sourcefile~~plantwateruse.f90~~EfferentGraph sourcefile~plantwateruse.f90 PlantWaterUse.f90 sourcefile~schedulemanager.f90 ScheduleManager.f90 sourcefile~schedulemanager.f90->sourcefile~plantwateruse.f90 sourcefile~watermanager.f90 WaterManager.f90 sourcefile~schedulemanager.f90->sourcefile~watermanager.f90 sourcefile~nodeinputmanager.f90 NodeInputManager.f90 sourcefile~schedulemanager.f90->sourcefile~nodeinputmanager.f90 sourcefile~outputprocessor.f90 OutputProcessor.f90 sourcefile~schedulemanager.f90->sourcefile~outputprocessor.f90 sourcefile~sqlitefortranroutines.f90 SQLiteFortranRoutines.f90 sourcefile~schedulemanager.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataloopnode.f90 DataLoopNode.f90 sourcefile~dataloopnode.f90->sourcefile~plantwateruse.f90 sourcefile~dataplant.f90 DataPlant.f90 sourcefile~dataloopnode.f90->sourcefile~dataplant.f90 sourcefile~dataloopnode.f90->sourcefile~nodeinputmanager.f90 sourcefile~plantutilities.f90 PlantUtilities.f90 sourcefile~dataloopnode.f90->sourcefile~plantutilities.f90 sourcefile~branchnodeconnections.f90 BranchNodeConnections.f90 sourcefile~dataloopnode.f90->sourcefile~branchnodeconnections.f90 sourcefile~branchinputmanager.f90 BranchInputManager.f90 sourcefile~dataloopnode.f90->sourcefile~branchinputmanager.f90 sourcefile~curvemanager.f90 CurveManager.f90 sourcefile~dataloopnode.f90->sourcefile~curvemanager.f90 sourcefile~watermanager.f90->sourcefile~plantwateruse.f90 sourcefile~general.f90 General.f90 sourcefile~general.f90->sourcefile~plantwateruse.f90 sourcefile~general.f90->sourcefile~schedulemanager.f90 sourcefile~general.f90->sourcefile~watermanager.f90 sourcefile~general.f90->sourcefile~dataplant.f90 sourcefile~psychroutines.f90 PsychRoutines.f90 sourcefile~general.f90->sourcefile~psychroutines.f90 sourcefile~general.f90->sourcefile~nodeinputmanager.f90 sourcefile~general.f90->sourcefile~plantutilities.f90 sourcefile~general.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataheatbalance.f90 DataHeatBalance.f90 sourcefile~general.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90 DataEnvironment.f90 sourcefile~general.f90->sourcefile~dataenvironment.f90 sourcefile~general.f90->sourcefile~branchinputmanager.f90 sourcefile~general.f90->sourcefile~curvemanager.f90 sourcefile~general.f90->sourcefile~outputprocessor.f90 sourcefile~fluidproperties.f90 FluidProperties.f90 sourcefile~general.f90->sourcefile~fluidproperties.f90 sourcefile~general.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datahvacglobals.f90 DataHVACGlobals.f90 sourcefile~datahvacglobals.f90->sourcefile~plantwateruse.f90 sourcefile~datahvacglobals.f90->sourcefile~watermanager.f90 sourcefile~datahvacglobals.f90->sourcefile~general.f90 sourcefile~datahvacglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataplant.f90->sourcefile~plantwateruse.f90 sourcefile~dataplant.f90->sourcefile~plantutilities.f90 sourcefile~psychroutines.f90->sourcefile~plantwateruse.f90 sourcefile~psychroutines.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataprecisionglobals.f90 DataPrecisionGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantwateruse.f90 sourcefile~dataprecisionglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataprecisionglobals.f90->sourcefile~watermanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~general.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataplant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90 DataGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataglobals.f90 sourcefile~dataipshortcuts.f90 DataIPShortCuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataheatbalfansys.f90 DataHeatBalFanSys.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalfansys.f90 sourcefile~datawater.f90 DataWater.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datawater.f90 sourcefile~datainterfaces.f90 DataInterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datainterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90 InputProcessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataenvironment.f90 sourcefile~datasystemvariables.f90 DataSystemVariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datasurfaces.f90 DataSurfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90 DataVectorTypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datavectortypes.f90 sourcefile~databsdfwindow.f90 DataBSDFWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataruntimelanguage.f90 DataRuntimeLanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~datasizing.f90 DataSizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataerrortracking.f90 DataErrorTracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataerrortracking.f90 sourcefile~databranchairloopplant.f90 DataBranchAirLoopPlant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~fluidproperties.f90 sourcefile~datacontaminantbalance.f90 DataContaminantBalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~outputreportpredefined.f90 OutputReportPredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataroomair.f90 DataRoomAir.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataroomair.f90 sourcefile~datacomplexfenestration.f90 DataComplexFenestration.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataequivalentlayerwindow.f90 DataEquivalentLayerWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataglobals.f90->sourcefile~plantwateruse.f90 sourcefile~dataglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataglobals.f90->sourcefile~watermanager.f90 sourcefile~dataglobals.f90->sourcefile~general.f90 sourcefile~dataglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataglobals.f90->sourcefile~dataplant.f90 sourcefile~dataglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataglobals.f90->sourcefile~datawater.f90 sourcefile~dataglobals.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~datasizing.f90 sourcefile~dataglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~sortandstringutilities.f90 SortAndStringUtilities.f90 sourcefile~dataglobals.f90->sourcefile~sortandstringutilities.f90 sourcefile~dataoutputs.f90 DataOutputs.f90 sourcefile~dataglobals.f90->sourcefile~dataoutputs.f90 sourcefile~dataglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataglobalconstants.f90 DataGlobalConstants.f90 sourcefile~dataglobals.f90->sourcefile~dataglobalconstants.f90 sourcefile~dataglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataglobals.f90->sourcefile~dataroomair.f90 sourcefile~databranchnodeconnections.f90 DataBranchNodeConnections.f90 sourcefile~dataglobals.f90->sourcefile~databranchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantwateruse.f90 sourcefile~dataipshortcuts.f90->sourcefile~schedulemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~general.f90 sourcefile~dataipshortcuts.f90->sourcefile~inputprocessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~curvemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~outputprocessor.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantwateruse.f90 sourcefile~nodeinputmanager.f90->sourcefile~branchinputmanager.f90 sourcefile~plantutilities.f90->sourcefile~plantwateruse.f90 sourcefile~dataheatbalfansys.f90->sourcefile~plantwateruse.f90 sourcefile~datawater.f90->sourcefile~plantwateruse.f90 sourcefile~datawater.f90->sourcefile~watermanager.f90 sourcefile~datainterfaces.f90->sourcefile~plantwateruse.f90 sourcefile~datainterfaces.f90->sourcefile~schedulemanager.f90 sourcefile~datainterfaces.f90->sourcefile~watermanager.f90 sourcefile~datainterfaces.f90->sourcefile~general.f90 sourcefile~datainterfaces.f90->sourcefile~dataplant.f90 sourcefile~datainterfaces.f90->sourcefile~psychroutines.f90 sourcefile~datainterfaces.f90->sourcefile~nodeinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~plantutilities.f90 sourcefile~datainterfaces.f90->sourcefile~branchnodeconnections.f90 sourcefile~datainterfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datainterfaces.f90->sourcefile~inputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~dataenvironment.f90 sourcefile~datainterfaces.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datainterfaces.f90->sourcefile~branchinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~curvemanager.f90 sourcefile~datainterfaces.f90->sourcefile~outputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~fluidproperties.f90 sourcefile~datainterfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantwateruse.f90 sourcefile~branchnodeconnections.f90->sourcefile~nodeinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~branchinputmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~plantwateruse.f90 sourcefile~dataheatbalance.f90->sourcefile~watermanager.f90 sourcefile~dataheatbalance.f90->sourcefile~outputprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~inputprocessor.f90->sourcefile~plantwateruse.f90 sourcefile~inputprocessor.f90->sourcefile~schedulemanager.f90 sourcefile~inputprocessor.f90->sourcefile~watermanager.f90 sourcefile~inputprocessor.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90->sourcefile~dataplant.f90 sourcefile~inputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~branchnodeconnections.f90 sourcefile~inputprocessor.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~curvemanager.f90 sourcefile~inputprocessor.f90->sourcefile~outputprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~fluidproperties.f90 sourcefile~inputprocessor.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~inputprocessor.f90->sourcefile~dataglobalconstants.f90 sourcefile~dataenvironment.f90->sourcefile~plantwateruse.f90 sourcefile~dataenvironment.f90->sourcefile~schedulemanager.f90 sourcefile~dataenvironment.f90->sourcefile~watermanager.f90 sourcefile~dataenvironment.f90->sourcefile~psychroutines.f90 sourcefile~dataenvironment.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataenvironment.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90->sourcefile~outputprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datastringglobals.f90 DataStringGlobals.f90 sourcefile~datastringglobals.f90->sourcefile~schedulemanager.f90 sourcefile~datastringglobals.f90->sourcefile~general.f90 sourcefile~datastringglobals.f90->sourcefile~inputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datastringglobals.f90->sourcefile~outputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasystemvariables.f90->sourcefile~schedulemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~inputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~curvemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasurfaces.f90->sourcefile~watermanager.f90 sourcefile~datasurfaces.f90->sourcefile~general.f90 sourcefile~datasurfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datasurfaces.f90->sourcefile~datacontaminantbalance.f90 sourcefile~datasurfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datavectortypes.f90->sourcefile~dataheatbalance.f90 sourcefile~datavectortypes.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90->sourcefile~databsdfwindow.f90 sourcefile~databsdfwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90->sourcefile~datasurfaces.f90 sourcefile~dataruntimelanguage.f90->sourcefile~general.f90 sourcefile~branchinputmanager.f90->sourcefile~dataplant.f90 sourcefile~datasizing.f90->sourcefile~dataplant.f90 sourcefile~datasizing.f90->sourcefile~plantutilities.f90 sourcefile~datasizing.f90->sourcefile~inputprocessor.f90 sourcefile~datasizing.f90->sourcefile~branchinputmanager.f90 sourcefile~curvemanager.f90->sourcefile~branchinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantutilities.f90 sourcefile~databranchairloopplant.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~curvemanager.f90 sourcefile~outputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~fluidproperties.f90->sourcefile~nodeinputmanager.f90 sourcefile~fluidproperties.f90->sourcefile~plantutilities.f90 sourcefile~datacontaminantbalance.f90->sourcefile~nodeinputmanager.f90 sourcefile~sortandstringutilities.f90->sourcefile~inputprocessor.f90 sourcefile~sortandstringutilities.f90->sourcefile~outputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~inputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~outputprocessor.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobalconstants.f90->sourcefile~outputprocessor.f90 sourcefile~outputreportpredefined.f90->sourcefile~outputprocessor.f90 sourcefile~dataroomair.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~databranchnodeconnections.f90->sourcefile~branchnodeconnections.f90 sourcefile~datacomplexfenestration.f90->sourcefile~dataheatbalance.f90 sourcefile~dataequivalentlayerwindow.f90->sourcefile~dataheatbalance.f90
Help

Files Dependent On This One

sourcefile~~plantwateruse.f90~~AfferentGraph sourcefile~plantwateruse.f90 PlantWaterUse.f90 sourcefile~nonzoneequipmentmanager.f90 NonZoneEquipmentManager.f90 sourcefile~plantwateruse.f90->sourcefile~nonzoneequipmentmanager.f90 sourcefile~plantloopequipment.f90 PlantLoopEquipment.f90 sourcefile~plantwateruse.f90->sourcefile~plantloopequipment.f90 sourcefile~heatbalanceinternalheatgains.f90 HeatBalanceInternalHeatGains.f90 sourcefile~plantwateruse.f90->sourcefile~heatbalanceinternalheatgains.f90 sourcefile~hvacmanager.f90 HVACManager.f90 sourcefile~nonzoneequipmentmanager.f90->sourcefile~hvacmanager.f90 sourcefile~plantmanager.f90 PlantManager.f90 sourcefile~plantloopequipment.f90->sourcefile~plantmanager.f90 sourcefile~plantloopsolver.f90 PlantLoopSolver.f90 sourcefile~plantloopequipment.f90->sourcefile~plantloopsolver.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~hvacmanager.f90 sourcefile~heatbalancesurfacemanager.f90 HeatBalanceSurfaceManager.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~heatbalancemanager.f90 HeatBalanceManager.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~heatbalancemanager.f90 sourcefile~zoneequipmentmanager.f90 Zoneequipmentmanager.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~daylightingmanager.f90 DaylightingManager.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~daylightingmanager.f90 sourcefile~roomairmodelcrossvent.f90 RoomAirModelCrossVent.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelcrossvent.f90 sourcefile~zonecontaminantpredictorcorrector.f90 ZoneContaminantPredictorCorrector.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~zonecontaminantpredictorcorrector.f90 sourcefile~roomairmodelusertemppattern.f90 RoomAirModelUserTempPattern.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelusertemppattern.f90 sourcefile~delightmanagerf.f90 DElightManagerF.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~delightmanagerf.f90 sourcefile~roomairmodelufad.f90 RoomAirModelUFAD.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelufad.f90 sourcefile~roomairmodeldisplacementvent.f90 RoomAirModelDisplacementVent.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodeldisplacementvent.f90 sourcefile~zonetemppredictorcorrector.f90 ZoneTempPredictorCorrector.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~zonetemppredictorcorrector.f90 sourcefile~roomairmodelmundt.f90 RoomAirModelMundt.f90 sourcefile~heatbalanceinternalheatgains.f90->sourcefile~roomairmodelmundt.f90 sourcefile~heatbalanceairmanager.f90 HeatBalanceAirManager.f90 sourcefile~hvacmanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~simulationmanager.f90 SimulationManager.f90 sourcefile~hvacmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~energyplus.f90 EnergyPlus.f90 sourcefile~simulationmanager.f90->sourcefile~energyplus.f90 sourcefile~utilityroutines.f90 UtilityRoutines.f90 sourcefile~simulationmanager.f90->sourcefile~utilityroutines.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~simulationmanager.f90 sourcefile~sizingmanager.f90 SizingManager.f90 sourcefile~heatbalancemanager.f90->sourcefile~sizingmanager.f90 sourcefile~sizingmanager.f90->sourcefile~simulationmanager.f90 sourcefile~plantmanager.f90->sourcefile~hvacmanager.f90 sourcefile~plantmanager.f90->sourcefile~simulationmanager.f90 sourcefile~plantmanager.f90->sourcefile~utilityroutines.f90 sourcefile~plantloopsolver.f90->sourcefile~plantmanager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~hvacmanager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~sizingmanager.f90 sourcefile~daylightingmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~daylightingmanager.f90->sourcefile~utilityroutines.f90 sourcefile~solarshading.f90 SolarShading.f90 sourcefile~daylightingmanager.f90->sourcefile~solarshading.f90 sourcefile~windowequivalentlayer.f90 WindowEquivalentLayer.f90 sourcefile~daylightingmanager.f90->sourcefile~windowequivalentlayer.f90 sourcefile~roomairmanager.f90 RoomAirManager.f90 sourcefile~roomairmodelcrossvent.f90->sourcefile~roomairmanager.f90 sourcefile~zonecontaminantpredictorcorrector.f90->sourcefile~hvacmanager.f90 sourcefile~zonecontaminantpredictorcorrector.f90->sourcefile~simulationmanager.f90 sourcefile~roomairmodelusertemppattern.f90->sourcefile~roomairmanager.f90 sourcefile~delightmanagerf.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~delightmanagerf.f90->sourcefile~daylightingmanager.f90 sourcefile~roomairmodelufad.f90->sourcefile~roomairmanager.f90 sourcefile~roomairmodeldisplacementvent.f90->sourcefile~roomairmanager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~hvacmanager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~simulationmanager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~zonetemppredictorcorrector.f90->sourcefile~zonecontaminantpredictorcorrector.f90 sourcefile~roomairmodelmundt.f90->sourcefile~roomairmanager.f90 sourcefile~solarshading.f90->sourcefile~simulationmanager.f90 sourcefile~solarshading.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~solarshading.f90->sourcefile~heatbalancemanager.f90 sourcefile~solarshading.f90->sourcefile~utilityroutines.f90 sourcefile~windowequivalentlayer.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~windowequivalentlayer.f90->sourcefile~heatbalancemanager.f90 sourcefile~windowequivalentlayer.f90->sourcefile~solarshading.f90 sourcefile~windowmanager.f90 WindowManager.f90 sourcefile~windowequivalentlayer.f90->sourcefile~windowmanager.f90 sourcefile~heatbalanceintradexchange.f90 HeatBalanceIntRadExchange.f90 sourcefile~windowequivalentlayer.f90->sourcefile~heatbalanceintradexchange.f90 sourcefile~windowmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~windowmanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalanceintradexchange.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~roomairmanager.f90->sourcefile~zonetemppredictorcorrector.f90
Help

