sourcefile~~hvacdxsystem.f90~~EfferentGraph sourcefile~hvacdxsystem.f90 HVACDXSystem.f90 sourcefile~schedulemanager.f90 ScheduleManager.f90 sourcefile~schedulemanager.f90->sourcefile~hvacdxsystem.f90 sourcefile~packagedthermalstoragecoil.f90 PackagedThermalStorageCoil.f90 sourcefile~schedulemanager.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dxcoil.f90 DXCoil.f90 sourcefile~schedulemanager.f90->sourcefile~dxcoil.f90 sourcefile~nodeinputmanager.f90 NodeInputManager.f90 sourcefile~schedulemanager.f90->sourcefile~nodeinputmanager.f90 sourcefile~emsmanager.f90 EMSManager.f90 sourcefile~schedulemanager.f90->sourcefile~emsmanager.f90 sourcefile~hvacwatertoairmultispeedhp.f90 HVACWatertoAirMultiSpeedHP.f90 sourcefile~schedulemanager.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~datazoneequipment.f90 DataZoneEquipment.f90 sourcefile~schedulemanager.f90->sourcefile~datazoneequipment.f90 sourcefile~watermanager.f90 WaterManager.f90 sourcefile~schedulemanager.f90->sourcefile~watermanager.f90 sourcefile~plantwaterthermaltank.f90 PlantWaterThermalTank.f90 sourcefile~schedulemanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~sqlitefortranroutines.f90 SQLiteFortranRoutines.f90 sourcefile~schedulemanager.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~hvacfancomponent.f90 HVACFanComponent.f90 sourcefile~schedulemanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~refrigeratedcase.f90 RefrigeratedCase.f90 sourcefile~schedulemanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~hvacwatercoilcomponent.f90 HVACWaterCoilComponent.f90 sourcefile~schedulemanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~heatrecovery.f90 HeatRecovery.f90 sourcefile~schedulemanager.f90->sourcefile~heatrecovery.f90 sourcefile~setpointmanager.f90 SetPointManager.f90 sourcefile~schedulemanager.f90->sourcefile~setpointmanager.f90 sourcefile~outputprocessor.f90 OutputProcessor.f90 sourcefile~schedulemanager.f90->sourcefile~outputprocessor.f90 sourcefile~dataloopnode.f90 DataLoopNode.f90 sourcefile~dataloopnode.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataloopnode.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataloopnode.f90->sourcefile~dxcoil.f90 sourcefile~hvachxassistedcoolingcoil.f90 HVACHXAssistedCoolingCoil.f90 sourcefile~dataloopnode.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataloopnode.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataloopnode.f90->sourcefile~emsmanager.f90 sourcefile~branchnodeconnections.f90 BranchNodeConnections.f90 sourcefile~dataloopnode.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataloopnode.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataloopnode.f90->sourcefile~datazoneequipment.f90 sourcefile~outairnodemanager.f90 OutAirNodeManager.f90 sourcefile~dataloopnode.f90->sourcefile~outairnodemanager.f90 sourcefile~curvemanager.f90 CurveManager.f90 sourcefile~dataloopnode.f90->sourcefile~curvemanager.f90 sourcefile~dataplant.f90 DataPlant.f90 sourcefile~dataloopnode.f90->sourcefile~dataplant.f90 sourcefile~dataloopnode.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~branchinputmanager.f90 BranchInputManager.f90 sourcefile~dataloopnode.f90->sourcefile~branchinputmanager.f90 sourcefile~dataloopnode.f90->sourcefile~hvacfancomponent.f90 sourcefile~plantutilities.f90 PlantUtilities.f90 sourcefile~dataloopnode.f90->sourcefile~plantutilities.f90 sourcefile~plantsolarcollectors.f90 PlantSolarCollectors.f90 sourcefile~dataloopnode.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataloopnode.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataloopnode.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataloopnode.f90->sourcefile~heatrecovery.f90 sourcefile~dataloopnode.f90->sourcefile~setpointmanager.f90 sourcefile~packagedthermalstoragecoil.f90->sourcefile~hvacdxsystem.f90 sourcefile~datahvacglobals.f90 DataHVACGlobals.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacdxsystem.f90 sourcefile~datahvacglobals.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~datahvacglobals.f90->sourcefile~dxcoil.f90 sourcefile~general.f90 General.f90 sourcefile~datahvacglobals.f90->sourcefile~general.f90 sourcefile~datahvacglobals.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~datahvacglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~datahvacglobals.f90->sourcefile~watermanager.f90 sourcefile~datahvacglobals.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datahvacglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~datahvacglobals.f90->sourcefile~plantsolarcollectors.f90 sourcefile~datahvacglobals.f90->sourcefile~refrigeratedcase.f90 sourcefile~standardratings.f90 StandardRatings.f90 sourcefile~datahvacglobals.f90->sourcefile~standardratings.f90 sourcefile~datahvacglobals.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datahvacglobals.f90->sourcefile~heatrecovery.f90 sourcefile~datahvacglobals.f90->sourcefile~setpointmanager.f90 sourcefile~runtimelanguageprocessor.f90 RuntimeLanguageProcessor.f90 sourcefile~datahvacglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dxcoil.f90->sourcefile~hvacdxsystem.f90 sourcefile~dxcoil.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dxcoil.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dxcoil.f90->sourcefile~heatrecovery.f90 sourcefile~general.f90->sourcefile~hvacdxsystem.f90 sourcefile~general.f90->sourcefile~schedulemanager.f90 sourcefile~general.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~general.f90->sourcefile~dxcoil.f90 sourcefile~general.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~psychroutines.f90 PsychRoutines.f90 sourcefile~general.f90->sourcefile~psychroutines.f90 sourcefile~general.f90->sourcefile~nodeinputmanager.f90 sourcefile~general.f90->sourcefile~emsmanager.f90 sourcefile~general.f90->sourcefile~branchnodeconnections.f90 sourcefile~general.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataheatbalance.f90 DataHeatBalance.f90 sourcefile~general.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90 DataEnvironment.f90 sourcefile~general.f90->sourcefile~dataenvironment.f90 sourcefile~general.f90->sourcefile~datazoneequipment.f90 sourcefile~reportsizingmanager.f90 ReportSizingManager.f90 sourcefile~general.f90->sourcefile~reportsizingmanager.f90 sourcefile~general.f90->sourcefile~watermanager.f90 sourcefile~general.f90->sourcefile~curvemanager.f90 sourcefile~general.f90->sourcefile~dataplant.f90 sourcefile~fluidproperties.f90 FluidProperties.f90 sourcefile~general.f90->sourcefile~fluidproperties.f90 sourcefile~general.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~general.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~general.f90->sourcefile~branchinputmanager.f90 sourcefile~general.f90->sourcefile~hvacfancomponent.f90 sourcefile~general.f90->sourcefile~plantutilities.f90 sourcefile~general.f90->sourcefile~plantsolarcollectors.f90 sourcefile~general.f90->sourcefile~refrigeratedcase.f90 sourcefile~general.f90->sourcefile~standardratings.f90 sourcefile~general.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~general.f90->sourcefile~heatrecovery.f90 sourcefile~general.f90->sourcefile~setpointmanager.f90 sourcefile~general.f90->sourcefile~outputprocessor.f90 sourcefile~general.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~hvachxassistedcoolingcoil.f90->sourcefile~hvacdxsystem.f90 sourcefile~psychroutines.f90->sourcefile~hvacdxsystem.f90 sourcefile~psychroutines.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~psychroutines.f90->sourcefile~dxcoil.f90 sourcefile~psychroutines.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~psychroutines.f90->sourcefile~nodeinputmanager.f90 sourcefile~psychroutines.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~psychroutines.f90->sourcefile~outairnodemanager.f90 sourcefile~psychroutines.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~psychroutines.f90->sourcefile~hvacfancomponent.f90 sourcefile~psychroutines.f90->sourcefile~plantsolarcollectors.f90 sourcefile~psychroutines.f90->sourcefile~refrigeratedcase.f90 sourcefile~psychroutines.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~psychroutines.f90->sourcefile~heatrecovery.f90 sourcefile~psychroutines.f90->sourcefile~setpointmanager.f90 sourcefile~psychroutines.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataprecisionglobals.f90 DataPrecisionGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataprecisionglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataprecisionglobals.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dxcoil.f90 sourcefile~dataprecisionglobals.f90->sourcefile~general.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataprecisionglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90 DataGlobals.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataglobals.f90 sourcefile~inputprocessor.f90 InputProcessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataipshortcuts.f90 DataIPShortCuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataprecisionglobals.f90->sourcefile~emsmanager.f90 sourcefile~datainterfaces.f90 DataInterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datainterfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataairloop.f90 DataAirLoop.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairloop.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataenvironment.f90 sourcefile~datasystemvariables.f90 DataSystemVariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~datasizing.f90 DataSizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasizing.f90 sourcefile~dataprecisionglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~globalnames.f90 GlobalNames.f90 sourcefile~dataprecisionglobals.f90->sourcefile~globalnames.f90 sourcefile~dataairsystems.f90 DataAirSystems.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataprecisionglobals.f90->sourcefile~watermanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataprecisionglobals.f90->sourcefile~curvemanager.f90 sourcefile~datawater.f90 DataWater.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datawater.f90 sourcefile~outputreportpredefined.f90 OutputReportPredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataplant.f90 sourcefile~databranchairloopplant.f90 DataBranchAirLoopPlant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataprecisionglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataprecisionglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasurfaces.f90 DataSurfaces.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataroomair.f90 DataRoomAir.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataroomair.f90 sourcefile~datavectortypes.f90 DataVectorTypes.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datavectortypes.f90 sourcefile~databsdfwindow.f90 DataBSDFWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~datacontaminantbalance.f90 DataContaminantBalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataprecisionglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataerrortracking.f90 DataErrorTracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataerrortracking.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataprecisionglobals.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataprecisionglobals.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataheatbalfansys.f90 DataHeatBalFanSys.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataheatbalfansys.f90 sourcefile~dataairflownetwork.f90 DataAirflowNetwork.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataairflownetwork.f90 sourcefile~datazoneenergydemands.f90 DataZoneEnergyDemands.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazoneenergydemands.f90 sourcefile~dataprecisionglobals.f90->sourcefile~standardratings.f90 sourcefile~dataruntimelanguage.f90 DataRuntimeLanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataprecisionglobals.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataprecisionglobals.f90->sourcefile~heatrecovery.f90 sourcefile~dataprecisionglobals.f90->sourcefile~setpointmanager.f90 sourcefile~datazonecontrols.f90 DataZoneControls.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~dataprecisionglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataprecisionglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datacomplexfenestration.f90 DataComplexFenestration.f90 sourcefile~dataprecisionglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataequivalentlayerwindow.f90 DataEquivalentLayerWindow.f90 sourcefile~dataprecisionglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~dataglobals.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataglobals.f90->sourcefile~schedulemanager.f90 sourcefile~dataglobals.f90->sourcefile~dataloopnode.f90 sourcefile~dataglobals.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataglobals.f90->sourcefile~datahvacglobals.f90 sourcefile~dataglobals.f90->sourcefile~dxcoil.f90 sourcefile~dataglobals.f90->sourcefile~general.f90 sourcefile~dataglobals.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataglobals.f90->sourcefile~psychroutines.f90 sourcefile~dataglobals.f90->sourcefile~inputprocessor.f90 sourcefile~dataglobals.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~dataipshortcuts.f90 sourcefile~dataglobals.f90->sourcefile~emsmanager.f90 sourcefile~dataglobals.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataglobals.f90->sourcefile~dataheatbalance.f90 sourcefile~dataglobals.f90->sourcefile~dataairloop.f90 sourcefile~dataglobals.f90->sourcefile~dataenvironment.f90 sourcefile~dataglobals.f90->sourcefile~datazoneequipment.f90 sourcefile~dataglobals.f90->sourcefile~datasizing.f90 sourcefile~dataglobals.f90->sourcefile~reportsizingmanager.f90 sourcefile~dataglobals.f90->sourcefile~globalnames.f90 sourcefile~dataglobals.f90->sourcefile~dataairsystems.f90 sourcefile~dataglobals.f90->sourcefile~watermanager.f90 sourcefile~dataglobals.f90->sourcefile~outairnodemanager.f90 sourcefile~dataglobals.f90->sourcefile~curvemanager.f90 sourcefile~dataglobals.f90->sourcefile~datawater.f90 sourcefile~dataglobals.f90->sourcefile~outputreportpredefined.f90 sourcefile~dataglobals.f90->sourcefile~dataplant.f90 sourcefile~dataglobals.f90->sourcefile~databranchairloopplant.f90 sourcefile~dataglobals.f90->sourcefile~fluidproperties.f90 sourcefile~dataglobals.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataglobals.f90->sourcefile~datasurfaces.f90 sourcefile~dataglobals.f90->sourcefile~dataroomair.f90 sourcefile~dataglobals.f90->sourcefile~databsdfwindow.f90 sourcefile~dataglobals.f90->sourcefile~datacontaminantbalance.f90 sourcefile~dataglobals.f90->sourcefile~branchinputmanager.f90 sourcefile~dataglobals.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataglobals.f90->sourcefile~plantutilities.f90 sourcefile~dataglobals.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataglobals.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataglobals.f90->sourcefile~dataairflownetwork.f90 sourcefile~dataglobals.f90->sourcefile~standardratings.f90 sourcefile~databranchnodeconnections.f90 DataBranchNodeConnections.f90 sourcefile~dataglobals.f90->sourcefile~databranchnodeconnections.f90 sourcefile~dataglobals.f90->sourcefile~dataruntimelanguage.f90 sourcefile~dataglobals.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataglobals.f90->sourcefile~heatrecovery.f90 sourcefile~dataglobals.f90->sourcefile~setpointmanager.f90 sourcefile~dataglobals.f90->sourcefile~datazonecontrols.f90 sourcefile~sortandstringutilities.f90 SortAndStringUtilities.f90 sourcefile~dataglobals.f90->sourcefile~sortandstringutilities.f90 sourcefile~dataoutputs.f90 DataOutputs.f90 sourcefile~dataglobals.f90->sourcefile~dataoutputs.f90 sourcefile~dataglobals.f90->sourcefile~outputprocessor.f90 sourcefile~dataglobalconstants.f90 DataGlobalConstants.f90 sourcefile~dataglobals.f90->sourcefile~dataglobalconstants.f90 sourcefile~dataglobals.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataglobals.f90->sourcefile~datacomplexfenestration.f90 sourcefile~dataglobals.f90->sourcefile~dataequivalentlayerwindow.f90 sourcefile~inputprocessor.f90->sourcefile~hvacdxsystem.f90 sourcefile~inputprocessor.f90->sourcefile~schedulemanager.f90 sourcefile~inputprocessor.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~inputprocessor.f90->sourcefile~dxcoil.f90 sourcefile~inputprocessor.f90->sourcefile~general.f90 sourcefile~inputprocessor.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~inputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~inputprocessor.f90->sourcefile~branchnodeconnections.f90 sourcefile~inputprocessor.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~inputprocessor.f90->sourcefile~dataheatbalance.f90 sourcefile~inputprocessor.f90->sourcefile~datazoneequipment.f90 sourcefile~inputprocessor.f90->sourcefile~globalnames.f90 sourcefile~inputprocessor.f90->sourcefile~watermanager.f90 sourcefile~inputprocessor.f90->sourcefile~outairnodemanager.f90 sourcefile~inputprocessor.f90->sourcefile~curvemanager.f90 sourcefile~inputprocessor.f90->sourcefile~dataplant.f90 sourcefile~inputprocessor.f90->sourcefile~fluidproperties.f90 sourcefile~inputprocessor.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~inputprocessor.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~inputprocessor.f90->sourcefile~branchinputmanager.f90 sourcefile~inputprocessor.f90->sourcefile~hvacfancomponent.f90 sourcefile~inputprocessor.f90->sourcefile~plantsolarcollectors.f90 sourcefile~inputprocessor.f90->sourcefile~refrigeratedcase.f90 sourcefile~inputprocessor.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~inputprocessor.f90->sourcefile~heatrecovery.f90 sourcefile~inputprocessor.f90->sourcefile~setpointmanager.f90 sourcefile~inputprocessor.f90->sourcefile~outputprocessor.f90 sourcefile~inputprocessor.f90->sourcefile~dataglobalconstants.f90 sourcefile~inputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacdxsystem.f90 sourcefile~nodeinputmanager.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~nodeinputmanager.f90->sourcefile~dxcoil.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~nodeinputmanager.f90->sourcefile~datazoneequipment.f90 sourcefile~nodeinputmanager.f90->sourcefile~outairnodemanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~nodeinputmanager.f90->sourcefile~branchinputmanager.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~plantsolarcollectors.f90 sourcefile~nodeinputmanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~nodeinputmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~nodeinputmanager.f90->sourcefile~heatrecovery.f90 sourcefile~nodeinputmanager.f90->sourcefile~setpointmanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataipshortcuts.f90->sourcefile~schedulemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataipshortcuts.f90->sourcefile~general.f90 sourcefile~dataipshortcuts.f90->sourcefile~inputprocessor.f90 sourcefile~dataipshortcuts.f90->sourcefile~curvemanager.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataipshortcuts.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataipshortcuts.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataipshortcuts.f90->sourcefile~heatrecovery.f90 sourcefile~dataipshortcuts.f90->sourcefile~outputprocessor.f90 sourcefile~emsmanager.f90->sourcefile~hvacdxsystem.f90 sourcefile~emsmanager.f90->sourcefile~dxcoil.f90 sourcefile~emsmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~emsmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~emsmanager.f90->sourcefile~heatrecovery.f90 sourcefile~emsmanager.f90->sourcefile~setpointmanager.f90 sourcefile~datainterfaces.f90->sourcefile~hvacdxsystem.f90 sourcefile~datainterfaces.f90->sourcefile~schedulemanager.f90 sourcefile~datainterfaces.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~datainterfaces.f90->sourcefile~dxcoil.f90 sourcefile~datainterfaces.f90->sourcefile~general.f90 sourcefile~datainterfaces.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~datainterfaces.f90->sourcefile~psychroutines.f90 sourcefile~datainterfaces.f90->sourcefile~inputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~nodeinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~emsmanager.f90 sourcefile~datainterfaces.f90->sourcefile~branchnodeconnections.f90 sourcefile~datainterfaces.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~datainterfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datainterfaces.f90->sourcefile~dataenvironment.f90 sourcefile~datainterfaces.f90->sourcefile~datazoneequipment.f90 sourcefile~datainterfaces.f90->sourcefile~reportsizingmanager.f90 sourcefile~datainterfaces.f90->sourcefile~globalnames.f90 sourcefile~datainterfaces.f90->sourcefile~watermanager.f90 sourcefile~datainterfaces.f90->sourcefile~outairnodemanager.f90 sourcefile~datainterfaces.f90->sourcefile~curvemanager.f90 sourcefile~datainterfaces.f90->sourcefile~dataplant.f90 sourcefile~datainterfaces.f90->sourcefile~fluidproperties.f90 sourcefile~datainterfaces.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datainterfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datainterfaces.f90->sourcefile~branchinputmanager.f90 sourcefile~datainterfaces.f90->sourcefile~hvacfancomponent.f90 sourcefile~datainterfaces.f90->sourcefile~plantutilities.f90 sourcefile~datainterfaces.f90->sourcefile~plantsolarcollectors.f90 sourcefile~datainterfaces.f90->sourcefile~refrigeratedcase.f90 sourcefile~datainterfaces.f90->sourcefile~standardratings.f90 sourcefile~datainterfaces.f90->sourcefile~dataruntimelanguage.f90 sourcefile~datainterfaces.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datainterfaces.f90->sourcefile~heatrecovery.f90 sourcefile~datainterfaces.f90->sourcefile~setpointmanager.f90 sourcefile~datainterfaces.f90->sourcefile~outputprocessor.f90 sourcefile~datainterfaces.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacdxsystem.f90 sourcefile~branchnodeconnections.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~branchnodeconnections.f90->sourcefile~dxcoil.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~branchnodeconnections.f90->sourcefile~nodeinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~branchnodeconnections.f90->sourcefile~datazoneequipment.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~branchnodeconnections.f90->sourcefile~branchinputmanager.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacfancomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~plantsolarcollectors.f90 sourcefile~branchnodeconnections.f90->sourcefile~refrigeratedcase.f90 sourcefile~branchnodeconnections.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~branchnodeconnections.f90->sourcefile~heatrecovery.f90 sourcefile~hvacwatertoairmultispeedhp.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataheatbalance.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataheatbalance.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataheatbalance.f90->sourcefile~dxcoil.f90 sourcefile~dataheatbalance.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~dataheatbalance.f90->sourcefile~emsmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~datazoneequipment.f90 sourcefile~dataheatbalance.f90->sourcefile~watermanager.f90 sourcefile~dataheatbalance.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataheatbalance.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataheatbalance.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataheatbalance.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataheatbalance.f90->sourcefile~setpointmanager.f90 sourcefile~dataheatbalance.f90->sourcefile~outputprocessor.f90 sourcefile~dataheatbalance.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataairloop.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataairloop.f90->sourcefile~dxcoil.f90 sourcefile~dataairloop.f90->sourcefile~emsmanager.f90 sourcefile~dataairloop.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataairloop.f90->sourcefile~setpointmanager.f90 sourcefile~dataenvironment.f90->sourcefile~hvacdxsystem.f90 sourcefile~dataenvironment.f90->sourcefile~schedulemanager.f90 sourcefile~dataenvironment.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataenvironment.f90->sourcefile~dxcoil.f90 sourcefile~dataenvironment.f90->sourcefile~psychroutines.f90 sourcefile~dataenvironment.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataenvironment.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataenvironment.f90->sourcefile~dataheatbalance.f90 sourcefile~dataenvironment.f90->sourcefile~watermanager.f90 sourcefile~dataenvironment.f90->sourcefile~outairnodemanager.f90 sourcefile~dataenvironment.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataenvironment.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~dataenvironment.f90->sourcefile~hvacfancomponent.f90 sourcefile~dataenvironment.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataenvironment.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataenvironment.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataenvironment.f90->sourcefile~heatrecovery.f90 sourcefile~dataenvironment.f90->sourcefile~setpointmanager.f90 sourcefile~dataenvironment.f90->sourcefile~outputprocessor.f90 sourcefile~dataenvironment.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datastringglobals.f90 DataStringGlobals.f90 sourcefile~datastringglobals.f90->sourcefile~schedulemanager.f90 sourcefile~datastringglobals.f90->sourcefile~general.f90 sourcefile~datastringglobals.f90->sourcefile~inputprocessor.f90 sourcefile~datastringglobals.f90->sourcefile~datasystemvariables.f90 sourcefile~datastringglobals.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datastringglobals.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~schedulemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~inputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~curvemanager.f90 sourcefile~datasystemvariables.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasystemvariables.f90->sourcefile~outputprocessor.f90 sourcefile~datasystemvariables.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datazoneequipment.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~datazoneequipment.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datazoneequipment.f90->sourcefile~hvacfancomponent.f90 sourcefile~datazoneequipment.f90->sourcefile~refrigeratedcase.f90 sourcefile~datazoneequipment.f90->sourcefile~setpointmanager.f90 sourcefile~datasizing.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~datasizing.f90->sourcefile~dxcoil.f90 sourcefile~datasizing.f90->sourcefile~inputprocessor.f90 sourcefile~datasizing.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~datasizing.f90->sourcefile~datazoneequipment.f90 sourcefile~datasizing.f90->sourcefile~dataplant.f90 sourcefile~datasizing.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datasizing.f90->sourcefile~branchinputmanager.f90 sourcefile~datasizing.f90->sourcefile~hvacfancomponent.f90 sourcefile~datasizing.f90->sourcefile~plantutilities.f90 sourcefile~datasizing.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datasizing.f90->sourcefile~heatrecovery.f90 sourcefile~reportsizingmanager.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~reportsizingmanager.f90->sourcefile~dxcoil.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~reportsizingmanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~reportsizingmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~reportsizingmanager.f90->sourcefile~heatrecovery.f90 sourcefile~globalnames.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~globalnames.f90->sourcefile~dxcoil.f90 sourcefile~globalnames.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~globalnames.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~globalnames.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataairsystems.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataairsystems.f90->sourcefile~dxcoil.f90 sourcefile~dataairsystems.f90->sourcefile~emsmanager.f90 sourcefile~dataairsystems.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataairsystems.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataairsystems.f90->sourcefile~setpointmanager.f90 sourcefile~watermanager.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~watermanager.f90->sourcefile~dxcoil.f90 sourcefile~watermanager.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~watermanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~watermanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~outairnodemanager.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~outairnodemanager.f90->sourcefile~dxcoil.f90 sourcefile~outairnodemanager.f90->sourcefile~emsmanager.f90 sourcefile~outairnodemanager.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~outairnodemanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~outairnodemanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~outairnodemanager.f90->sourcefile~setpointmanager.f90 sourcefile~curvemanager.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~curvemanager.f90->sourcefile~dxcoil.f90 sourcefile~curvemanager.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~curvemanager.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~curvemanager.f90->sourcefile~branchinputmanager.f90 sourcefile~curvemanager.f90->sourcefile~hvacfancomponent.f90 sourcefile~curvemanager.f90->sourcefile~refrigeratedcase.f90 sourcefile~curvemanager.f90->sourcefile~standardratings.f90 sourcefile~curvemanager.f90->sourcefile~setpointmanager.f90 sourcefile~curvemanager.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~datawater.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~datawater.f90->sourcefile~dxcoil.f90 sourcefile~datawater.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~datawater.f90->sourcefile~watermanager.f90 sourcefile~datawater.f90->sourcefile~refrigeratedcase.f90 sourcefile~datawater.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~outputreportpredefined.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~outputreportpredefined.f90->sourcefile~dxcoil.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~outputreportpredefined.f90->sourcefile~reportsizingmanager.f90 sourcefile~outputreportpredefined.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacfancomponent.f90 sourcefile~outputreportpredefined.f90->sourcefile~standardratings.f90 sourcefile~outputreportpredefined.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~outputreportpredefined.f90->sourcefile~outputprocessor.f90 sourcefile~dataplant.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~dataplant.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~dataplant.f90->sourcefile~dataairsystems.f90 sourcefile~dataplant.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataplant.f90->sourcefile~plantutilities.f90 sourcefile~dataplant.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataplant.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataplant.f90->sourcefile~standardratings.f90 sourcefile~dataplant.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~dataplant.f90->sourcefile~setpointmanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~databranchairloopplant.f90->sourcefile~curvemanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~databranchairloopplant.f90->sourcefile~branchinputmanager.f90 sourcefile~databranchairloopplant.f90->sourcefile~plantutilities.f90 sourcefile~databranchairloopplant.f90->sourcefile~standardratings.f90 sourcefile~databranchairloopplant.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~fluidproperties.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~fluidproperties.f90->sourcefile~nodeinputmanager.f90 sourcefile~fluidproperties.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~fluidproperties.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~fluidproperties.f90->sourcefile~plantutilities.f90 sourcefile~fluidproperties.f90->sourcefile~plantsolarcollectors.f90 sourcefile~fluidproperties.f90->sourcefile~refrigeratedcase.f90 sourcefile~fluidproperties.f90->sourcefile~standardratings.f90 sourcefile~fluidproperties.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~plantwaterthermaltank.f90->sourcefile~packagedthermalstoragecoil.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~reportsizingmanager.f90 sourcefile~sqlitefortranroutines.f90->sourcefile~outputprocessor.f90 sourcefile~datasurfaces.f90->sourcefile~general.f90 sourcefile~datasurfaces.f90->sourcefile~emsmanager.f90 sourcefile~datasurfaces.f90->sourcefile~dataheatbalance.f90 sourcefile~datasurfaces.f90->sourcefile~watermanager.f90 sourcefile~datasurfaces.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~datasurfaces.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datasurfaces.f90->sourcefile~datacontaminantbalance.f90 sourcefile~datasurfaces.f90->sourcefile~plantsolarcollectors.f90 sourcefile~dataroomair.f90->sourcefile~sqlitefortranroutines.f90 sourcefile~datavectortypes.f90->sourcefile~dataheatbalance.f90 sourcefile~datavectortypes.f90->sourcefile~datasurfaces.f90 sourcefile~datavectortypes.f90->sourcefile~databsdfwindow.f90 sourcefile~databsdfwindow.f90->sourcefile~dataheatbalance.f90 sourcefile~databsdfwindow.f90->sourcefile~datasurfaces.f90 sourcefile~datacontaminantbalance.f90->sourcefile~dxcoil.f90 sourcefile~datacontaminantbalance.f90->sourcefile~nodeinputmanager.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~datacontaminantbalance.f90->sourcefile~outairnodemanager.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacfancomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datacontaminantbalance.f90->sourcefile~heatrecovery.f90 sourcefile~branchinputmanager.f90->sourcefile~dataplant.f90 sourcefile~dataerrortracking.f90->sourcefile~nodeinputmanager.f90 sourcefile~dataerrortracking.f90->sourcefile~branchinputmanager.f90 sourcefile~hvacfancomponent.f90->sourcefile~dxcoil.f90 sourcefile~hvacfancomponent.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~plantutilities.f90->sourcefile~hvacwatertoairmultispeedhp.f90 sourcefile~plantutilities.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~plantutilities.f90->sourcefile~plantsolarcollectors.f90 sourcefile~plantutilities.f90->sourcefile~refrigeratedcase.f90 sourcefile~plantutilities.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~plantsolarcollectors.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~refrigeratedcase.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataheatbalfansys.f90->sourcefile~plantwaterthermaltank.f90 sourcefile~dataheatbalfansys.f90->sourcefile~refrigeratedcase.f90 sourcefile~dataairflownetwork.f90->sourcefile~hvacfancomponent.f90 sourcefile~datazoneenergydemands.f90->sourcefile~refrigeratedcase.f90 sourcefile~datazoneenergydemands.f90->sourcefile~setpointmanager.f90 sourcefile~standardratings.f90->sourcefile~dxcoil.f90 sourcefile~databranchnodeconnections.f90->sourcefile~dxcoil.f90 sourcefile~databranchnodeconnections.f90->sourcefile~branchnodeconnections.f90 sourcefile~dataruntimelanguage.f90->sourcefile~general.f90 sourcefile~dataruntimelanguage.f90->sourcefile~emsmanager.f90 sourcefile~dataruntimelanguage.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~hvacwatercoilcomponent.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~heatrecovery.f90->sourcefile~hvachxassistedcoolingcoil.f90 sourcefile~setpointmanager.f90->sourcefile~hvacwatercoilcomponent.f90 sourcefile~datazonecontrols.f90->sourcefile~emsmanager.f90 sourcefile~datazonecontrols.f90->sourcefile~setpointmanager.f90 sourcefile~sortandstringutilities.f90->sourcefile~inputprocessor.f90 sourcefile~sortandstringutilities.f90->sourcefile~outputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~inputprocessor.f90 sourcefile~dataoutputs.f90->sourcefile~outputprocessor.f90 sourcefile~outputprocessor.f90->sourcefile~nodeinputmanager.f90 sourcefile~outputprocessor.f90->sourcefile~emsmanager.f90 sourcefile~outputprocessor.f90->sourcefile~runtimelanguageprocessor.f90 sourcefile~dataglobalconstants.f90->sourcefile~outputprocessor.f90 sourcefile~runtimelanguageprocessor.f90->sourcefile~emsmanager.f90 sourcefile~datacomplexfenestration.f90->sourcefile~dataheatbalance.f90 sourcefile~dataequivalentlayerwindow.f90->sourcefile~dataheatbalance.f90
Help

