnit(UnitNum)%Name),ZoneEvapUnit(UnitNum)%UnitVSControlLimitsErrorIndex)
    ENDIF
    ZoneEvapUnit(UnitNum)%FanSpeedRatio = FanSpeedRatio
  ENDIF

  RETURN

END SUBROUTINE ControlVSEvapUnitToMeetLoad

FUNCTION VSEvapUnitLoadResidual(FanSpeedRatio, Par) RESULT (Residual)

          ! FUNCTION INFORMATION:
          !       AUTHOR         <author>
          !       DATE WRITTEN   <date_written>
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          ! <description>

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHVACGlobals,       ONLY: ZoneCompTurnFansOn, ZoneCompTurnFansOff
  USE Fans,                  ONLY: SimulateFanComponents

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! FUNCTION ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN)   :: FanSpeedRatio
  REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! parameters
  REAL(r64)   :: Residual

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER :: UnitNum
  INTEGER :: ZoneNum
  INTEGER :: ZoneNodeNum
  REAL(r64) :: LoadToBeMet      ! sensible load to be met
  REAL(r64) :: MinHumRat
  REAL(r64) :: SensibleOutputProvided


  UnitNum = INT(Par(1))
  ZoneNum = INT(Par(2))
  ZoneNodeNum = INT(Par(3))
  LoadToBeMet = Par(5)

  Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate = ZoneEvapUnit(UnitNum)%DesignAirMassFlowRate &
                                                            * FanSpeedRatio
  Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRateMaxAvail  = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
  Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
  Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRateMaxAvail = &
                                                Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate

  IF (ZoneEvapUnit(UnitNum)%UnitReliefNodeNum > 0) THEN
    Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
    Node(ZoneEvapUnit(UnitNum)%UnitReliefNodeNum)%MassFlowRateMaxAvail = &
                                                                Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
  ENDIF
  IF (ZoneEvapUnit(UnitNum)%FanLocation == BlowThruFan) THEN
    Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRate = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
    Node(ZoneEvapUnit(UnitNum)%FanOutletNodeNum)%MassFlowRateMaxAvail = Node(ZoneEvapUnit(UnitNum)%OAInletNodeNum)%MassFlowRate
    CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,FanSpeedRatio,&
                              ZoneCompTurnFansOn,ZoneCompTurnFansOff)
  ENDIF

  IF (ZoneEvapUnit(UnitNum)%EvapCooler_1_AvailStatus) THEN
    CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_1_Name , ZoneEvapUnit(UnitNum)%EvapCooler_1_Index)
  ENDIF

  IF ((ZoneEvapUnit(UnitNum)%EvapCooler_2_Index > 0) .AND. ZoneEvapUnit(UnitNum)%EvapCooler_2_AvailStatus) THEN
    CALL SimEvapCooler(ZoneEvapUnit(UnitNum)%EvapCooler_2_Name , ZoneEvapUnit(UnitNum)%EvapCooler_2_Index)
  ENDIF
  IF (ZoneEvapUnit(UnitNum)%FanLocation == DrawThruFan) THEN
    CALL SimulateFanComponents(ZoneEvapUnit(UnitNum)%FanName,.FALSE.,ZoneEvapUnit(UnitNum)%FanIndex,FanSpeedRatio,&
                              ZoneCompTurnFansOn,ZoneCompTurnFansOff)
  ENDIF

  MinHumRat = MIN(Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum )%HumRat,Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%HumRat)
  SensibleOutputProvided   = Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%MassFlowRate &
                         * (PsyHFnTdbW(Node(ZoneEvapUnit(UnitNum)%UnitOutletNodeNum)%Temp,MinHumRat) &
                                - PsyHFnTdbW(Node(ZoneEvapUnit(UnitNum)%ZoneNodeNum)%Temp,MinHumRat))

  Residual = SensibleOutputProvided - LoadToBeMet

  RETURN

END FUNCTION VSEvapUnitLoadResidual


SUBROUTINE ReportZoneEvaporativeCoolerUnit(UnitNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith
          !       DATE WRITTEN   July 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! update output variables for the zone evap unit

          ! METHODOLOGY EMPLOYED:
          ! <description>

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  Use DataHVACGlobals, ONLY: TimeStepSys

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,          INTENT    (IN) :: UnitNum             ! unit number

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: ZoneNodeNum
  INTEGER :: UnitOutletNodeNum
  REAL(r64) :: AirMassFlow
  REAL(r64) :: MinHumRat
  REAL(r64) :: QTotUnitOut
  REAL(r64) :: QSensUnitOut

  ZoneNodeNum       = ZoneEvapUnit(UnitNum)%ZoneNodeNum
  UnitOutletNodeNum = ZoneEvapUnit(UnitNum)%UnitOutletNodeNum
  AirMassFlow       = Node(UnitOutletNodeNum)%MassFlowRate
  QTotUnitOut  = AirMassFlow * (Node(UnitOutletNodeNum)%Enthalpy - Node(ZoneNodeNum)%Enthalpy)
  MinHumRat =  Min(Node(ZoneNodeNum)%HumRat, Node(UnitOutletNodeNum)%HumRat)
  QSensUnitOut = AirMassFlow * (PsyHFnTdbW(Node(UnitOutletNodeNum)%Temp,MinHumRat, 'ReportZoneEvaporativeCoolerUnit') &
                                                - PsyHFnTdbW(Node(ZoneNodeNum)%Temp,MinHumRat, 'ReportZoneEvaporativeCoolerUnit'))