Source Code


Source Code

MODULE WaterUse

          ! MODULE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       Brent Griffith, plant upgrade
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS MODULE:
          !

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
USE DataPrecisionGlobals
USE DataGlobals, ONLY: WarmupFlag, MaxNameLength, BeginEnvrnFlag, InitConvTemp, NumOfZones
USE DataInterfaces

IMPLICIT NONE ! Enforce explicit typing of all variables

PRIVATE ! Everything private unless explicitly made public

          ! MODULE PARAMETER DEFINITIONS:
INTEGER, PARAMETER :: HeatRecoveryHXIdeal = 1
INTEGER, PARAMETER :: HeatRecoveryHXCounterFlow = 2
INTEGER, PARAMETER :: HeatRecoveryHXCrossFlow = 3

INTEGER, PARAMETER :: HeatRecoveryConfigPlant = 1
INTEGER, PARAMETER :: HeatRecoveryConfigEquipment = 2
INTEGER, PARAMETER :: HeatRecoveryConfigPlantAndEquip= 3

          ! DERIVED TYPE DEFINITIONS:
TYPE WaterEquipmentType
  CHARACTER(len=MaxNameLength) :: Name = ''                ! Name of DHW
  CHARACTER(len=MaxNameLength) :: EndUseSubcatName = ''
  INTEGER                      :: Connections = 0          ! Index for WATER USE CONNECTIONS object

  REAL(r64)                    :: PeakVolFlowRate = 0.0d0    ! Peak volumetric flow rate, also water consumption rate (m3/s)
  INTEGER                      :: FlowRateFracSchedule = 0 ! Pointer to schedule object

  REAL(r64)                    :: ColdVolFlowRate = 0.0d0
  REAL(r64)                    :: HotVolFlowRate = 0.0d0
  REAL(r64)                    :: TotalVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)

  REAL(r64)                    :: ColdMassFlowRate = 0.0d0
  REAL(r64)                    :: HotMassFlowRate = 0.0d0
  REAL(r64)                    :: TotalMassFlowRate = 0.0d0       ! Mass flow rate (kg/s)
  REAL(r64)                    :: DrainMassFlowRate = 0.0d0

  INTEGER                      :: ColdTempSchedule = 0     ! Index for schedule object
  INTEGER                      :: HotTempSchedule = 0      ! Index for schedule object
  INTEGER                      :: TargetTempSchedule = 0   ! Index for schedule object

  REAL(r64)                    :: ColdTemp = 0.0d0           ! Cold supply water temperature (C)
  REAL(r64)                    :: HotTemp = 0.0d0            ! Hot supply water temperature (C)
  REAL(r64)                    :: TargetTemp = 0.0d0         ! Target (mixed) water temperature (C)
  REAL(r64)                    :: MixedTemp = 0.0d0         ! Actual outlet (mixed) water temperature (C)
  REAL(r64)                    :: DrainTemp = 0.0d0

  INTEGER                      :: Zone = 0                 ! Index for zone object
  INTEGER                      :: SensibleFracSchedule = 0 ! Pointer to schedule object
  REAL(r64)                    :: SensibleRate = 0.0d0
  REAL(r64)                    :: SensibleEnergy = 0.0d0
  REAL(r64)                    :: SensibleRateNoMultiplier = 0.d0
  INTEGER                      :: LatentFracSchedule = 0   ! Pointer to schedule object
  REAL(r64)                    :: LatentRate = 0.0d0
  REAL(r64)                    :: LatentEnergy = 0.0d0
  REAL(r64)                    :: LatentRateNoMultiplier = 0.d0
  REAL(r64)                    :: MoistureRate = 0.0d0
  REAL(r64)                    :: MoistureMass = 0.0d0

  REAL(r64)                    :: ColdVolume = 0.0d0             ! Water consumption (m3)
  REAL(r64)                    :: HotVolume = 0.0d0             ! Water consumption (m3)
  REAL(r64)                    :: TotalVolume = 0.0d0             ! Water consumption (m3)

  REAL(r64)                    :: Power = 0.0d0              ! Heating rate required to meet the mixed water temperature (W)
  REAL(r64)                    :: Energy = 0.0d0             ! Heating energy required to meet the mixed water temperature (J)
END TYPE WaterEquipmentType

TYPE WaterConnectionsType
  CHARACTER(len=MaxNameLength) :: Name = ''                ! Name of DHW
  LOGICAL                      :: Init = .TRUE.            ! Flag for initialization:  TRUE means do the init
  LOGICAL                      :: InitSizing = .TRUE.      ! Flag for initialization of plant sizing
  LOGICAL                      :: StandAlone = .FALSE.     ! Flag for operation with no plant connections
  INTEGER                      :: InletNode = 0            ! Hot water demand node
  INTEGER                      :: OutletNode = 0           ! Cold water supply node
  INTEGER                      :: SupplyTankNum = 0
  INTEGER                      :: RecoveryTankNum = 0
  INTEGER                      :: TankDemandID = 0  ! array to request flow from supply tank
  INTEGER                      :: TankSupplyID = 0 ! array to send flow to recovery tank

  LOGICAL                      :: HeatRecovery = .FALSE.
  INTEGER                      :: HeatRecoveryHX = HeatRecoveryHXIdeal
  INTEGER                      :: HeatRecoveryConfig = HeatRecoveryConfigPlant
  REAL(r64)                    :: HXUA = 0.0d0
  REAL(r64)                    :: Effectiveness = 0.0d0
  REAL(r64)                    :: RecoveryRate = 0.0d0
  REAL(r64)                    :: RecoveryEnergy = 0.0d0

  REAL(r64)                    :: MainsMassFlowRate = 0.0d0       ! Mass flow rate (kg/s)
  REAL(r64)                    :: TankMassFlowRate = 0.0d0       ! Mass flow rate (kg/s)
  REAL(r64)                    :: ColdMassFlowRate = 0.0d0       ! Mass flow rate (kg/s)  cold = mains + tank
  REAL(r64)                    :: HotMassFlowRate = 0.0d0       ! Mass flow rate (kg/s)
  REAL(r64)                    :: TotalMassFlowRate = 0.0d0       ! Mass flow rate (kg/s) total = cold + hot
  REAL(r64)                    :: DrainMassFlowRate = 0.0d0
  REAL(r64)                    :: RecoveryMassFlowRate = 0.0d0

  REAL(r64)                    :: PeakVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)
  REAL(r64)                    :: MainsVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)
  REAL(r64)                    :: TankVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)
  REAL(r64)                    :: ColdVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)
  REAL(r64)                    :: HotVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)
  REAL(r64)                    :: TotalVolFlowRate = 0.0d0        ! Volumetric flow rate, also water consumption rate (m3/s)
  REAL(r64)                    :: DrainVolFlowRate = 0.0d0
  REAL(r64)                    :: PeakMassFlowRate = 0.0D0 ! Peak Mass flow rate for MassFlowRateMax

  INTEGER                      :: ColdTempSchedule = 0     ! Index for schedule object
  INTEGER                      :: HotTempSchedule = 0      ! Index for schedule object

  REAL(r64)                    :: MainsTemp = 0.0d0           ! Cold supply water temperature (C)
  REAL(r64)                    :: TankTemp = 0.0d0           ! Cold supply water temperature (C)
  REAL(r64)                    :: ColdSupplyTemp = 0.0d0     ! cold from mains, schedule, or tank, depending
  REAL(r64)                    :: ColdTemp = 0.0d0           ! Cold supply water temperature (C)  actual cold (could be reheated)
  REAL(r64)                    :: HotTemp = 0.0d0            ! Hot supply water temperature (C)
  REAL(r64)                    :: DrainTemp = 0.0d0          !
  REAL(r64)                    :: RecoveryTemp = 0.0d0          !
  REAL(r64)                    :: ReturnTemp = 0.0d0         !
  REAL(r64)                    :: WasteTemp = 0.0d0         !

  REAL(r64)                    :: TempError = 0.0d0         !

  REAL(r64)                    :: MainsVolume = 0.0d0             ! Water consumption (m3)
  REAL(r64)                    :: TankVolume = 0.0d0             ! Water consumption (m3)
  REAL(r64)                    :: ColdVolume = 0.0d0             ! Water consumption (m3)
  REAL(r64)                    :: HotVolume = 0.0d0             ! Water consumption (m3)
  REAL(r64)                    :: TotalVolume = 0.0d0             ! Water consumption (m3)

  REAL(r64)                    :: Power = 0.0d0              ! Heating rate required to raise temperature from cold to hot (W)
  REAL(r64)                    :: Energy = 0.0d0             ! Heating energy required to raise temperature from cold to hot (J)

  INTEGER                      :: NumWaterEquipment = 0
  INTEGER                      :: MaxIterationsErrorIndex = 0   ! recurring error index
  INTEGER, DIMENSION(:), ALLOCATABLE :: WaterEquipment

  INTEGER                      :: PlantLoopNum       = 0
  INTEGER                      :: PlantLoopSide      = 0
  INTEGER                      :: PlantLoopBranchNum = 0
  INTEGER                      :: PlantLoopCompNum   = 0

END TYPE WaterConnectionsType

          ! MODULE VARIABLE TYPE DECLARATIONS:
TYPE (WaterEquipmentType), ALLOCATABLE, DIMENSION(:) :: WaterEquipment
TYPE (WaterConnectionsType), ALLOCATABLE, DIMENSION(:) :: WaterConnections

          ! MODULE VARIABLE DECLARATIONS:
INTEGER :: NumWaterEquipment       =0
INTEGER :: NumWaterConnections     =0
!INTEGER :: MaxIterationsErrorCount =0
LOGICAL :: GetWaterUseInputFlag = .TRUE.

LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckEquipName
LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckPlantLoop

          ! SUBROUTINE SPECIFICATIONS:
PUBLIC SimulateWaterUse
PUBLIC SimulateWaterUseConnection
PUBLIC CalcWaterUseZoneGains
PRIVATE GetWaterUseInput
PRIVATE CalcEquipmentFlowRates
PRIVATE CalcEquipmentDrainTemp
PRIVATE InitConnections
PRIVATE CalcConnectionsFlowRates
PRIVATE CalcConnectionsDrainTemp
PRIVATE CalcConnectionsHeatRecovery
PRIVATE UpdateWaterConnections
PRIVATE ReportWaterUse

CONTAINS

          ! MODULE SUBROUTINES:
SUBROUTINE SimulateWaterUse(FirstHVACIteration)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       Brent Griffith, March 2010, seperated plant connected to different sim routine
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This routine is called from non zone equipment manager and serves to call
          ! water use and connections that are not connected to a full plant loop


          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE General, ONLY: RoundSigDigits

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER :: MaxIterations = 100
  REAL(r64), PARAMETER    :: Tolerance = 0.1d0  ! Make input?

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  LOGICAL, INTENT(IN) :: FirstHVACIteration

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: WaterEquipNum
  INTEGER :: WaterConnNum
  INTEGER :: NumIteration
  INTEGER, SAVE :: MaxIterationsErrorCount
  LOGICAL, SAVE :: MyEnvrnFlag = .TRUE.

          ! FLOW:
  IF (GetWaterUseInputFlag) THEN
    CALL GetWaterUseInput
    GetWaterUseInputFlag = .FALSE.
  END IF

  IF (BeginEnvrnFlag .and. MyEnvrnFlag) THEN
    MaxIterationsErrorCount = 0
    IF (NumWaterEquipment > 0) THEN
      WaterEquipment%SensibleRate = 0.0d0
      WaterEquipment%SensibleEnergy = 0.0d0
      WaterEquipment%LatentRate = 0.0d0
      WaterEquipment%LatentEnergy = 0.0d0
      WaterEquipment%MixedTemp = 0.0d0
      WaterEquipment%TotalMassFlowRate = 0.0d0
      WaterEquipment%DrainTemp = 0.0d0
    ENDIF

    IF (NumWaterConnections > 0) THEN
      WaterConnections%TotalMassFlowRate = 0.0d0
    ENDIF

    MyEnvrnFlag = .false.
  END IF

  If ( .NOT. BeginEnvrnFlag) MyEnvrnFlag = .TRUE.