Files Dependent On This One

sourcefile~~hvacdxsystem.f90~~AfferentGraph sourcefile~hvacdxsystem.f90 HVACDXSystem.f90 sourcefile~hvacunitarysystem.f90 HVACUnitarySystem.f90 sourcefile~hvacdxsystem.f90->sourcefile~hvacunitarysystem.f90 sourcefile~simairservingzones.f90 SimAirServingZones.f90 sourcefile~hvacdxsystem.f90->sourcefile~simairservingzones.f90 sourcefile~outdoorairunit.f90 OutdoorAirUnit.f90 sourcefile~hvacdxsystem.f90->sourcefile~outdoorairunit.f90 sourcefile~mixedair.f90 MixedAir.f90 sourcefile~hvacdxsystem.f90->sourcefile~mixedair.f90 sourcefile~hvacunitarysystem.f90->sourcefile~simairservingzones.f90 sourcefile~hvacunitarysystem.f90->sourcefile~outdoorairunit.f90 sourcefile~hvacunitarysystem.f90->sourcefile~mixedair.f90 sourcefile~zoneequipmentmanager.f90 Zoneequipmentmanager.f90 sourcefile~hvacunitarysystem.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~sizingmanager.f90 SizingManager.f90 sourcefile~simairservingzones.f90->sourcefile~sizingmanager.f90 sourcefile~hvacmanager.f90 HVACManager.f90 sourcefile~simairservingzones.f90->sourcefile~hvacmanager.f90 sourcefile~outdoorairunit.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~generalroutines.f90 GeneralRoutines.f90 sourcefile~outdoorairunit.f90->sourcefile~generalroutines.f90 sourcefile~mixedair.f90->sourcefile~simairservingzones.f90 sourcefile~simulationmanager.f90 SimulationManager.f90 sourcefile~mixedair.f90->sourcefile~simulationmanager.f90 sourcefile~hvacstandaloneerv.f90 HVACStandAloneERV.f90 sourcefile~mixedair.f90->sourcefile~hvacstandaloneerv.f90 sourcefile~hvaccontrollers.f90 HVACControllers.f90 sourcefile~mixedair.f90->sourcefile~hvaccontrollers.f90 sourcefile~packagedterminalheatpump.f90 PackagedTerminalHeatPump.f90 sourcefile~mixedair.f90->sourcefile~packagedterminalheatpump.f90 sourcefile~airflownetworkbalancemanager.f90 AirflowNetworkBalanceManager.f90 sourcefile~mixedair.f90->sourcefile~airflownetworkbalancemanager.f90 sourcefile~hvacvariablerefrigerantflow.f90 HVACVariableRefrigerantFlow.f90 sourcefile~mixedair.f90->sourcefile~hvacvariablerefrigerantflow.f90 sourcefile~hvacunitarybypassvav.f90 HVACUnitaryBypassVAV.f90 sourcefile~mixedair.f90->sourcefile~hvacunitarybypassvav.f90 sourcefile~fancoilunits.f90 FanCoilUnits.f90 sourcefile~mixedair.f90->sourcefile~fancoilunits.f90 sourcefile~windowac.f90 WindowAC.f90 sourcefile~mixedair.f90->sourcefile~windowac.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~sizingmanager.f90 sourcefile~zoneequipmentmanager.f90->sourcefile~hvacmanager.f90 sourcefile~sizingmanager.f90->sourcefile~simulationmanager.f90 sourcefile~hvacmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalanceairmanager.f90 HeatBalanceAirManager.f90 sourcefile~hvacmanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~energyplus.f90 EnergyPlus.f90 sourcefile~simulationmanager.f90->sourcefile~energyplus.f90 sourcefile~utilityroutines.f90 UtilityRoutines.f90 sourcefile~simulationmanager.f90->sourcefile~utilityroutines.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancesurfacemanager.f90 HeatBalanceSurfaceManager.f90 sourcefile~heatbalanceairmanager.f90->sourcefile~heatbalancesurfacemanager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~simulationmanager.f90 sourcefile~heatbalancemanager.f90 HeatBalanceManager.f90 sourcefile~heatbalancesurfacemanager.f90->sourcefile~heatbalancemanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~sizingmanager.f90 sourcefile~heatbalancemanager.f90->sourcefile~simulationmanager.f90 sourcefile~hvacstandaloneerv.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~hvacstandaloneerv.f90->sourcefile~hvacmanager.f90 sourcefile~systemreports.f90 SystemReports.f90 sourcefile~hvacstandaloneerv.f90->sourcefile~systemreports.f90 sourcefile~hvaccontrollers.f90->sourcefile~simairservingzones.f90 sourcefile~hvaccontrollers.f90->sourcefile~simulationmanager.f90 sourcefile~hvacfurnace.f90 HVACFurnace.f90 sourcefile~hvaccontrollers.f90->sourcefile~hvacfurnace.f90 sourcefile~packagedterminalheatpump.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~packagedterminalheatpump.f90->sourcefile~systemreports.f90 sourcefile~airflownetworkbalancemanager.f90->sourcefile~hvacmanager.f90 sourcefile~systemavailabilitymanager.f90 SystemAvailabilityManager.f90 sourcefile~airflownetworkbalancemanager.f90->sourcefile~systemavailabilitymanager.f90 sourcefile~hvacvariablerefrigerantflow.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~plantloopequipment.f90 PlantLoopEquipment.f90 sourcefile~hvacvariablerefrigerantflow.f90->sourcefile~plantloopequipment.f90 sourcefile~hvacunitarybypassvav.f90->sourcefile~simairservingzones.f90 sourcefile~fancoilunits.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~fancoilunits.f90->sourcefile~generalroutines.f90 sourcefile~fancoilunits.f90->sourcefile~systemreports.f90 sourcefile~windowac.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~windowac.f90->sourcefile~systemreports.f90 sourcefile~systemreports.f90->sourcefile~hvacmanager.f90 sourcefile~systemreports.f90->sourcefile~simulationmanager.f90 sourcefile~systemreports.f90->sourcefile~utilityroutines.f90 sourcefile~hvacfurnace.f90->sourcefile~simairservingzones.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~simairservingzones.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~zoneequipmentmanager.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~hvacmanager.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~heatbalanceairmanager.f90 sourcefile~plantmanager.f90 PlantManager.f90 sourcefile~systemavailabilitymanager.f90->sourcefile~plantmanager.f90 sourcefile~plantmanager.f90->sourcefile~hvacmanager.f90 sourcefile~plantmanager.f90->sourcefile~simulationmanager.f90 sourcefile~plantmanager.f90->sourcefile~utilityroutines.f90 sourcefile~plantloopequipment.f90->sourcefile~plantmanager.f90 sourcefile~plantloopsolver.f90 PlantLoopSolver.f90 sourcefile~plantloopequipment.f90->sourcefile~plantloopsolver.f90 sourcefile~plantloopsolver.f90->sourcefile~plantmanager.f90
Help

Source Code


Source Code

! note that there are two modules in this file

!  HVACDXSystem is for cooling DX coils

!  HVACDXHeatPumpSystem is for heating DX coils


MODULE HVACDXSystem
  ! Module containing the DXCoolingSystem simulation routines

  ! MODULE INFORMATION:
  !       AUTHOR         Richard Liesen
  !       DATE WRITTEN   March 2001
  !                      Feb 2005 M. J. Witte, GARD Analytics, Inc.
  !                        Add dehumidification controls and support for multimode DX coil
  !                        Work supported by ASHRAE research project 1254-RP
  !                      Feb 2013 Bereket Nigusse, FSEC
  !                        Added DX Coil Model For 100% OA systems
  !                      Feb 2013 Bo Shen, Oak Ridge National Lab
  !                      Add Coil:Cooling:DX:VariableSpeed, capable of both sensible and latent cooling
  !       RE-ENGINEERED  na

  ! PURPOSE OF THIS MODULE:
  ! To encapsulate the data and algorithms required to
  ! manage the DXCoolingSystem System Component

  ! METHODOLOGY EMPLOYED:
  !

  ! REFERENCES:


  ! OTHER NOTES:
  !

  ! USE STATEMENTS:
  ! Use statements for data only modules
USE DataPrecisionGlobals
USE DataLoopNode
USE DataGlobals
USE DataHVACGlobals
USE DataInterfaces

  ! Use statements for access to subroutines in other modules
USE ScheduleManager

IMPLICIT NONE         ! Enforce explicit typing of all variables

PRIVATE ! Everything private unless explicitly made public

  !MODULE PARAMETER DEFINITIONS
REAL(r64), PARAMETER :: MinAirMassFlow = 0.001d0
! Compressor operation
INTEGER, PARAMETER :: On =  1              ! normal compressor operation
INTEGER, PARAMETER :: Off = 0              ! signal DXCoil that compressor shouldn't run
! Dehumidification control modes (DehumidControlMode)
INTEGER, PARAMETER :: DehumidControl_None       = 0
INTEGER, PARAMETER :: DehumidControl_Multimode  = 1
INTEGER, PARAMETER :: DehumidControl_CoolReheat = 2
LOGICAL,SAVE       :: GetInputFlag = .True.   ! Flag to get input only once

!packaged TES modes
INTEGER, PARAMETER :: OffMode                 = 0 !
INTEGER, PARAMETER :: CoolingOnlyMode         = 1
INTEGER, PARAMETER :: CoolingAndChargeMode    = 2
INTEGER, PARAMETER :: CoolingAndDischargeMode = 3
INTEGER, PARAMETER :: ChargeOnlyMode          = 4
INTEGER, PARAMETER :: DischargeOnlyMode       = 5

  ! DERIVED TYPE DEFINITIONS

TYPE DXCoolingConditions
  CHARACTER(len=MaxNameLength) :: DXCoolingSystemType=' ' ! Type of DXCoolingSystem
  CHARACTER(len=MaxNameLength) :: Name               =' ' ! Name of the DXCoolingSystem
  INTEGER                      :: SchedPtr           =0
  CHARACTER(len=MaxNameLength) :: CoolingCoilType    =' ' !
  INTEGER                      :: CoolingCoilType_Num=0
  CHARACTER(len=MaxNameLength) :: CoolingCoilName    =' ' !
  INTEGER                      :: CoolingCoilIndex   =0
  INTEGER      :: DXCoolingCoilInletNodeNum          =0
  INTEGER      :: DXCoolingCoilOutletNodeNum         =0
  Integer      :: DXSystemControlNodeNum             =0   ! the node number of the node with the setpoint
  REAL(r64)    :: DesiredOutletTemp                  =0.0d0 ! the temperature at the unit outlet node needed
                                                          ! to meet the supply air setpoint.
  REAL(r64)    :: DesiredOutletHumRat                =1.0d0 ! the humidity ratio at the unit outlet node needed
                                                          ! to meet the supply air setpoint.
  REAL(r64)    :: PartLoadFrac                       =0.0d0 ! part load fraction for current time step (single speed)
  REAL(r64)    :: SpeedRatio                         =0.0d0 ! current compressor speed ratio (variable speed)
  REAL(r64)    :: CycRatio                           =0.0d0 ! cycling part load ratio (variable speed)
  LOGICAL      :: RunOnSensibleLoad              =.true.  ! logical determines if this system will run to
                                                          ! meet a sensible load - for future use
  LOGICAL      :: RunOnLatentLoad                =.false. ! logical determines if this system will run to
                                                          ! meet a latent-only load - for future use
  INTEGER      :: DehumidControlType                 =0   ! Dehumidification control type (currently only for multimode coil)
  INTEGER      :: DehumidificationMode               =0   ! Dehumidification mode for multimode coil,
                                                          ! 0=normal, 1+=enhanced dehumidification mode
  INTEGER      :: FanOpMode                          =0   ! Fan operating mode (see parameter above)

! Warning message variables
  INTEGER      :: HXAssistedSensPLRIter               =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedSensPLRIterIndex          =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedSensPLRFail               =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedSensPLRFailIndex          =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedSensPLRFail2              =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedSensPLRFailIndex2         =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedLatPLRIter                =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedLatPLRIterIndex           =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedLatPLRFail                =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedLatPLRFailIndex           =0   ! used in HX Assisted calculations

  INTEGER      :: HXAssistedCRLatPLRIter              =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedCRLatPLRIterIndex         =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedCRLatPLRFail              =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedCRLatPLRFailIndex         =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedCRLatPLRFail2             =0   ! used in HX Assisted calculations
  INTEGER      :: HXAssistedCRLatPLRFailIndex2        =0   ! used in HX Assisted calculations

  INTEGER      :: DXCoilSensPLRIter                   =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilSensPLRIterIndex              =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilSensPLRFail                   =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilSensPLRFailIndex              =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilLatPLRIter                    =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilLatPLRIterIndex               =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilLatPLRFail                    =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilLatPLRFailIndex               =0   ! used in DXCoil calculations

  INTEGER      :: MSpdSensPLRIter                     =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdSensPLRIterIndex                =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdCycSensPLRIter                  =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdCycSensPLRIterIndex             =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdLatPLRIter                      =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdLatPLRIterIndex                 =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdCycLatPLRIter                   =0   ! used in MultiSpeed calculations
  INTEGER      :: MSpdCycLatPLRIterIndex              =0   ! used in MultiSpeed calculations

  INTEGER      :: MModeSensPLRIter                    =0   ! used in MultiMode calculations
  INTEGER      :: MModeSensPLRIterIndex               =0   ! used in MultiMode calculations
  INTEGER      :: MModeLatPLRIter                     =0   ! used in MultiMode calculations
  INTEGER      :: MModeLatPLRIterIndex                =0   ! used in MultiMode calculations
  INTEGER      :: MModeLatPLRIter2                    =0   ! used in MultiMode calculations
  INTEGER      :: MModeLatPLRIterIndex2               =0   ! used in MultiMode calculations
! When the Dx system is a part of Outdoor Air Unit
  REAL(r64)    :: OAUnitSetTemp                        =0.0d0 ! set
  ! DOAS DX Cooling coil
  LOGICAL      :: ISHundredPercentDOASDXCoil     =.false. ! logical determines if this system will run as 100% DOAS
                                                          ! DX Coil, false is regular DX coil
  REAL(r64)    :: DOASDXCoolingCoilMinTout           =0.0d0 ! DOAS DX Cooling coil outlet air minimum temperature
  INTEGER      :: FrostControlStatus                 =0   ! DOAS coil system frost control status
! variable-speed coil
  INTEGER      :: SpeedNum                             =0   ! select speed number for variable-speed coil

  ! Packaged thermal energy storage coil
  INTEGER      :: TESOpMode                           = 0
END TYPE DXCoolingConditions

!MODULE VARIABLE DECLARATIONS:
INTEGER :: NumDXSystem=0   ! The Number of DXCoolingSystems found in the Input
LOGICAL :: EconomizerFlag=.FALSE. ! holds air loop economizer status

! Make this type allocatable
TYPE (DXCoolingConditions), ALLOCATABLE, DIMENSION(:) :: DXCoolingSystem
LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckEquipName

! Subroutine Specifications for the Module
          ! Driver/Manager Routines
Public  SimDXCoolingSystem

          ! Get Input routines for module
PRIVATE GetDXCoolingSystemInput

PRIVATE InitDXCoolingSystem

          ! Update routine to check convergence and update nodes
Private ControlDXSystem

PRIVATE DXCoilVarSpeedResidual
PRIVATE DXCoilVarSpeedHumRatResidual
PRIVATE DXCoilCyclingResidual
PRIVATE DXCoilCyclingHumRatResidual
PRIVATE DOE2DXCoilResidual
PRIVATE DOE2DXCoilHumRatResidual
PRIVATE MultiModeDXCoilResidual
PRIVATE MultiModeDXCoilHumRatResidual
PRIVATE HXAssistedCoolCoilTempResidual
PRIVATE HXAssistedCoolCoilHRResidual
PRIVATE FrostControlSetPointLimit
PUBLIC  CheckDXCoolingCoilInOASysExists
PUBLIC  GetCoolingCoilTypeNameAndIndex
PRIVATE VSCoilCyclingResidual
PRIVATE VSCoilSpeedResidual
PRIVATE VSCoilCyclingHumResidual
PRIVATE VSCoilSpeedHumResidual
PRIVATE TESCoilResidual
PRIVATE TESCoilHumRatResidual


CONTAINS

! MODULE SUBROUTINES:
!*************************************************************************
SUBROUTINE SimDXCoolingSystem(DXCoolingSystemName, FirstHVACIteration, AirLoopNum,CompIndex,OAUnitNum,OAUCoilOutTemp,QTotOut)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard Liesen
          !       DATE WRITTEN   Mar 2001
          !       MODIFIED       Richard Raustad, Sept 2003 (added HVACHXAssistedCoolingCoil)
          !                      Feb 2005 M. J. Witte, GARD Analytics, Inc.
          !                        Add support for multimode DX coil
          !                      Feb 2013 Bo Shen, Oak Ridge National Lab
          !                      Add Coil:Cooling:DX:VariableSpeed, capable of both sensible and latent cooling
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine manages DXCoolingSystem component simulation.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DXCoils,          ONLY: SimDXCoil, SimDXCoilMultiSpeed, SimDXCoilMultiMode
  USE General,          ONLY: TrimSigDigits
  USE DataAirLoop,      ONLY: AirLoopControlInfo
  USE InputProcessor,   ONLY: FindItemInList
  USE HVACHXAssistedCoolingCoil, ONLY: SimHXAssistedCoolingCoil
  USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils
  USE PackagedThermalStorageCoil, ONLY: SimTESCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  CHARACTER(len=*), INTENT(IN) :: DXCoolingSystemName ! Name of DXSystem:Airloop object
  LOGICAL, INTENT(IN)          :: FirstHVACIteration  ! True when first HVAC iteration
  INTEGER, INTENT(IN)          :: AirLoopNum          ! Primary air loop number
  INTEGER, INTENT(INOUT)       :: CompIndex           ! Index to DXSystem:Airloop object
  INTEGER, INTENT(IN), OPTIONAL:: OAUnitNum           ! If the system is an equipment of OutdoorAirUnit
  REAL(r64), INTENT(IN), OPTIONAL :: OAUCoilOutTemp   ! the coil inlet temperature of OutdoorAirUnit
  REAL(r64), INTENT(INOUT), OPTIONAL :: QTotOut       ! the total cooling output of unit
          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DEFINITIONS:
          ! na

          ! FLOW:


          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  CHARACTER(len=MaxNameLength)  :: CompName              ! Name of DXSystem:Airloop object
  INTEGER                       :: DXSystemNum           ! Index to DXSystem:Airloop object
  LOGICAL                       :: HXUnitOn              ! Flag to control HX for HXAssisted Cooling Coil
  REAL(r64)                     :: AirMassFlow           ! DX System air mass flow rate
  INTEGER                       :: InletNodeNum          ! DX System inlet node number
  INTEGER                       :: OutletNodeNum         ! DX System outlet node number
  !local variables for calling variable speed coil
  REAL(r64)                     :: QZnReq  = 0.001d0                 ! Zone load (W), input to variable-speed DX coil
  REAL(r64)                     :: QLatReq = 0.0d0                     ! Zone latent load, input to variable-speed DX coil
  REAL(r64)                     :: MaxONOFFCyclesperHour = 4.0d0       ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)                     :: HPTimeConstant = 0.0d0              ! Heat pump time constant [s]
  REAL(r64)                     :: FanDelayTime   = 0.0d0              ! Fan delay time, time delay for the HP's fan to
  REAL(r64)                     :: OnOffAirFlowRatio = 1.0d0           ! ratio of compressor on flow to average flow over time step

    ! Obtains and Allocates DX Cooling System related parameters from input file
  IF (GetInputFlag) THEN  !First time subroutine has been entered
        !Get the DXCoolingSystem input
    CALL GetDXCoolingSystemInput
    GetInputFlag=.false.
  End If

    ! Find the correct DXSystemNumber
  IF (CompIndex == 0) THEN
    DXSystemNum = FindItemInList(DXCoolingSystemName,DXCoolingSystem%Name,NumDXSystem)
    IF (DXSystemNum == 0) THEN
      CALL ShowFatalError('SimDXCoolingSystem: DXUnit not found='//TRIM(DXCoolingSystemName))
    ENDIF
    CompIndex=DXSystemNum
  ELSE
    DXSystemNum=CompIndex
    IF (DXSystemNum > NumDXSystem .or. DXSystemNum < 1) THEN
      CALL ShowFatalError('SimulateDXCoolingSystem:  Invalid CompIndex passed='//  &
                          TRIM(TrimSigDigits(DXSystemNum))// &
                          ', Number of DX Units='//TRIM(TrimSigDigits(NumDXSystem))//  &
                          ', DX Unit name='//TRIM(DXCoolingSystemName))
    ENDIF
    IF (CheckEquipName(DXSystemNum)) THEN
      IF (DXCoolingSystemName /= DXCoolingSystem(DXSystemNum)%Name) THEN
        CALL ShowFatalError('SimulateDXCoolingSystem: Invalid CompIndex passed='//  &
                            TRIM(TrimSigDigits(DXSystemNum))// &
                            ', DX Unit name='//TRIM(DXCoolingSystemName)//', stored DX Unit Name for that index='//  &
                            TRIM(DXCoolingSystem(DXSystemNum)%Name))
      ENDIF
      CheckEquipName(DXSystemNum)=.false.
    ENDIF
  ENDIF