  ZoneEvapUnit(UnitNum)%UnitTotalCoolingRate    = ABS(MIN(0.0d0, QTotUnitOut))
  ZoneEvapUnit(UnitNum)%UnitTotalCoolingEnergy  = ZoneEvapUnit(UnitNum)%UnitTotalCoolingRate *TimeStepSys*SecInHour
  ZoneEvapUnit(UnitNum)%UnitSensibleCoolingRate = ABS(MIN(0.0d0, QSensUnitOut))
  ZoneEvapUnit(UnitNum)%UnitSensibleCoolingEnergy = ZoneEvapUnit(UnitNum)%UnitSensibleCoolingRate *TimeStepSys*SecInHour
  ZoneEvapUnit(UnitNum)%UnitLatentHeatingRate   = ABS(MAX(0.0d0, (QTotUnitOut - QSensUnitOut)))
  ZoneEvapUnit(UnitNum)%UnitLatentHeatingEnergy = ZoneEvapUnit(UnitNum)%UnitLatentHeatingRate *TimeStepSys*SecInHour
  ZoneEvapUnit(UnitNum)%UnitLatentCoolingRate   = ABS(MIN(0.0d0, (QTotUnitOut - QSensUnitOut)))
  ZoneEvapUnit(UnitNum)%UnitLatentCoolingEnergy = ZoneEvapUnit(UnitNum)%UnitLatentCoolingRate *TimeStepSys*SecInHour
  ZoneEvapUnit(UnitNum)%UnitFanSpeedRatio       = ZoneEvapUnit(UnitNum)%FanSpeedRatio

  RETURN

END SUBROUTINE ReportZoneEvaporativeCoolerUnit

!        End of Reporting subroutines for the EvaporativeCoolers Module
! *****************************************************************************

!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!