  ! Simulate all unconnected WATER USE EQUIPMENT objects
  DO WaterEquipNum = 1, NumWaterEquipment
    IF (WaterEquipment(WaterEquipNum)%Connections == 0) THEN
      CALL CalcEquipmentFlowRates(WaterEquipNum)
      CALL CalcEquipmentDrainTemp(WaterEquipNum)
    END IF
  END DO  ! WaterEquipNum

  CALL ReportStandAloneWaterUse

  ! Simulate WATER USE CONNECTIONS objects and connected WATER USE EQUIPMENT objects
  DO WaterConnNum = 1, NumWaterConnections

    IF (.NOT. WaterConnections(WaterConnNum)%StandAlone ) CYCLE ! only model non plant connections here

    CALL InitConnections(WaterConnNum)

    NumIteration = 0

    DO WHILE (.TRUE.)
      NumIteration = NumIteration + 1

      CALL CalcConnectionsFlowRates(WaterConnNum, FirstHVACIteration)
      CALL CalcConnectionsDrainTemp(WaterConnNum)
      CALL CalcConnectionsHeatRecovery(WaterConnNum)

      IF (WaterConnections(WaterConnNum)%TempError < Tolerance) THEN
        EXIT
      ELSE IF (NumIteration > MaxIterations) THEN
        IF (.NOT. WarmupFlag) THEN
          IF (WaterConnections(WaterConnNum)%MaxIterationsErrorIndex == 0) THEN
            CALL ShowWarningError('WaterUse:Connections = '//TRIM(WaterConnections(WaterConnNum)%Name)// &
              ':  Heat recovery temperature did not converge')
            CALL ShowContinueErrorTimeStamp(' ')
          ENDIF
          CALL ShowRecurringWarningErrorAtEnd('WaterUse:Connections = '//TRIM(WaterConnections(WaterConnNum)%Name)// &
              ':  Heat recovery temperature did not converge',  &
            WaterConnections(WaterConnNum)%MaxIterationsErrorIndex)
        END IF
        EXIT
      END IF

    END DO  ! WHILE

    CALL UpdateWaterConnections(WaterConnNum)

    CALL ReportWaterUse(WaterConnNum)

  END DO  ! WaterConnNum

  RETURN

END SUBROUTINE SimulateWaterUse

SUBROUTINE SimulateWaterUseConnection(EquipTypeNum, CompName, CompIndex, InitLoopEquip, FirstHVACIteration)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith March 2010, Demand Side Update
          !       DATE WRITTEN   August 2006
          !       MODIFIED
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Plant sim call for plant loop connected water use and connections
          ! (based on SimulateWaterUse by P. Ellis)

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE General, ONLY: RoundSigDigits, TrimSigDigits
  USE InputProcessor, ONLY: FindItemInList

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER :: MaxIterations = 100
  REAL(r64), PARAMETER    :: Tolerance = 0.1d0  ! Make input?

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN)          :: EquipTypeNum
  CHARACTER(len=*), INTENT(IN) :: CompName
  INTEGER, INTENT(INOUT)       :: CompIndex
  LOGICAL, INTENT(IN)          :: InitLoopEquip
  LOGICAL, INTENT(IN)          :: FirstHVACIteration

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
!  INTEGER :: WaterEquipNum
  INTEGER :: WaterConnNum
  INTEGER :: NumIteration
  INTEGER, SAVE :: MaxIterationsErrorCount
  LOGICAL, SAVE :: MyEnvrnFlag = .TRUE.

          ! FLOW:
  IF (GetWaterUseInputFlag) THEN
    CALL GetWaterUseInput
    GetWaterUseInputFlag = .FALSE.
  END IF

  IF (CompIndex == 0) THEN
    WaterConnNum = FindItemInList(CompName , WaterConnections%Name, NumWaterConnections )
    IF (WaterConnNum == 0) THEN
      CALL ShowFatalError('SimulateWaterUseConnection: Unit not found='//TRIM(CompName))
    ENDIF
    CompIndex = WaterConnNum
  ELSE
    WaterConnNum = CompIndex
    IF (WaterConnNum > NumWaterConnections .OR. WaterConnNum < 1) THEN
      Call ShowFatalError('SimulateWaterUseConnection: Invalid CompIndex passed='//  &
                          TRIM(TrimSigDigits(WaterConnNum))// &
                          ', Number of Units='//Trim(TrimSigDigits(NumWaterConnections))//  &
                          ', Entered Unit name='//Trim(CompName))
    ENDIF
    IF (CheckEquipName(WaterConnNum)) THEN
      IF (CompName /= WaterConnections(WaterConnNum)%Name) THEN
        CALL ShowFatalError('SimulateWaterUseConnection: Invalid CompIndex passed='//  &
                          TRIM(TrimSigDigits(WaterConnNum))// &
                          ', Unit name='//Trim(CompName )// ', stored Unit Name for that index='// &
                          TRIM(WaterConnections(WaterConnNum)%Name) )
      ENDIF
      CheckEquipName(WaterConnNum) = .FALSE.
    ENDIF
  ENDIF

  IF (InitLoopEquip) THEN
    RETURN
  ENDIF

  IF (BeginEnvrnFlag .and. MyEnvrnFlag) THEN
    MaxIterationsErrorCount = 0
    IF (NumWaterEquipment > 0) THEN
      WaterEquipment%SensibleRate = 0.0d0
      WaterEquipment%SensibleEnergy = 0.0d0
      WaterEquipment%LatentRate = 0.0d0
      WaterEquipment%LatentEnergy = 0.0d0
      WaterEquipment%MixedTemp = 0.0d0
      WaterEquipment%TotalMassFlowRate = 0.0d0
      WaterEquipment%DrainTemp = 0.0d0
    ENDIF

    IF (NumWaterConnections > 0) THEN
      WaterConnections%TotalMassFlowRate = 0.0d0
    ENDIF

    MyEnvrnFlag = .false.
  END IF

  IF ( .NOT. BeginEnvrnFlag) MyEnvrnFlag = .true.

  CALL InitConnections(WaterConnNum)

  NumIteration = 0

  DO WHILE (.TRUE.)
    NumIteration = NumIteration + 1

    CALL CalcConnectionsFlowRates(WaterConnNum, FirstHVACIteration)
    CALL CalcConnectionsDrainTemp(WaterConnNum)
    CALL CalcConnectionsHeatRecovery(WaterConnNum)

    IF (WaterConnections(WaterConnNum)%TempError < Tolerance) THEN
      EXIT
    ELSE IF (NumIteration > MaxIterations) THEN
      IF (.NOT. WarmupFlag) THEN
        IF (WaterConnections(WaterConnNum)%MaxIterationsErrorIndex == 0) THEN
          CALL ShowWarningError('WaterUse:Connections = '//TRIM(WaterConnections(WaterConnNum)%Name)// &
            ':  Heat recovery temperature did not converge')
          CALL ShowContinueErrorTimeStamp(' ')
        ENDIF
        CALL ShowRecurringWarningErrorAtEnd('WaterUse:Connections = '//TRIM(WaterConnections(WaterConnNum)%Name)// &
            ':  Heat recovery temperature did not converge',  &
          WaterConnections(WaterConnNum)%MaxIterationsErrorIndex)
      END IF
      EXIT
    END IF

  END DO  ! WHILE

  CALL UpdateWaterConnections(WaterConnNum)


  CALL ReportWaterUse(WaterConnNum)

  RETURN

END SUBROUTINE SimulateWaterUseConnection


SUBROUTINE GetWaterUseInput

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          !

          ! METHODOLOGY EMPLOYED:
          ! Standard EnergyPlus methodology.

          ! USE STATEMENTS:
  USE InputProcessor, ONLY: GetObjectDefMaxArgs, GetNumObjectsFound, FindItemInList, GetObjectItem, VerifyName
  USE DataIPShortCuts  ! Data for field names, blank numerics
  USE ScheduleManager, ONLY: GetScheduleIndex
  USE NodeInputManager, ONLY: GetOnlySingleNode
  USE BranchNodeConnections, ONLY: TestCompSet
  USE DataLoopNode
  USE DataHeatBalance
  USE WaterManager,   ONLY:SetupTankSupplyComponent,SetupTankDemandComponent
  USE Psychrometrics, ONLY: RhoH2O
  USE PlantUtilities, ONLY: RegisterPlantCompDesignFlow
  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE PARAMETER DEFINITIONS:
  CHARACTER(len=*), PARAMETER :: Blank = ' '

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  LOGICAL                        :: ErrorsFound = .FALSE. ! Set to true if errors in input, fatal at end of routine
  INTEGER                        :: IOStatus              ! Used in GetObjectItem
  LOGICAL                        :: IsBlank               ! TRUE if the name is blank
  LOGICAL                        :: IsNotOk               ! TRUE if there was a problem with a list name
  INTEGER                        :: NumAlphas             ! Number of Alphas for each GetObjectItem call
  INTEGER                        :: NumNumbers            ! Number of Numbers for each GetObjectItem call
!unused1208  INTEGER                        :: NumArgs
  INTEGER                        :: WaterEquipNum
  INTEGER                        :: WaterConnNum
  INTEGER                        :: AlphaNum
  INTEGER                        :: thisWaterEquipNum

          ! FLOW:

  cCurrentModuleObject = 'WaterUse:Equipment'
  NumWaterEquipment = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumWaterEquipment > 0) THEN
    ALLOCATE(WaterEquipment(NumWaterEquipment))

    DO WaterEquipNum = 1, NumWaterEquipment
      CALL GetObjectItem( cCurrentModuleObject, WaterEquipNum, cAlphaArgs, NumAlphas, rNumericArgs, NumNumbers, IOStatus, &
                    AlphaBlank=lAlphaFieldBlanks, AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)

      IsNotOK = .FALSE.
      IsBlank = .FALSE.
      CALL VerifyName(cAlphaArgs(1), WaterEquipment%Name, WaterEquipNum-1, IsNotOK, IsBlank,  TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound = .TRUE.
        IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
      END IF
      WaterEquipment(WaterEquipNum)%Name = cAlphaArgs(1)

      WaterEquipment(WaterEquipNum)%EndUseSubcatName = cAlphaArgs(2)

      WaterEquipment(WaterEquipNum)%PeakVolFlowRate = rNumericArgs(1)

      IF ((NumAlphas > 2) .AND. ( .NOT. lAlphaFieldBlanks(3) )) THEN
        WaterEquipment(WaterEquipNum)%FlowRateFracSchedule = GetScheduleIndex(cAlphaArgs(3))
        ! If no FlowRateFracSchedule, fraction defaults to 1.0

        IF (WaterEquipment(WaterEquipNum)%FlowRateFracSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(3))//'='//TRIM(cAlphaArgs(3)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((NumAlphas > 3) .AND. (.NOT. lAlphaFieldBlanks(4))) THEN
        WaterEquipment(WaterEquipNum)%TargetTempSchedule = GetScheduleIndex(cAlphaArgs(4))

        IF (WaterEquipment(WaterEquipNum)%TargetTempSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(4))//'='//TRIM(cAlphaArgs(4)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((NumAlphas > 4) .AND. (.NOT. lAlphaFieldBlanks(5))) THEN
        WaterEquipment(WaterEquipNum)%HotTempSchedule = GetScheduleIndex(cAlphaArgs(5))
        ! If no HotTempSchedule, there is no hot water.
        ! HotTempSchedule is ignored if connected to a plant loop via WATER USE CONNECTIONS

        IF (WaterEquipment(WaterEquipNum)%HotTempSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(5))//'='//TRIM(cAlphaArgs(5)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((NumAlphas > 5) .AND. ( .NOT. lAlphaFieldBlanks(6))) THEN
        WaterEquipment(WaterEquipNum)%ColdTempSchedule = GetScheduleIndex(cAlphaArgs(6))
        ! If no ColdTempSchedule, temperatures will be calculated by WATER MAINS TEMPERATURES object

        IF (WaterEquipment(WaterEquipNum)%ColdTempSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(6))//'='//TRIM(cAlphaArgs(6)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((NumAlphas > 6) .AND. (.NOT. lAlphaFieldBlanks(7) )) THEN
        WaterEquipment(WaterEquipNum)%Zone = FindItemInList(cAlphaArgs(7), Zone%Name, NumOfZones)

        IF (WaterEquipment(WaterEquipNum)%Zone == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(7))//'='//TRIM(cAlphaArgs(7)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((NumAlphas > 7) .AND. (.NOT. lAlphaFieldBlanks(8) )) THEN
        WaterEquipment(WaterEquipNum)%SensibleFracSchedule = GetScheduleIndex(cAlphaArgs(8))

        IF (WaterEquipment(WaterEquipNum)%SensibleFracSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(8))//'='//TRIM(cAlphaArgs(8)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((NumAlphas > 8) .AND. (.NOT. lAlphaFieldBlanks(9) )) THEN
        WaterEquipment(WaterEquipNum)%LatentFracSchedule = GetScheduleIndex(cAlphaArgs(9))

        IF (WaterEquipment(WaterEquipNum)%LatentFracSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(9))//'='//TRIM(cAlphaArgs(9)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

    END DO ! WaterEquipNum

    IF (ErrorsFound) CALL ShowFatalError('Errors found in processing input for '//TRIM(cCurrentModuleObject))

  END IF

  cCurrentModuleObject = 'WaterUse:Connections'
  NumWaterConnections = GetNumObjectsFound(cCurrentModuleObject)

  IF (NumWaterConnections > 0) THEN
    ALLOCATE(WaterConnections(NumWaterConnections))

    DO WaterConnNum = 1, NumWaterConnections
      CALL GetObjectItem(cCurrentModuleObject, WaterConnNum, cAlphaArgs, NumAlphas, rNumericArgs, NumNumbers, IOStatus, &
                    AlphaBlank=lAlphaFieldBlanks, AlphaFieldnames=cAlphaFieldNames,NumericFieldNames=cNumericFieldNames)