  Call InitDXCoolingSystem(DXSystemNum,AirLoopNum,OAUnitNUm,OAUCoilOutTemp)

  !Call the series of components that simulate a DX Cooling System
   ! Control the DX Cooling System
  HXUnitOn = .FALSE.
  Call ControlDXSystem(DXSystemNum, FirstHVACIteration, HXUnitOn)

    ! simulate DX Cooling System
  CompName = DXCoolingSystem(DXSystemNum)%CoolingCoilName
  !Need a cooling System call here I think
    SELECT CASE(DXCoolingSystem(DXSystemNum)%CoolingCoilType_Num)

    CASE (CoilDX_CoolingSingleSpeed) ! COIL:DX:COOLINGBYPASSFACTOREMPIRICAL

      CALL SimDXCoil(CompName,On,FirstHVACIteration, DXCoolingSystem(DXSystemNum)%PartLoadFrac,  &
         DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, &
         DXCoolingSystem(DXSystemNum)%FanOpMode)

    CASE (CoilDX_CoolingHXAssisted)  ! CoilSystem:Cooling:DX:HeatExchangerAssisted

      CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,DXCoolingSystem(DXSystemNum)%PartLoadFrac,  &
                                   DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, DXCoolingSystem(DXSystemNum)%FanOpMode, &
                                   HXUnitEnable=HXUnitOn,EconomizerFlag=EconomizerFlag)

    CASE (CoilDX_CoolingTwoSpeed)  ! Coil:Cooling:DX:TwoSpeed
                                   ! formerly (v3 and beyond)COIL:DX:MULTISPEED:COOLINGEMPIRICAL

      CALL SimDXCoilMultiSpeed(CompName,DXCoolingSystem(DXSystemNum)%SpeedRatio,&
                     DXCoolingSystem(DXSystemNum)%CycRatio,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

    CASE (CoilDX_CoolingTwoStageWHumControl)  ! Coil:Cooling:DX:TwoStageWithHumidityControlMode
                                     ! formerly (v3 and beyond) COIL:DX:MULTIMODE:COOLINGEMPIRICAL

      CALL SimDXCoilMultiMode(CompName,On,FirstHVACIteration,DXCoolingSystem(DXSystemNum)%PartLoadFrac, &
                     DXCoolingSystem(DXSystemNum)%DehumidificationMode,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, &
                     DXCoolingSystem(DXSystemNum)%FanOpMode)
    CASE (Coil_CoolingAirToAirVariableSpeed)  ! Coil:Cooling:DX:VariableSpeed

      Call SimVariableSpeedCoils(CompName,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,&
           DXCoolingSystem(DXSystemNum)%FanOpMode, MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, DXCoolingSystem(DXSystemNum)%PartLoadFrac, OnOffAirFlowRatio, &
           DXCoolingSystem(DXSystemNum)%SpeedNum, DXCoolingSystem(DXSystemNum)%SpeedRatio, QZnReq, QLatReq)

    CASE ( CoilDX_PackagedThermalStorageCooling )

      CALL SimTESCoil( CompName,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,&
           DXCoolingSystem(DXSystemNum)%FanOpMode, DXCoolingSystem(DXSystemNum)%TESOpMode, &
           DXCoolingSystem(DXSystemNum)%PartLoadFrac)

    CASE DEFAULT
      CALL ShowFatalError('SimDXCoolingSystem: Invalid DX Cooling System/Coil='//  &
                          TRIM(DXCoolingSystem(DXSystemNum)%CoolingCoilType))

  END SELECT
  ! set econo lockout flag
    ! set econo lockout flag
  IF (AirLoopNum /=-1) THEN ! IF the sysem is not an equipment of outdoor air unit

  IF ( (DXCoolingSystem(DXSystemNum)%PartLoadFrac > 0.0d0 .OR. &
        DXCoolingSystem(DXSystemNum)%SpeedRatio > 0.0d0 .OR. &
        DXCoolingSystem(DXSystemNum)%CycRatio > 0.0d0) .AND. &
       AirLoopControlInfo(AirLoopNum)%CanLockoutEconoWithCompressor) THEN
       AirLoopControlInfo(AirLoopNum)%ReqstEconoLockoutWithCompressor = .TRUE.
  ELSE
    AirLoopControlInfo(AirLoopNum)%ReqstEconoLockoutWithCompressor = .FALSE.
  END IF
  END IF

  IF(PRESENT(QTotOut))THEN
    InletNodeNum  = DXCoolingSystem(DXSystemNum)%DXCoolingCoilInletNodeNum
    OutletNodeNum = DXCoolingSystem(DXSystemNum)%DXCoolingCoilOutletNodeNum
    AirMassFlow = Node(OutletNodeNum)%MassFlowRate
    QTotOut = AirMassFlow * (Node(InletNodeNum)%Enthalpy - Node(OutletNodeNum)%Enthalpy)
  END IF

  RETURN

END SUBROUTINE SimDXCoolingSystem

! Get Input Section of the Module
!******************************************************************************
SUBROUTINE GetDXCoolingSystemInput

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard Liesen
          !       DATE WRITTEN   Mar 2001
          !                      Feb 2005 M. J. Witte, GARD Analytics, Inc.
          !                        Add dehumidification controls and support for multimode DX coil
          !                      Feb 2013 Bo Shen, Oak Ridge National Lab
          !                      Add Coil:Cooling:DX:VariableSpeed, capable of both sensible and latent cooling
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Obtains input data for system and stores it in System data structures

          ! METHODOLOGY EMPLOYED:
          ! Uses "Get" routines to read in data.

          ! REFERENCES:

          ! USE STATEMENTS:
    USE InputProcessor
    USE NodeInputManager,      ONLY: GetOnlySingleNode
    USE DataHeatBalance,       ONLY: Zone
    USE BranchNodeConnections, ONLY: SetUpCompSets, TestCompSet
    USE HVACHXAssistedCoolingCoil,  ONLY: GetHXDXCoilName, GetHXDXCoilIndex
    USE VariableSpeedCoils,    ONLY: GetCoilIndexVariableSpeed
    USE PackagedThermalStorageCoil, ONLY: GetTESCoilIndex
    USE DataIPShortCuts
    USE DXCoils,               ONLY: SetCoilSystemCoolingData, SetDXCoilTypeData, GetDXCoilIndex

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
    INTEGER :: DXSystemNum      ! The DXCoolingSystem that you are currently loading input into
    INTEGER :: NumAlphas
    INTEGER :: NumNums
    INTEGER :: IOSTAT
    CHARACTER(len=*), PARAMETER    :: RoutineName='GetDXCoolingSystemInput: ' ! include trailing blank space
    LOGICAL :: ErrorsFound = .FALSE. ! If errors detected in input
    LOGICAL :: ErrFound = .FALSE.    ! used for mining functions
    LOGICAL :: IsNotOK               ! Flag to verify name
    LOGICAL :: IsBlank               ! Flag for blank name
    Integer :: DXCoolSysNum
    LOGICAL :: FanErrorsFound        ! flag returned on fan operating mode check
    LOGICAL :: DXErrorsFound         ! flag returned on DX coil name check
    CHARACTER(len=MaxNameLength) :: HXDXCoolCoilName     ! Name of DX cooling coil used with Heat Exchanger Assisted Cooling Coil
    CHARACTER(len=MaxNameLength) :: CurrentModuleObject  ! for ease in getting objects
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: Alphas         ! Alpha input items for object
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cAlphaFields   ! Alpha field names
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cNumericFields ! Numeric field names
    REAL(r64), ALLOCATABLE, DIMENSION(:) :: Numbers           ! Numeric input items for object
    LOGICAL, ALLOCATABLE, DIMENSION(:)   :: lAlphaBlanks      ! Logical array, alpha field input BLANK = .true.
    LOGICAL, ALLOCATABLE, DIMENSION(:)   :: lNumericBlanks    ! Logical array, numeric field input BLANK = .true.
    INTEGER                              :: TotalArgs=0       ! Total number of alpha and numeric arguments (max) for a
                                                              !  certain object in the input file

          ! Flow

    CurrentModuleObject='CoilSystem:Cooling:DX'
    NumDXSystem = GetNumObjectsFound(CurrentModuleObject)

    ALLOCATE(DXCoolingSystem(NumDXSystem))
    ALLOCATE(CheckEquipName(NumDXSystem))
    CheckEquipName=.true.

    CALL GetObjectDefMaxArgs('CoilSystem:Cooling:DX',TotalArgs,NumAlphas,NumNums)

    ALLOCATE(Alphas(NumAlphas))
    Alphas=' '
    ALLOCATE(cAlphaFields(NumAlphas))
    cAlphaFields=' '
    ALLOCATE(cNumericFields(NumNums))
    cNumericFields=' '
    ALLOCATE(Numbers(NumNums))
    Numbers=0.0d0
    ALLOCATE(lAlphaBlanks(NumAlphas))
    lAlphaBlanks=.TRUE.
    ALLOCATE(lNumericBlanks(NumNums))
    lNumericBlanks=.TRUE.


      ! Get the data for the DX Cooling System
      DO DXCoolSysNum = 1,  NumDXSystem

        CALL GetObjectItem(CurrentModuleObject,DXCoolSysNum,Alphas,NumAlphas, &
                     Numbers,NumNums,IOSTAT,NumBlank=lNumericBlanks,AlphaBlank=lAlphaBlanks, &
                     AlphaFieldNames=cAlphaFields,NumericFieldNames=cNumericFields)

        IsNotOK=.false.
        IsBlank=.false.
        CALL VerifyName(Alphas(1),DXCoolingSystem%Name,DXCoolSysNum-1,IsNotOK,IsBlank,TRIM(CurrentModuleObject)//' Name')
        IF (IsNotOK) THEN
          ErrorsFound=.true.
          IF (IsBlank) Alphas(1) ='xxxxx'
        ENDIF
        DXCoolingSystem(DXCoolSysNum)%DXCoolingSystemType = CurrentModuleObject ! push Object Name into data array
        DXCoolingSystem(DXCoolSysNum)%Name            = Alphas(1)
        IF (lAlphaBlanks(2)) THEN
          DXCoolingSystem(DXCoolSysNum)%SchedPtr        = ScheduleAlwaysOn
        ELSE
          DXCoolingSystem(DXCoolSysNum)%SchedPtr        = GetScheduleIndex(Alphas(2))
          IF (DXCoolingSystem(DXCoolSysNum)%SchedPtr == 0) THEN
            CALL ShowSevereError(RoutineName//TRIM(CurrentModuleObject)//': invalid '//TRIM(cAlphaFields(2))//  &
               ' entered ='//TRIM(Alphas(2))// &
               ' for '//TRIM(cAlphaFields(1))//'='//TRIM(Alphas(1)))
            ErrorsFound=.true.
          END IF
        END IF

        DXCoolingSystem(DXCoolSysNum)%DXCoolingCoilInletNodeNum      = &
               GetOnlySingleNode(Alphas(3),ErrorsFound,TRIM(CurrentModuleObject),Alphas(1), &
                            NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsParent)
        DXCoolingSystem(DXCoolSysNum)%DXCoolingCoilOutletNodeNum     = &
               GetOnlySingleNode(Alphas(4),ErrorsFound,TRIM(CurrentModuleObject),Alphas(1), &
                            NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsParent)

        CALL TestCompSet(TRIM(CurrentModuleObject),Alphas(1),Alphas(3),Alphas(4),'Air Nodes')

        DXCoolingSystem(DXCoolSysNum)%DXSystemControlNodeNum      = &
               GetOnlySingleNode(Alphas(5),ErrorsFound,TRIM(CurrentModuleObject),Alphas(1), &
                            NodeType_Air,NodeConnectionType_Sensor,1,ObjectIsParent)
        IF (DXCoolingSystem(DXCoolSysNum)%DXSystemControlNodeNum .EQ. 0) THEN
          CALL ShowSevereError(TRIM(CurrentModuleObject)//': control node must be input')
          CALL ShowContinueError('Error occurred in '//TRIM(cAlphaFields(1))//'='//TRIM(Alphas(1)))
          ErrorsFound=.true.
        ENDIF

        ! Get Cooling System Information if available
        IF (SameString(Alphas(6),'Coil:Cooling:DX:SingleSpeed') .OR. &
            SameString(Alphas(6),'Coil:Cooling:DX:VariableSpeed') .OR. &
            SameString(Alphas(6),'Coil:Cooling:DX:TwoSpeed') .OR. &
            SameString(Alphas(6),'Coil:Cooling:DX:TwoStageWithHumidityControlMode') .OR. &
            SameString(Alphas(6),'CoilSystem:Cooling:DX:HeatExchangerAssisted') .OR. &
            SameString(Alphas(6),'Coil:Cooling:DX:SingleSpeed:ThermalStorage') ) THEN

          DXCoolingSystem(DXCoolSysNum)%CoolingCoilType = Alphas(6)
          DXCoolingSystem(DXCoolSysNum)%CoolingCoilName = Alphas(7)

          ErrFound = .FALSE.
          IF (SameString(Alphas(6),'Coil:Cooling:DX:SingleSpeed')) THEN
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num=CoilDX_CoolingSingleSpeed
            CALL GetDXCoilIndex(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex, &
                                ErrFound,CurrentModuleObject)
            IF(ErrFound)THEN
              CALL ShowContinueError('...occurs in '//TRIM(CurrentModuleObject)//' = '//TRIM(DXCoolingSystem(DXCoolSysNum)%Name))
              ErrorsFound = .TRUE.
            END IF
          ELSEIF (SameString(Alphas(6),'Coil:Cooling:DX:VariableSpeed')) THEN
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num=Coil_CoolingAirToAirVariableSpeed
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex = &
               GetCoilIndexVariableSpeed('Coil:Cooling:DX:VariableSpeed',DXCoolingSystem(DXCoolSysNum)%CoolingCoilName,ErrFound)
            IF(ErrFound)THEN
              CALL ShowContinueError('...occurs in '//TRIM(CurrentModuleObject)//' = '//TRIM(DXCoolingSystem(DXCoolSysNum)%Name))
              ErrorsFound = .TRUE.
            END IF
          ELSEIF (SameString(Alphas(6),'Coil:Cooling:DX:TwoSpeed')) THEN
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num=CoilDX_CoolingTwoSpeed
            CALL GetDXCoilIndex(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex, &
                                ErrFound,CurrentModuleObject)
            IF(ErrFound)THEN
              CALL ShowContinueError('...occurs in '//TRIM(CurrentModuleObject)//' = '//TRIM(DXCoolingSystem(DXCoolSysNum)%Name))
              ErrorsFound = .TRUE.
            END IF
          ELSEIF (SameString(Alphas(6),'CoilSystem:Cooling:DX:HeatExchangerAssisted')) THEN
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num=CoilDX_CoolingHXAssisted
            CALL GetHXDXCoilIndex(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex, &
                                ErrFound,CurrentModuleObject)
            IF(ErrFound)THEN
              CALL ShowContinueError('...occurs in '//TRIM(CurrentModuleObject)//' = '//TRIM(DXCoolingSystem(DXCoolSysNum)%Name))
              ErrorsFound = .TRUE.
            END IF

            DXErrorsFound = .FALSE.
            HXDXCoolCoilName = GetHXDXCoilName(Alphas(6),Alphas(7),DXErrorsFound)
            IF(DXErrorsFound)THEN
              CALL ShowWarningError(TRIM(CurrentModuleObject)//' = "'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'"')
              CALL ShowContinueError('CoilSystem:Cooling:DX:HeatExchangerAssisted "'//TRIM(Alphas(7))//'" not found.')
              ErrorsFound = .TRUE.
            END IF

          ELSEIF (SameString(Alphas(6),'Coil:Cooling:DX:TwoStageWithHumidityControlMode')) THEN
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num=CoilDX_CoolingTwoStageWHumControl
            CALL GetDXCoilIndex(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex, &
                                ErrFound,CurrentModuleObject)
            IF(ErrFound)THEN
              CALL ShowContinueError('...occurs in '//TRIM(CurrentModuleObject)//' = '//TRIM(DXCoolingSystem(DXCoolSysNum)%Name))
              ErrorsFound = .TRUE.
            END IF
          ELSEIF (SameString(Alphas(6), 'Coil:Cooling:DX:SingleSpeed:ThermalStorage')) THEN
            DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num=CoilDX_PackagedThermalStorageCooling
            CALL GetTESCoilIndex(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex, &
                                ErrFound,CurrentModuleObject)
            IF(ErrFound)THEN
              CALL ShowContinueError('...occurs in '//TRIM(CurrentModuleObject)//' = '//TRIM(DXCoolingSystem(DXCoolSysNum)%Name))
              ErrorsFound = .TRUE.
            END IF
          ENDIF

        ELSE
          CALL ShowSevereError('Invalid entry for '//TRIM(cAlphaFields(6))//' :'//TRIM(Alphas(6)))
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
          ErrorsFound=.true.
        END IF

        CALL ValidateComponent(DXCoolingSystem(DXCoolSysNum)%CoolingCoilType,DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, &
                               IsNotOK,TRIM(CurrentModuleObject))
        IF (IsNotOK) THEN
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//' = "'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
          ErrorsFound=.true.
        ENDIF

        CALL SetUpCompSets(DXCoolingSystem(DXCoolSysNum)%DXCoolingSystemType, DXCoolingSystem(DXCoolSysNum)%Name, &
                           Alphas(6),Alphas(7),Alphas(3),Alphas(4))


        FanErrorsFound = .FALSE.

        ! Supply air fan operating mode defaulted to constant fan cycling coil/compressor
        DXCoolingSystem(DXCoolSysNum)%FanOpMode = ContFanCycCoil

        ! Dehumidification control mode
        IF (SameString(Alphas(8),'None')) THEN
          DXCoolingSystem(DXCoolSysNum)%DehumidControlType=DehumidControl_None
        ELSEIF (SameString(Alphas(8),' ')) THEN
          DXCoolingSystem(DXCoolSysNum)%DehumidControlType=DehumidControl_None
        ELSEIF (SameString(Alphas(8),'Multimode')) THEN
          IF (DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num == CoilDX_CoolingTwoStageWHumControl) THEN
            DXCoolingSystem(DXCoolSysNum)%DehumidControlType=DehumidControl_Multimode
          ELSE IF (DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num == CoilDX_CoolingHXAssisted) THEN
            DXCoolingSystem(DXCoolSysNum)%DehumidControlType=DehumidControl_Multimode
          ELSE
            CALL ShowWarningError('Invalid entry for '//TRIM(cAlphaFields(8))//' :'//TRIM(Alphas(8)))
            CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
            CALL ShowContinueError('Valid only with cooling coil type = Coil:Cooling:DX:TwoStageWithHumidityControlMode or '// &
                                    'CoilSystem:Cooling:DX:HeatExchangerAssisted.')
            CALL ShowContinueError('Setting '//TRIM(cAlphaFields(8))//' to None.')
            DXCoolingSystem(DXCoolSysNum)%DehumidControlType=DehumidControl_None
          END IF
        ELSEIF (SameString(Alphas(8),'CoolReheat')) THEN
          DXCoolingSystem(DXCoolSysNum)%DehumidControlType=DehumidControl_CoolReheat
        ELSE
          CALL ShowSevereError('Invalid entry for '//TRIM(cAlphaFields(8))//' :'//TRIM(Alphas(8)))
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
        END IF

        ! Run on sensible load
        IF (SameString(Alphas(9),'Yes')) THEN
          DXCoolingSystem(DXCoolSysNum)%RunOnSensibleLoad= .TRUE.
        ELSEIF (SameString(Alphas(9),' ')) THEN
          DXCoolingSystem(DXCoolSysNum)%RunOnSensibleLoad= .TRUE.
        ELSEIF (SameString(Alphas(9),'No')) THEN
          DXCoolingSystem(DXCoolSysNum)%RunOnSensibleLoad= .FALSE.
        ELSE
          CALL ShowSevereError('Invalid entry for '//TRIM(cAlphaFields(9))//' :'//TRIM(Alphas(9)))
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
          CALL ShowContinueError('Must be Yes or No.')
        END IF

        ! Run on latent load
        IF (SameString(Alphas(10),'Yes')) THEN
          DXCoolingSystem(DXCoolSysNum)%RunOnLatentLoad= .TRUE.
        ELSEIF (SameString(Alphas(10),' ')) THEN
          DXCoolingSystem(DXCoolSysNum)%RunOnLatentLoad= .FALSE.
        ELSEIF (SameString(Alphas(10),'No')) THEN
          DXCoolingSystem(DXCoolSysNum)%RunOnLatentLoad= .FALSE.
        ELSE
          CALL ShowSevereError('Invalid entry for '//TRIM(cAlphaFields(10))//' :'//TRIM(Alphas(10)))
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
          CALL ShowContinueError('Must be Yes or No.')
        END IF

        ! Run as 100% DOAS DX coil
        IF (lAlphaBlanks(11) .AND. NumAlphas <= 10)THEN
            DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil= .FALSE.
        ELSE
            IF (SameString(Alphas(11),'Yes')) THEN
              DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil= .TRUE.
            ELSEIF (SameString(Alphas(11),' ')) THEN
              DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil= .FALSE.
            ELSEIF (SameString(Alphas(11),'No')) THEN
              DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil= .FALSE.
            ELSE
              CALL ShowSevereError('Invalid entry for '//TRIM(cAlphaFields(11))//' :'//TRIM(Alphas(11)))
              CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXCoolingSystem(DXCoolSysNum)%Name)//'".')
              CALL ShowContinueError('Must be Yes or No.')
            END IF
        ENDIF

        ! considered as as 100% DOAS DX cooling coil
        IF (DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil) THEN
           ! set the system DX Coil application type to the child DX coil
           CALL SetDXCoilTypeData(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName)
        ENDIF
        ! DOAS DX Cooling Coil Leaving Minimum Air Temperature
        IF (NumNums > 0)THEN
          IF (.NOT. lNumericBlanks(1))THEN
             DXCoolingSystem(DXCoolSysNum)%DOASDXCoolingCoilMinTout = Numbers(1)
          ENDIF
        ENDIF
        IF (DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num == CoilDX_CoolingTwoSpeed) THEN
          CALL SetCoilSystemCoolingData(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName, &
                                        DXCoolingSystem(DXCoolSysNum)%Name )
        ENDIF

      END DO  !End of the DX System Loop


      IF (ErrorsFound) THEN
          CALL ShowFatalError(RoutineName//'Errors found in input.  Program terminates.')
      ENDIF

      DO DXSystemNum=1,NumDXSystem
        ! Setup Report variables for the DXCoolingSystem that is not reported in the components themselves
        IF (SameString(DXCoolingSystem(DXSystemNum)%CoolingCoilType,'Coil:Cooling:DX:Twospeed') ) THEN
          CALL SetupOutputVariable('Coil System Cycling Ratio []',DXCoolingSystem(DXSystemNum)%CycRatio, &
                                'System','Average',DXCoolingSystem(DXSystemNum)%Name)
          CALL SetupOutputVariable('Coil System Compressor Speed Ratio []',DXCoolingSystem(DXSystemNum)%SpeedRatio, &
                                'System','Average',DXCoolingSystem(DXSystemNum)%Name)
        ELSE
          CALL SetupOutputVariable('Coil System Part Load Ratio []',DXCoolingSystem(DXSystemNum)%PartLoadFrac, &
                                'System','Average',DXCoolingSystem(DXSystemNum)%Name)
        END IF
        CALL SetupOutputVariable('Coil System Frost Control Status []',DXCoolingSystem(DXSystemNum)%FrostControlStatus, &
                                 'System','Average',DXCoolingSystem(DXSystemNum)%Name)
      END DO

      DEALLOCATE(Alphas)
      DEALLOCATE(cAlphaFields)
      DEALLOCATE(cNumericFields)
      DEALLOCATE(Numbers)
      DEALLOCATE(lAlphaBlanks)
      DEALLOCATE(lNumericBlanks)

  RETURN

END SUBROUTINE GetDXCoolingSystemInput


! End of Get Input subroutines for the Module
!******************************************************************************

! Beginning of Initialization subroutines for the Module
! *****************************************************************************

SUBROUTINE InitDXCoolingSystem(DXSystemNum,AirLoopNum,OAUnitNum,OAUCoilOutTemp)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Fred Buhl
          !       DATE WRITTEN   May 2001
          !                      Feb 2005 M. J. Witte, GARD Analytics, Inc.
          !                        Add dehumidification controls
          !                      May 2009, B. Griffith, NREL added EMS setpoint checks
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine is for initializations of the DX Cooling Systems.