End Module EvaporativeCoolers

AirflowNetworkBalanceManager.f90 AirflowNetworkSolver.f90 BaseboardRadiator.f90 BaseboardRadiatorElectric.f90 BaseboardRadiatorSteam.f90 BaseboardRadiatorWater.f90 BranchInputManager.f90 BranchNodeConnections.f90 ConductionTransferFunctionCalc.f90 CoolTower.f90 CostEstimateManager.f90 CurveManager.f90 CVFOnlyRoutines.f90 DataAirflowNetwork.f90 DataAirLoop.f90 DataAirSystems.f90 DataBranchAirLoopPlant.f90 DataBranchNodeConnections.f90 DataBSDFWindow.f90 DataComplexFenestration.f90 DataContaminantBalance.f90 DataConvergParams.f90 DataConversions.f90 DataCostEstimate.f90 DataDaylighting.f90 DataDaylightingDevices.f90 Datadefineequip.f90 DataDElight.f90 DataEnvironment.f90 DataEquivalentLayerWindow.f90 DataErrorTracking.f90 DataGenerators.f90 DataGlobalConstants.f90 DataGlobals.f90 DataHeatBalance.f90 DataHeatBalFanSys.f90 DataHeatBalSurface.f90 DataHVACControllers.f90 DataHVACGlobals.f90 DataInterfaces.f90 DataIPShortCuts.f90 DataLoopNode.f90 DataMoistureBalance.f90 DataMoistureBalanceEMPD.f90 DataOutputs.f90 DataPhotovoltaics.f90 DataPlant.f90 DataPlantPipingSystems.f90 DataPrecisionGlobals.f90 DataReportingFlags.f90 DataRoomAir.f90 DataRootFinder.f90 DataRuntimeLanguage.f90 DataShadowingCombinations.f90 DataSizing.f90 DataStringGlobals.f90 DataSurfaceColors.f90 DataSurfaceLists.f90 DataSurfaces.f90 DataSystemVariables.f90 DataTimings.f90 DataUCSDSharedData.f90 DataVectorTypes.f90 DataViewFactorInformation.f90 DataWater.f90 DataZoneControls.f90 DataZoneEnergyDemands.f90 DataZoneEquipment.f90 DaylightingDevices.f90 DaylightingManager.f90 DElightManagerF.f90 DElightManagerF_NO.f90 DemandManager.f90 DesiccantDehumidifiers.f90 DirectAir.f90 DisplayRoutines.f90 DXCoil.f90 EarthTube.f90 EconomicLifeCycleCost.f90 EconomicTariff.f90 EcoRoof.f90 ElectricPowerGenerators.f90 ElectricPowerManager.f90 EMSManager.f90 EnergyPlus.f90 ExteriorEnergyUseManager.f90 ExternalInterface_NO.f90 FanCoilUnits.f90 FaultsManager.f90 FluidProperties.f90 General.f90 GeneralRoutines.f90 GlobalNames.f90 HeatBalanceAirManager.f90 HeatBalanceConvectionCoeffs.f90 HeatBalanceHAMTManager.f90 HeatBalanceInternalHeatGains.f90 HeatBalanceIntRadExchange.f90 HeatBalanceManager.f90 HeatBalanceMovableInsulation.f90 HeatBalanceSurfaceManager.f90 HeatBalFiniteDifferenceManager.f90 HeatRecovery.f90 Humidifiers.f90 HVACControllers.f90 HVACCooledBeam.f90 HVACDualDuctSystem.f90 HVACDuct.f90 HVACDXSystem.f90 HVACEvapComponent.f90 HVACFanComponent.f90 HVACFurnace.f90 HVACHeatingCoils.f90 HVACHXAssistedCoolingCoil.f90 HVACInterfaceManager.f90 HVACManager.f90 HVACMixerComponent.f90 HVACMultiSpeedHeatPump.f90 HVACSingleDuctInduc.f90 HVACSingleDuctSystem.f90 HVACSplitterComponent.f90 HVACStandAloneERV.f90 HVACSteamCoilComponent.f90 HVACTranspiredCollector.f90 HVACUnitaryBypassVAV.f90 HVACUnitarySystem.f90 HVACVariableRefrigerantFlow.f90 HVACWaterCoilComponent.f90 HVACWatertoAir.f90 HVACWatertoAirMultiSpeedHP.f90 InputProcessor.f90 MatrixDataManager.f90 MixedAir.f90 MoistureBalanceEMPDManager.f90 NodeInputManager.f90 NonZoneEquipmentManager.f90 OutAirNodeManager.f90 OutdoorAirUnit.f90 OutputProcessor.f90 OutputReportPredefined.f90 OutputReports.f90 OutputReportTabular.f90 PackagedTerminalHeatPump.f90 PackagedThermalStorageCoil.f90 Photovoltaics.f90 PhotovoltaicThermalCollectors.f90 PlantAbsorptionChillers.f90 PlantBoilers.f90 PlantBoilersSteam.f90 PlantCentralGSHP.f90 PlantChillers.f90 PlantCondLoopOperation.f90 PlantCondLoopTowers.f90 PlantEIRChillers.f90 PlantEvapFluidCoolers.f90 PlantExhaustAbsorptionChiller.f90 PlantFluidCoolers.f90 PlantGasAbsorptionChiller.f90 PlantGroundHeatExchangers.f90 PlantHeatExchanger.f90 PlantIceThermalStorage.f90 PlantLoadProfile.f90 PlantLoopEquipment.f90 PlantLoopSolver.f90 PlantManager.f90 PlantOutsideEnergySources.f90 PlantPipeHeatTransfer.f90 PlantPipes.f90 PlantPipingSystemManager.f90 PlantPondGroundHeatExchanger.f90 PlantPressureSystem.f90 PlantPumps.f90 PlantSolarCollectors.f90 PlantSurfaceGroundHeatExchanger.f90 PlantUtilities.f90 PlantValves.f90 PlantWaterSources.f90 PlantWaterThermalTank.f90 PlantWatertoWaterGSHP.f90 PlantWaterUse.f90 PollutionAnalysisModule.f90 PoweredInductionUnits.f90 PsychRoutines.f90 Purchasedairmanager.f90 RadiantSystemHighTemp.f90 RadiantSystemLowTemp.f90 RefrigeratedCase.f90 ReportSizingManager.f90 ReturnAirPath.f90 RoomAirManager.f90 RoomAirModelCrossVent.f90 RoomAirModelDisplacementVent.f90 RoomAirModelMundt.f90 RoomAirModelUFAD.f90 RoomAirModelUserTempPattern.f90 RootFinder.f90 RuntimeLanguageProcessor.f90 ScheduleManager.f90 SetPointManager.f90 SimAirServingZones.f90 SimulationManager.f90 SizingManager.f90 SolarReflectionManager.f90 SolarShading.f90 SortAndStringUtilities.f90 sqlite3.c SQLiteCRoutines.c SQLiteFortranRoutines.f90 SQLiteFortranRoutines_NO.f90 StandardRatings.f90 SurfaceGeometry.f90 SystemAvailabilityManager.f90 SystemReports.f90 TarcogComplexFenestration.f90 ThermalChimney.f90 ThermalComfort.f90 UnitHeater.f90 UnitVentilator.f90 UserDefinedComponents.f90 UtilityRoutines.f90 VectorUtilities.f90 VentilatedSlab.f90 WaterManager.f90 WeatherManager.f90 WindowAC.f90 WindowComplexManager.f90 WindowEquivalentLayer.f90 WindowManager.f90 WindTurbine.f90 Zoneairloopequipmentmanager.f90 ZoneContaminantPredictorCorrector.f90 ZoneDehumidifier.f90 Zoneequipmentmanager.f90 ZonePlenumComponent.f90 ZoneTempPredictorCorrector.f90