      IsNotOK = .FALSE.
      IsBlank = .FALSE.
      CALL VerifyName(cAlphaArgs(1), WaterConnections%Name, WaterConnNum-1, IsNotOK, IsBlank, TRIM(cCurrentModuleObject)//' Name')
      IF (IsNotOK) THEN
        ErrorsFound = .TRUE.
        IF (IsBlank) cAlphaArgs(1) = 'xxxxx'
      END IF
      WaterConnections(WaterConnNum)%Name = cAlphaArgs(1)

      IF ((.NOT. lAlphaFieldBlanks(2)) .OR. (.NOT. lAlphaFieldBlanks(3))) THEN
        WaterConnections(WaterConnNum)%InletNode = GetOnlySingleNode(cAlphaArgs(2), ErrorsFound, TRIM(cCurrentModuleObject), &
          cAlphaArgs(1), NodeType_Water, NodeConnectionType_Inlet, 1, ObjectIsNotParent)
        WaterConnections(WaterConnNum)%OutletNode = GetOnlySingleNode(cAlphaArgs(3), ErrorsFound, TRIM(cCurrentModuleObject), &
          cAlphaArgs(1), NodeType_Water,NodeConnectionType_Outlet, 1, ObjectIsNotParent)

        ! Check plant connections
        CALL TestCompSet(TRIM(cCurrentModuleObject),cAlphaArgs(1), cAlphaArgs(2), cAlphaArgs(3), 'DHW Nodes')
      ELSE
        ! If no plant nodes are connected, simulate in stand-alone mode.
        WaterConnections(WaterConnNum)%StandAlone = .TRUE.
      END IF

      IF (.NOT. lAlphaFieldBlanks(4) ) THEN
        CALL SetupTankDemandComponent(WaterConnections(WaterConnNum)%Name, TRIM(cCurrentModuleObject), cAlphaArgs(4), ErrorsFound, &
          WaterConnections(WaterConnNum)%SupplyTankNum, WaterConnections(WaterConnNum)%TankDemandID)
      END IF

      IF (.NOT. lAlphaFieldBlanks(5) ) THEN
        CALL SetupTankSupplyComponent(WaterConnections(WaterConnNum)%Name, TRIM(cCurrentModuleObject), cAlphaArgs(5), ErrorsFound, &
          WaterConnections(WaterConnNum)%RecoveryTankNum, WaterConnections(WaterConnNum)%TankSupplyID)
      END IF

      IF (.NOT. lAlphaFieldBlanks(6) ) THEN
        WaterConnections(WaterConnNum)%HotTempSchedule = GetScheduleIndex(cAlphaArgs(6))
        ! If no HotTempSchedule, there is no hot water.
        ! HotTempSchedule is ignored if connected to a plant loop via WATER USE CONNECTIONS

        IF (WaterConnections(WaterConnNum)%HotTempSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(6))//'='//TRIM(cAlphaArgs(6)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF (.NOT. lAlphaFieldBlanks(7) ) THEN
        WaterConnections(WaterConnNum)%ColdTempSchedule = GetScheduleIndex(cAlphaArgs(7))
        ! If no ColdTempSchedule, temperatures will be calculated by WATER MAINS TEMPERATURES object

        IF (WaterConnections(WaterConnNum)%ColdTempSchedule == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(7))//'='//TRIM(cAlphaArgs(7)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        END IF
      END IF

      IF ((.NOT. lAlphaFieldBlanks(8) ) .AND. (cAlphaArgs(8) /= 'NONE')) THEN
        WaterConnections(WaterConnNum)%HeatRecovery = .TRUE.

        SELECT CASE (cAlphaArgs(8))
          CASE ('IDEAL')
            WaterConnections(WaterConnNum)%HeatRecoveryHX = HeatRecoveryHXIdeal
          CASE ('COUNTERFLOW')
            WaterConnections(WaterConnNum)%HeatRecoveryHX = HeatRecoveryHXCounterFlow
          CASE ('CROSSFLOW')
            WaterConnections(WaterConnNum)%HeatRecoveryHX = HeatRecoveryHXCrossFlow
          CASE DEFAULT
            CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(8))//'='//TRIM(cAlphaArgs(8)))
            CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
            ErrorsFound = .TRUE.
        END SELECT

        SELECT CASE (cAlphaArgs(9))
          CASE ('PLANT')
            WaterConnections(WaterConnNum)%HeatRecoveryConfig = HeatRecoveryConfigPlant
          CASE ('EQUIPMENT')
            WaterConnections(WaterConnNum)%HeatRecoveryConfig = HeatRecoveryConfigEquipment
          CASE ('PLANTANDEQUIPMENT')
            WaterConnections(WaterConnNum)%HeatRecoveryConfig = HeatRecoveryConfigPlantAndEquip
          CASE DEFAULT
            CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(9))//'='//TRIM(cAlphaArgs(9)))
            CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
            ErrorsFound = .TRUE.
        END SELECT
      END IF

      WaterConnections(WaterConnNum)%HXUA = rNumericArgs(1)

      ALLOCATE(WaterConnections(WaterConnNum)%WaterEquipment(NumAlphas - 9))

      DO AlphaNum = 10, NumAlphas
        WaterEquipNum = FindItemInList(cAlphaArgs(AlphaNum), WaterEquipment%Name, NumWaterEquipment)

        IF (WaterEquipNum == 0) THEN
          CALL ShowSevereError('Invalid '//TRIM(cAlphaFieldNames(AlphaNum))//'='//TRIM(cAlphaArgs(AlphaNum)))
          CALL ShowContinueError('Entered in '//TRIM(cCurrentModuleObject)//'='//TRIM(cAlphaArgs(1)))
          ErrorsFound = .TRUE.
        ELSE
          IF (WaterEquipment(WaterEquipNum)%Connections > 0) THEN
            CALL ShowSevereError(TRIM(cCurrentModuleObject)//' = '//TRIM(cAlphaArgs(1))// &
              ':  WaterUse:Equipment = '//TRIM(cAlphaArgs(AlphaNum))//' is already referenced by another object.')
            ErrorsFound = .TRUE.
          ELSE
            WaterEquipment(WaterEquipNum)%Connections = WaterConnNum

            WaterConnections(WaterConnNum)%NumWaterEquipment = WaterConnections(WaterConnNum)%NumWaterEquipment + 1
            WaterConnections(WaterConnNum)%WaterEquipment(WaterConnections(WaterConnNum)%NumWaterEquipment) = WaterEquipNum

            WaterConnections(WaterConnNum)%PeakVolFlowRate = WaterConnections(WaterConnNum)%PeakVolFlowRate &
              + WaterEquipment(WaterEquipNum)%PeakVolFlowRate ! this does not include possible multipliers
          END IF
        END IF
      END DO

    END DO ! WaterConnNum

    IF (ErrorsFound) CALL ShowFatalError('Errors found in processing input for '//TRIM(cCurrentModuleObject))

    IF (NumWaterConnections > 0) THEN
      ALLOCATE(CheckEquipName(NumWaterConnections) )
      ALLOCATE(CheckPlantLoop(NumWaterConnections) )
      CheckEquipName = .TRUE.
      CheckPlantLoop = .TRUE.
    ENDIF


  END IF

  ! determine connection's peak mass flow rates.
  IF (NumWaterConnections > 0) THEN
    DO WaterConnNum = 1, NumWaterConnections
      WaterConnections(WaterConnNum)%PeakMassFlowRate = 0.0D0
      Do WaterEquipNum = 1, WaterConnections(WaterConnNum)%NumWaterEquipment
        thisWaterEquipNum = WaterConnections(WaterConnNum)%WaterEquipment(WaterEquipNum)
        IF (WaterEquipment(thisWaterEquipNum)%zone > 0) then
          WaterConnections(WaterConnNum)%PeakMassFlowRate = WaterConnections(WaterConnNum)%PeakMassFlowRate &
           + WaterEquipment(thisWaterEquipNum)%PeakVolFlowRate * RhoH2O(InitConvTemp)                               &
            * Zone(WaterEquipment(thisWaterEquipNum)%zone)%Multiplier                                         &
            * Zone(WaterEquipment(thisWaterEquipNum)%zone)%ListMultiplier
        ELSE ! can't have multipliers
          WaterConnections(WaterConnNum)%PeakMassFlowRate = WaterConnections(WaterConnNum)%PeakMassFlowRate &
           + WaterEquipment(thisWaterEquipNum)%PeakVolFlowRate * RhoH2O(InitConvTemp)
        ENDIF
      ENDDO
      CALL RegisterPlantCompDesignFlow(WaterConnections(WaterConnNum)%InletNode, &
                                WaterConnections(WaterConnNum)%PeakMassFlowRate/RhoH2O(InitConvTemp) )
    ENDDO
  ENDIF

  ! Setup EQUIPMENT report variables (now that connections have been established)
  ! CurrentModuleObject='WaterUse:Equipment'
  DO WaterEquipNum = 1, NumWaterEquipment

    CALL SetupOutputVariable('Water Use Equipment Hot Water Mass Flow Rate [kg/s]', &
      WaterEquipment(WaterEquipNum)%HotMassFlowRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Cold Water Mass Flow Rate [kg/s]', &
      WaterEquipment(WaterEquipNum)%ColdMassFlowRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Total Mass Flow Rate [kg/s]', &
      WaterEquipment(WaterEquipNum)%TotalMassFlowRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)


    CALL SetupOutputVariable('Water Use Equipment Hot Water Volume Flow Rate [m3/s]', &
      WaterEquipment(WaterEquipNum)%HotVolFlowRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Cold Water Volume Flow Rate [m3/s]', &
      WaterEquipment(WaterEquipNum)%ColdVolFlowRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Total Volume Flow Rate [m3/s]', &
      WaterEquipment(WaterEquipNum)%TotalVolFlowRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)


    CALL SetupOutputVariable('Water Use Equipment Hot Water Volume [m3]', &
      WaterEquipment(WaterEquipNum)%HotVolume, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Cold Water Volume [m3]', &
      WaterEquipment(WaterEquipNum)%ColdVolume, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Total Volume [m3]', &
      WaterEquipment(WaterEquipNum)%TotalVolume, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name, &
      ResourceTypeKey='Water', EndUseKey='WATERSYSTEMS', EndUseSubKey=WaterEquipment(WaterEquipNum)%EndUseSubcatName, &
      GroupKey='Plant')
    CALL SetupOutputVariable('Water Use Equipment Mains Water Volume [m3]', &
      WaterEquipment(WaterEquipNum)%TotalVolume, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name, &
      ResourceTypeKey='MainsWater', EndUseKey='WATERSYSTEMS', EndUseSubKey=WaterEquipment(WaterEquipNum)%EndUseSubcatName, &
      GroupKey='Plant')


    CALL SetupOutputVariable('Water Use Equipment Hot Water Temperature [C]', &
      WaterEquipment(WaterEquipNum)%HotTemp, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Cold Water Temperature [C]', &
      WaterEquipment(WaterEquipNum)%ColdTemp, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Target Water Temperature [C]', &
      WaterEquipment(WaterEquipNum)%TargetTemp, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Mixed Water Temperature [C]', &
      WaterEquipment(WaterEquipNum)%MixedTemp, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    CALL SetupOutputVariable('Water Use Equipment Drain Water Temperature [C]', &
      WaterEquipment(WaterEquipNum)%DrainTemp, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)


    CALL SetupOutputVariable('Water Use Equipment Heating Rate [W]', &
      WaterEquipment(WaterEquipNum)%Power, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)

    IF (WaterEquipment(WaterEquipNum)%Connections == 0) THEN
      CALL SetupOutputVariable('Water Use Equipment Heating Energy [J]', &
        WaterEquipment(WaterEquipNum)%Energy, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name, &
        ResourceTypeKey='DISTRICTHEATING', EndUseKey='WATERSYSTEMS', &
        EndUseSubKey=WaterEquipment(WaterEquipNum)%EndUseSubcatName, GroupKey='Plant')

    ELSE IF (WaterConnections(WaterEquipment(WaterEquipNum)%Connections)%StandAlone) THEN
      CALL SetupOutputVariable('Water Use Equipment Heating Energy [J]', &
        WaterEquipment(WaterEquipNum)%Energy, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name, &
        ResourceTypeKey='DISTRICTHEATING', EndUseKey='WATERSYSTEMS', &
        EndUseSubKey=WaterEquipment(WaterEquipNum)%EndUseSubcatName, GroupKey='Plant')

    ELSE  ! The EQUIPMENT is coupled to a plant loop via a CONNECTIONS object
      CALL SetupOutputVariable('Water Use Equipment Heating Energy [J]', &
        WaterEquipment(WaterEquipNum)%Energy, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name, &
        ResourceTypeKey='ENERGYTRANSFER', EndUseKey='WATERSYSTEMS', &
        EndUseSubKey=WaterEquipment(WaterEquipNum)%EndUseSubcatName, GroupKey='Plant')
    END IF

    IF (WaterEquipment(WaterEquipNum)%Zone > 0) THEN
      CALL SetupOutputVariable('Water Use Equipment Zone Sensible Heat Gain Rate [W]', &
        WaterEquipment(WaterEquipNum)%SensibleRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)
      CALL SetupOutputVariable('Water Use Equipment Zone Sensible Heat Gain Energy [J]', &
        WaterEquipment(WaterEquipNum)%SensibleEnergy, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name)

      CALL SetupOutputVariable('Water Use Equipment Zone Latent Gain Rate [W]', &
        WaterEquipment(WaterEquipNum)%LatentRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)
      CALL SetupOutputVariable('Water Use Equipment Zone Latent Gain Energy [J]', &
        WaterEquipment(WaterEquipNum)%LatentEnergy, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name)

      CALL SetupOutputVariable('Water Use Equipment Zone Moisture Gain Mass Flow Rate [kg/s]', &
        WaterEquipment(WaterEquipNum)%MoistureRate, 'System', 'Average', WaterEquipment(WaterEquipNum)%Name)
      CALL SetupOutputVariable('Water Use Equipment Zone Moisture Gain Mass [kg]', &
        WaterEquipment(WaterEquipNum)%MoistureMass, 'System', 'Sum', WaterEquipment(WaterEquipNum)%Name)