          ! METHODOLOGY EMPLOYED:
          ! Uses the status flags to trigger initializations.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHVACGlobals, ONLY: DoSetPointTest
  USE DataAirLoop,     ONLY: AirLoopControlInfo
  USE EMSManager,      ONLY: iTemperatureSetpoint, CheckIfNodeSetpointManagedByEMS, iHumidityRatioMaxSetpoint
  USE DataGlobals,     ONLY: AnyEnergyManagementSystemInModel
  USE DataEnvironment, ONLY: OutBaroPress

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT (IN) :: DXSystemNum ! number of the current DX Sys being simulated
  INTEGER, INTENT (IN) :: AirLoopNum  ! number of the current air loop being simulated
  INTEGER, INTENT (IN), Optional :: OAUnitNum  ! number of the current outdoor air unit being simulated
  REAL(r64), INTENT(IN), OPTIONAL :: OAUCoilOutTemp    ! the coil inlet temperature of OutdoorAirUnit

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  Integer             :: OutNode ! outlet node number
  INTEGER             :: ControlNode ! control node number
  INTEGER             :: DXSysIndex
  LOGICAL,SAVE        :: MyOneTimeFlag = .true.
  LOGICAL,SAVE        :: MySetPointCheckFlag = .TRUE.
  INTEGER             :: OutdoorAirUnitNum ! "ONLY" for ZoneHVAC:OutdoorAirUnit
  REAL(r64)           :: OAUCoilOutletTemp  ! "ONLY" for zoneHVAC:OutdoorAirUnit
          ! FLOW:

IF (MyOneTimeFlag) THEN

  MyOneTimeFlag = .false.
END IF
IF (AirLoopNum .EQ.-1) THEN ! This Dx system is component of ZoneHVAC:OutdoorAirUnit
   OutdoorAirUnitNum=OAUnitNum
   OAUCoilOutletTemp=OAUCoilOutTemp
END IF

IF ( .NOT. SysSizingCalc .AND. MySetPointCheckFlag .AND. DoSetPointTest) THEN
  DO DXSysIndex=1,NumDXSystem
    ControlNode = DXCoolingSystem(DXSysIndex)%DXSystemControlNodeNum
    IF (ControlNode > 0) THEN
     IF (AirLoopNum .EQ.-1) THEN                           ! Outdoor Air Unit
       Node(ControlNode)%TempSetPoint = OAUCoilOutletTemp  ! Set the coil outlet temperature
       IF(DXCoolingSystem(DXSystemNum)%ISHundredPercentDOASDXCoil) THEN
         CALL FrostControlSetPointLimit(DXSystemNum,DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(ControlNode)%HumRatMax, &
                                        OutBaroPress, DXCoolingSystem(DXSystemNum)%DOASDXCoolingCoilMinTout,1)
       ENDIF
     ELSE IF (AirLoopNum /= -1) THEN ! Not an outdoor air unit

      IF (Node(ControlNode)%TempSetPoint == SensedNodeFlagValue) THEN
        IF (.NOT. AnyEnergyManagementSystemInModel) THEN
          CALL ShowSevereError(TRIM(DXCoolingSystem(DXSysIndex)%DXCoolingSystemType)//&
                               ': Missing temperature setpoint for DX unit= ' //TRIM(DXCoolingSystem(DXSysIndex)%Name))
          CALL ShowContinueError('  use a Setpoint Manager to establish a setpoint at the unit control node.')
          SetPointErrorFlag = .TRUE.
        ELSE
          CALL CheckIfNodeSetpointManagedByEMS(ControlNode,iTemperatureSetpoint, SetpointErrorFlag)
          IF (SetpointErrorFlag) THEN
            CALL ShowSevereError(TRIM(DXCoolingSystem(DXSysIndex)%DXCoolingSystemType)//&
                               ': Missing temperature setpoint for DX unit= ' //TRIM(DXCoolingSystem(DXSysIndex)%Name))
            CALL ShowContinueError('  use a Setpoint Manager to establish a setpoint at the unit control node.')
            CALL ShowContinueError('  or use an EMS actuator to establish a temperature setpoint at the unit control node.')
          ENDIF
        ENDIF
      END IF
      IF ((DXCoolingSystem(DXSysIndex)%DehumidControlType .NE. DehumidControl_None) .AND. &
          (Node(ControlNode)%HumRatMax == SensedNodeFlagValue)) THEN
        IF (.NOT. AnyEnergyManagementSystemInModel) THEN
          CALL ShowSevereError(TRIM(DXCoolingSystem(DXSysIndex)%DXCoolingSystemType)//&
                               ': Missing humidity ratio setpoint (HUMRATMAX) for DX unit= ' &
                                          //TRIM(DXCoolingSystem(DXSysIndex)%Name))
          CALL ShowContinueError('  use a Setpoint Manager to establish a setpoint at the unit control node.')
          SetPointErrorFlag = .TRUE.
        ELSE
          CALL CheckIfNodeSetpointManagedByEMS(ControlNode,iHumidityRatioMaxSetpoint, SetpointErrorFlag)
          IF (SetpointErrorFlag) THEN
            CALL ShowSevereError(TRIM(DXCoolingSystem(DXSysIndex)%DXCoolingSystemType)//&
                               ': Missing maximum humidity ratio setpoint (HUMRATMAX) for DX unit= ' &
                                         //TRIM(DXCoolingSystem(DXSysIndex)%Name))
            CALL ShowContinueError('  use a Setpoint Manager to establish a setpoint at the unit control node.')
            CALL ShowContinueError('  or use an EMS actuator to establish a maximum humidity ratio setpoint.')
          ENDIF
        ENDIF

      END IF
    END IF
   END IF
  END DO
  MySetPointCheckFlag = .FALSE.
END IF

! These initializations are done every iteration
IF (AirLoopNum .EQ.-1) THEN ! This IF-TEHN routine is just for ZoneHVAC:OUTDOORAIRUNIT
OutNode = DXCoolingSystem(DXSystemNum)%DXCoolingCoilOutletNodeNum
ControlNode = DXCoolingSystem(DXSystemNum)%DXSystemControlNodeNum

  IF (ControlNode.EQ.0) THEN
  DXCoolingSystem(DXSystemNum)%DesiredOutletTemp = 0.0d0
  DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = 1.0d0
  ELSE IF (ControlNode.EQ.OutNode) THEN
  DXCoolingSystem(DXSystemNum)%DesiredOutletTemp =OAUCoilOutletTemp
    IF (DXCoolingSystem(DXSystemNum)%ISHundredPercentDOASDXCoil .AND. DXCoolingSystem(DXSystemNum)%RunOnSensibleLoad) THEN
      CALL FrostControlSetPointLimit(DXSystemNum,DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(ControlNode)%HumRatMax, &
                                     OutBaroPress,DXCoolingSystem(DXSystemNum)%DOASDXCoolingCoilMinTout,1)
    ENDIF
  END IF
 !  If the Dxsystem is an equipment of Outdoor Air Unit, the desiered coiloutlet humidity level is set to zero
    DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = 1.0d0


ELSE IF (AirLoopNum /=-1) THEN ! Not Outdoor Air Unit

OutNode = DXCoolingSystem(DXSystemNum)%DXCoolingCoilOutletNodeNum
ControlNode = DXCoolingSystem(DXSystemNum)%DXSystemControlNodeNum
EconomizerFlag = AirLoopControlInfo(AirLoopNum)%EconoActive
IF (ControlNode.EQ.0) THEN
  DXCoolingSystem(DXSystemNum)%DesiredOutletTemp = 0.0d0
  DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = 1.0d0
ELSE IF (ControlNode.EQ.OutNode) THEN
  IF (DXCoolingSystem(DXSystemNum)%ISHundredPercentDOASDXCoil .AND. DXCoolingSystem(DXSystemNum)%RunOnSensibleLoad) THEN
    CALL FrostControlSetPointLimit(DXSystemNum, Node(ControlNode)%TempSetPoint,Node(ControlNode)%HumRatMax,OutBaroPress, &
                                   DXCoolingSystem(DXSystemNum)%DOASDXCoolingCoilMinTout,1)
  ENDIF
  DXCoolingSystem(DXSystemNum)%DesiredOutletTemp = Node(ControlNode)%TempSetPoint
  !  If HumRatMax is zero, then there is no request from SetpointManager:SingleZone:Humidity:Maximum
  IF ((DXCoolingSystem(DXSystemNum)%DehumidControlType .NE. DehumidControl_None) .AND. &
      (Node(ControlNode)%HumRatMax .GT. 0.0d0)) THEN
    IF (DXCoolingSystem(DXSystemNum)%ISHundredPercentDOASDXCoil .AND. DXCoolingSystem(DXSystemNum)%RunOnLatentLoad) THEN
      CALL FrostControlSetPointLimit(DXSystemNum,Node(ControlNode)%TempSetPoint,Node(ControlNode)%HumRatMax,OutBaroPress, &
                                     DXCoolingSystem(DXSystemNum)%DOASDXCoolingCoilMinTout,2)
    ENDIF
    DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = Node(ControlNode)%HumRatMax
  ELSE
    DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = 1.0d0
  END IF
ELSE
  IF (DXCoolingSystem(DXSystemNum)%ISHundredPercentDOASDXCoil .AND. DXCoolingSystem(DXSystemNum)%RunOnSensibleLoad) THEN
    CALL FrostControlSetPointLimit(DXSystemNum,Node(ControlNode)%TempSetPoint,Node(ControlNode)%HumRatMax,OutBaroPress, &
                                   DXCoolingSystem(DXSystemNum)%DOASDXCoolingCoilMinTout,1)
  ENDIF
  DXCoolingSystem(DXSystemNum)%DesiredOutletTemp = Node(ControlNode)%TempSetPoint - &
    (Node(ControlNode)%Temp - Node(OutNode)%Temp)
  IF (DXCoolingSystem(DXSystemNum)%DehumidControlType .NE. DehumidControl_None) THEN
    IF (DXCoolingSystem(DXSystemNum)%ISHundredPercentDOASDXCoil .AND. DXCoolingSystem(DXSystemNum)%RunOnLatentLoad) THEN
      CALL FrostControlSetPointLimit(DXSystemNum,Node(ControlNode)%TempSetPoint,Node(ControlNode)%HumRatMax,OutBaroPress, &
                                     DXCoolingSystem(DXSystemNum)%DOASDXCoolingCoilMinTout,2)
    ENDIF
    DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = Node(ControlNode)%HumRatMax - &
      (Node(ControlNode)%HumRat - Node(OutNode)%HumRat)
  ELSE
    DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat = 1.0d0
  END IF
END IF
END IF
RETURN
END SUBROUTINE InitDXCoolingSystem

! End of Initialization subroutines for the Module
! *****************************************************************************

! Beginning of Calculation subroutines for the DXCoolingSystem Module
! *****************************************************************************

SUBROUTINE ControlDXSystem(DXSystemNum, FirstHVACIteration, HXUnitOn)
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard Liesen
          !       DATE WRITTEN   Feb 2001
          !       MODIFIED       Richard Raustad, FSEC Nov 2003
          !                      Feb 2005 M. J. Witte, GARD Analytics, Inc.
          !                        Add dehumidification controls and support for multimode DX coil
          !                      Jan 2008 R. Raustad, FSEC. Added coolreheat to all coil types
          !                      Feb 2013 Bo Shen, Oak Ridge National Lab
          !                      Add Coil:Cooling:DX:VariableSpeed, capable of both sensible and latent cooling
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          !  This subroutine updates the System outlet nodes.

          ! METHODOLOGY EMPLOYED:
          !  Data is moved from the System data structure to the System outlet nodes.

          ! REFERENCES:
          !  na

          ! USE STATEMENTS:
  USE ScheduleManager
  USE DataEnvironment, ONLY: OutBaroPress
  USE DataHVACGlobals, ONLY: TempControlTol
  USE InputProcessor,  ONLY: FindItemInList
  USE Psychrometrics , ONLY: PsyHFnTdbW, PsyTdpFnWPb
  USE General,         ONLY: SolveRegulaFalsi, RoundSigDigits
  USE DXCoils,         ONLY: SimDXCoil, SimDXCoilMultiSpeed, DXCoilOutletTemp, SimDXCoilMultiMode, DXCoilOutletHumRat
  USE HVACHXAssistedCoolingCoil, ONLY: SimHXAssistedCoolingCoil, HXAssistedCoilOutletTemp, HXAssistedCoilOutletHumRat
  USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil
  USE PackagedThermalStorageCoil, ONLY: SimTESCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,  Intent(In)    :: DXSystemNum             ! index to DXSystem
  LOGICAL,  Intent(In)    :: FirstHVACIteration      ! First HVAC iteration flag
  LOGICAL,  Intent(InOut) :: HXUnitOn                ! flag to enable heat exchanger heat recovery

          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER          :: MaxIte    = 500     ! Maximum number of iterations for solver
  REAL(r64), PARAMETER :: Acc       = 1.d-3   ! Accuracy of solver result
  REAL(r64), PARAMETER :: HumRatAcc = 1.d-6   ! Accuracy of solver result

          ! INTERFACE BLOCK SPECIFICATIONS
          !  na

          ! DERIVED TYPE DEFINITIONS
          !  na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  CHARACTER(len=MaxNameLength)  :: CompName  ! Name of the DX cooling coil
  REAL(r64)           :: NoOutput            ! Sensible capacity (outlet - inlet) when the compressor is off
  REAL(r64)           :: FullOutput          ! Sensible capacity (outlet - inlet) when the compressor is on
  REAL(r64)           :: ReqOutput           ! Sensible capacity (outlet - inlet) required to meet load or setpoint temperature
  Integer             :: InletNode           ! Inlet node number of the DX cooling coil
  Integer             :: OutletNode          ! Outlet node number of the DX cooling coil
  Integer             :: ControlNode         ! The node number where a setpoint is placed to control the DX cooling coil
  REAL(r64)           :: PartLoadFrac        ! The part-load fraction of the compressor
  REAL(r64)           :: SpeedRatio          ! SpeedRatio = (CompressorSpeed - CompressorSpeedMin) /
                                             !              (CompressorSpeedMax - CompressorSpeedMin)
                                             ! for variable speed or 2 speed compressors
  REAL(r64)           :: CycRatio            ! Cycling part-load ratio for variable speed or 2 speed compressors
  REAL(r64)           :: DesOutTemp          ! Desired outlet temperature of the DX cooling coil
  REAL(r64)           :: DesOutHumRat        ! Desired outlet humidity ratio of the DX cooling coil
  REAL(r64)           :: OutletTempDXCoil    ! Actual outlet temperature of the DX cooling coil
  REAL(r64)           :: OutletTempLS        ! Actual outlet temperature of the variable speed DX cooling coil at low speed
  REAL(r64)           :: OutletTempHS        ! Actual outlet temperature of the variable speed DX cooling coil at high speed
  REAL(r64)           :: OutletHumRatLS      ! Actual outlet humrat of the variable speed DX cooling coil at low speed
  REAL(r64)           :: OutletHumRatHS      ! Actual outlet humrat of the variable speed DX cooling coil at high speed
  REAL(r64)           :: OutletHumRatDXCoil  ! Actual outlet humidity ratio of the DX cooling coil
  INTEGER             :: SolFla              ! Flag of solver
  REAL(r64), DIMENSION(5)  :: Par                 ! Parameter array passed to solver
  LOGICAL             :: SensibleLoad        ! True if there is a sensible cooling load on this system
  LOGICAL             :: LatentLoad          ! True if there is a latent   cooling load on this system
  INTEGER             :: DehumidMode         ! Dehumidification mode (0=normal, 1=enhanced)
  INTEGER             :: FanOpMode           ! Supply air fan operating mode
  REAL(r64)           :: TempMinPLR          ! Used to find latent PLR when max iterations exceeded
  REAL(r64)           :: TempMaxPLR          ! Used to find latent PLR when max iterations exceeded
  REAL(r64)           :: TempOutletTempDXCoil   ! Used to find latent PLR when max iterations exceeded
  REAL(r64)           :: TempOutletHumRatDXCoil ! Used to find latent PLR when max iterations exceeded
  REAL(r64)           :: NoLoadHumRatOut     ! DX coil outlet air humidity ratio with comprssor off
  REAL(r64)           :: FullLoadHumRatOut   ! DX coil outlet air humidity ratio with comprssor full on
  !added variables to call variable speed DX coils
  INTEGER             :: SpeedNum            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime                 ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio  ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: TempSpeedOut         ! output at one speed level
  REAL(r64)           :: TempSpeedReqst         ! request capacity at one speed level
  INTEGER             :: NumOfSpeeds      !maximum number of speed
  INTEGER             :: VSCoilIndex      !variable-speed coil index
  INTEGER             :: I               ! interation increment

      ! Set local variables
      ! Retrieve the load on the controlled zone
  OutletNode   = DXCoolingSystem(DXSystemNum)%DXCoolingCoilOutletNodeNum
  InletNode    = DXCoolingSystem(DXSystemNum)%DXCoolingCoilInletNodeNum
  ControlNode  = DXCoolingSystem(DXSystemNum)%DXSystemControlNodeNum
  DesOutTemp   = DXCoolingSystem(DXSystemNum)%DesiredOutletTemp
  DesOutHumRat = DXCoolingSystem(DXSystemNum)%DesiredOutletHumRat
  CompName     = DXCoolingSystem(DXSystemNum)%CoolingCoilName
  FanOpMode    = DXCoolingSystem(DXSystemNum)%FanOpMode
  SpeedRatio   = 0.0d0
  CycRatio     = 0.0d0
  PartLoadFrac = 0.0d0
  DehumidMode  = 0
  SensibleLoad = .FALSE.
  LatentLoad   = .FALSE.
  SpeedNum     = 1
  QZnReq       = 0.0d0
  QLatReq      = 0.0d0
  MaxONOFFCyclesperHour = 4.0d0 !default number
  HPTimeConstant= 0.0d0
  FanDelayTime  = 0.0d0
  OnOffAirFlowRatio = 1.0d0
  TempSpeedOut  = 0.0d0
  TempSpeedReqst  = 0.0d0
  NumOfSpeeds = 0
  VSCoilIndex = 0
  I = 1

  ! If DXCoolingSystem is scheduled on and there is flow
  If((GetCurrentScheduleValue(DXCoolingSystem(DXSystemNum)%SchedPtr) .gt. 0.0d0) .and. &
     (Node(InletNode)%MassFlowRate .gt. MinAirMassFlow)) THEN

    ! Determine if there is a sensible load on this system
    IF((Node(InletNode)%Temp > Node(ControlNode)%TempSetPoint) .and. &
       (Node(InletNode)%Temp > DesOutTemp) .and. &
       (ABS(Node(InletNode)%Temp - DesOutTemp) .gt. TempControlTol) ) SensibleLoad = .true.

    ! Determine if there is a latent load on this system - for future use to serve latent-only loads
    IF((Node(InletNode)%HumRat > Node(ControlNode)%HumRatMax) .and. &
       (Node(InletNode)%HumRat > DesOutHumRat)) LatentLoad = .true.

    ! If DXCoolingSystem runs with a cooling load then set PartLoadFrac on Cooling System and the Mass Flow
    ! Multimode coil will switch to enhanced dehumidification if available and needed, but it
    ! still runs to meet the sensible load. Multimode applies to Multimode or HXAssistedCooling coils.
    IF ((SensibleLoad .and. DXCoolingSystem(DXSystemNum)%RunOnSensibleLoad) .OR. &
        (LatentLoad .and. DXCoolingSystem(DXSystemNum)%RunOnLatentLoad)) THEN
      ! calculate sensible PLR, don't care if latent is true here but need to gaurd for
      ! when LatentLoad=TRUE and SensibleLoad=FALSE
      SELECT CASE(DXCoolingSystem(DXSystemNum)%CoolingCoilType_Num)

        CASE (CoilDX_CoolingSingleSpeed)  ! COIL:DX:COOLINGBYPASSFACTOREMPIRICAL

          ! Get no load result
          PartLoadFrac = 0.0d0
          CALL SimDXCoil(CompName,On,FirstHVACIteration,PartLoadFrac,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,FanOpMode)
          NoOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
          NoLoadHumRatOut = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          ! Get full load result
          PartLoadFrac = 1.0d0
          CALL SimDXCoil(CompName,On,FirstHVACIteration,PartLoadFrac,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,FanOpMode)
          FullLoadHumRatOut = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

!         IF NoOutput is lower than (more cooling than required) or very near the ReqOutput, do not run the compressor
          IF ((NoOutput-ReqOutput) .LT. Acc) THEN
            PartLoadFrac = 0.0d0
!         If the FullOutput is greater than (insufficient cooling) or very near the ReqOutput,
!         run the compressor at PartLoadFrac = 1.
          ELSE IF ((FullOutput - ReqOutput) .GT. Acc) THEN
            PartLoadFrac = 1.0d0
!         Else find the PLR to meet the load
          ELSE
!           OutletTempDXCoil is the full capacity outlet temperature at PartLoadFrac = 1 from the CALL above. If this temp is
!           greater than the desired outlet temp, then run the compressor at PartLoadFrac = 1, otherwise find the operating PLR.
            OutletTempDXCoil = DXCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
            IF (OutletTempDXCoil > DesOutTemp) THEN
              PartLoadFrac = 1.0d0
            ELSE
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutTemp
              Par(5) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, DOE2DXCoilResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible '// &
                                          'part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                    CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                END IF
              ELSE IF (SolFla == -2) THEN
                PartLoadFrac = ReqOutput/FullOutput
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - DX unit sensible part-'// &
                                    'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                                     TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                      ' failed error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                END IF

              END IF
            END IF
          END IF

!         If system does not operate to meet sensible load, use no load humidity ratio to test against humidity setpoint,
!         else use operating humidity ratio to test against humidity setpoint
          IF (PartLoadFrac .EQ. 0.0d0)THEN
            OutletHumRatDXCoil = NoLoadHumRatOut
          ELSE
            OutletHumRatDXCoil = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
          END IF

          ! If humidity setpoint is not satisfied and humidity control type is CoolReheat,
          ! then overcool to meet moisture load

          IF (( OutletHumRatDXCoil > DesOutHumRat) .AND. (PartLoadFrac .LT. 1.0d0) .AND. &
              (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_CoolReheat)) THEN

!           IF NoLoadHumRatOut is lower than (more dehumidification than required) or very near the DesOutHumRat,
!           do not run the compressor
            IF ((NoLoadHumRatOut-DesOutHumRat) .LT. HumRatAcc) THEN
              PartLoadFrac = PartLoadFrac  ! keep part-load fraction from sensible calculation
!           If the FullLoadHumRatOut is greater than (insufficient dehumidification) or very near the DesOutHumRat,
!           run the compressor at PartLoadFrac = 1.
            ELSE IF ((DesOutHumRat-FullLoadHumRatOut) .LT. HumRatAcc) THEN
              PartLoadFrac = 1.0d0
!           Else find the PLR to meet the load
            ELSE
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutHumRat
              Par(5) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, PartLoadFrac, DOE2DXCoilHumRatResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit latent part-load'// &
                                          ' ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio   = '//RoundSigDigits((ReqOutput/FullOutput),3))
                    CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                  ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' latent part-load ratio error continues. Latent PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                END IF
              ELSE IF (SolFla == -2) THEN
!               RegulaFalsi returns PLR = minPLR when a solution cannot be found, recalculate PartLoadFrac.
                IF(NoLoadHumRatOut-FullLoadHumRatOut .NE. 0.0d0)THEN
                  PartLoadFrac = (NoLoadHumRatOut-DesOutHumRat)/(NoLoadHumRatOut-FullLoadHumRatOut)
                ELSE
                  PartLoadFrac = 1.0d0
                END IF
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - DX unit latent part-'// &
                                    'load ratio calculation failed: part-load ratio limits exceeded, for unit = '//&
                                    TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit latent part-load ratio calculation'// &
                      ' failed error continues. Latent PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFailIndex,PartLoadFrac,PartLoadFrac)
                END IF
              END IF
            END IF
          END IF ! End if humidity ratio setpoint not met - CoolReheat humidity control

          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF

        CASE (CoilDX_CoolingHXAssisted)  ! CoilSystem:Cooling:DX:HeatExchangerAssisted

!         Check the dehumidification control type. If it's multimode, turn off the HX to find the sensible PLR. Then check to
!         see if the humidity load is met without the use of the HX. Always run the HX for the other modes.
          IF (DXCoolingSystem(DXSystemNum)%DehumidControlType .NE. DehumidControl_Multimode)THEN
            HXUnitOn = .TRUE.
          ELSE
            HXUnitOn = .FALSE.
          END IF

          ! Get no load result
          PartLoadFrac = 0.0d0
          CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,PartLoadFrac, &
                                        DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMode, &
                                        HXUnitEnable=HXUnitOn,EconomizerFlag=EconomizerFlag)
          NoOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
          NoLoadHumRatOut = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          ! Get full load result
          PartLoadFrac = 1.0d0
          CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,PartLoadFrac, &
                                        DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMode, &
                                        HXUnitEnable=HXUnitOn,EconomizerFlag=EconomizerFlag)
          FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
          FullLoadHumRatOut = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

!         IF NoOutput is lower than (more cooling than required) or very near the ReqOutput, do not run the compressor
          IF ((NoOutput-ReqOutput) .LT. Acc) THEN
            PartLoadFrac = 0.0d0
!         If the FullOutput is greater than or very near the ReqOutput, then run the compressor at PartLoadFrac = 1.
          ELSE IF ((FullOutput - ReqOutput) .GT. Acc) THEN
            PartLoadFrac = 1.0d0
!         Else find the PLR to meet the load
          ELSE
!           OutletTempDXCoil is the full capacity outlet temperature at PartLoadFrac = 1 from the CALL above.
!           If this temp is greater than or very near the desired outlet temp, then run the compressor at PartLoadFrac = 1.
!           (i.e. HX iterates to find solution, don't allow the tolerance in solution to trip up RegulaFalsi. So if
!           solution is very near request, run compressor at PLR = 1)
            OutletTempDXCoil = HXAssistedCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
            IF ((OutletTempDXCoil > DesOutTemp) .OR. ABS(OutletTempDXCoil - DesOutTemp) .LE. (Acc*2.0d0)) THEN
               PartLoadFrac = 1.0d0
            ELSE
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutTemp
              ! FirstHVACIteration is a logical, Par is REAL(r64), so make TRUE = 1 and FALSE = 0
              IF(FirstHVACIteration)THEN
                Par(3) = 1.0d0
              ELSE
                Par(3) = 0.0d0
              END IF
              IF(HXUnitOn)THEN
                Par(4) = 1.0d0
              ELSE
                Par(4) = 0.0d0
              END IF
              Par(5) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, HXAssistedCoolCoilTempResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN

!               RegulaFalsi may not find sensible PLR when the latent degradation model is used.
!               If iteration limit is exceeded, find tighter boundary of solution and repeat RegulaFalsi
                TempMaxPLR = -0.1d0
                TempOutletTempDXCoil = Node(InletNode)%Temp
                DO WHILE((TempOutletTempDXCoil-DesOutTemp) .GT. 0.0d0 .AND. TempMaxPLR .LE. 1.0d0)
!                 find upper limit of PLR
                  TempMaxPLR = TempMaxPLR + 0.1d0
                  CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,TempMaxPLR, &
                                                DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMOde, &
                                                HXUnitEnable=HXUnitOn, EconomizerFlag=EconomizerFlag)
                  TempOutletTempDXCoil = HXAssistedCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
                END DO
                TempMinPLR = TempMaxPLR
                DO WHILE((TempOutletTempDXCoil-DesOutTemp) .LT. 0.0d0 .AND. TempMinPLR .GE. 0.0d0)
!                 pull upper limit of PLR down to last valid limit (i.e. outlet temp still exceeds DesOutTemp)
                  TempMaxPLR = TempMinPLR
!                 find minimum limit of PLR
                  TempMinPLR = TempMinPLR - 0.01d0
                  CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,TempMinPLR, &
                                                DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMode, &
                                                HXUnitEnable=HXUnitOn, EconomizerFlag=EconomizerFlag)
                  TempOutletTempDXCoil = HXAssistedCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
                END DO
!               Relax boundary slightly to assure a solution can be found using RegulaFalsi (i.e. one boundary may be
!               very near the desired result)
                TempMinPLR = MAX(0.0d0,(TempMinPLR - 0.01d0))
                TempMaxPLR = MIN(1.0d0,(TempMaxPLR + 0.01d0))
!               tighter boundary of solution has been found, call RegulaFalsi a second time
                CALL SolveRegulaFalsi(Acc,MaxIte,SolFla,PartLoadFrac,HXAssistedCoolCoilTempResidual,TempMinPLR,TempMaxPLR,Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRIter = DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - Iteration limit'// &
                                            ' exceeded calculating DX unit sensible part-load ratio for unit = '// &
                                            TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio   = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  PartLoadFrac = ReqOutput/FullOutput
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFail = DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - DX unit sensible part-load ratio calculation unexpectedly failed: part-load '// &
                                            'ratio limits exceeded, for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                        ' unexpectedly failed error continues. Sensible PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF

              ELSE IF (SolFla == -2) THEN
                PartLoadFrac = ReqOutput/FullOutput
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFail2 .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFail2 = DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFail2+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - DX unit sensible part-load ratio calculation failed: part-load '// &
                                          'ratio limits exceeded, for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                      ' failed error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%HXAssistedSensPLRFailIndex2,PartLoadFrac,PartLoadFrac)
                END IF
              END IF
            END IF
          END IF

!         If system does not operate to meet sensible load, use no load humidity ratio to test against humidity setpoint,
!         else use operating humidity ratio to test against humidity setpoint
          IF (PartLoadFrac .EQ. 0.0d0)THEN
            OutletHumRatDXCoil = NoLoadHumRatOut
          ELSE
            OutletHumRatDXCoil = HXAssistedCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
          END IF

          ! If humidity setpoint is not satisfied and humidity control type is MultiMode,
          ! then enable heat exchanger and run to meet sensible load

          IF (( OutletHumRatDXCoil > DesOutHumRat) .AND. &
              (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_Multimode)) THEN

            ! Determine required part load when heat exchanger is ON
            HXUnitOn = .TRUE.
            PartLoadFrac = 1.0d0
            CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,PartLoadFrac, &
                                          DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMode, &
                                          HXUnitEnable=HXUnitOn, EconomizerFlag=EconomizerFlag)

            OutletTempDXCoil = HXAssistedCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

!           FullOutput will be different than the FullOutput determined above during sensible PLR calculations
            FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

            ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

!           Check to see if the system can meet the load with the compressor off
!           IF NoOutput is lower than (more cooling than required) or very near the ReqOutput, do not run the compressor
            IF ((NoOutput-ReqOutput) .LT. Acc) THEN
              PartLoadFrac = 0.0d0
!           OutletTempDXCoil is the full capacity outlet temperature at PartLoadFrac = 1 from the CALL above.
!           If this temp is greater than or very near the desired outlet temp, then run the compressor at PartLoadFrac = 1.
            ELSE IF ((OutletTempDXCoil > DesOutTemp) .OR. ABS(OutletTempDXCoil - DesOutTemp) .LE. (Acc*2.0d0)) THEN
               PartLoadFrac = 1.0d0
            ELSE
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutTemp
              ! FirstHVACIteration is a logical, Par is REAL(r64), so make TRUE = 1.0 and FALSE = 0.0
              IF(FirstHVACIteration)THEN
                Par(3) = 1.0d0
              ELSE
                Par(3) = 0.0d0
              END IF
              IF(HXUnitOn)THEN
                Par(4) = 1.0d0
              ELSE
                Par(4) = 0.0d0
              END IF
              Par(5) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, HXAssistedCoolCoilTempResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRIter .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRIter = DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRIter+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit latent'// &
                                          ' part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated latent part-load ratio   = '//RoundSigDigits((ReqOutput/FullOutput),3))
                    CALL ShowContinueError('Calculated latent part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The calculated latent part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' latent part-load ratio error continues. Latent PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                END IF
              ELSE IF (SolFla == -2) THEN
                PartLoadFrac = ReqOutput/FullOutput
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRFail .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRFail = DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRFail+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - DX unit latent part-load ratio calculation failed: part-load '// &
                                          'ratio limits exceeded, for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit latent part-load ratio calculation'// &
                      ' failed error continues. Latent PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%HXAssistedLatPLRFailIndex,PartLoadFrac,PartLoadFrac)
                END IF
              END IF
            END IF
          END IF ! End if humidity ratio setpoint not met - Multimode humidity control

          ! If humidity setpoint is not satisfied and humidity control type is CoolReheat, then calculate
          ! a new latent PLR

          IF (OutletHumRatDXCoil .GT. DesOutHumRat .AND. PartLoadFrac .LT. 1.0d0 .AND. &
              DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_CoolReheat) THEN

!           IF NoLoadHumRatOut is lower than (more dehumidification than required) or very near the DesOutHumRat,
!           do not run the compressor
            IF ((NoLoadHumRatOut-DesOutHumRat) .LT. HumRatAcc*2.0d0) THEN
              PartLoadFrac = PartLoadFrac  ! keep part-load fraction from sensible calculation
!           If the FullLoadHumRatOut is greater than (insufficient dehumidification) or very near the DesOutHumRat,
!           run the compressor at PartLoadFrac = 1.
            ELSE IF ((DesOutHumRat-FullLoadHumRatOut) .LT. HumRatAcc*2.0d0) THEN
              PartLoadFrac = 1.0d0
!           Else find the PLR to meet the load
            ELSE
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutHumRat
              ! FirstHVACIteration is a logical, Par is REAL(r64), so make TRUE = 1 and FALSE = 0
              IF(FirstHVACIteration)THEN
                Par(3) = 1.0d0
              ELSE
                Par(3) = 0.0d0
              END IF
              IF(HXUnitOn)THEN
                Par(4) = 1.0d0
              ELSE
                Par(4) = 0.0d0
              END IF
              Par(5) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, PartLoadFrac, HXAssistedCoolCoilHRResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN

!               RegulaFalsi may not find latent PLR when the latent degradation model is used.
!               If iteration limit is exceeded, find tighter boundary of solution and repeat RegulaFalsi
                TempMaxPLR = -0.1d0
                TempOutletHumRatDXCoil = OutletHumRatDXCoil
                DO WHILE((OutletHumRatDXCoil - TempOutletHumRatDXCoil) .GE. 0.0d0 .AND. TempMaxPLR .LE. 1.0d0)
!                 find upper limit of LatentPLR
                  TempMaxPLR = TempMaxPLR + 0.1d0
                  CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,TempMaxPLR, &
                                                DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMode, &
                                                HXUnitEnable=HXUnitOn, EconomizerFlag=EconomizerFlag)
                  OutletHumRatDXCoil = HXAssistedCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
                END DO
                TempMinPLR = TempMaxPLR
                DO WHILE((OutletHumRatDXCoil - TempOutletHumRatDXCoil) .LE. 0.0d0 .AND. TempMinPLR .GE. 0.0d0)
!                 pull upper limit of LatentPLR down to last valid limit (i.e. latent output still exceeds SystemMoisuterLoad)
                  TempMaxPLR = TempMinPLR
!                 find minimum limit of Latent PLR
                  TempMinPLR = TempMinPLR - 0.01d0
                  CALL SimHXAssistedCoolingCoil(CompName,FirstHVACIteration,On,TempMaxPLR, &
                                                DXCoolingSystem(DXSystemNum)%CoolingCoilIndex, FanOpMode, &
                                                HXUnitEnable=HXUnitOn, EconomizerFlag=EconomizerFlag)
                  OutletHumRatDXCoil = HXAssistedCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
                END DO
!               tighter boundary of solution has been found, call RegulaFalsi a second time
                CALL SolveRegulaFalsi(HumRatAcc,MaxIte,SolFla,PartLoadFrac,HXAssistedCoolCoilHRResidual, &
                                      TempMinPLR,TempMaxPLR,Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRIter = DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - Iteration limit exceeded calculating DX unit latent'// &
                                            ' part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated latent part-load ratio   = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated latent part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated latent part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' latent part-load ratio error continues. Latent PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF

                ELSE IF (SolFla == -2) THEN
                  PartLoadFrac = ReqOutput/FullOutput
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFail = DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                         ' - DX unit latent part-load ratio calculation failed unexpectedly:'// &
                                         ' part-load ratio limits exceeded, for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit latent part-load ratio calculation'// &
                        ' failed unexpectedly error continues. Latent PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF
              ELSE IF (SolFla == -2) THEN
                PartLoadFrac = ReqOutput/FullOutput
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFail2 .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFail2 = DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFail2+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - DX unit latent part-load ratio calculation failed: part-load '// &
                                          'ratio limits exceeded, for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit latent part-load ratio calculation'// &
                      ' failed error continues. Latent PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%HXAssistedCRLatPLRFailIndex2,PartLoadFrac,PartLoadFrac)
                END IF
              END IF
            END IF
          END IF ! End if humidity ratio setpoint not met - CoolReheat humidity control

          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF

        CASE (CoilDX_CoolingTwoSpeed)  ! Coil:Cooling:DX:TwoSpeed
                                       ! formerly (v3 and beyond)COIL:DX:MULTISPEED:COOLINGEMPIRICAL
!         SUBROUTINE SimDXCoilMultiSpeed(CompName,SpeedRatio,CycRatio,CompIndex,SpeedNum,FanMode,CompOp)
          CALL SimDXCoilMultiSpeed(CompName,0.0d0,1.0d0,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
          OutletTempLS = DXCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
          IF (OutletTempLS > DesOutTemp .AND. SensibleLoad) THEN
            CycRatio = 1.0d0
            CALL SimDXCoilMultiSpeed(CompName,1.0d0,1.0d0,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
            OutletTempHS = DXCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
            IF (OutletTempHS < DesOutTemp) THEN
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutTemp
              CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, SpeedRatio, DXCoilVarSpeedResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%MSpdSensPLRIter .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%MSpdSensPLRIter = DXCoolingSystem(DXSystemNum)%MSpdSensPLRIter+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible'// &
                                          ' speed ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Calculated speed ratio = '//RoundSigDigits(SpeedRatio,3))
                    CALL ShowContinueErrorTimeStamp('The calculated speed ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible speed ratio error continues. Sensible speed ratio statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%MSpdSensPLRIterIndex,SpeedRatio,SpeedRatio)
                END IF
              ELSE IF (SolFla == -2) THEN
                IF(.NOT. WarmupFlag) &
                  CALL ShowFatalError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                      ' - compressor speed calculation failed: speed limits exceeded, for unit='// &
                                      TRIM(DXCoolingSystem(DXSystemNum)%Name))
              END IF
            ELSE
              SpeedRatio = 1.0d0
            END IF
          ELSE IF(SensibleLoad)THEN
            SpeedRatio = 0.0d0
            Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
            Par(2) = DesOutTemp
            CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, CycRatio, DXCoilCyclingResidual, 0.0d0,   &
                                            1.0d0, Par)
            IF (SolFla == -1) THEN
              IF(.NOT. WarmupFlag)THEN
                IF(DXCoolingSystem(DXSystemNum)%MSpdCycSensPLRIter .LT. 1)THEN
                  DXCoolingSystem(DXSystemNum)%MSpdCycSensPLRIter = DXCoolingSystem(DXSystemNum)%MSpdCycSensPLRIter+1
                  CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                        ' - Iteration limit exceeded calculating DX unit sensible'// &
                                        ' cycling ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                  CALL ShowContinueError('Calculated cycling ratio = '//RoundSigDigits(CycRatio,3))
                  CALL ShowContinueErrorTimeStamp('The calculated cycling ratio will be used and the simulation'// &
                                                  ' continues. Occurrence info: ')
                END IF
                CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                    //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                    ' sensible cycling ratio error continues. Sensible cycling ratio statistics follow.' &
                    ,DXCoolingSystem(DXSystemNum)%MSpdCycSensPLRIterIndex,CycRatio,CycRatio)
              END IF
            ELSE IF (SolFla == -2) THEN ! should never get here, if it does logic above to protect from this
              IF(.NOT. WarmupFlag) &
                CALL ShowFatalError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                    ' - cycling ratio calculation failed: cycling limits exceeded, for unit='// &
                                    TRIM(DXCoolingSystem(DXSystemNum)%Name))
            END IF
          ELSE
            PartLoadFrac = 0.0d0
            SpeedRatio = 0.0d0
            CycRatio = 0.0d0
            DehumidMode  = 0
          END IF

          IF (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_CoolReheat) THEN

!           Simulate MultiSpeed DX coil at sensible result
            CALL SimDXCoilMultiSpeed(CompName,SpeedRatio,CycRatio,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

            OutletHumRatDXCoil = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
            ! If humidity setpoint is not satisfied and humidity control type is CoolReheat,
            ! then overcool to meet moisture load

            IF (OutletHumRatDXCoil > DesOutHumRat) THEN

              CycRatio = 0.0d0
              SpeedRatio = 0.0d0

!             SUBROUTINE SimDXCoilMultiSpeed(CompName,SpeedRatio,CycRatio,CompIndex,SpeedNum,FanMode,CompOp)
              CALL SimDXCoilMultiSpeed(CompName,0.0d0,1.0d0,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
              OutletHumRatLS = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
              IF (OutletHumRatLS > DesOutHumRat) THEN
                CycRatio = 1.0d0
                CALL SimDXCoilMultiSpeed(CompName,1.0d0,1.0d0,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
                OutletHumRatHS = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
                IF (OutletHumRatHS < DesOutHumRat) THEN
                  Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
                  Par(2) = DesOutHumRat
                  CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, SpeedRatio, DXCoilVarSpeedHumRatResidual, 0.0d0,   &
                                            1.0d0, Par)
                  IF (SolFla == -1) THEN
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXCoolingSystem(DXSystemNum)%MSpdLatPLRIter .LT. 1)THEN
                        DXCoolingSystem(DXSystemNum)%MSpdLatPLRIter = DXCoolingSystem(DXSystemNum)%MSpdLatPLRIter+1
                        CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                              ' - Iteration limit exceeded calculating DX unit latent'// &
                                              ' speed ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Calculated speed ratio = '//RoundSigDigits(SpeedRatio,3))
                        CALL ShowContinueErrorTimeStamp('The calculated speed ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                      END IF
                      CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                          //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                          ' latent speed ratio error continues. Latent speed ratio statistics follow.' &
                          ,DXCoolingSystem(DXSystemNum)%MSpdLatPLRIterIndex,SpeedRatio,SpeedRatio)
                    END IF
                  ELSE IF (SolFla == -2) THEN
                    IF(.NOT. WarmupFlag) &
                      CALL ShowFatalError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - compressor speed'// &
                                          ' calculation failed:speed limits exceeded, for unit='// &
                                          TRIM(DXCoolingSystem(DXSystemNum)%Name))
                  END IF
                ELSE
                  SpeedRatio = 1.0d0
                END IF
              ELSE
                SpeedRatio = 0.0d0
                Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
                Par(2) = DesOutHumRat
                CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, CycRatio, DXCoilCyclingHumRatResidual, 0.0d0,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%MSpdCycLatPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%MSpdCycLatPLRIter = DXCoolingSystem(DXSystemNum)%MSpdCycLatPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - Iteration limit exceeded calculating DX unit latent'// &
                                            ' cycling ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Calculated cycling ratio = '//RoundSigDigits(CycRatio,3))
                      CALL ShowContinueErrorTimeStamp('The calculated cycling ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' latent cycling ratio error continues. Latent cycling ratio statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%MSpdCycLatPLRIterIndex,CycRatio,CycRatio)
                  END IF
                ELSE IF (SolFla == -2) THEN ! should never get here, if it does logic above to protect from this
                  IF(.NOT. WarmupFlag) &
                    CALL ShowFatalError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - cycling ratio' // &
                                        ' calculation failed: cycling limits exceeded, for unit='// &
                                        TRIM(DXCoolingSystem(DXSystemNum)%Name))
                END IF
              END IF

            END IF

          END IF

        CASE (CoilDX_CoolingTwoStageWHumControl) ! Coil:Cooling:DX:TwoStageWithHumidityControlMode
                                        ! formerly (v3 and beyond) COIL:DX:MULTIMODE:COOLINGEMPIRICAL)

          ! Get no load result
          PartLoadFrac = 0.0d0
          CALL SimDXCoilMultiMode(CompName,On,FirstHVACIteration,PartLoadFrac,DehumidMode,  &
                                  DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,FanOpMode)
          NoOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
          NoLoadHumRatOut = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          ! Get full load result
          PartLoadFrac = 1.0d0
          CALL SimDXCoilMultiMode(CompName,On,FirstHVACIteration,PartLoadFrac,DehumidMode,  &
                                  DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,FanOpMode)
          FullLoadHumRatOut = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

!         IF NoOutput is lower than (more cooling than required) or very near the ReqOutput, do not run the compressor
          IF ((NoOutput-ReqOutput) .LT. Acc) THEN
            PartLoadFrac = 0.0d0
!         If the FullOutput is greater than (insufficient cooling) or very near the ReqOutput,
!         run the compressor at PartLoadFrac = 1.
          ELSE IF ((FullOutput - ReqOutput) .GT. Acc) THEN
            PartLoadFrac = 1.0d0
!         Else find the PLR to meet the load
          ELSE
            OutletTempDXCoil = DXCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
            IF (OutletTempDXCoil > DesOutTemp) THEN
              PartLoadFrac = 1.0d0
            ELSE
              Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
              Par(2) = DesOutTemp
              ! Dehumidification mode = 0 for normal mode, 1+ for enhanced mode
              Par(3) = REAL(DehumidMode,r64)
              Par(4) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, MultiModeDXCoilResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN
                IF(.NOT. WarmupFlag)THEN
                  IF(DXCoolingSystem(DXSystemNum)%MModeSensPLRIter .LT. 1)THEN
                    DXCoolingSystem(DXSystemNum)%MModeSensPLRIter = DXCoolingSystem(DXSystemNum)%MModeSensPLRIter+1
                    CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible'// &
                                          ' part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                    CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  END IF
                  CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%MModeSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                END IF
              ELSE IF (SolFla == -2) THEN
                IF(.NOT. WarmupFlag) THEN
                  CALL ShowSevereError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                       ' : part-load ratio calculation failed: '//  &
                                       'part-load ratio limits exceeded, for unit='// &
                                       TRIM(DXCoolingSystem(DXSystemNum)%Name))
                  CALL ShowFatalError('Program terminates due to previous condition.')
                END IF
              END IF
            END IF
          END IF

          OutletHumRatDXCoil = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)

          ! If humidity setpoint is not satisfied and humidity control type is Multimode,
          ! then turn on enhanced dehumidification mode 1

          IF (( OutletHumRatDXCoil > DesOutHumRat) .AND. &
              (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_Multimode)) THEN

            ! Determine required part load for enhanced dehumidification mode 1

            ! Get full load result
            PartLoadFrac = 1.0d0
            DehumidMode  = 1
            DXCoolingSystem(DXSystemNum)%DehumidificationMode = DehumidMode
            CALL SimDXCoilMultiMode(CompName,On,FirstHVACIteration,PartLoadFrac,DehumidMode,  &
                                    DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,FanOpMode)
            FullOutput = Node(InletNode)%MassFlowRate *  &
                         (PsyHFnTdbW(Node(OutletNode)%Temp,Node(InletNode)%HumRat)  &
                          - PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

            ReqOutput = Node(InletNode)%MassFlowRate *  &
                         (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(InletNode)%HumRat) - &
                          PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

            ! Since we are cooling, we expect FullOutput to be < 0 and FullOutput < NoCoolOutput
            ! Check that this is the case; if not set PartLoadFrac = 0.0d0 (off) and return
            ! Calculate the part load fraction
            IF (FullOutput .GE. 0) THEN
              PartLoadFrac = 0.0d0
            ELSE
              OutletTempDXCoil = DXCoilOutletTemp(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
              OutletHumRatDXCoil = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
              ! if sensible load and setpoint cannot be met, set PLR = 1. If no sensible load and
              ! latent load exists and setpoint cannot be met, set PLR = 1.
              IF ((OutletTempDXCoil >= DesOutTemp .AND. SensibleLoad .and. DXCoolingSystem(DXSystemNum)%RunOnSensibleLoad) .OR. &
                  (OutletHumRatDXCoil >= DesOutHumRat .AND. &
                  .NOT. SensibleLoad .AND. LatentLoad .AND. DXCoolingSystem(DXSystemNum)%RunOnLatentLoad)) THEN
                PartLoadFrac = 1.0d0
              ! if no sensible load and latent load can be met, find PLR
              ELSE IF (.NOT. SensibleLoad .AND. &
                  (OutletHumRatDXCoil < DesOutHumRat .AND. LatentLoad .AND. DXCoolingSystem(DXSystemNum)%RunOnLatentLoad)) THEN
                ! is a latent load with no sensible load, iterate on humidity ratio
                Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
                Par(2) = DesOutHumRat
                ! Dehumidification mode = 0 for normal mode, 1+ for enhanced mode
                Par(3) = REAL(DehumidMode,r64)
                Par(4) = REAL(FanOpMode,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, MultiModeDXCoilHumRatResidual, 0.0d0,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%MModeLatPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%MModeLatPLRIter = DXCoolingSystem(DXSystemNum)%MModeLatPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - Iteration limit exceeded calculating DX unit multimode'// &
                                            ' latent (no sensible) part-load ratio for unit = '// &
                                            TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      IF(NoLoadHumRatOut-OutletHumRatDXCoil > 0.d0)THEN
                        TempMinPLR = (DesOutHumRat-OutletHumRatDXCoil)/(NoLoadHumRatOut-OutletHumRatDXCoil)
                      ELSE
                        TempMinPLR = PartLoadFrac + 0.001d0
                      END IF
                      CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits(TempMinPLR,3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' multimode latent (no sensible) part-load ratio error continues. Latent PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%MModeLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  IF(.NOT. WarmupFlag) THEN
                    CALL ShowSevereError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                         ' : part-load ratio calculation failed: '//  &
                                         'part-load ratio limits exceeded, for unit='// &
                                         TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowFatalError('Program terminates due to previous condition.')
                  END IF
                END IF

              ELSE ! must be a sensible load so find PLR
                PartLoadFrac = ReqOutput/FullOutput
                Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
                Par(2) = DesOutTemp
                ! Dehumidification mode = 0 for normal mode, 1+ for enhanced mode
                Par(3) = REAL(DehumidMode,r64)
                Par(4) = REAL(FanOpMode,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, MultiModeDXCoilResidual, 0.0d0,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%MModeLatPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%MModeLatPLRIter = DXCoolingSystem(DXSystemNum)%MModeLatPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - Iteration limit exceeded calculating DX unit multimode'// &
                                            ' latent part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' multimode latent part-load ratio error continues. Latent PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%MModeLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  IF(.NOT. WarmupFlag) THEN
                    CALL ShowSevereError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                         ' : part-load ratio calculation failed: '//  &
                                         'part-load ratio limits exceeded, for unit='// &
                                         TRIM(DXCoolingSystem(DXSystemNum)%Name))
                    CALL ShowFatalError('Program terminates due to previous condition.')
                  END IF
                END IF
              END IF
            ENDIF
          END IF ! End if humidity ratio setpoint not met - multimode humidity control


!         If humidity setpoint is not satisfied and humidity control type is CoolReheat, then run to meet latent load
!         If system does not operate to meet sensible load, use no load humidity ratio to test against humidity setpoint,
!         else use operating humidity ratio to test against humidity setpoint
          IF (PartLoadFrac .EQ. 0.0d0)THEN
              OutletHumRatDXCoil = NoLoadHumRatOut
          ELSE
              OutletHumRatDXCoil = DXCoilOutletHumRat(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)
          END IF

          IF (( OutletHumRatDXCoil > DesOutHumRat) .AND. &
                (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_CoolReheat)) THEN

!            CoolReheat operates cooling stage 1 and/or 2 to meet DesOutHumRat. Dehumidification mode is not active.
             DehumidMode  = 0

!            IF NoLoadHumRatOut is lower than (more dehumidification than required) or very near the DesOutHumRat,
!            do not run the compressor
             IF ((NoLoadHumRatOut-DesOutHumRat) .LT. HumRatAcc) THEN
                PartLoadFrac = PartLoadFrac  ! keep part-load fraction from sensible calculation
!            If the FullLoadHumRatOut is greater than (insufficient dehumidification) or very near the DesOutHumRat,
!            run the compressor at PartLoadFrac = 1.
             ELSE IF ((DesOutHumRat-FullLoadHumRatOut) .LT. HumRatAcc) THEN
                PartLoadFrac = 1.0d0
!            Else find the PLR to meet the load
             ELSE
               Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
               Par(2) = DesOutHumRat
               ! Dehumidification mode = 0 for normal mode, 1+ for enhanced mode
               Par(3) = REAL(DehumidMode,r64)
               Par(4) = REAL(FanOpMode,r64)
               CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, MultiModeDXCoilHumRatResidual, 0.0d0,   &
                                           1.0d0, Par)
               IF (SolFla == -1) THEN
                 IF(.NOT. WarmupFlag)THEN
                   IF(DXCoolingSystem(DXSystemNum)%MModeLatPLRIter2 .LT. 1)THEN
                     DXCoolingSystem(DXSystemNum)%MModeLatPLRIter2 = DXCoolingSystem(DXSystemNum)%MModeLatPLRIter2+1
                     CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                           ' - Iteration limit exceeded calculating DX unit coolreheat'// &
                                           ' latent part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                     CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                     CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                     CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                   END IF
                   CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                       //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                       ' coolreheat latent part-load ratio error continues. Latent PLR statistics follow.' &
                       ,DXCoolingSystem(DXSystemNum)%MModeLatPLRIterIndex2,PartLoadFrac,PartLoadFrac)
                 END IF
               ELSE IF (SolFla == -2) THEN
                 IF(.NOT. WarmupFlag) THEN
                   CALL ShowSevereError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                        ' : part-load ratio calculation failed: '//  &
                                        'part-load ratio limits exceeded, for unit='// &
                                        TRIM(DXCoolingSystem(DXSystemNum)%Name))
                   CALL ShowFatalError('Program terminates due to previous condition.')
                 END IF
               END IF
             END IF
          END IF ! End if humidity ratio setpoint not met - CoolReheat humidity control

          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF
        CASE (Coil_CoolingAirToAirVariableSpeed)  ! Coil:Cooling:DX:VariableSpeed
        !variable-speed air-to-air cooling coil, begin -------------------------
          ! Get no load result
          PartLoadFrac = 0.0d0
          SpeedNum     = 1
          QZnReq       = 0.0d0
          QLatReq      = 0.0d0
          MaxONOFFCyclesperHour = 4.0d0 !default number
          HPTimeConstant= 0.0d0
          FanDelayTime  = 0.0d0
          OnOffAirFlowRatio = 1.0d0
          SpeedRatio = 0.0d0