      CALL SetupZoneInternalGain(WaterEquipment(WaterEquipNum)%Zone, &
                     'WaterUse:Equipment',  &
                     WaterEquipment(WaterEquipNum)%Name, &
                     IntGainTypeOf_WaterUseEquipment,    &
                     ConvectionGainRate    = WaterEquipment(WaterEquipNum)%SensibleRateNoMultiplier, &
                     LatentGainRate        = WaterEquipment(WaterEquipNum)%LatentRateNoMultiplier)

    END IF

  END DO ! WaterEquipNum


  ! Setup CONNECTIONS report variables (don't put any on meters; they are metered at WATER USE EQUIPMENT level)
  ! CurrentModuleObject='WaterUse:Connections'
  DO WaterConnNum = 1, NumWaterConnections

    CALL SetupOutputVariable('Water Use Connections Hot Water Mass Flow Rate [kg/s]', &
      WaterConnections(WaterConnNum)%HotMassFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Cold Water Mass Flow Rate [kg/s]', &
      WaterConnections(WaterConnNum)%ColdMassFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Total Mass Flow Rate [kg/s]', &
      WaterConnections(WaterConnNum)%TotalMassFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Drain Water Mass Flow Rate [kg/s]', &
      WaterConnections(WaterConnNum)%DrainMassFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Heat Recovery Mass Flow Rate [kg/s]', &
      WaterConnections(WaterConnNum)%RecoveryMassFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)


    CALL SetupOutputVariable('Water Use Connections Hot Water Volume Flow Rate [m3/s]', &
      WaterConnections(WaterConnNum)%HotVolFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Cold Water Volume Flow Rate [m3/s]', &
      WaterConnections(WaterConnNum)%ColdVolFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Total Volume Flow Rate [m3/s]', &
      WaterConnections(WaterConnNum)%TotalVolFlowRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)


    CALL SetupOutputVariable('Water Use Connections Hot Water Volume [m3]', &
      WaterConnections(WaterConnNum)%HotVolume, 'System', 'Sum', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Cold Water Volume [m3]', &
      WaterConnections(WaterConnNum)%ColdVolume, 'System', 'Sum', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Total Volume [m3]', &
      WaterConnections(WaterConnNum)%TotalVolume, 'System', 'Sum', WaterConnections(WaterConnNum)%Name) !, &
     ! ResourceTypeKey='Water', EndUseKey='DHW', EndUseSubKey=EndUseSubcategoryName, GroupKey='Plant')
! tHIS WAS double counting

    CALL SetupOutputVariable('Water Use Connections Hot Water Temperature [C]', &
      WaterConnections(WaterConnNum)%HotTemp, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Cold Water Temperature [C]', &
      WaterConnections(WaterConnNum)%ColdTemp, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Drain Water Temperature [C]', &
      WaterConnections(WaterConnNum)%DrainTemp, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Return Water Temperature [C]', &
      WaterConnections(WaterConnNum)%ReturnTemp, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Waste Water Temperature [C]', &
      WaterConnections(WaterConnNum)%WasteTemp, 'System', 'Average', WaterConnections(WaterConnNum)%Name)


    CALL SetupOutputVariable('Water Use Connections Heat Recovery Water Temperature [C]', &
      WaterConnections(WaterConnNum)%RecoveryTemp, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Heat Recovery Effectiveness []', &
      WaterConnections(WaterConnNum)%Effectiveness, 'System', 'Average', WaterConnections(WaterConnNum)%Name)

    CALL SetupOutputVariable('Water Use Connections Heat Recovery Rate [W]', &
      WaterConnections(WaterConnNum)%RecoveryRate, 'System', 'Average', WaterConnections(WaterConnNum)%Name)
    CALL SetupOutputVariable('Water Use Connections Heat Recovery Energy [J]', &
      WaterConnections(WaterConnNum)%RecoveryEnergy, 'System', 'Sum', WaterConnections(WaterConnNum)%Name)
      ! Does this go on a meter?

    ! To do:  Add report variable for starved flow when tank can't deliver?

    IF (.NOT. WaterConnections(WaterConnNum)%StandAlone) THEN
      CALL SetupOutputVariable('Water Use Connections Plant Hot Water Energy [J]', &
        WaterConnections(WaterConnNum)%Energy, 'System', 'Sum', WaterConnections(WaterConnNum)%Name, &
        ResourceTypeKey='PLANTLOOPHEATINGDEMAND', EndUseKey='WATERSYSTEMS', GroupKey='Plant')
    END IF

  END DO ! WaterConnNum

  RETURN

END SUBROUTINE GetWaterUseInput


SUBROUTINE CalcEquipmentFlowRates(WaterEquipNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculate desired hot and cold water flow rates

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE Psychrometrics, ONLY: RhoH2O
  USE DataEnvironment, ONLY: WaterMainsTemp
  USE DataHeatBalance, ONLY: Zone

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterEquipNum

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: WaterConnNum

          ! FLOW:
  WaterConnNum = WaterEquipment(WaterEquipNum)%Connections

  IF (WaterConnNum > 0) THEN
    ! Get water temperature conditions from the CONNECTIONS object
    WaterEquipment(WaterEquipNum)%ColdTemp = WaterConnections(WaterConnNum)%ColdTemp
    WaterEquipment(WaterEquipNum)%HotTemp = WaterConnections(WaterConnNum)%HotTemp

  ELSE
    ! Get water temperature conditions from the WATER USE EQUIPMENT schedules
    IF (WaterEquipment(WaterEquipNum)%ColdTempSchedule > 0) THEN
      WaterEquipment(WaterEquipNum)%ColdTemp = GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%ColdTempSchedule)
    ELSE  ! If no ColdTempSchedule, use the mains temperature
      WaterEquipment(WaterEquipNum)%ColdTemp = WaterMainsTemp
    END IF

    IF (WaterEquipment(WaterEquipNum)%HotTempSchedule > 0) THEN
      WaterEquipment(WaterEquipNum)%HotTemp = GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%HotTempSchedule)
    ELSE  ! If no HotTempSchedule, use all cold water
      WaterEquipment(WaterEquipNum)%HotTemp = WaterEquipment(WaterEquipNum)%ColdTemp
    END IF
  END IF

  IF (WaterEquipment(WaterEquipNum)%TargetTempSchedule > 0) THEN
    WaterEquipment(WaterEquipNum)%TargetTemp = GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%TargetTempSchedule)
  ELSE  ! If no TargetTempSchedule, use all hot water
    WaterEquipment(WaterEquipNum)%TargetTemp = WaterEquipment(WaterEquipNum)%HotTemp
  END IF

  ! Get the requested total flow rate
  ! 11-17-2006 BG Added multipliers in next block
  IF (WaterEquipment(WaterEquipNum)%zone > 0) THEN
    IF (WaterEquipment(WaterEquipNum)%FlowRateFracSchedule > 0) THEN
      WaterEquipment(WaterEquipNum)%TotalVolFlowRate = WaterEquipment(WaterEquipNum)%PeakVolFlowRate &
        * GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%FlowRateFracSchedule)                &
        * Zone(WaterEquipment(WaterEquipNum)%zone)%Multiplier                                        &
        * Zone(WaterEquipment(WaterEquipNum)%zone)%ListMultiplier
    ELSE
      WaterEquipment(WaterEquipNum)%TotalVolFlowRate = WaterEquipment(WaterEquipNum)%PeakVolFlowRate &
        * Zone(WaterEquipment(WaterEquipNum)%zone)%Multiplier                                        &
        * Zone(WaterEquipment(WaterEquipNum)%zone)%ListMultiplier
    END IF
  ELSE
    IF (WaterEquipment(WaterEquipNum)%FlowRateFracSchedule > 0) THEN
      WaterEquipment(WaterEquipNum)%TotalVolFlowRate = WaterEquipment(WaterEquipNum)%PeakVolFlowRate &
        * GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%FlowRateFracSchedule)
    ELSE
      WaterEquipment(WaterEquipNum)%TotalVolFlowRate = WaterEquipment(WaterEquipNum)%PeakVolFlowRate
    ENDIF
  ENDIF

  WaterEquipment(WaterEquipNum)%TotalMassFlowRate = WaterEquipment(WaterEquipNum)%TotalVolFlowRate * RhoH2O(InitConvTemp)

  ! Calculate hot and cold water mixing at the tap
  IF (WaterEquipment(WaterEquipNum)%TotalMassFlowRate > 0.0d0) THEN
    ! Calculate the flow rates needed to meet the target temperature
    IF (WaterEquipment(WaterEquipNum)%HotTemp == WaterEquipment(WaterEquipNum)%ColdTemp) THEN  ! Avoid divide by zero
      ! There is no hot water
      WaterEquipment(WaterEquipNum)%HotMassFlowRate = 0.0d0

! Need a special case for HotTemp < ColdTemp, due to bad user input  (but could happen in a plant loop accidentally)

    ELSE IF (WaterEquipment(WaterEquipNum)%TargetTemp > WaterEquipment(WaterEquipNum)%HotTemp) THEN
      WaterEquipment(WaterEquipNum)%HotMassFlowRate = WaterEquipment(WaterEquipNum)%TotalMassFlowRate

    ELSE
      WaterEquipment(WaterEquipNum)%HotMassFlowRate = WaterEquipment(WaterEquipNum)%TotalMassFlowRate &
        * (WaterEquipment(WaterEquipNum)%TargetTemp - WaterEquipment(WaterEquipNum)%ColdTemp) &
        / (WaterEquipment(WaterEquipNum)%HotTemp - WaterEquipment(WaterEquipNum)%ColdTemp)
    END IF

    IF (WaterEquipment(WaterEquipNum)%HotMassFlowRate < 0.0d0) THEN
      ! Target temp is colder than the cold water temp; don't allow colder
      WaterEquipment(WaterEquipNum)%HotMassFlowRate = 0.0d0
    END IF

    WaterEquipment(WaterEquipNum)%ColdMassFlowRate = WaterEquipment(WaterEquipNum)%TotalMassFlowRate &
      - WaterEquipment(WaterEquipNum)%HotMassFlowRate

    IF (WaterEquipment(WaterEquipNum)%ColdMassFlowRate < 0.0d0) WaterEquipment(WaterEquipNum)%ColdMassFlowRate = 0.0d0

    WaterEquipment(WaterEquipNum)%MixedTemp = &
      (WaterEquipment(WaterEquipNum)%ColdMassFlowRate * WaterEquipment(WaterEquipNum)%ColdTemp &
      + WaterEquipment(WaterEquipNum)%HotMassFlowRate * WaterEquipment(WaterEquipNum)%HotTemp) &
      / WaterEquipment(WaterEquipNum)%TotalMassFlowRate
  ELSE
    WaterEquipment(WaterEquipNum)%HotMassFlowRate = 0.0d0
    WaterEquipment(WaterEquipNum)%ColdMassFlowRate = 0.0d0
    WaterEquipment(WaterEquipNum)%MixedTemp = WaterEquipment(WaterEquipNum)%TargetTemp
  END IF

  RETURN

END SUBROUTINE CalcEquipmentFlowRates


SUBROUTINE CalcEquipmentDrainTemp(WaterEquipNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculate drainwater temperature and heat and moisture gains to zone.

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE Psychrometrics, ONLY: CPHW, PsyWFnTdbRhPb, PsyRhoAirFnPbTdbW, PsyHfgAirFnWTdb
  USE DataHeatBalFanSys, ONLY: MAT, ZoneAirHumRat
  USE DataHeatBalance, ONLY: ZONE
  USE DataEnvironment, ONLY: OutBaroPress
  USE DataGlobals, ONLY: SecInHour
  Use DataHVACGlobals, ONLY: TimeStepSys

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterEquipNum

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: ZoneNum
  REAL(r64) :: ZoneMAT
  REAL(r64) :: ZoneHumRat
  REAL(r64) :: ZoneHumRatSat
  REAL(r64) :: RhoAirDry
  REAL(r64) :: ZoneMassMax
  REAL(r64) :: FlowMassMax
  REAL(r64) :: MoistureMassMax

          ! FLOW:

  WaterEquipment(WaterEquipNum)%SensibleRate = 0.0d0
  WaterEquipment(WaterEquipNum)%SensibleEnergy = 0.0d0
  WaterEquipment(WaterEquipNum)%LatentRate = 0.0d0
  WaterEquipment(WaterEquipNum)%LatentEnergy = 0.0d0

  IF ((WaterEquipment(WaterEquipNum)%Zone == 0) .OR. (WaterEquipment(WaterEquipNum)%TotalMassFlowRate == 0.0d0)) THEN
    WaterEquipment(WaterEquipNum)%DrainTemp = WaterEquipment(WaterEquipNum)%MixedTemp
    WaterEquipment(WaterEquipNum)%DrainMassFlowRate = WaterEquipment(WaterEquipNum)%TotalMassFlowRate

  ELSE
    ZoneNum = WaterEquipment(WaterEquipNum)%Zone
    ZoneMAT = MAT(ZoneNum)

    IF (WaterEquipment(WaterEquipNum)%SensibleFracSchedule == 0) THEN
      WaterEquipment(WaterEquipNum)%SensibleRate = 0.0d0
      WaterEquipment(WaterEquipNum)%SensibleEnergy = 0.0d0
    ELSE
      WaterEquipment(WaterEquipNum)%SensibleRate = GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%SensibleFracSchedule) &
        * WaterEquipment(WaterEquipNum)%TotalMassFlowRate * CPHW(InitConvTemp) * (WaterEquipment(WaterEquipNum)%MixedTemp &
        - ZoneMAT)
      WaterEquipment(WaterEquipNum)%SensibleEnergy = WaterEquipment(WaterEquipNum)%SensibleRate * TimeStepSys * SecInHour
    END IF

    IF (WaterEquipment(WaterEquipNum)%LatentFracSchedule == 0) THEN
      WaterEquipment(WaterEquipNum)%LatentRate = 0.0d0
      WaterEquipment(WaterEquipNum)%LatentEnergy = 0.0d0
    ELSE
      ZoneHumRat = ZoneAirHumRat(ZoneNum)
      ZoneHumRatSat = PsyWFnTdbRhPb(ZoneMAT, 1.0d0, OutBaroPress, 'CalcEquipmentDrainTemp')  ! Humidratio at 100% relative humidity
      RhoAirDry = PsyRhoAirFnPbTdbW(OutBaroPress, ZoneMAT, 0.0d0)