         Call SimVariableSpeedCoils(CompName,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

          VSCoilIndex = DXCoolingSystem(DXSystemNum)%CoolingCoilIndex
          NumOfSpeeds = VarSpeedCoil(VSCoilIndex)%NumOfSpeeds

          NoOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
          NoLoadHumRatOut = VarSpeedCoil(VSCoilIndex)%OutletAirHumRat

          ! Get full load result
          PartLoadFrac = 1.0d0

          SpeedNum     = NumOfSpeeds
          SpeedRatio = 1.0d0
          QZnReq = 0.001d0  !to indicate the coil is running
          Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

          FullLoadHumRatOut = VarSpeedCoil(VSCoilIndex)%OutletAirHumRat
          FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

!         IF NoOutput is lower than (more cooling than required) or very near the ReqOutput, do not run the compressor
          IF ((NoOutput-ReqOutput) .LT. Acc) THEN
            PartLoadFrac = 0.0d0
            SpeedNum = 1
            SpeedRatio = 0.0d0
!         If the FullOutput is greater than (insufficient cooling) or very near the ReqOutput,
!         run the compressor at PartLoadFrac = 1.
          ELSE IF ((FullOutput - ReqOutput) .GT. Acc) THEN
            PartLoadFrac = 1.0d0
            SpeedNum = NumOfSpeeds
            SpeedRatio = 1.0d0
!         Else find the PLR to meet the load
          ELSE
!           OutletTempDXCoil is the full capacity outlet temperature at PartLoadFrac = 1 from the CALL above. If this temp is
!           greater than the desired outlet temp, then run the compressor at PartLoadFrac = 1, otherwise find the operating PLR.
            OutletTempDXCoil = VarSpeedCoil(VSCoilIndex)%OutletAirDBTemp
            IF (OutletTempDXCoil > DesOutTemp) THEN
              PartLoadFrac = 1.0d0
              SpeedNum = NumOfSpeeds
              SpeedRatio = 1.0d0
            ELSE
              PartLoadFrac = 1.0d0
              SpeedNum     = 1
              SpeedRatio = 1.0d0
              QZnReq = 0.001d0  !to indicate the coil is running
              Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
                 FanOpMode,MaxONOFFCyclesperHour, &
                 HPTimeConstant,FanDelayTime,&
                 On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

              TempSpeedOut =  Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
              TempSpeedReqst = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

              IF((TempSpeedOut - TempSpeedReqst) .GT. Acc) THEN
                   ! Check to see which speed to meet the load
                PartLoadFrac = 1.0d0
                SpeedRatio = 1.0d0
                DO I=2,NumOfSpeeds
                  SpeedNum = I
                  Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
                     FanOpMode,MaxONOFFCyclesperHour, &
                     HPTimeConstant,FanDelayTime,&
                     On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

                  TempSpeedOut =  Node(InletNode)%MassFlowRate *  &
                           (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                            - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
                  TempSpeedReqst = Node(InletNode)%MassFlowRate *  &
                           (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                            PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

                  IF ((TempSpeedOut - TempSpeedReqst) .LT. Acc) THEN
                    SpeedNum = I
                    Exit
                  END IF
                END DO
                Par(1) = REAL(VSCoilIndex,r64)
                Par(2) = DesOutTemp
                Par(5) = REAL(FanOpMode,r64)
                Par(3) = REAL(SpeedNum,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, SpeedRatio, VSCoilSpeedResidual, 1.0d-10, 1.0d0, Par)

                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible '// &
                                          'part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  PartLoadFrac = TempSpeedReqst/TempSpeedOut
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                    ' - DX unit sensible part-'// &
                                    'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                                     TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                      ' failed error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF
              ELSE
                Par(1) = REAL(VSCoilIndex,r64)
                Par(2) = DesOutTemp
                Par(5) = REAL(FanOpMode,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, VSCoilCyclingResidual, 1.0d-10,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible '// &
                                          'part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  PartLoadFrac = TempSpeedReqst/TempSpeedOut
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                    ' - DX unit sensible part-'// &
                                    'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                                     TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                      ' failed error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF
              END IF
            END IF
          END IF

!         If system does not operate to meet sensible load, use no load humidity ratio to test against humidity setpoint,
!         else use operating humidity ratio to test against humidity setpoint
          IF (PartLoadFrac .EQ. 0.0d0)THEN
            OutletHumRatDXCoil = NoLoadHumRatOut
          ELSE
            OutletHumRatDXCoil = VarSpeedCoil(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex)%OutletAirHumRat
          END IF

          ! If humidity setpoint is not satisfied and humidity control type is CoolReheat,
          ! then overcool to meet moisture load

          IF (( OutletHumRatDXCoil > DesOutHumRat) .AND. (PartLoadFrac .LT. 1.0d0) .AND. &
              (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_CoolReheat)) THEN

!           IF NoLoadHumRatOut is lower than (more dehumidification than required) or very near the DesOutHumRat,
!           do not run the compressor
            IF ((NoLoadHumRatOut-DesOutHumRat) .LT. HumRatAcc) THEN
              PartLoadFrac = PartLoadFrac  ! keep part-load fraction from sensible calculation
!           If the FullLoadHumRatOut is greater than (insufficient dehumidification) or very near the DesOutHumRat,
!           run the compressor at PartLoadFrac = 1.
            ELSE IF ((DesOutHumRat-FullLoadHumRatOut) .LT. HumRatAcc) THEN
              PartLoadFrac = 1.0d0
!           Else find the PLR to meet the load
            ELSE
              PartLoadFrac = 1.0d0
              SpeedNum     = 1
              SpeedRatio = 1.0d0
              QZnReq = 0.001d0  !to indicate the coil is running
              Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
                 FanOpMode,MaxONOFFCyclesperHour, &
                 HPTimeConstant,FanDelayTime,&
                 On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

              TempSpeedOut =  VarSpeedCoil(VSCoilIndex)%OutletAirHumRat

              IF((DesOutHumRat-FullLoadHumRatOut) .LT. HumRatAcc) THEN
                   ! Check to see which speed to meet the load
                PartLoadFrac = 1.0d0
                SpeedRatio = 1.0d0
                DO I=2,NumOfSpeeds
                  SpeedNum = I
                  Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
                     FanOpMode,MaxONOFFCyclesperHour, &
                     HPTimeConstant,FanDelayTime,&
                     On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

                  TempSpeedOut =  VarSpeedCoil(VSCoilIndex)%OutletAirHumRat

                  IF ((DesOutHumRat-TempSpeedOut) .GT. HumRatAcc) THEN
                    SpeedNum = I
                    Exit
                  END IF
                END DO
                Par(1) = REAL(VSCoilIndex,r64)
                Par(2) = DesOutHumRat
                Par(5) = REAL(FanOpMode,r64)
                Par(3) = REAL(SpeedNum,r64)
                CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, SpeedRatio, VSCoilSpeedHumResidual, 1.0d-10, 1.0d0, Par)

                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible '// &
                                          'part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  PartLoadFrac = TempSpeedReqst/TempSpeedOut
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - DX unit sensible part-'// &
                                    'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                                     TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                      //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                      ' failed error continues. Sensible PLR statistics follow.' &
                      ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF
              ELSE
                  Par(1) = REAL(VSCoilIndex,r64)
                  Par(2) = DesOutHumRat
                  Par(5) = REAL(FanOpMode,r64)
                  CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, PartLoadFrac, VSCoilCyclingHumResidual, 1.0d-10,   &
                                                1.0d0, Par)
                  IF (SolFla == -1) THEN
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter .LT. 1)THEN
                        DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter+1
                        CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                              ' - Iteration limit exceeded calculating DX unit latent part-load'// &
                                              ' ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Estimated part-load ratio   = '//RoundSigDigits((ReqOutput/FullOutput),3))
                        CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                        CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                      END IF
                      CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                          //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                          ' latent part-load ratio error continues. Latent PLR statistics follow.' &
                          ,DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                    END IF
                  ELSE IF (SolFla == -2) THEN
    !               RegulaFalsi returns PLR = minPLR when a solution cannot be found, recalculate PartLoadFrac.
                    IF(NoLoadHumRatOut-FullLoadHumRatOut .NE. 0.0d0)THEN
                      PartLoadFrac = (NoLoadHumRatOut-DesOutHumRat)/(NoLoadHumRatOut-FullLoadHumRatOut)
                    ELSE
                      PartLoadFrac = 1.0d0
                    END IF
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail .LT. 1)THEN
                        DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail+1
                        CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - DX unit latent part-'// &
                                        'load ratio calculation failed: part-load ratio limits exceeded, for unit = '//&
                                        TRIM(DXCoolingSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                        CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                        ' continues. Occurrence info: ')
                      END IF
                      CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                          //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit latent part-load ratio calculation'// &
                          ' failed error continues. Latent PLR statistics follow.' &
                          ,DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFailIndex,PartLoadFrac,PartLoadFrac)
                    END IF
                  END IF
               END IF
            END IF
          END IF ! End if humidity ratio setpoint not met - CoolReheat humidity control

          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF
        !variable-speed air-to-air cooling coil, end -------------------------

        CASE (CoilDX_PackagedThermalStorageCooling)

          ! First get the control mode that the child coil is in
          CALL SimTESCoil( CompName,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,&
               DXCoolingSystem(DXSystemNum)%FanOpMode, DXCoolingSystem(DXSystemNum)%TESOpMode, &
               DXCoolingSystem(DXSystemNum)%PartLoadFrac)
          IF (DXCoolingSystem(DXSystemNum)%TESOpMode == OffMode .or. &
              DXCoolingSystem(DXSystemNum)%TESOpMode == ChargeOnlyMode) THEN ! cannot cool
            PartLoadFrac = 0.0d0
          ELSE
            ! Get no load result
            PartLoadFrac = 0.0d0
            CALL SimTESCoil( CompName,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,&
               DXCoolingSystem(DXSystemNum)%FanOpMode, DXCoolingSystem(DXSystemNum)%TESOpMode, &
               PartLoadFrac)
            NoOutput = Node(InletNode)%MassFlowRate *  &
                         (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                          - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
            NoLoadHumRatOut = Node(OutletNode)%HumRat

            ! Get full load result
            PartLoadFrac = 1.0d0
            CALL SimTESCoil( CompName,DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,&
               DXCoolingSystem(DXSystemNum)%FanOpMode, DXCoolingSystem(DXSystemNum)%TESOpMode, &
               PartLoadFrac)
            FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
            FullLoadHumRatOut  = Node(OutletNode)%HumRat

            ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXCoolingSystem(DXSystemNum)%DesiredOutletTemp,Node(OutletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))
  !         IF NoOutput is lower than (more cooling than required) or very near the ReqOutput, do not run the compressor
            IF ((NoOutput-ReqOutput) .LT. Acc) THEN
              PartLoadFrac = 0.0d0
  !         If the FullOutput is greater than (insufficient cooling) or very near the ReqOutput,
  !         run the compressor at PartLoadFrac = 1.
            ELSE IF ((FullOutput - ReqOutput) .GT. Acc) THEN
              PartLoadFrac = 1.0d0
  !         Else find the PLR to meet the load
            ELSE
              IF (Node(OutletNode)%Temp > DesOutTemp) THEN
                PartLoadFrac = 1.0d0
              ELSE
                Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
                Par(2) = DesOutTemp
                Par(3) = DXCoolingSystem(DXSystemNum)%TESOpMode
                Par(4) = DXCoolingSystem(DXSystemNum)%DXCoolingCoilOutletNodeNum
                Par(5) = REAL(FanOpMode,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, TESCoilResidual, 0.0d0,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - Iteration limit exceeded calculating DX unit sensible '// &
                                            'part-load ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
                  PartLoadFrac = ReqOutput/FullOutput
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - DX unit sensible part-'// &
                                      'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                                       TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                        ' failed error continues. Sensible PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF

                END IF

              ENDIF
            ENDIF
  !         If system does not operate to meet sensible load, use no load humidity ratio to test against humidity setpoint,
  !         else use operating humidity ratio to test against humidity setpoint
            IF (PartLoadFrac .EQ. 0.0d0)THEN
              OutletHumRatDXCoil = NoLoadHumRatOut
            ELSE
              OutletHumRatDXCoil = Node(OutletNode)%HumRat
            END IF
            ! If humidity setpoint is not satisfied and humidity control type is CoolReheat,
            ! then overcool to meet moisture load

            IF (( OutletHumRatDXCoil > DesOutHumRat) .AND. (PartLoadFrac .LT. 1.0d0) .AND. &
                (DXCoolingSystem(DXSystemNum)%DehumidControlType .EQ. DehumidControl_CoolReheat)) THEN
  !           IF NoLoadHumRatOut is lower than (more dehumidification than required) or very near the DesOutHumRat,
  !           do not run the compressor
              IF ((NoLoadHumRatOut-DesOutHumRat) .LT. HumRatAcc) THEN
                PartLoadFrac = PartLoadFrac  ! keep part-load fraction from sensible calculation
  !           If the FullLoadHumRatOut is greater than (insufficient dehumidification) or very near the DesOutHumRat,
  !           run the compressor at PartLoadFrac = 1.
              ELSE IF ((DesOutHumRat-FullLoadHumRatOut) .LT. HumRatAcc) THEN
                PartLoadFrac = 1.0d0
  !           Else find the PLR to meet the load
              ELSE
                Par(1) = REAL(DXCoolingSystem(DXSystemNum)%CoolingCoilIndex,r64)
                Par(2) = DesOutHumRat
                Par(3) = DXCoolingSystem(DXSystemNum)%TESOpMode
                Par(4) = DXCoolingSystem(DXSystemNum)%DXCoolingCoilOutletNodeNum
                Par(5) = REAL(FanOpMode,r64)
                CALL SolveRegulaFalsi(HumRatAcc, MaxIte, SolFla, PartLoadFrac, TESCoilHumRatResidual, 0.0d0,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter = DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIter+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)// &
                                            ' - Iteration limit exceeded calculating DX unit latent part-load'// &
                                            ' ratio for unit = '//TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio   = '//RoundSigDigits((ReqOutput/FullOutput),3))
                      CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                        ' latent part-load ratio error continues. Latent PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%DXCoilLatPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                ELSE IF (SolFla == -2) THEN
  !               RegulaFalsi returns PLR = minPLR when a solution cannot be found, recalculate PartLoadFrac.
                  IF(NoLoadHumRatOut-FullLoadHumRatOut .NE. 0.0d0)THEN
                    PartLoadFrac = (NoLoadHumRatOut-DesOutHumRat)/(NoLoadHumRatOut-FullLoadHumRatOut)
                  ELSE
                    PartLoadFrac = 1.0d0
                  END IF
                  IF(.NOT. WarmupFlag)THEN
                    IF(DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail .LT. 1)THEN
                      DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail = DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFail+1
                      CALL ShowWarningError(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' - DX unit latent part-'// &
                                      'load ratio calculation failed: part-load ratio limits exceeded, for unit = '//&
                                      TRIM(DXCoolingSystem(DXSystemNum)%Name))
                      CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                      CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                      ' continues. Occurrence info: ')
                    END IF
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXCoolingSystem(DXSystemNum)%DXCoolingSystemType)//' "'&
                        //TRIM(DXCoolingSystem(DXSystemNum)%Name)//'" - DX unit latent part-load ratio calculation'// &
                        ' failed error continues. Latent PLR statistics follow.' &
                        ,DXCoolingSystem(DXSystemNum)%DXCoilLatPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF
              ENDIF
            ENDIF ! End if humidity ratio setpoint not met - CoolReheat humidity control

          ENDIF ! operating mode can cool
          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF

        CASE DEFAULT
          CALL ShowFatalError('ControlDXSystem: Invalid DXCoolingSystem coil type = '//  &
                              TRIM(DXCoolingSystem(DXSystemNum)%CoolingCoilType))

      END SELECT
    END IF ! End of cooling load type (sensible or latent) if block
  END IF   ! End of If DXCoolingSystem is scheduled on and there is flow
  !Set the final results
  DXCoolingSystem(DXSystemNum)%PartLoadFrac = PartLoadFrac
  DXCoolingSystem(DXSystemNum)%SpeedRatio = SpeedRatio
  DXCoolingSystem(DXSystemNum)%CycRatio = CycRatio
  DXCoolingSystem(DXSystemNum)%DehumidificationMode = DehumidMode
  DXCoolingSystem(DXSystemNum)%SpeedNum = SpeedNum

RETURN
END Subroutine ControlDXSystem

FUNCTION DXCoilVarSpeedResidual(SpeedRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Fred Buhl
          !       DATE WRITTEN   September 2002
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp).
          ! DX Coil output depends on the compressor speed which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcMultiSpeedDXCoil to get outlet temperature at the given compressor speed
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletTemp, CalcMultiSpeedDXCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: SpeedRatio ! compressor speed ratio (1.0 is max, 0.0 is min)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]

  CoilIndex = INT(Par(1))
  CALL CalcMultiSpeedDXCoil(CoilIndex,SpeedRatio,1.0d0)
  OutletAirTemp = DXCoilOutletTemp(CoilIndex)
  Residuum = Par(2) - OutletAirTemp

  RETURN
END FUNCTION DXCoilVarSpeedResidual

FUNCTION DXCoilVarSpeedHumRatResidual(SpeedRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad
          !       DATE WRITTEN   January 2008
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet humrat - actual outlet humrat).
          ! DX Coil output depends on the compressor speed which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcMultiSpeedDXCoil to get outlet humidity ratio at the given compressor speed
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletHumRat, CalcMultiSpeedDXCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: SpeedRatio ! compressor speed ratio (1.0 is max, 0.0 is min)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet humidity ratio [kg/kg]
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex        ! index of this coil
  REAL(r64) :: OutletAirHumRat  ! outlet air humidity ratio [kg/kg]

  CoilIndex = INT(Par(1))
  CALL CalcMultiSpeedDXCoil(CoilIndex,SpeedRatio,1.0d0)
  OutletAirHumRat = DXCoilOutletHumRat(CoilIndex)
  Residuum = Par(2) - OutletAirHumRat

  RETURN
END FUNCTION DXCoilVarSpeedHumRatResidual

FUNCTION DXCoilCyclingResidual(CycRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Fred Buhl
          !       DATE WRITTEN   September 2002
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp)
          ! DX Coil output depends on the cycling ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcMultiSpeedDXCoil to get outlet temperature at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletTemp, CalcMultiSpeedDXCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: CycRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]

  CoilIndex = INT(Par(1))
  CALL CalcMultiSpeedDXCoil(CoilIndex,0.0d0,CycRatio)
  OutletAirTemp = DXCoilOutletTemp(CoilIndex)
  Residuum = Par(2) - OutletAirTemp

  RETURN
END FUNCTION DXCoilCyclingResidual

FUNCTION DXCoilCyclingHumRatResidual(CycRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Fred Buhl
          !       DATE WRITTEN   September 2002
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp)
          ! DX Coil output depends on the cycling ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcMultiSpeedDXCoil to get outlet temperature at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletHumRat, CalcMultiSpeedDXCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: CycRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet humidity ratio [kg/kg]
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex        ! index of this coil
  REAL(r64) :: OutletAirHumRat  ! outlet air humidity ratio [kg/kg]

  CoilIndex = INT(Par(1))
  CALL CalcMultiSpeedDXCoil(CoilIndex,0.0d0,CycRatio)
  OutletAirHumRat = DXCoilOutletHumRat(CoilIndex)
  Residuum = Par(2) - OutletAirHumRat

  RETURN
END FUNCTION DXCoilCyclingHumRatResidual

FUNCTION DOE2DXCoilResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   November 2003
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp)
          ! DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcDoe2DXCoil to get outlet temperature at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletTemp, CalcDoe2DXCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))
  CALL CalcDoe2DXCoil(CoilIndex,On,.TRUE., PartLoadRatio,FanOpMode)
  OutletAirTemp = DXCoilOutletTemp(CoilIndex)
  Residuum = Par(2) - OutletAirTemp

  RETURN
END FUNCTION DOE2DXCoilResidual

FUNCTION DOE2DXCoilHumRatResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   January 2008
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet humrat - actual outlet humrat)
          ! DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcDoe2DXCoil to get outlet humidity ratio at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletHumRat, CalcDoe2DXCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet humidity ratio [kg/kg]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirHumRat ! outlet air humidity ratio [kg/kg]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))
  CALL CalcDoe2DXCoil(CoilIndex,On,.TRUE., PartLoadRatio,FanOpMode)
  OutletAirHumRat = DXCoilOutletHumRat(CoilIndex)
  Residuum = Par(2) - OutletAirHumRat

  RETURN
END FUNCTION DOE2DXCoilHumRatResidual

FUNCTION MultiModeDXCoilResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         M. J. Witte, GARD Analytics, Inc.
          !       DATE WRITTEN   February 2005
          !                      (based on DOE2DXCoilResidual by Richard Raustad, FSEC)
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp)
          ! DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls SimDXCoilMultiMode to get outlet temperature at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletTemp, SimDXCoilMultiMode

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(3) = dehumidification mode (0=normal, 1=enhanced)
                                                    ! par(4) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: DehumidMode     ! dehumidification mode (par3)
  INTEGER   :: FanOpMode       ! supply air fan operating mode

  CoilIndex   = INT(Par(1))
  DehumidMode = INT(Par(3))
  FanOpMode   = INT(Par(4))
  CALL SimDXCoilMultiMode('',On,.FALSE.,PartLoadRatio,DehumidMode,CoilIndex,FanOpMode)
  OutletAirTemp = DXCoilOutletTemp(CoilIndex)
  Residuum = Par(2) - OutletAirTemp

  RETURN
END FUNCTION MultiModeDXCoilResidual

FUNCTION MultiModeDXCoilHumRatResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   January 2008
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet humrat - actual outlet humrat)
          ! DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls SimDXCoilMultiMode to get outlet humidity ratio at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletHumRat, SimDXCoilMultiMode

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet humidity ratio [kg/kg]
                                                    ! par(3) = dehumidification mode (0=normal, 1=enhanced)
                                                    ! par(4) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirHumRat ! outlet air humidity ratio [kg/kg]
  INTEGER   :: DehumidMode     ! dehumidification mode (par3)
  INTEGER   :: FanOpMode       ! supply air fan operating mode

  CoilIndex   = INT(Par(1))
  DehumidMode = INT(Par(3))
  FanOpMode   = INT(Par(4))
  CALL SimDXCoilMultiMode('',On,.FALSE.,PartLoadRatio,DehumidMode,CoilIndex,FanOpMode)
  OutletAirHumRat = DXCoilOutletHumRat(CoilIndex)
  Residuum = Par(2) - OutletAirHumRat

  RETURN
END FUNCTION MultiModeDXCoilHumRatResidual

FUNCTION HXAssistedCoolCoilTempResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   November 2003
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (desired outlet temp - actual outlet temp)
          !  DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          !  Calls CalcHXAssistedCoolingCoil to get outlet temperature at the given part load ratio
          !  and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE HVACHXAssistedCoolingCoil, ONLY: HXAssistedCoilOutletTemp, CalcHXAssistedCoolingCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN)     :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
  REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                  ! par(2) = desired air outlet temperature [C]
                                                  ! par(3) = FirstHVACIteration logical converted to numeric (1=TRUE,0=FALSE)
                                                  ! par(4) = HX control (On/Off)
                                                  ! par(5) = supply air fan operating mode (ContFanCycCoil)
  REAL(r64)         :: Residuum  ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          !  na

          ! INTERFACE BLOCK SPECIFICATIONS
          !  na

          ! DERIVED TYPE DEFINITIONS
          !  na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex          ! index of this coil
  REAL(r64) :: OutletAirTemp      ! outlet air temperature [C]
  LOGICAL   :: FirstHVACIteration ! FirstHVACIteration flag
  LOGICAL   :: HXUnitOn           ! flag to enable heat exchanger heat recovery
  INTEGER   :: FanOpMode          ! Supply air fan operating mode

  CoilIndex = INT(Par(1))
  ! FirstHVACIteration is a logical, Par is REAL(r64), so make 1=TRUE and 0=FALSE
  IF(Par(3) .EQ. 1.0d0)THEN
    FirstHVACIteration = .TRUE.
  ELSE
    FirstHVACIteration = .FALSE.
  END IF
  IF(Par(4) .EQ. 1.0d0)THEN
    HXUnitOn = .TRUE.
  ELSE
    HXUnitOn = .FALSE.
  END IF
  FanOpMode = INT(Par(5))
  CALL CalcHXAssistedCoolingCoil(CoilIndex,FirstHVACIteration,On,PartLoadRatio, HXUnitOn, FanOpMode)
  OutletAirTemp = HXAssistedCoilOutletTemp(CoilIndex)
  Residuum = Par(2) - OutletAirTemp
  RETURN

END FUNCTION HXAssistedCoolCoilTempResidual

FUNCTION HXAssistedCoolCoilHRResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   January 2008
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (desired outlet humrat - actual outlet humrat)
          !  DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          !  Calls CalcHXAssistedCoolingCoil to get outlet humidity ratio at the given part load ratio
          !  and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE HVACHXAssistedCoolingCoil, ONLY: HXAssistedCoilOutletHumRat, CalcHXAssistedCoolingCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN)     :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
  REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                  ! par(2) = desired air outlet humidity ratio [kg/kg]
                                                  ! par(3) = FirstHVACIteration logical converted to numeric (1=TRUE,0=FALSE)
                                                  ! par(4) = HX control (On/Off)
                                                  ! par(5) = supply air fan operating mode (ContFanCycCoil)
  REAL(r64)         :: Residuum  ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          !  na

          ! INTERFACE BLOCK SPECIFICATIONS
          !  na

          ! DERIVED TYPE DEFINITIONS
          !  na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex          ! index of this coil
  REAL(r64) :: OutletAirHumRat    ! outlet air humidity ratio [kg/kg]
  LOGICAL   :: FirstHVACIteration ! FirstHVACIteration flag
  LOGICAL   :: HXUnitOn           ! flag to enable heat exchanger heat recovery
  INTEGER   :: FanOpMode          ! Supply air fan operating mode