      ZoneMassMax = (ZoneHumRatSat - ZoneHumRat) * RhoAirDry * Zone(ZoneNum)%Volume  ! Max water that can be evaporated to zone
      FlowMassMax = WaterEquipment(WaterEquipNum)%TotalMassFlowRate * TimeStepSys * SecInHour  ! Max water in flow
      MoistureMassMax = MIN(ZoneMassMax, FlowMassMax)

      WaterEquipment(WaterEquipNum)%MoistureMass = GetCurrentScheduleValue(WaterEquipment(WaterEquipNum)%LatentFracSchedule) &
        * MoistureMassMax
      WaterEquipment(WaterEquipNum)%MoistureRate = WaterEquipment(WaterEquipNum)%MoistureMass / (TimeStepSys * SecInHour)

      WaterEquipment(WaterEquipNum)%LatentRate = WaterEquipment(WaterEquipNum)%MoistureRate * PsyHfgAirFnWTdb(ZoneHumRat, ZoneMAT)
      WaterEquipment(WaterEquipNum)%LatentEnergy = WaterEquipment(WaterEquipNum)%LatentRate * TimeStepSys * SecInHour
    END IF

    WaterEquipment(WaterEquipNum)%DrainMassFlowRate = WaterEquipment(WaterEquipNum)%TotalMassFlowRate &
      - WaterEquipment(WaterEquipNum)%MoistureRate

    IF (WaterEquipment(WaterEquipNum)%DrainMassFlowRate == 0.0d0) THEN
      WaterEquipment(WaterEquipNum)%DrainTemp = WaterEquipment(WaterEquipNum)%MixedTemp
    ELSE
      WaterEquipment(WaterEquipNum)%DrainTemp = (WaterEquipment(WaterEquipNum)%TotalMassFlowRate * CPHW(InitConvTemp) &
        * WaterEquipment(WaterEquipNum)%MixedTemp - WaterEquipment(WaterEquipNum)%SensibleRate &
        - WaterEquipment(WaterEquipNum)%LatentRate) / (WaterEquipment(WaterEquipNum)%DrainMassFlowRate * CPHW(InitConvTemp))
    END IF
  END IF

  RETURN

END SUBROUTINE CalcEquipmentDrainTemp


SUBROUTINE InitConnections(WaterConnNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       Brent Griffith 2010, demand side update
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          !

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE DataGlobals, ONLY: SysSizingCalc, DoingSizing
  USE ScheduleManager, ONLY: GetCurrentScheduleValue
  USE DataLoopNode, ONLY: Node
  USE DataEnvironment, ONLY: WaterMainsTemp
  USE DataWater,   ONLY: WaterStorage
  USE DataHeatBalance, ONLY: Zone
  USE DataPlant,       ONLY: PlantLoop, ScanPlantLoopsForObject, TypeOf_WaterUseConnection
  USE PlantUtilities,  ONLY: InitComponentNodes

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterConnNum

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: InletNode
  INTEGER :: OutletNode
  LOGICAL, SAVE                            :: MyOneTimeFlag = .TRUE. ! one time flag                    !DSU
  LOGICAL, ALLOCATABLE, SAVE, DIMENSION(:) :: SetLoopIndexFlag       ! get loop number flag             !DSU
  LOGICAL :: errFlag

  IF (MyOneTimeFlag) THEN                                                                               !DSU
    ALLOCATE(SetLoopIndexFlag(NumWaterConnections))
    SetLoopIndexFlag = .TRUE.                                                                           !DSU
    MyOneTimeFlag    = .FALSE.                                                                          !DSU
  END IF                                                                                                !DSU

  IF(SetLoopIndexFlag(WaterConnNum))THEN                                                                !DSU
    IF(ALLOCATED(PlantLoop) .and. .NOT. WaterConnections(WaterConnNum)%StandAlone) THEN                 !DSU
      errFlag=.false.
      CALL ScanPlantLoopsForObject(WaterConnections(WaterConnNum)%Name, &                               !DSU
                                   TypeOf_WaterUseConnection, &                                         !DSU
                                   WaterConnections(WaterConnNum)%PlantLoopNum, &                       !DSU
                                   WaterConnections(WaterConnNum)%PlantLoopSide, &                      !DSU
                                   WaterConnections(WaterConnNum)%PlantLoopBranchNum, &                 !DSU
                                   WaterConnections(WaterConnNum)%PlantLoopCompNum,  &                  !DSU
                                   errFlag=errFlag)                                                     !DSU
      IF (errFlag) THEN                                                                                 !DSU
        CALL ShowFatalError('InitConnections: Program terminated due to previous condition(s).')        !DSU
      ENDIF                                                                                             !DSU
      SetLoopIndexFlag(WaterConnNum) = .FALSE.                                                          !DSU
    ENDIF                                                                                               !DSU
    IF (WaterConnections(WaterConnNum)%StandAlone) SetLoopIndexFlag(WaterConnNum) = .FALSE.
  ENDIF

  ! Set the cold water temperature
  IF (WaterConnections(WaterConnNum)%SupplyTankNum > 0) THEN
    WaterConnections(WaterConnNum)%ColdSupplyTemp = WaterStorage(WaterConnections(WaterConnNum)%SupplyTankNum)%Twater

  ELSE IF (WaterConnections(WaterConnNum)%ColdTempSchedule > 0) THEN
    WaterConnections(WaterConnNum)%ColdSupplyTemp = GetCurrentScheduleValue(WaterConnections(WaterConnNum)%ColdTempSchedule)

  ELSE
    WaterConnections(WaterConnNum)%ColdSupplyTemp = WaterMainsTemp
  END IF

  ! Initially set ColdTemp to the ColdSupplyTemp; with heat recovery, ColdTemp will change during iteration
  WaterConnections(WaterConnNum)%ColdTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp

  ! Set the hot water temperature
  IF (WaterConnections(WaterConnNum)%StandAlone) THEN
    IF (WaterConnections(WaterConnNum)%HotTempSchedule > 0) THEN
      WaterConnections(WaterConnNum)%HotTemp = GetCurrentScheduleValue(WaterConnections(WaterConnNum)%HotTempSchedule)
    ELSE
      ! If no HotTempSchedule, use all cold water
      WaterConnections(WaterConnNum)%HotTemp = WaterConnections(WaterConnNum)%ColdTemp
    END IF

  ELSE
    InletNode  = WaterConnections(WaterConnNum)%InletNode
    OutletNode = WaterConnections(WaterConnNum)%OutletNode

    IF (BeginEnvrnFlag .AND. WaterConnections(WaterConnNum)%Init) THEN
      ! Clear node initial conditions
      IF (InletNode > 0 .AND. OutletNode > 0) THEN
        CALL InitComponentNodes(0.d0,WaterConnections(WaterConnNum)%PeakMassFlowRate, &
                                 InletNode,       &
                                 OutletNode,       &
                                 WaterConnections(WaterConnNum)%PlantLoopNum,         &
                                 WaterConnections(WaterConnNum)%PlantLoopSide,        &
                                 WaterConnections(WaterConnNum)%PlantLoopBranchNum,   &
                                 WaterConnections(WaterConnNum)%PlantLoopCompNum)

        WaterConnections(WaterConnNum)%ReturnTemp  = Node(InletNode)%Temp
      END IF

      WaterConnections(WaterConnNum)%Init = .FALSE.
    END IF

    IF (.NOT. BeginEnvrnFlag) WaterConnections(WaterConnNum)%Init = .TRUE.

    IF (InletNode > 0) THEN
      If (.not. DoingSizing) THEN
        WaterConnections(WaterConnNum)%HotTemp = Node(InletNode)%Temp
      ELSE
        ! plant loop will not be running so need a value here.
        ! should change to use tank setpoint but water use connections don't have knowledge of the tank they are fed by
        WaterConnections(WaterConnNum)%HotTemp = 60.0d0  !
      ENDIF
    END IF
  END IF

  RETURN

END SUBROUTINE InitConnections


SUBROUTINE CalcConnectionsFlowRates(WaterConnNum, FirstHVACIteration)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculate summed values for WATER USE CONNECTIONS (to prepare to request flow from plant, and for reporting).

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE DataLoopNode,   ONLY : Node
  USE Psychrometrics, ONLY : RhoH2O
  USE DataWater,      ONLY : WaterStorage
  USE PlantUtilities, ONLY : SetComponentFlowRate

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterConnNum
  LOGICAL, INTENT(IN) :: FirstHVACIteration

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: WaterEquipNum, Loop
  INTEGER :: InletNode
  INTEGER :: OutletNode
  INTEGER :: LoopNum
  INTEGER :: LoopSideNum
  REAL(r64) :: AvailableFraction
  REAL(r64) :: DesiredHotWaterMassFlow ! store original request

          ! FLOW:
  WaterConnections(WaterConnNum)%ColdMassFlowRate = 0.0d0
  WaterConnections(WaterConnNum)%HotMassFlowRate = 0.0d0

  DO Loop = 1, WaterConnections(WaterConnNum)%NumWaterEquipment
    WaterEquipNum = WaterConnections(WaterConnNum)%WaterEquipment(Loop)

    CALL CalcEquipmentFlowRates(WaterEquipNum)

    WaterConnections(WaterConnNum)%ColdMassFlowRate = WaterConnections(WaterConnNum)%ColdMassFlowRate &
      + WaterEquipment(WaterEquipNum)%ColdMassFlowRate
    WaterConnections(WaterConnNum)%HotMassFlowRate = WaterConnections(WaterConnNum)%HotMassFlowRate &
      + WaterEquipment(WaterEquipNum)%HotMassFlowRate
  END DO  ! Loop

  WaterConnections(WaterConnNum)%TotalMassFlowRate = WaterConnections(WaterConnNum)%ColdMassFlowRate &
    + WaterConnections(WaterConnNum)%HotMassFlowRate


  IF (.NOT. WaterConnections(WaterConnNum)%StandAlone) THEN  ! Interact with the plant loop
    InletNode  = WaterConnections(WaterConnNum)%InletNode
    OutletNode = WaterConnections(WaterConnNum)%OutletNode
    LoopNum    = WaterConnections(WaterConnNum)%PlantLoopNum
    LoopSideNum = WaterConnections(WaterConnNum)%PlantLoopSide
    IF (InletNode > 0) THEN
      IF (FirstHVACIteration) THEN
        ! Request the mass flow rate from the demand side manager
!        Node(InletNode)%MassFlowRate = WaterConnections(WaterConnNum)%HotMassFlowRate
!        Node(InletNode)%MassFlowRateMaxAvail = WaterConnections(WaterConnNum)%PeakMassFlowRate
!        Node(InletNode)%MassFlowRateMinAvail = 0.0D0
        CALL  SetComponentFlowRate(WaterConnections(WaterConnNum)%HotMassFlowRate,InletNode,OutletNode,LoopNum,LoopSideNum, &
                                   WaterConnections(WaterConnNum)%PlantLoopBranchNum, &
                                   WaterConnections(WaterConnNum)%PlantLoopCompNum)

      ELSE
        DesiredHotWaterMassFlow = WaterConnections(WaterConnNum)%HotMassFlowRate
        CALL  SetComponentFlowRate(DesiredHotWaterMassFlow,InletNode,OutletNode,LoopNum,LoopSideNum, &
                                   WaterConnections(WaterConnNum)%PlantLoopBranchNum, &
                                   WaterConnections(WaterConnNum)%PlantLoopCompNum)
!DSU3   Node(InletNode)%MassFlowRate = Min(WaterConnections(WaterConnNum)%HotMassFlowRate, Node(InletNode)%MassFlowRateMaxAvail)
!DSU3   Node(InletNode)%MassFlowRate = Max(WaterConnections(WaterConnNum)%HotMassFlowRate, Node(InletNode)%MassFlowRateMinAvail)
        ! readjust if more than actual available mass flow rate determined by the demand side manager
        IF ((WaterConnections(WaterConnNum)%HotMassFlowRate /= DesiredHotWaterMassFlow) &
          .AND. (WaterConnections(WaterConnNum)%HotMassFlowRate > 0.0d0)) THEN ! plant didn't give what was asked for

       !DSU3   Node(InletNode)%MassFlowRate = Node(InletNode)%MassFlowRateMaxAvail

          AvailableFraction = DesiredHotWaterMassFlow / WaterConnections(WaterConnNum)%HotMassFlowRate

      !DSU3    WaterConnections(WaterConnNum)%HotMassFlowRate = Node(InletNode)%MassFlowRateMaxAvail
          WaterConnections(WaterConnNum)%ColdMassFlowRate = WaterConnections(WaterConnNum)%TotalMassFlowRate &
            - WaterConnections(WaterConnNum)%HotMassFlowRate  ! Preserve the total mass flow rate

          ! Proportionally reduce hot water and increase cold water for all WATER USE EQUIPMENT
          DO Loop = 1, WaterConnections(WaterConnNum)%NumWaterEquipment
            WaterEquipNum = WaterConnections(WaterConnNum)%WaterEquipment(Loop)

            ! Recalculate flow rates for water equipment within connection
            WaterEquipment(WaterEquipNum)%HotMassFlowRate = AvailableFraction * WaterEquipment(WaterEquipNum)%HotMassFlowRate
            WaterEquipment(WaterEquipNum)%ColdMassFlowRate = WaterEquipment(WaterEquipNum)%TotalMassFlowRate &
              - WaterEquipment(WaterEquipNum)%HotMassFlowRate

            ! Recalculate mixed water temperature
            IF (WaterEquipment(WaterEquipNum)%TotalMassFlowRate > 0.0d0) THEN
              WaterEquipment(WaterEquipNum)%MixedTemp = &
                (WaterEquipment(WaterEquipNum)%ColdMassFlowRate * WaterEquipment(WaterEquipNum)%ColdTemp &
                + WaterEquipment(WaterEquipNum)%HotMassFlowRate * WaterEquipment(WaterEquipNum)%HotTemp) &
                / WaterEquipment(WaterEquipNum)%TotalMassFlowRate
            ELSE
              WaterEquipment(WaterEquipNum)%MixedTemp = WaterEquipment(WaterEquipNum)%TargetTemp
            END IF
          END DO  ! Loop
        END IF
      END IF
    END IF
  END IF

  IF (WaterConnections(WaterConnNum)%SupplyTankNum > 0) THEN
    ! Set the demand request for supply water from water storage tank
    WaterConnections(WaterConnNum)%ColdVolFlowRate = WaterConnections(WaterConnNum)%ColdMassFlowRate / RhoH2O(InitConvTemp)
    WaterStorage(WaterConnections(WaterConnNum)%SupplyTankNum)%VdotRequestDemand(WaterConnections(WaterConnNum)%TankDemandID) = &
      WaterConnections(WaterConnNum)%ColdVolFlowRate

    ! Check if cold flow rate should be starved by restricted flow from tank
    ! Currently, the tank flow is not really starved--water continues to flow at the tank water temperature
    ! But the user can see the error by comparing report variables for TankVolFlowRate < ColdVolFlowRate
    WaterConnections(WaterConnNum)%TankVolFlowRate = &
      WaterStorage(WaterConnections(WaterConnNum)%SupplyTankNum)%VdotAvailDemand(WaterConnections(WaterConnNum)%TankDemandID)
    WaterConnections(WaterConnNum)%TankMassFlowRate = WaterConnections(WaterConnNum)%TankVolFlowRate * RhoH2O(InitConvTemp)
  END IF

  RETURN

END SUBROUTINE CalcConnectionsFlowRates


SUBROUTINE CalcConnectionsDrainTemp(WaterConnNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculate

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE Psychrometrics, ONLY: RhoH2O

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterConnNum

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: WaterEquipNum, Loop
  REAL(r64) :: MassFlowTempSum

          ! FLOW:
  WaterConnections(WaterConnNum)%DrainMassFlowRate = 0.0d0
  MassFlowTempSum = 0.0d0

  DO Loop = 1, WaterConnections(WaterConnNum)%NumWaterEquipment
    WaterEquipNum = WaterConnections(WaterConnNum)%WaterEquipment(Loop)

    CALL CalcEquipmentDrainTemp(WaterEquipNum)

    WaterConnections(WaterConnNum)%DrainMassFlowRate = WaterConnections(WaterConnNum)%DrainMassFlowRate &
      + WaterEquipment(WaterEquipNum)%DrainMassFlowRate
    MassFlowTempSum = MassFlowTempSum + WaterEquipment(WaterEquipNum)%DrainMassFlowRate * WaterEquipment(WaterEquipNum)%DrainTemp
  END DO  ! Loop

  IF (WaterConnections(WaterConnNum)%DrainMassFlowRate > 0.0d0) THEN
    WaterConnections(WaterConnNum)%DrainTemp = MassFlowTempSum / WaterConnections(WaterConnNum)%DrainMassFlowRate
  ELSE
    WaterConnections(WaterConnNum)%DrainTemp = WaterConnections(WaterConnNum)%HotTemp
  END IF

  WaterConnections(WaterConnNum)%DrainVolFlowRate = WaterConnections(WaterConnNum)%DrainMassFlowRate * RhoH2O(InitConvTemp)

  RETURN

END SUBROUTINE CalcConnectionsDrainTemp


SUBROUTINE CalcConnectionsHeatRecovery(WaterConnNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculate drainwater heat recovery

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE Psychrometrics, ONLY: CPHW
!unused0909  USE DataEnvironment, ONLY: WaterMainsTemp
  USE DataWater,   ONLY: WaterStorage

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterConnNum

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64) :: CapacityRatio, NTU, ExpVal, HXCapacityRate, DrainCapacityRate, MinCapacityRate

          ! FLOW:
  IF (.NOT. WaterConnections(WaterConnNum)%HeatRecovery) THEN
    WaterConnections(WaterConnNum)%RecoveryTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp
    WaterConnections(WaterConnNum)%ReturnTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp
    WaterConnections(WaterConnNum)%WasteTemp = WaterConnections(WaterConnNum)%DrainTemp

  ELSE IF (WaterConnections(WaterConnNum)%TotalMassFlowRate == 0.0d0) THEN
    WaterConnections(WaterConnNum)%Effectiveness = 0.0d0
    WaterConnections(WaterConnNum)%RecoveryRate = 0.0d0
    WaterConnections(WaterConnNum)%RecoveryTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp
    WaterConnections(WaterConnNum)%ReturnTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp
    WaterConnections(WaterConnNum)%WasteTemp = WaterConnections(WaterConnNum)%DrainTemp

  ELSE  ! WaterConnections(WaterConnNum)%TotalMassFlowRate > 0.0

    SELECT CASE (WaterConnections(WaterConnNum)%HeatRecoveryConfig)
      CASE (HeatRecoveryConfigPlant)
        WaterConnections(WaterConnNum)%RecoveryMassFlowRate = WaterConnections(WaterConnNum)%HotMassFlowRate
      CASE (HeatRecoveryConfigEquipment)
        WaterConnections(WaterConnNum)%RecoveryMassFlowRate = WaterConnections(WaterConnNum)%ColdMassFlowRate
      CASE (HeatRecoveryConfigPlantAndEquip)
        WaterConnections(WaterConnNum)%RecoveryMassFlowRate = WaterConnections(WaterConnNum)%TotalMassFlowRate
    END SELECT

    HXCapacityRate = CPHW(InitConvTemp) * WaterConnections(WaterConnNum)%RecoveryMassFlowRate
    DrainCapacityRate = CPHW(InitConvTemp) * WaterConnections(WaterConnNum)%DrainMassFlowRate
    MinCapacityRate = MIN(DrainCapacityRate, HXCapacityRate)

    SELECT CASE (WaterConnections(WaterConnNum)%HeatRecoveryHX)
      CASE (HeatRecoveryHXIdeal)
        WaterConnections(WaterConnNum)%Effectiveness = 1.0d0

      CASE (HeatRecoveryHXCounterFlow)  ! Unmixed
        CapacityRatio = MinCapacityRate / MAX(DrainCapacityRate, HXCapacityRate)
        NTU = WaterConnections(WaterConnNum)%HXUA / MinCapacityRate
        IF (CapacityRatio == 1.0d0) THEN
          WaterConnections(WaterConnNum)%Effectiveness = NTU / (1.0d0 + NTU)
        ELSE
          ExpVal = EXP(-NTU * (1.0d0 - CapacityRatio))
          WaterConnections(WaterConnNum)%Effectiveness = (1.0d0 - ExpVal) / (1.0d0 - CapacityRatio * ExpVal)
        END IF

      CASE (HeatRecoveryHXCrossFlow)  ! Unmixed
        CapacityRatio = MinCapacityRate / MAX(DrainCapacityRate, HXCapacityRate)
        NTU = WaterConnections(WaterConnNum)%HXUA / MinCapacityRate
        WaterConnections(WaterConnNum)%Effectiveness = 1.0d0 - EXP((NTU ** 0.22d0 / CapacityRatio) * &
          (EXP(-CapacityRatio * NTU ** 0.78d0) - 1.0d0))
    END SELECT

    WaterConnections(WaterConnNum)%RecoveryRate = WaterConnections(WaterConnNum)%Effectiveness * MinCapacityRate * &
      (WaterConnections(WaterConnNum)%DrainTemp - WaterConnections(WaterConnNum)%ColdSupplyTemp)

    WaterConnections(WaterConnNum)%RecoveryTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp + &
      WaterConnections(WaterConnNum)%RecoveryRate / (CPHW(InitConvTemp) * WaterConnections(WaterConnNum)%TotalMassFlowRate)

    WaterConnections(WaterConnNum)%WasteTemp = WaterConnections(WaterConnNum)%DrainTemp - &
      WaterConnections(WaterConnNum)%RecoveryRate / (CPHW(InitConvTemp) * WaterConnections(WaterConnNum)%TotalMassFlowRate)

    IF (WaterConnections(WaterConnNum)%RecoveryTankNum > 0) THEN
      WaterStorage(WaterConnections(WaterConnNum)%RecoveryTankNum)%VdotAvailSupply(WaterConnections(WaterConnNum)%TankSupplyID) &
        = WaterConnections(WaterConnNum)%DrainVolFlowRate
      WaterStorage(WaterConnections(WaterConnNum)%RecoveryTankNum)%TwaterSupply(WaterConnections(WaterConnNum)%TankSupplyID) &
        = WaterConnections(WaterConnNum)%WasteTemp
    END IF

    SELECT CASE (WaterConnections(WaterConnNum)%HeatRecoveryConfig)
      CASE (HeatRecoveryConfigPlant)
        WaterConnections(WaterConnNum)%TempError = 0.0d0  ! No feedback back to the cold supply
        !WaterConnections(WaterConnNum)%ColdTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp
        WaterConnections(WaterConnNum)%ReturnTemp = WaterConnections(WaterConnNum)%RecoveryTemp

      CASE (HeatRecoveryConfigEquipment)
        WaterConnections(WaterConnNum)%TempError = ABS(WaterConnections(WaterConnNum)%ColdTemp &
          - WaterConnections(WaterConnNum)%RecoveryTemp)

        WaterConnections(WaterConnNum)%ColdTemp = WaterConnections(WaterConnNum)%RecoveryTemp
        WaterConnections(WaterConnNum)%ReturnTemp = WaterConnections(WaterConnNum)%ColdSupplyTemp

      CASE (HeatRecoveryConfigPlantAndEquip)
        WaterConnections(WaterConnNum)%TempError = ABS(WaterConnections(WaterConnNum)%ColdTemp &
          - WaterConnections(WaterConnNum)%RecoveryTemp)

        WaterConnections(WaterConnNum)%ColdTemp = WaterConnections(WaterConnNum)%RecoveryTemp
        WaterConnections(WaterConnNum)%ReturnTemp = WaterConnections(WaterConnNum)%RecoveryTemp
    END SELECT
  END IF

  RETURN

END SUBROUTINE CalcConnectionsHeatRecovery


SUBROUTINE UpdateWaterConnections(WaterConnNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Updates the node variables with local variables.

          ! METHODOLOGY EMPLOYED:
          ! Standard EnergyPlus methodology.

          ! USE STATEMENTS:
  USE DataLoopNode, ONLY: Node
  USE PlantUtilities, ONLY: SafeCopyPlantNode

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterConnNum

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: InletNode
  INTEGER :: OutletNode
  INTEGER :: LoopNum

          ! FLOW:
  InletNode  = WaterConnections(WaterConnNum)%InletNode
  OutletNode = WaterConnections(WaterConnNum)%OutletNode
  LoopNum    = WaterConnections(WaterConnNum)%PlantLoopNum

  IF (InletNode > 0 .AND. OutletNode > 0) THEN
    ! Pass all variables from inlet to outlet node
    CALL SafeCopyPlantNode( InletNode, OutletNode, LoopNum )
   ! DSU3 Node(OutletNode) = Node(InletNode)

    ! Set outlet node variables that are possibly changed
    Node(OutletNode)%Temp = WaterConnections(WaterConnNum)%ReturnTemp
    ! should add enthalpy update to return?
  END IF

  RETURN

END SUBROUTINE UpdateWaterConnections

SUBROUTINE ReportStandAloneWaterUse

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         B. Griffith, Peter Graham Ellis
          !       DATE WRITTEN   Nov. 2011
          !       MODIFIED       Brent Griffith, March 2010 added argument
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculates report variables for stand alone water use

          ! METHODOLOGY EMPLOYED:
          ! Standard EnergyPlus methodology.

          ! USE STATEMENTS:
  USE DataGlobals, ONLY: SecInHour
  Use DataHVACGlobals, ONLY: TimeStepSys
  USE Psychrometrics, ONLY: RhoH2O, CPHW

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:


  INTEGER :: WaterEquipNum


          ! FLOW:
  DO WaterEquipNum = 1, NumWaterEquipment
    WaterEquipment(WaterEquipNum)%ColdVolFlowRate = WaterEquipment(WaterEquipNum)%ColdMassFlowRate / RhoH2O(InitConvTemp)
    WaterEquipment(WaterEquipNum)%HotVolFlowRate = WaterEquipment(WaterEquipNum)%HotMassFlowRate / RhoH2O(InitConvTemp)
    WaterEquipment(WaterEquipNum)%TotalVolFlowRate = WaterEquipment(WaterEquipNum)%ColdVolFlowRate &
      + WaterEquipment(WaterEquipNum)%HotVolFlowRate

    WaterEquipment(WaterEquipNum)%ColdVolume = WaterEquipment(WaterEquipNum)%ColdVolFlowRate * TimeStepSys * SecInHour
    WaterEquipment(WaterEquipNum)%HotVolume = WaterEquipment(WaterEquipNum)%HotVolFlowRate * TimeStepSys * SecInHour
    WaterEquipment(WaterEquipNum)%TotalVolume = WaterEquipment(WaterEquipNum)%TotalVolFlowRate * TimeStepSys * SecInHour

    IF (WaterEquipment(WaterEquipNum)%Connections == 0) THEN
      WaterEquipment(WaterEquipNum)%Power = WaterEquipment(WaterEquipNum)%HotMassFlowRate * CPHW(InitConvTemp) &
        * (WaterEquipment(WaterEquipNum)%HotTemp - WaterEquipment(WaterEquipNum)%ColdTemp)
    ELSE
      WaterEquipment(WaterEquipNum)%Power = WaterEquipment(WaterEquipNum)%HotMassFlowRate * CPHW(InitConvTemp) &
        * (WaterEquipment(WaterEquipNum)%HotTemp - WaterConnections(WaterEquipment(WaterEquipNum)%Connections)%ReturnTemp)
    END IF

    WaterEquipment(WaterEquipNum)%Energy = WaterEquipment(WaterEquipNum)%Power * TimeStepSys * SecInHour
  END DO

  RETURN

END SUBROUTINE ReportStandAloneWaterUse

SUBROUTINE ReportWaterUse(WaterConnNum)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED       Brent Griffith, March 2010 added argument
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculates report variables.

          ! METHODOLOGY EMPLOYED:
          ! Standard EnergyPlus methodology.