  CoilIndex = INT(Par(1))
  ! FirstHVACIteration is a logical, Par is REAL(r64), so make 1=TRUE and 0=FALSE
  IF(Par(3) .EQ. 1.0d0)THEN
    FirstHVACIteration = .TRUE.
  ELSE
    FirstHVACIteration = .FALSE.
  END IF
  IF(Par(4) .EQ. 1.0d0)THEN
    HXUnitOn = .TRUE.
  ELSE
    HXUnitOn = .FALSE.
  END IF
  FanOpMode = INT(Par(5))
  CALL CalcHXAssistedCoolingCoil(CoilIndex,FirstHVACIteration,On,PartLoadRatio, HXUnitOn, FanOpMode, &
                                 EconomizerFlag=EconomizerFlag)
  OutletAirHumRat = HXAssistedCoilOutletHumRat(CoilIndex)
  Residuum = Par(2) - OutletAirHumRat
  RETURN

END FUNCTION HXAssistedCoolCoilHRResidual

FUNCTION TESCoilResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   April 2013
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp)
          ! TES Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls appropriate calculation routine depending on operating mode
          ! to get outlet temperature at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE PackagedThermalStorageCoil, ONLY: CalcTESCoilCoolingOnlyMode, CalcTESCoilCoolingAndChargeMode, &
                                       CalcTESCoilCoolingAndDischargeMode, CalcTESCoilDischargeOnlyMode

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
  REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                  ! par(2) = desired air outlet temperature [C]
                                                  ! par(3) = TES coil operating mode
                                                  ! par(4) = outlet node number
                                                  ! par(5) = supply air fan operating mode (ContFanCycCoil)
  REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER   :: TESOpMode
  INTEGER   :: OutletNodeNum

  CoilIndex     = INT(Par(1))
  FanOpMode     = INT(Par(5))
  OutletNodeNum = INT(Par(4))
  TESOpMode     = INT(Par(3))

  SELECT CASE (TESOpMode)
  CASE (CoolingOnlyMode)
    CALL CalcTESCoilCoolingOnlyMode(CoilIndex, FanOpMode, PartLoadRatio)
  CASE (CoolingAndChargeMode)
    CALL CalcTESCoilCoolingAndChargeMode(CoilIndex, FanOpMode, PartLoadRatio)
  CASE (CoolingAndDischargeMode)
    CALL CalcTESCoilCoolingAndDischargeMode(CoilIndex, FanOpMode, PartLoadRatio)
  CASE (DischargeOnlyMode)
    CALL CalcTESCoilDischargeOnlyMode(CoilIndex, PartLoadRatio)
  END SELECT


  OutletAirTemp = Node(OutletNodeNum)%Temp
  Residuum = Par(2) - OutletAirTemp

  RETURN
END FUNCTION TESCoilResidual

FUNCTION TESCoilHumRatResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Brent Griffith
          !       DATE WRITTEN   April 2013
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet humrat - actual outlet humrat)
          ! TES Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls appropriate calculation routine depending on operating mode
          ! to get outlet hum rat at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE PackagedThermalStorageCoil, ONLY: CalcTESCoilCoolingOnlyMode, CalcTESCoilCoolingAndChargeMode, &
                                       CalcTESCoilCoolingAndDischargeMode, CalcTESCoilDischargeOnlyMode

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet hum rat [kg_h20/kg_dryair]
                                                    ! par(3) = TES coil operating mode
                                                    ! par(4) = outlet node number
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirHumRat   ! outlet air humidity ratio [kg_H20/Kg_dryair]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER   :: TESOpMode
  INTEGER   :: OutletNodeNum

  CoilIndex     = INT(Par(1))
  FanOpMode     = INT(Par(5))
  OutletNodeNum = INT(Par(4))
  TESOpMode     = INT(Par(3))

  SELECT CASE (TESOpMode)
  CASE (CoolingOnlyMode)
    CALL CalcTESCoilCoolingOnlyMode(CoilIndex, FanOpMode, PartLoadRatio)
  CASE (CoolingAndChargeMode)
    CALL CalcTESCoilCoolingAndChargeMode(CoilIndex, FanOpMode, PartLoadRatio)
  CASE (CoolingAndDischargeMode)
    CALL CalcTESCoilCoolingAndDischargeMode(CoilIndex, FanOpMode, PartLoadRatio)
  CASE (DischargeOnlyMode)
    CALL CalcTESCoilDischargeOnlyMode(CoilIndex, PartLoadRatio)
  END SELECT


  OutletAirHumRat = Node(OutletNodeNum)%HumRat
  Residuum = Par(2) - OutletAirHumRat

  RETURN
END FUNCTION TESCoilHumRatResidual

SUBROUTINE FrostControlSetPointLimit(DXSystemNum,TempSetPoint,HumRatSetPoint,BaroPress,TfrostControl,ControlMode)
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Bereket Nigusse, FSEC
          !       DATE WRITTEN   January 2013
          !       MODIFIED
          !       RE-ENGINEERED
          !
          ! PURPOSE OF THIS SUBROUTINE:
          ! Controls the forst formation condition based on user specified minimum DX coil outlet
          ! air temperature. Resets the cooling setpoint based on the user specified limiting
          ! temperature for frost control.
          !
          ! METHODOLOGY EMPLOYED:
          !  na
          !
          ! REFERENCES:
          !  na
          ! USE STATEMENTS:
  USE Psychrometrics,     ONLY: PsyWFnTdpPb
          !
  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine
          !
          ! SUBROUTINE ARGUMENT DEFINITIONS:
    INTEGER, INTENT(IN)       :: DXSystemNum           ! dx cooling coil system index
    REAL(r64), INTENT(INOUT)  :: TempSetPoint          ! temperature setpoint of the sensor node
    REAL(r64), INTENT(INOUT)  :: HumRatSetPoint        ! humidity ratio setpoint of the sensor node
    REAL(r64), INTENT(IN)     :: BaroPress             ! baromtric pressure, Pa [N/m^2]
    REAL(r64), INTENT(IN)     :: TfrostControl         ! minimum temperature limit for forst control
    INTEGER, INTENT(IN)       :: ControlMode           ! temperature or humidity control mode
          !
          ! SUBROUTINE PARAMETER DEFINITIONS:
    INTEGER, PARAMETER        :: RunOnSensible = 1     ! identifier for temperature (sensible load) control
    INTEGER, PARAMETER        :: RunOnLatent = 2       ! identifier for humidity (latent load) control

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na
          !
          ! DERIVED TYPE DEFINITIONS
          ! na
          !
          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  REAL(r64)                   :: HumRatioSat     ! saturation humidity ratio at forst control temperature
  REAL(r64)                   :: AirMassFlow     ! air masss flow rate through the DX coil
  !
  AirMassFlow = Node(DXCoolingSystem(DXSystemNum)%DXCoolingCoilInletNodeNum)%MassFlowRate
  IF (ControlMode == RunOnSensible .AND. AirMassFlow > MinAirMassFlow .AND. &
      TempSetPoint .LT. Node(DXCoolingSystem(DXSystemNum)%DXCoolingCoilInletNodeNum)%Temp) THEN
    IF (TempSetPoint .lt. TfrostControl) THEN
        TempSetPoint = TfrostControl
        DXCoolingSystem(DXSystemNum)%FrostControlStatus = 1
    ENDIF
  ELSEIF(ControlMode == RunOnLatent .AND. AirMassFlow > MinAirMassFlow .AND. &
         HumRatSetPoint .LT. Node(DXCoolingSystem(DXSystemNum)%DXCoolingCoilInletNodeNum)%HumRat) THEN
    HumRatioSat = PsyWFnTdpPb(TfrostControl,BaroPress,'FrostControlSetPointLimit')
    IF (HumRatioSat .gt. HumRatSetPoint) THEN
        HumRatSetPoint = HumRatioSat
        DXCoolingSystem(DXSystemNum)%FrostControlStatus = 2
    ENDIF
  ELSE
    DXCoolingSystem(DXSystemNum)%FrostControlStatus = 0
  ENDIF
  RETURN
END SUBROUTINE FrostControlSetPointLimit

SUBROUTINE CheckDXCoolingCoilInOASysExists(DXCoilSysName)
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Bereket Nigusse
          !       DATE WRITTEN   Feb 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na
          !
          ! PURPOSE OF THIS SUBROUTINE:
          ! After making sure get input is done, checks if the Coil System DX coil is in the
          ! OA System.  If exists then the DX cooling coil is 100% DOAS DX coil.
          !
          ! METHODOLOGY EMPLOYED:
          ! na
          !
          ! REFERENCES:
          ! na
          !
          ! USE STATEMENTS:
  USE InputProcessor, ONLY: FindItemInList
  USE DXCoils,        ONLY: SetDXCoilTypeData

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine
          !
          ! SUBROUTINE ARGUMENT DEFINITIONS:
  CHARACTER(len=MaxNameLength), INTENT(IN) :: DXCoilSysName
          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER                       :: DXCoolSysNum

  IF (GetInputFlag) THEN             !First time subroutine has been entered
    CALL GetDXCoolingSystemInput
    GetInputFlag=.false.
  End If

  DXCoolSysNum=0
  IF (NumDXSystem > 0) THEN
     DXCoolSysNum=FindItemInList(DXCoilSysName,DXCoolingSystem%Name,NumDXSystem)
     IF (DXCoolSysNum > 0 .AND. DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil) THEN
        !DXCoolingSystem(DXCoolSysNum)%ISHundredPercentDOASDXCoil = .true.
        CALL SetDXCoilTypeData(DXCoolingSystem(DXCoolSysNum)%CoolingCoilName)
     ENDIF
  ENDIF


  RETURN

END SUBROUTINE CheckDXCoolingCoilInOASysExists

SUBROUTINE GetCoolingCoilTypeNameAndIndex(DXCoilSysName,CoolCoilType,CoolCoilIndex,CoolCoilName,ErrFound)
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   Aug 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na
          !
          ! PURPOSE OF THIS SUBROUTINE:
          ! After making sure get input is done, checks if the Coil System DX coil is in the
          ! OA System.  If exists then the DX cooling coil is 100% DOAS DX coil.
          !
          ! METHODOLOGY EMPLOYED:
          ! na
          !
          ! REFERENCES:
          ! na
          !
          ! USE STATEMENTS:
  USE InputProcessor, ONLY: FindItemInList
  USE DXCoils,        ONLY: SetDXCoilTypeData

  IMPLICIT NONE ! Enforce explicit typing of all variables in this routine
          !
          ! SUBROUTINE ARGUMENT DEFINITIONS:
  CHARACTER(len=MaxNameLength), INTENT(IN) :: DXCoilSysName
  INTEGER, INTENT(INOUT) :: CoolCoilType
  INTEGER, INTENT(INOUT) :: CoolCoilIndex
  CHARACTER(len=MaxNameLength), INTENT(INOUT) :: CoolCoilName
  LOGICAL, INTENT(INOUT) :: ErrFound
          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS:
          ! na

          ! DERIVED TYPE DEFINITIONS:
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  INTEGER                       :: DXCoolSysNum

  IF (GetInputFlag) THEN             !First time subroutine has been entered
    CALL GetDXCoolingSystemInput
    GetInputFlag=.false.
  End If

  DXCoolSysNum=0
  IF (NumDXSystem > 0) THEN
     DXCoolSysNum=FindItemInList(DXCoilSysName,DXCoolingSystem%Name,NumDXSystem)
     IF (DXCoolSysNum > 0 .AND. DXCoolSysNum <= NumDXSystem) THEN
       CoolCoilType = DXCoolingSystem(DXCoolSysNum)%CoolingCoilType_Num
       CoolCoilIndex = DXCoolingSystem(DXCoolSysNum)%CoolingCoilIndex
       CoolCoilName = DXCoolingSystem(DXCoolSysNum)%CoolingCoilName
     ENDIF
  ENDIF


  RETURN

END SUBROUTINE GetCoolingCoilTypeNameAndIndex

!******************************************************************************

FUNCTION VSCoilCyclingResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Bo Shen
          !       DATE WRITTEN   Feb, 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (Temperature) by comparing with the output of variable-speed DX coil
          ! interate part-load ratio

          ! REFERENCES:

          ! USE STATEMENTS:
          ! na
   USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

   IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero


          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER             :: SpeedNum = 1            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq = 0.001d0               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq = 0.0d0              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour = 4.0d0        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant = 0.0d0               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime = 0.0d0                ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio = 1.0d0 ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: SpeedRatio = 0.0d0        ! SpeedRatio varies between 1.0 (higher speed) and 0.0 (lower speed)

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))

  Call SimVariableSpeedCoils('  ', CoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadRatio, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

  OutletAirTemp = VarSpeedCoil(CoilIndex)%OutletAirDBTemp
  Residuum = Par(2) - OutletAirTemp

  RETURN

END FUNCTION VSCoilCyclingResidual


!******************************************************************************

FUNCTION VSCoilSpeedResidual(SpeedRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Bo Shen
          !       DATE WRITTEN   Feb, 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (Temperature) by comparing with the output of variable-speed DX coil
          ! interate speed ratio between two neighboring speeds
          ! REFERENCES:

          ! USE STATEMENTS:
          ! na
   USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

   IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: SpeedRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER             :: SpeedNum = 1            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq = 0.001d0               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq = 0.0d0              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour = 4.0d0        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant = 0.0d0               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime = 0.0d0                ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio = 1.0d0 ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: PartLoadRatio = 1.0d0        ! SpeedRatio varies between 1.0 (higher speed) and 0.0 (lower speed)

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))
  SpeedNum  = INT(Par(3))

  Call SimVariableSpeedCoils('  ', CoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadRatio, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

  OutletAirTemp = VarSpeedCoil(CoilIndex)%OutletAirDBTemp
  Residuum = Par(2) - OutletAirTemp

  RETURN

END FUNCTION VSCoilSpeedResidual

FUNCTION VSCoilCyclingHumResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Bo Shen
          !       DATE WRITTEN   Feb, 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (Humidity) by comparing with the output of variable-speed DX coil
          ! interate part-load ratio
          ! REFERENCES:

          ! USE STATEMENTS:
          ! na
   USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

   IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirHumRat ! outlet air humidity ratio [kg/kg]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER             :: SpeedNum = 1            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq = 0.001d0               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq = 0.0d0              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour = 4.0d0        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant = 0.0d0               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime = 0.0d0                ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio = 1.0d0 ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: SpeedRatio = 0.0d0        ! SpeedRatio varies between 1.0 (higher speed) and 0.0 (lower speed)

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))

  Call SimVariableSpeedCoils('  ', CoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadRatio, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

  OutletAirHumRat = VarSpeedCoil(CoilIndex)%OutletAirHumRat
  Residuum = Par(2) - OutletAirHumRat

  RETURN

END FUNCTION VSCoilCyclingHumResidual


!******************************************************************************

FUNCTION VSCoilSpeedHumResidual(SpeedRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Bo Shen
          !       DATE WRITTEN   Feb, 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function (Humidity) by comparing with the output of variable-speed DX coil
          ! interate speed ratio between two neighboring speeds

          ! REFERENCES:

          ! USE STATEMENTS:
          ! na
   USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

   IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: SpeedRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirHumRat ! outlet air humidity ratio [kg/kg]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER             :: SpeedNum = 1            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq = 0.001d0               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq = 0.0d0              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour = 4.0d0        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant = 0.0d0               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime = 0.0d0                ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio = 1.0d0 ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: PartLoadRatio = 1.0d0        ! SpeedRatio varies between 1.0 (higher speed) and 0.0 (lower speed)

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))
  SpeedNum  = INT(Par(3))

  Call SimVariableSpeedCoils('  ', CoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadRatio, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

  OutletAirHumRat = VarSpeedCoil(CoilIndex)%OutletAirHumRat
  Residuum = Par(2) - OutletAirHumRat

  RETURN

END FUNCTION VSCoilSpeedHumResidual

!        End of Calculation subroutines for the DXCoolingSystem Module
! *****************************************************************************


!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!

End Module HVACDXSystem

!******************************************************************************************************

MODULE HVACDXHeatPumpSystem
  ! Module containing the DXHeatPumpSystem simulation routines

  ! MODULE INFORMATION:
  !       AUTHOR         Brent Griffith (derived from HVACDXSystem.f90 by R.Liesen)
  !       DATE WRITTEN   May 2011
  !                      Feb 2013, Bo Shen, Oak Ridge National Lab
  !                      Add Coil:Heating:DX:VariableSpeed
  !
  !       RE-ENGINEERED  na

  ! PURPOSE OF THIS MODULE:
  ! To encapsulate the data and algorithms required to
  ! manage the DX Heat Pump System System Component
  ! this wraps heat pump air-heating coils in coil-only wrapper with no fans.

  ! METHODOLOGY EMPLOYED:
  !

  ! REFERENCES:


  ! OTHER NOTES:
  !

  ! USE STATEMENTS:
  ! Use statements for data only modules
USE DataPrecisionGlobals
USE DataLoopNode
USE DataGlobals
USE DataHVACGlobals
USE DataInterfaces

  ! Use statements for access to subroutines in other modules
USE ScheduleManager

IMPLICIT NONE         ! Enforce explicit typing of all variables

PRIVATE ! Everything private unless explicitly made public

  !MODULE PARAMETER DEFINITIONS
REAL(r64), PARAMETER :: MinAirMassFlow = 0.001d0
! Compressor operation
INTEGER, PARAMETER :: On =  1              ! normal compressor operation
INTEGER, PARAMETER :: Off = 0              ! signal DXCoil that compressor shouldn't run



  ! DERIVED TYPE DEFINITIONS

TYPE DXHeatPumpSystemStruct
  CHARACTER(len=MaxNameLength) :: DXHeatPumpSystemType=' ' ! Type of DXHeatingSystem
  CHARACTER(len=MaxNameLength) :: Name               =' ' ! Name of the DXHeatingSystem
  INTEGER                      :: SchedPtr           =0
  CHARACTER(len=MaxNameLength) :: HeatPumpCoilType    =' ' !
  INTEGER                      :: HeatPumpCoilType_Num=0
  CHARACTER(len=MaxNameLength) :: HeatPumpCoilName    =' ' !
  INTEGER                      :: HeatPumpCoilIndex   =0
  INTEGER      :: DXHeatPumpCoilInletNodeNum          =0
  INTEGER      :: DXHeatPumpCoilOutletNodeNum         =0
  Integer      :: DXSystemControlNodeNum             =0   ! the node number of the node with the set point
  REAL(r64)    :: DesiredOutletTemp                  =0.0d0 ! the temperature at the unit outlet node needed
                                                          ! to meet the supply air set point.

  REAL(r64)    :: PartLoadFrac                       =0.0d0 ! part load fraction for current time step (single speed)
  REAL(r64)    :: SpeedRatio                         =0.0d0 ! current compressor speed ratio (variable speed)
  REAL(r64)    :: CycRatio                           =0.0d0 ! cycling part load ratio (variable speed)
  INTEGER      :: FanOpMode                          =0   ! Fan operating mode (see parameter above)

! Warning message variables



  INTEGER      :: DXCoilSensPLRIter                   =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilSensPLRIterIndex              =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilSensPLRFail                   =0   ! used in DXCoil calculations
  INTEGER      :: DXCoilSensPLRFailIndex              =0   ! used in DXCoil calculations

! When the Dx system is a part of Outdoor Air Unit
  REAL(r64)    :: OAUnitSetTemp                        =0.0d0 ! set
! variable-speed coil
  INTEGER      :: SpeedNum                             =0   ! select speed number for variable-speed coil

END TYPE DXHeatPumpSystemStruct

!MODULE VARIABLE DECLARATIONS:
INTEGER :: NumDXHeatPumpSystems=0   ! The Number of DXHeatPumpSystems found in the Input
LOGICAL :: EconomizerFlag=.FALSE. ! holds air loop economizer status

! Make this type allocatable
TYPE (DXHeatPumpSystemStruct), ALLOCATABLE, DIMENSION(:) :: DXHeatPumpSystem
LOGICAL, ALLOCATABLE, DIMENSION(:) :: CheckEquipName

! Subroutine Specifications for the Module
          ! Driver/Manager Routines
PUBLIC  SimDXHeatPumpSystem

          ! Get Input routines for module
PRIVATE GetDXHeatPumpSystemInput

PRIVATE InitDXHeatPumpSystem

          ! Update routine to check convergence and update nodes
PRIVATE ControlDXHeatingSystem

PRIVATE DXHeatingCoilResidual

PRIVATE VSCoilCyclingResidual
PRIVATE VSCoilSpeedResidual


CONTAINS

! MODULE SUBROUTINES:
!*************************************************************************
SUBROUTINE SimDXHeatPumpSystem(DXHeatPumpSystemName, FirstHVACIteration, AirLoopNum,CompIndex,OAUnitNum,OAUCoilOutTemp,QTotOut)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith (derived from HVACDXSystem.f90 by R.Liesen)
          !       DATE WRITTEN   May 2011
          !                      Feb 2013, Bo Shen, Oak Ridge National Lab
          !                      Add Coil:Heating:DX:VariableSpeed

          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine manages DXHeatPumpSystem component simulation.

          ! METHODOLOGY EMPLOYED:
          ! na

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DXCoils,          ONLY: SimDXCoil
  USE General,          ONLY: TrimSigDigits
  USE DataAirLoop,      ONLY: AirLoopControlInfo
  USE InputProcessor,   ONLY: FindItemInList
  USE HVACHXAssistedCoolingCoil, ONLY: SimHXAssistedCoolingCoil
  USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  CHARACTER(len=*), INTENT(IN) :: DXHeatPumpSystemName ! Name of DXSystem:Airloop object
  LOGICAL, INTENT(IN)          :: FirstHVACIteration  ! True when first HVAC iteration
  INTEGER, INTENT(IN)          :: AirLoopNum          ! Primary air loop number
  INTEGER, INTENT(INOUT)       :: CompIndex           ! Index to CoilSystem:Heating:DX object
  INTEGER, INTENT(IN), OPTIONAL:: OAUnitNum           ! If the system is an equipment of OutdoorAirUnit
  REAL(r64), INTENT(IN), OPTIONAL :: OAUCoilOutTemp   ! the coil inlet temperature of OutdoorAirUnit
  REAL(r64), INTENT(INOUT), OPTIONAL :: QTotOut       ! the total cooling output of unit
          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DEFINITIONS:
          ! na

          ! FLOW:


          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  CHARACTER(len=MaxNameLength)  :: CompName              ! Name of CoilSystem:Heating:DX object
  INTEGER                       :: DXSystemNum           ! Index to CoilSystem:Heating:DX object
  LOGICAL,SAVE                  :: GetInputFlag = .True. ! Flag to get input only once
  LOGICAL                       :: HXUnitOn              ! Flag to control HX for HXAssisted Cooling Coil
  REAL(r64)                     :: AirMassFlow           ! DX System air mass flow rate
  INTEGER                       :: InletNodeNum          ! DX System inlet node number
  INTEGER                       :: OutletNodeNum         ! DX System outlet node number
!local variables for calling variable speed coil
  REAL(r64)                     :: QZnReq  = 0.001d0                   ! Zone load (W), input to variable-speed DX coil
  REAL(r64)                     :: QLatReq = 0.0d0                     ! Zone latent load, input to variable-speed DX coil
  REAL(r64)                     :: MaxONOFFCyclesperHour = 4.0d0       ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)                     :: HPTimeConstant = 0.0d0              ! Heat pump time constant [s]
  REAL(r64)                     :: FanDelayTime   = 0.0d0              ! Fan delay time, time delay for the HP's fan to
  REAL(r64)                     :: OnOffAirFlowRatio = 1.0d0           ! ratio of compressor on flow to average flow over time step


    ! Obtains and Allocates DX Cooling System related parameters from input file
  IF (GetInputFlag) THEN  !First time subroutine has been entered
        !Get the DXCoolingSystem input
    CALL GetDXHeatPumpSystemInput
    GetInputFlag=.false.
  End If

    ! Find the correct DXSystemNumber
  IF (CompIndex == 0) THEN
    DXSystemNum = FindItemInList(DXHeatPumpSystemName,DXHeatPumpSystem%Name,NumDXHeatPumpSystems)
    IF (DXSystemNum == 0) THEN
      CALL ShowFatalError('SimDXHeatPumpSystem: DXUnit not found='//TRIM(DXHeatPumpSystemName))
    ENDIF
    CompIndex=DXSystemNum
  ELSE
    DXSystemNum=CompIndex
    IF (DXSystemNum > NumDXHeatPumpSystems .or. DXSystemNum < 1) THEN
      CALL ShowFatalError('SimDXHeatPumpSystem:  Invalid CompIndex passed='//  &
                          TRIM(TrimSigDigits(DXSystemNum))// &
                          ', Number of DX Units='//TRIM(TrimSigDigits(NumDXHeatPumpSystems))//  &
                          ', DX Unit name='//TRIM(DXHeatPumpSystemName))
    ENDIF
    IF (CheckEquipName(DXSystemNum)) THEN
      IF (DXHeatPumpSystemName /= DXHeatPumpSystem(DXSystemNum)%Name) THEN
        CALL ShowFatalError('SimDXHeatPumpSystem: Invalid CompIndex passed='//  &
                            TRIM(TrimSigDigits(DXSystemNum))// &
                            ', DX Unit name='//TRIM(DXHeatPumpSystemName)//', stored DX Unit Name for that index='//  &
                            TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
      ENDIF
      CheckEquipName(DXSystemNum)=.false.
    ENDIF
  ENDIF

  IF (PRESENT(OAUnitNum)) THEN
    CALL InitDXHeatPumpSystem(DXSystemNum,AirLoopNum,OAUnitNum=OAUnitNum,OAUCoilOutTemp=OAUCoilOutTemp)
  ELSE
    CALL InitDXHeatPumpSystem(DXSystemNum,AirLoopNum)
  ENDIF

  !Call the series of components that simulate a DX Heating System
   ! Control the DX Heating System
  CALL ControlDXHeatingSystem(DXSystemNum, FirstHVACIteration)

    ! simulate DX Heating System
  CompName = DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilName

    SELECT CASE(DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilType_Num)

    CASE (CoilDX_HeatingEmpirical) ! COIL:DX:COOLINGBYPASSFACTOREMPIRICAL

      CALL SimDXCoil(CompName,On,FirstHVACIteration, DXHeatPumpSystem(DXSystemNum)%PartLoadFrac,  &
         DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex, &
         DXHeatPumpSystem(DXSystemNum)%FanOpMode)

    CASE (Coil_HeatingAirToAirVariableSpeed)  ! Coil:Heating:DX:VariableSpeed
      Call SimVariableSpeedCoils(CompName,DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex,&
           DXHeatPumpSystem(DXSystemNum)%FanOpMode, MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, DXHeatPumpSystem(DXSystemNum)%PartLoadFrac, OnOffAirFlowRatio, &
           DXHeatPumpSystem(DXSystemNum)%SpeedNum, DXHeatPumpSystem(DXSystemNum)%SpeedRatio, QZnReq, QLatReq)


    CASE DEFAULT
      CALL ShowFatalError('SimDXCoolingSystem: Invalid DX Heating System/Coil='//  &
                          TRIM(DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilType))

  END SELECT
  ! set econo lockout flag
    ! set econo lockout flag
  IF (AirLoopNum /=-1) THEN ! IF the sysem is not an equipment of outdoor air unit

  IF ( (DXHeatPumpSystem(DXSystemNum)%PartLoadFrac > 0.0d0 ) .AND. &
       AirLoopControlInfo(AirLoopNum)%CanLockoutEconoWithCompressor) THEN
       AirLoopControlInfo(AirLoopNum)%ReqstEconoLockoutWithCompressor = .TRUE.
  ELSE
    AirLoopControlInfo(AirLoopNum)%ReqstEconoLockoutWithCompressor = .FALSE.
  END IF
  END IF

  IF(PRESENT(QTotOut))THEN
    InletNodeNum  = DXHeatPumpSystem(DXSystemNum)%DXHeatPumpCoilInletNodeNum
    OutletNodeNum = DXHeatPumpSystem(DXSystemNum)%DXHeatPumpCoilOutletNodeNum
    AirMassFlow = Node(OutletNodeNum)%MassFlowRate
    QTotOut = AirMassFlow * (Node(InletNodeNum)%Enthalpy - Node(OutletNodeNum)%Enthalpy)
  END IF

  RETURN

END SUBROUTINE SimDXHeatPumpSystem

! Get Input Section of the Module
!******************************************************************************
SUBROUTINE GetDXHeatPumpSystemInput

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith (derived from HVACDXSystem.f90 by R.Liesen)
          !       DATE WRITTEN   May 2011
          !                      Feb 2013, Bo Shen, Oak Ridge National Lab
          !                      Add Coil:Heating:DX:VariableSpeed
          !
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! Obtains input data for system and stores it in System data structures

          ! METHODOLOGY EMPLOYED:
          ! Uses "Get" routines to read in data.