          ! USE STATEMENTS:
  USE DataGlobals, ONLY: SecInHour
  Use DataHVACGlobals, ONLY: TimeStepSys
  USE Psychrometrics, ONLY: RhoH2O, CPHW

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT(IN) :: WaterConnNum

  INTEGER :: Loop
  INTEGER :: WaterEquipNum


          ! FLOW:
  DO Loop = 1, WaterConnections(WaterConnNum)%NumWaterEquipment
    WaterEquipNum  = WaterConnections(WaterConnNum)%WaterEquipment(Loop)
    WaterEquipment(WaterEquipNum)%ColdVolFlowRate = WaterEquipment(WaterEquipNum)%ColdMassFlowRate / RhoH2O(InitConvTemp)
    WaterEquipment(WaterEquipNum)%HotVolFlowRate = WaterEquipment(WaterEquipNum)%HotMassFlowRate / RhoH2O(InitConvTemp)
    WaterEquipment(WaterEquipNum)%TotalVolFlowRate = WaterEquipment(WaterEquipNum)%ColdVolFlowRate &
      + WaterEquipment(WaterEquipNum)%HotVolFlowRate

    WaterEquipment(WaterEquipNum)%ColdVolume = WaterEquipment(WaterEquipNum)%ColdVolFlowRate * TimeStepSys * SecInHour
    WaterEquipment(WaterEquipNum)%HotVolume = WaterEquipment(WaterEquipNum)%HotVolFlowRate * TimeStepSys * SecInHour
    WaterEquipment(WaterEquipNum)%TotalVolume = WaterEquipment(WaterEquipNum)%TotalVolFlowRate * TimeStepSys * SecInHour

    IF (WaterEquipment(WaterEquipNum)%Connections == 0) THEN
      WaterEquipment(WaterEquipNum)%Power = WaterEquipment(WaterEquipNum)%HotMassFlowRate * CPHW(InitConvTemp) &
        * (WaterEquipment(WaterEquipNum)%HotTemp - WaterEquipment(WaterEquipNum)%ColdTemp)
    ELSE
      WaterEquipment(WaterEquipNum)%Power = WaterEquipment(WaterEquipNum)%HotMassFlowRate * CPHW(InitConvTemp) &
        * (WaterEquipment(WaterEquipNum)%HotTemp - WaterConnections(WaterEquipment(WaterEquipNum)%Connections)%ReturnTemp)
    END IF

    WaterEquipment(WaterEquipNum)%Energy = WaterEquipment(WaterEquipNum)%Power * TimeStepSys * SecInHour
  END DO


  WaterConnections(WaterConnNum)%ColdVolFlowRate = WaterConnections(WaterConnNum)%ColdMassFlowRate / RhoH2O(InitConvTemp)
  WaterConnections(WaterConnNum)%HotVolFlowRate = WaterConnections(WaterConnNum)%HotMassFlowRate / RhoH2O(InitConvTemp)
  WaterConnections(WaterConnNum)%TotalVolFlowRate = WaterConnections(WaterConnNum)%ColdVolFlowRate &
    + WaterConnections(WaterConnNum)%HotVolFlowRate

  WaterConnections(WaterConnNum)%ColdVolume = WaterConnections(WaterConnNum)%ColdVolFlowRate * TimeStepSys * SecInHour
  WaterConnections(WaterConnNum)%HotVolume = WaterConnections(WaterConnNum)%HotVolFlowRate * TimeStepSys * SecInHour
  WaterConnections(WaterConnNum)%TotalVolume = WaterConnections(WaterConnNum)%TotalVolFlowRate * TimeStepSys * SecInHour

  WaterConnections(WaterConnNum)%Power = WaterConnections(WaterConnNum)%HotMassFlowRate * CPHW(InitConvTemp) &
    * (WaterConnections(WaterConnNum)%HotTemp - WaterConnections(WaterConnNum)%ReturnTemp)
  WaterConnections(WaterConnNum)%Energy = WaterConnections(WaterConnNum)%Power * TimeStepSys * SecInHour

  WaterConnections(WaterConnNum)%RecoveryEnergy = WaterConnections(WaterConnNum)%RecoveryRate * TimeStepSys * SecInHour


  RETURN

END SUBROUTINE ReportWaterUse


SUBROUTINE CalcWaterUseZoneGains

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Peter Graham Ellis
          !       DATE WRITTEN   August 2006
          !       MODIFIED
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Calculates the zone internal gains due to water use sensible and latent loads.

          ! METHODOLOGY EMPLOYED:
          !

          ! USE STATEMENTS:
  USE DataGlobals, ONLY: BeginEnvrnFlag
  USE DataHeatBalance, ONLY: ZoneIntGain, Zone

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER :: WaterEquipNum
  INTEGER :: ZoneNum
  LOGICAL, SAVE :: MyEnvrnFlag=.true.

          ! FLOW:
  IF (NumWaterEquipment == 0) RETURN

  IF (BeginEnvrnFlag .and. MyEnvrnFlag) THEN
    WaterEquipment%SensibleRate = 0.0d0
    WaterEquipment%SensibleEnergy = 0.0d0
    WaterEquipment%SensibleRateNoMultiplier = 0.d0
    WaterEquipment%LatentRate = 0.0d0
    WaterEquipment%LatentEnergy = 0.0d0
    WaterEquipment%LatentRateNoMultiplier = 0.d0
    WaterEquipment%MixedTemp = 0.0d0
    WaterEquipment%TotalMassFlowRate = 0.0d0
    WaterEquipment%DrainTemp = 0.0d0
    WaterEquipment%ColdVolFlowRate = 0.0d0
    WaterEquipment%HotVolFlowRate = 0.0d0
    WaterEquipment%TotalVolFlowRate = 0.0d0
    WaterEquipment%ColdMassFlowRate = 0.0d0
    WaterEquipment%HotMassFlowRate = 0.0d0
    MyEnvrnFlag=.false.
  ENDIF

  IF (.not. BeginEnvrnFlag) MyEnvrnFlag=.true.

  DO WaterEquipNum = 1, NumWaterEquipment
    IF (WaterEquipment(WaterEquipNum)%Zone == 0) CYCLE
    ZoneNum = WaterEquipment(WaterEquipNum)%Zone
    WaterEquipment(WaterEquipNum)%SensibleRateNoMultiplier =  WaterEquipment(WaterEquipNum)%SensibleRate  &
          / ( Zone(ZoneNum)%Multiplier                             & ! CR7401, back out multipliers
              * Zone(ZoneNum)%ListMultiplier)
    WaterEquipment(WaterEquipNum)%LatentRateNoMultiplier =  WaterEquipment(WaterEquipNum)%LatentRate  &
          / ( Zone(ZoneNum)%Multiplier                             & ! CR7401, back out multipliers
              * Zone(ZoneNum)%ListMultiplier)
  END DO

!  ! this routine needs to model approx zone gains for use during sizing
!  IF(DoingSizing)THEN
!    DO WaterEquipNum = 1, NumWaterEquipment
!      WaterEquipment(WaterEquipNum)%SensibleRateNoMultiplier =
!      WaterEquipment(WaterEquipNum)%LatentRateNoMultiplier   =
!    END DO
!  ENDIF

  RETURN

END SUBROUTINE CalcWaterUseZoneGains

!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!

END MODULE WaterUse

AirflowNetworkBalanceManager.f90 AirflowNetworkSolver.f90 BaseboardRadiator.f90 BaseboardRadiatorElectric.f90 BaseboardRadiatorSteam.f90 BaseboardRadiatorWater.f90 BranchInputManager.f90 BranchNodeConnections.f90 ConductionTransferFunctionCalc.f90 CoolTower.f90 CostEstimateManager.f90 CurveManager.f90 CVFOnlyRoutines.f90 DataAirflowNetwork.f90 DataAirLoop.f90 DataAirSystems.f90 DataBranchAirLoopPlant.f90 DataBranchNodeConnections.f90 DataBSDFWindow.f90 DataComplexFenestration.f90 DataContaminantBalance.f90 DataConvergParams.f90 DataConversions.f90 DataCostEstimate.f90 DataDaylighting.f90 DataDaylightingDevices.f90 Datadefineequip.f90 DataDElight.f90 DataEnvironment.f90 DataEquivalentLayerWindow.f90 DataErrorTracking.f90 DataGenerators.f90 DataGlobalConstants.f90 DataGlobals.f90 DataHeatBalance.f90 DataHeatBalFanSys.f90 DataHeatBalSurface.f90 DataHVACControllers.f90 DataHVACGlobals.f90 DataInterfaces.f90 DataIPShortCuts.f90 DataLoopNode.f90 DataMoistureBalance.f90 DataMoistureBalanceEMPD.f90 DataOutputs.f90 DataPhotovoltaics.f90 DataPlant.f90 DataPlantPipingSystems.f90 DataPrecisionGlobals.f90 DataReportingFlags.f90 DataRoomAir.f90 DataRootFinder.f90 DataRuntimeLanguage.f90 DataShadowingCombinations.f90 DataSizing.f90 DataStringGlobals.f90 DataSurfaceColors.f90 DataSurfaceLists.f90 DataSurfaces.f90 DataSystemVariables.f90 DataTimings.f90 DataUCSDSharedData.f90 DataVectorTypes.f90 DataViewFactorInformation.f90 DataWater.f90 DataZoneControls.f90 DataZoneEnergyDemands.f90 DataZoneEquipment.f90 DaylightingDevices.f90 DaylightingManager.f90 DElightManagerF.f90 DElightManagerF_NO.f90 DemandManager.f90 DesiccantDehumidifiers.f90 DirectAir.f90 DisplayRoutines.f90 DXCoil.f90 EarthTube.f90 EconomicLifeCycleCost.f90 EconomicTariff.f90 EcoRoof.f90 ElectricPowerGenerators.f90 ElectricPowerManager.f90 EMSManager.f90 EnergyPlus.f90 ExteriorEnergyUseManager.f90 ExternalInterface_NO.f90 FanCoilUnits.f90 FaultsManager.f90 FluidProperties.f90 General.f90 GeneralRoutines.f90 GlobalNames.f90 HeatBalanceAirManager.f90 HeatBalanceConvectionCoeffs.f90 HeatBalanceHAMTManager.f90 HeatBalanceInternalHeatGains.f90 HeatBalanceIntRadExchange.f90 HeatBalanceManager.f90 HeatBalanceMovableInsulation.f90 HeatBalanceSurfaceManager.f90 HeatBalFiniteDifferenceManager.f90 HeatRecovery.f90 Humidifiers.f90 HVACControllers.f90 HVACCooledBeam.f90 HVACDualDuctSystem.f90 HVACDuct.f90 HVACDXSystem.f90 HVACEvapComponent.f90 HVACFanComponent.f90 HVACFurnace.f90 HVACHeatingCoils.f90 HVACHXAssistedCoolingCoil.f90 HVACInterfaceManager.f90 HVACManager.f90 HVACMixerComponent.f90 HVACMultiSpeedHeatPump.f90 HVACSingleDuctInduc.f90 HVACSingleDuctSystem.f90 HVACSplitterComponent.f90 HVACStandAloneERV.f90 HVACSteamCoilComponent.f90 HVACTranspiredCollector.f90 HVACUnitaryBypassVAV.f90 HVACUnitarySystem.f90 HVACVariableRefrigerantFlow.f90 HVACWaterCoilComponent.f90 HVACWatertoAir.f90 HVACWatertoAirMultiSpeedHP.f90 InputProcessor.f90 MatrixDataManager.f90 MixedAir.f90 MoistureBalanceEMPDManager.f90 NodeInputManager.f90 NonZoneEquipmentManager.f90 OutAirNodeManager.f90 OutdoorAirUnit.f90 OutputProcessor.f90 OutputReportPredefined.f90 OutputReports.f90 OutputReportTabular.f90 PackagedTerminalHeatPump.f90 PackagedThermalStorageCoil.f90 Photovoltaics.f90 PhotovoltaicThermalCollectors.f90 PlantAbsorptionChillers.f90 PlantBoilers.f90 PlantBoilersSteam.f90 PlantCentralGSHP.f90 PlantChillers.f90 PlantCondLoopOperation.f90 PlantCondLoopTowers.f90 PlantEIRChillers.f90 PlantEvapFluidCoolers.f90 PlantExhaustAbsorptionChiller.f90 PlantFluidCoolers.f90 PlantGasAbsorptionChiller.f90 PlantGroundHeatExchangers.f90 PlantHeatExchanger.f90 PlantIceThermalStorage.f90 PlantLoadProfile.f90 PlantLoopEquipment.f90 PlantLoopSolver.f90 PlantManager.f90 PlantOutsideEnergySources.f90 PlantPipeHeatTransfer.f90 PlantPipes.f90 PlantPipingSystemManager.f90 PlantPondGroundHeatExchanger.f90 PlantPressureSystem.f90 PlantPumps.f90 PlantSolarCollectors.f90 PlantSurfaceGroundHeatExchanger.f90 PlantUtilities.f90 PlantValves.f90 PlantWaterSources.f90 PlantWaterThermalTank.f90 PlantWatertoWaterGSHP.f90 PlantWaterUse.f90 PollutionAnalysisModule.f90 PoweredInductionUnits.f90 PsychRoutines.f90 Purchasedairmanager.f90 RadiantSystemHighTemp.f90 RadiantSystemLowTemp.f90 RefrigeratedCase.f90 ReportSizingManager.f90 ReturnAirPath.f90 RoomAirManager.f90 RoomAirModelCrossVent.f90 RoomAirModelDisplacementVent.f90 RoomAirModelMundt.f90 RoomAirModelUFAD.f90 RoomAirModelUserTempPattern.f90 RootFinder.f90 RuntimeLanguageProcessor.f90 ScheduleManager.f90 SetPointManager.f90 SimAirServingZones.f90 SimulationManager.f90 SizingManager.f90 SolarReflectionManager.f90 SolarShading.f90 SortAndStringUtilities.f90 sqlite3.c SQLiteCRoutines.c SQLiteFortranRoutines.f90 SQLiteFortranRoutines_NO.f90 StandardRatings.f90 SurfaceGeometry.f90 SystemAvailabilityManager.f90 SystemReports.f90 TarcogComplexFenestration.f90 ThermalChimney.f90 ThermalComfort.f90 UnitHeater.f90 UnitVentilator.f90 UserDefinedComponents.f90 UtilityRoutines.f90 VectorUtilities.f90 VentilatedSlab.f90 WaterManager.f90 WeatherManager.f90 WindowAC.f90 WindowComplexManager.f90 WindowEquivalentLayer.f90 WindowManager.f90 WindTurbine.f90 Zoneairloopequipmentmanager.f90 ZoneContaminantPredictorCorrector.f90 ZoneDehumidifier.f90 Zoneequipmentmanager.f90 ZonePlenumComponent.f90 ZoneTempPredictorCorrector.f90