          ! REFERENCES:

          ! USE STATEMENTS:
    USE InputProcessor
    USE NodeInputManager,      ONLY: GetOnlySingleNode
    USE DataHeatBalance,       ONLY: Zone
    USE BranchNodeConnections, ONLY: SetUpCompSets, TestCompSet
    USE HVACHXAssistedCoolingCoil,  ONLY: GetHXDXCoilName
    USE DataIPShortCuts
    USE DXCoils,               ONLY: GetCoilInletNode, GetCoilOutletNode, SetCoilSystemHeatingDXFlag
    USE VariableSpeedCoils,      ONLY:    GetCoilInletNodeVariableSpeed, GetCoilOutletNodeVariableSpeed

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
          ! na

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
    INTEGER :: DXSystemNum      ! The DXHeatingSystem that you are currently loading input into
    INTEGER :: NumAlphas
    INTEGER :: NumNums
    INTEGER :: IOSTAT
    CHARACTER(len=*), PARAMETER    :: RoutineName='GetDXHeatPumpSystemInput: ' ! include trailing blank space
    LOGICAL :: ErrorsFound = .false.   ! If errors detected in input
    LOGICAL :: IsNotOK               ! Flag to verify name
    LOGICAL :: IsBlank               ! Flag for blank name
    Integer :: DXHeatSysNum
    LOGICAL :: FanErrorsFound        ! flag returned on fan operating mode check
    LOGICAL :: DXErrorsFound         ! flag returned on DX coil name check
    CHARACTER(len=MaxNameLength) :: CurrentModuleObject  ! for ease in getting objects
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: Alphas         ! Alpha input items for object
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cAlphaFields   ! Alpha field names
    CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cNumericFields ! Numeric field names
    REAL(r64), ALLOCATABLE, DIMENSION(:) :: Numbers           ! Numeric input items for object
    LOGICAL, ALLOCATABLE, DIMENSION(:)   :: lAlphaBlanks      ! Logical array, alpha field input BLANK = .true.
    LOGICAL, ALLOCATABLE, DIMENSION(:)   :: lNumericBlanks    ! Logical array, numeric field input BLANK = .true.
    INTEGER                              :: TotalArgs=0       ! Total number of alpha and numeric arguments (max) for a
                                                              !  certain object in the input file

          ! Flow

    CurrentModuleObject='CoilSystem:Heating:DX'
    NumDXHeatPumpSystems = GetNumObjectsFound(CurrentModuleObject)

    ALLOCATE(DXHeatPumpSystem(NumDXHeatPumpSystems))
    ALLOCATE(CheckEquipName(NumDXHeatPumpSystems))
    CheckEquipName=.true.

    CALL GetObjectDefMaxArgs('CoilSystem:Heating:DX',TotalArgs,NumAlphas,NumNums)

    ALLOCATE(Alphas(NumAlphas))
    Alphas=' '
    ALLOCATE(cAlphaFields(NumAlphas))
    cAlphaFields=' '
    ALLOCATE(cNumericFields(NumNums))
    cNumericFields=' '
    ALLOCATE(Numbers(NumNums))
    Numbers=0.0d0
    ALLOCATE(lAlphaBlanks(NumAlphas))
    lAlphaBlanks=.TRUE.
    ALLOCATE(lNumericBlanks(NumNums))
    lNumericBlanks=.TRUE.


      ! Get the data for the DX Cooling System
      DO DXHeatSysNum = 1,  NumDXHeatPumpSystems

        CALL GetObjectItem(CurrentModuleObject,DXHeatSysNum,Alphas,NumAlphas, &
                     Numbers,NumNums,IOSTAT,NumBlank=lNumericBlanks,AlphaBlank=lAlphaBlanks, &
                     AlphaFieldNames=cAlphaFields,NumericFieldNames=cNumericFields)

        IsNotOK=.false.
        IsBlank=.false.
        CALL VerifyName(Alphas(1),DXHeatPumpSystem%Name,DXHeatSysNum-1,IsNotOK,IsBlank,TRIM(CurrentModuleObject)//' Name')
        IF (IsNotOK) THEN
          ErrorsFound=.true.
          IF (IsBlank) Alphas(1) ='xxxxx'
        ENDIF
        DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpSystemType = CurrentModuleObject ! push Object Name into data array
        DXHeatPumpSystem(DXHeatSysNum)%Name            = Alphas(1)
        IF (lAlphaBlanks(2)) THEN
          DXHeatPumpSystem(DXHeatSysNum)%SchedPtr        = ScheduleAlwaysOn
        ELSE
          DXHeatPumpSystem(DXHeatSysNum)%SchedPtr        = GetScheduleIndex(Alphas(2))
          IF (DXHeatPumpSystem(DXHeatSysNum)%SchedPtr == 0) THEN
            CALL ShowSevereError(RoutineName//TRIM(CurrentModuleObject)//': invalid '//TRIM(cAlphaFields(2))//  &
               ' entered ='//TRIM(Alphas(2))// &
               ' for '//TRIM(cAlphaFields(1))//'='//TRIM(Alphas(1)))
            ErrorsFound=.true.
          END IF
        END IF

        IF (SameString(Alphas(3),'Coil:Heating:DX:SingleSpeed'))  THEN

          DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType = Alphas(3)
          DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType_Num=CoilDX_HeatingEmpirical

          DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName = Alphas(4)
        ELSE IF (SameString(Alphas(3),'Coil:Heating:DX:VariableSpeed'))  THEN

          DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType = Alphas(3)
          DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType_Num=Coil_HeatingAirToAirVariableSpeed

          DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName = Alphas(4)


        ELSE
          CALL ShowSevereError('Invalid entry for '//TRIM(cAlphaFields(3))//' :'//TRIM(Alphas(3)))
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//'="'//TRIM(DXHeatPumpSystem(DXHeatSysNum)%Name)//'".')
          ErrorsFound=.true.
        END IF


        IF(DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType_Num == Coil_HeatingAirToAirVariableSpeed) THEN
          DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilInletNodeNum = GetCoilInletNodeVariableSpeed(&
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType, &
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName, &
                                                                           ErrorsFound )
          DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilOutletNodeNum =  GetCoilOutletNodeVariableSpeed(&
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType, &
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName, &
                                                                           ErrorsFound )
        ELSE
          DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilInletNodeNum      = GetCoilInletNode(  &
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType, &
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName, &
                                                                           ErrorsFound )

          DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilOutletNodeNum     = GetCoilOutletNode(  &
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType, &
                                                                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName, &
                                                                           ErrorsFound )
        END IF

        DXHeatPumpSystem(DXHeatSysNum)%DXSystemControlNodeNum = DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilOutletNodeNum

        CALL TestCompSet(TRIM(CurrentModuleObject),DXHeatPumpSystem(DXHeatSysNum)%Name,  &
                                                   NodeID(DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilInletNodeNum), &
                                                   NodeID(DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilOutletNodeNum) ,&
                                                   'Air Nodes')

        CALL ValidateComponent(DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType,DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName, &
                               IsNotOK,TRIM(CurrentModuleObject))
        IF (IsNotOK) THEN
          CALL ShowContinueError('In '//TRIM(CurrentModuleObject)//' = "'//TRIM(DXHeatPumpSystem(DXHeatSysNum)%Name)//'".')
          ErrorsFound=.true.
        ENDIF

        CALL SetUpCompSets(DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpSystemType, &
                           DXHeatPumpSystem(DXHeatSysNum)%Name, &
                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType, &
                           DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName, &
                           NodeID(DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilInletNodeNum), &
                           NodeID(DXHeatPumpSystem(DXHeatSysNum)%DXHeatPumpCoilOutletNodeNum) )


        ! Supply air fan operating mode defaulted to constant fan cycling coil/compressor
        DXHeatPumpSystem(DXHeatSysNum)%FanOpMode = ContFanCycCoil

        IF(DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType_Num /= Coil_HeatingAirToAirVariableSpeed) THEN
           CALL SetCoilSystemHeatingDXFlag(DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilType, &
                                   DXHeatPumpSystem(DXHeatSysNum)%HeatPumpCoilName)
        END IF

      END DO  !End of the DX System Loop


      IF (ErrorsFound) THEN
        CALL ShowFatalError(RoutineName//'Errors found in input.  Program terminates.')
      ENDIF

      DO DXHeatSysNum=1,NumDXHeatPumpSystems
        ! Setup Report variables for the DXHeatingSystem that is not reported in the components themselves
        CALL SetupOutputVariable('Coil System Part Load Ratio []',DXHeatPumpSystem(DXHeatSysNum)%PartLoadFrac, &
                                'System','Average',DXHeatPumpSystem(DXHeatSysNum)%Name)
      END DO

      DEALLOCATE(Alphas)
      DEALLOCATE(cAlphaFields)
      DEALLOCATE(cNumericFields)
      DEALLOCATE(Numbers)
      DEALLOCATE(lAlphaBlanks)
      DEALLOCATE(lNumericBlanks)

  RETURN

END SUBROUTINE GetDXHeatPumpSystemInput


! End of Get Input subroutines for the Module
!******************************************************************************

! Beginning of Initialization subroutines for the Module
! *****************************************************************************

SUBROUTINE InitDXHeatPumpSystem(DXSystemNum,AirLoopNum,OAUnitNum,OAUCoilOutTemp)

          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith (derived from HVACDXSystem.f90 by R.Liesen)
          !
          !       DATE WRITTEN   May 2011
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          ! This subroutine is for initializations of the DX heat pump Systems.

          ! METHODOLOGY EMPLOYED:
          ! Uses the status flags to trigger initializations.

          ! REFERENCES:
          ! na

          ! USE STATEMENTS:
  USE DataHVACGlobals, ONLY: DoSetPointTest
  USE DataAirLoop,     ONLY: AirLoopControlInfo
  USE EMSManager,      ONLY: iTemperatureSetpoint, CheckIfNodeSetpointManagedByEMS, iHumidityRatioMaxSetpoint
  USE DataGlobals,     ONLY: AnyEnergyManagementSystemInModel

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER, INTENT (IN) :: DXSystemNum ! number of the current DX Sys being simulated
  INTEGER, INTENT (IN) :: AirLoopNum  ! number of the current air loop being simulated
  INTEGER, INTENT (IN), OPTIONAL :: OAUnitNum  ! number of the current outdoor air unit being simulated
  REAL(r64), INTENT(IN), OPTIONAL :: OAUCoilOutTemp    ! the coil inlet temperature of OutdoorAirUnit

          ! SUBROUTINE PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  Integer             :: OutNode ! outlet node number
  INTEGER             :: ControlNode ! control node number
  INTEGER             :: DXSysIndex
!  LOGICAL,SAVE        :: MyOneTimeFlag = .true.
  LOGICAL,SAVE        :: MySetPointCheckFlag = .TRUE.
  INTEGER             :: OutdoorAirUnitNum ! "ONLY" for ZoneHVAC:OutdoorAirUnit
  REAL(r64)           :: OAUCoilOutletTemp  ! "ONLY" for zoneHVAC:OutdoorAirUnit
          ! FLOW:

!  IF (MyOneTimeFlag) THEN
!
!    MyOneTimeFlag = .false.
!  END IF
  IF (PRESENT(OAUnitNum)) THEN ! This Dx system is component of ZoneHVAC:OutdoorAirUnit
    OutdoorAirUnitNum=OAUnitNum
    OAUCoilOutletTemp=OAUCoilOutTemp
  END IF

  IF ( .NOT. SysSizingCalc .AND. MySetPointCheckFlag .AND. DoSetPointTest) THEN
    DO DXSysIndex=1,NumDXHeatPumpSystems
      ControlNode = DXHeatPumpSystem(DXSysIndex)%DXSystemControlNodeNum
      IF (ControlNode > 0) THEN
        IF (AirLoopNum .EQ.-1) THEN                           ! Outdoor Air Unit
          Node(ControlNode)%TempSetPoint = OAUCoilOutletTemp  ! Set the coil outlet temperature
        ELSE IF (AirLoopNum /= -1) THEN ! Not an outdoor air unit

          IF (Node(ControlNode)%TempSetPoint == SensedNodeFlagValue) THEN
            IF (.NOT. AnyEnergyManagementSystemInModel) THEN
              CALL ShowSevereError(TRIM(DXHeatPumpSystem(DXSysIndex)%DXHeatPumpSystemType)//&
                               ': Missing temperature setpoint for DX unit= ' //TRIM(DXHeatPumpSystem(DXSysIndex)%Name))
              CALL ShowContinueError('  use a Set Point Manager to establish a setpoint at the unit control node.')
              SetPointErrorFlag = .TRUE.
            ELSE
              CALL CheckIfNodeSetpointManagedByEMS(ControlNode,iTemperatureSetpoint, SetpointErrorFlag)
              IF (SetpointErrorFlag) THEN
                CALL ShowSevereError(TRIM(DXHeatPumpSystem(DXSysIndex)%DXHeatPumpSystemType)//&
                               ': Missing temperature setpoint for DX unit= ' //TRIM(DXHeatPumpSystem(DXSysIndex)%Name))
                CALL ShowContinueError('  use a Set Point Manager to establish a setpoint at the unit control node.')
                CALL ShowContinueError('  or use an EMS actuator to establish a temperature setpoint at the unit control node.')
              ENDIF
            ENDIF
          END IF
        END IF
      END IF
    END DO
    MySetPointCheckFlag = .FALSE.
  END IF

! These initializations are done every iteration
IF (AirLoopNum .EQ.-1) THEN ! This IF-Then routine is just for ZoneHVAC:OUTDOORAIRUNIT

  DXHeatPumpSystem(DXSystemNum)%DesiredOutletTemp =OAUCoilOutletTemp

ELSEIF (AirLoopNum /=-1) THEN ! Not Outdoor Air Unit
  ControlNode = DXHeatPumpSystem(DXSystemNum)%DXSystemControlNodeNum
  EconomizerFlag = AirLoopControlInfo(AirLoopNum)%EconoActive
  DXHeatPumpSystem(DXSystemNum)%DesiredOutletTemp = Node(ControlNode)%TempSetPoint

END IF
RETURN
END SUBROUTINE InitDXHeatPumpSystem

! End of Initialization subroutines for the Module
! *****************************************************************************

! Beginning of Calculation subroutines for the DXCoolingSystem Module
! *****************************************************************************

SUBROUTINE ControlDXHeatingSystem(DXSystemNum, FirstHVACIteration )
          ! SUBROUTINE INFORMATION:
          !       AUTHOR         Brent Griffith (derived from ControlDXSystem by Richard Liesen)
          !       DATE WRITTEN   Jan 2012
          !       MODIFIED       Richard Raustad, FSEC Nov 2003
          !                      Feb 2005 M. J. Witte, GARD Analytics, Inc.
          !                        Add dehumidification controls and support for multimode DX coil
          !                      Jan 2008 R. Raustad, FSEC. Added coolreheat to all coil types
          !                      Feb 2013, Bo Shen, Oak Ridge National Lab
          !                      Add Coil:Heating:DX:VariableSpeed
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS SUBROUTINE:
          !  This subroutine updates the System outlet nodes.

          ! METHODOLOGY EMPLOYED:
          !  Data is moved from the System data structure to the System outlet nodes.

          ! REFERENCES:
          !  na

          ! USE STATEMENTS:
  USE ScheduleManager
  USE DataEnvironment, ONLY: OutBaroPress
  USE DataHVACGlobals, ONLY: TempControlTol
  USE InputProcessor,  ONLY: FindItemInList
  USE Psychrometrics , ONLY: PsyHFnTdbW, PsyTdpFnWPb
  USE General,         ONLY: SolveRegulaFalsi, RoundSigDigits
  USE DXCoils,         ONLY: SimDXCoil, DXCoilOutletTemp
  USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
  INTEGER,  INTENT(In)    :: DXSystemNum             ! index to DXSystem
  LOGICAL,  INTENT(In)    :: FirstHVACIteration      ! First HVAC iteration flag

          ! SUBROUTINE PARAMETER DEFINITIONS:
  INTEGER, PARAMETER          :: MaxIte    = 500     ! Maximum number of iterations for solver
  REAL(r64), PARAMETER :: Acc       = 1.d-3   ! Accuracy of solver result
  REAL(r64), PARAMETER :: HumRatAcc = 1.d-6   ! Accuracy of solver result

          ! INTERFACE BLOCK SPECIFICATIONS
          !  na

          ! DERIVED TYPE DEFINITIONS
          !  na

          ! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
  CHARACTER(len=MaxNameLength)  :: CompName  ! Name of the DX cooling coil
  REAL(r64)           :: NoOutput            ! Sensible capacity (outlet - inlet) when the compressor is off
  REAL(r64)           :: FullOutput          ! Sensible capacity (outlet - inlet) when the compressor is on
  REAL(r64)           :: ReqOutput           ! Sensible capacity (outlet - inlet) required to meet load or set point temperature
  Integer             :: InletNode           ! Inlet node number of the DX cooling coil
  Integer             :: OutletNode          ! Outlet node number of the DX cooling coil
  Integer             :: ControlNode         ! The node number where a set point is placed to control the DX cooling coil
  REAL(r64)           :: PartLoadFrac        ! The part-load fraction of the compressor

  REAL(r64)           :: DesOutTemp          ! Desired outlet temperature of the DX cooling coil
  REAL(r64)           :: OutletTempDXCoil    ! Actual outlet temperature of the DX cooling coil

  INTEGER             :: SolFla              ! Flag of solver
  REAL(r64), DIMENSION(5)  :: Par                 ! Parameter array passed to solver
  LOGICAL             :: SensibleLoad        ! True if there is a sensible cooling load on this system
  LOGICAL             :: LatentLoad          ! True if there is a latent   cooling load on this system
  INTEGER             :: FanOpMode           ! Supply air fan operating mode
  REAL(r64)           :: TempMinPLR          ! Used to find latent PLR when max iterations exceeded
  REAL(r64)           :: TempMaxPLR          ! Used to find latent PLR when max iterations exceeded
  REAL(r64)           :: TempOutletTempDXCoil   ! Used to find latent PLR when max iterations exceeded
!added variables to call variable speed DX coils
  INTEGER             :: SpeedNum            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime                 ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio  ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: TempSpeedOut         ! output at one speed level
  REAL(r64)           :: TempSpeedReqst         ! request capacity at one speed level
  INTEGER             :: NumOfSpeeds      !maximum number of speed
  INTEGER             :: VSCoilIndex      !variable-speed coil index
  INTEGER             :: I               ! interation increment
  REAL(r64)           :: SpeedRatio      ! speed ratio between two neighboring speeds

      ! Set local variables
      ! Retrieve the load on the controlled zone
  OutletNode   = DXHeatPumpSystem(DXSystemNum)%DXHeatPumpCoilOutletNodeNum
  InletNode    = DXHeatPumpSystem(DXSystemNum)%DXHeatPumpCoilInletNodeNum
  ControlNode  = DXHeatPumpSystem(DXSystemNum)%DXSystemControlNodeNum
  DesOutTemp   = DXHeatPumpSystem(DXSystemNum)%DesiredOutletTemp
  CompName     = DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilName
  FanOpMode    = DXHeatPumpSystem(DXSystemNum)%FanOpMode

  PartLoadFrac = 0.0d0

  SensibleLoad = .FALSE.


  SpeedNum     = 1
  QZnReq       = 0.0d0
  QLatReq      = 0.0d0
  MaxONOFFCyclesperHour = 4.0d0 !default number
  HPTimeConstant= 0.0d0
  FanDelayTime  = 0.0d0
  OnOffAirFlowRatio = 1.0d0
  TempSpeedOut  = 0.0d0
  TempSpeedReqst  = 0.0d0
  NumOfSpeeds = 0
  VSCoilIndex = 0
  I = 1
  SpeedRatio = 0.0d0

  ! If DXHeatingSystem is scheduled on and there is flow
  If((GetCurrentScheduleValue(DXHeatPumpSystem(DXSystemNum)%SchedPtr) > 0.d0) .AND. &
     (Node(InletNode)%MassFlowRate .gt. MinAirMassFlow)) THEN

    ! Determine if there is a sensible load on this system
    IF((Node(InletNode)%Temp < Node(ControlNode)%TempSetPoint) .AND. &
       (Node(InletNode)%Temp < DesOutTemp) .AND. &
       (ABS(Node(InletNode)%Temp - DesOutTemp) .gt. TempControlTol) ) SensibleLoad = .TRUE.


    ! If DXHeatingSystem runs with a heating load then set PartLoadFrac on Heating System
    IF (SensibleLoad ) THEN
      SELECT CASE(DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilType_Num)

        CASE (CoilDX_HeatingEmpirical)  ! Coil:Heating:DX:SingleSpeed

          ! Get no load result
          PartLoadFrac = 0.0d0
          CALL SimDXCoil(CompName,On,FirstHVACIteration,PartLoadFrac,DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex,FanOpMode)
          NoOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

          ! Get full load result
          PartLoadFrac = 1.0d0
          CALL SimDXCoil(CompName,On,FirstHVACIteration,PartLoadFrac,DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex,FanOpMode)

          FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(InletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXHeatPumpSystem(DXSystemNum)%DesiredOutletTemp,Node(InletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

!         IF NoOutput is higher than (more heating than required) or very near the ReqOutput, do not run the compressor
          IF ((NoOutput-ReqOutput) > Acc) THEN
            PartLoadFrac = 0.0d0
!         If the FullOutput is greater than (insufficient heating) or very near the ReqOutput,
!         run the compressor at PartLoadFrac = 1.
          ELSE IF ((FullOutput - ReqOutput) < Acc) THEN
            PartLoadFrac = 1.0d0
!         Else find the PLR to meet the load
          ELSE
!           OutletTempDXCoil is the full capacity outlet temperature at PartLoadFrac = 1 from the CALL above. If this temp is
!           greater than the desired outlet temp, then run the compressor at PartLoadFrac = 1, otherwise find the operating PLR.
            OutletTempDXCoil = DXCoilOutletTemp(DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex)
            IF (OutletTempDXCoil < DesOutTemp) THEN
              PartLoadFrac = 1.0d0
            ELSE
              Par(1) = REAL(DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex,r64)
              Par(2) = DesOutTemp
              Par(3) = 1.d0  !OnOffAirFlowFrac assume = 1.0 for continuous fan dx system
              Par(5) = REAL(FanOpMode,r64)
              CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, DXHeatingCoilResidual, 0.0d0,   &
                                            1.0d0, Par)
              IF (SolFla == -1) THEN
                IF(.NOT. WarmupFlag)THEN
                  IF(DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                    DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter = DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter+1
                    CALL ShowWarningError(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)// &
                                          ' - Iteration limit exceeded calculating DX unit sensible '// &
                                          'part-load ratio for unit = '//TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                    CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  ELSE
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' "'&
                      //TRIM(DXHeatPumpSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                      ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                      ,DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF
              ELSE IF (SolFla == -2) THEN
                PartLoadFrac = ReqOutput/FullOutput
                IF(.NOT. WarmupFlag)THEN
                  IF(DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                    DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail = DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail+1
                    CALL ShowWarningError(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' - DX unit sensible part-'// &
                                    'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                                     TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
                    CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                    CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                    ' continues. Occurrence info: ')
                  ELSE
                    CALL ShowRecurringWarningErrorAtEnd(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' "'&
                      //TRIM(DXHeatPumpSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                      ' failed error continues. Sensible PLR statistics follow.' &
                      ,DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                  END IF
                END IF

              END IF
            END IF
          END IF

          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF

        CASE( Coil_HeatingAirToAirVariableSpeed )
            !variable-speed air-to-air heating coil, begin -------------------------
          ! Get no load result
          PartLoadFrac = 0.0d0
          SpeedNum     = 1
          QZnReq       = 0.0d0
          QLatReq      = 0.0d0
          MaxONOFFCyclesperHour = 4.0d0 !default number
          HPTimeConstant= 0.0d0
          FanDelayTime  = 0.0d0
          OnOffAirFlowRatio = 1.0d0
          SpeedRatio = 0.0d0

         Call SimVariableSpeedCoils(CompName,DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

          VSCoilIndex = DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilIndex
          NumOfSpeeds = VarSpeedCoil(VSCoilIndex)%NumOfSpeeds

          NoOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(OutletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(OutletNode)%HumRat))

          ! Get full load result
          PartLoadFrac = 1.0d0

          SpeedNum     = NumOfSpeeds
          SpeedRatio = 1.0d0
          QZnReq = 0.001d0  !to indicate the coil is running
          Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

          FullOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(Node(OutletNode)%Temp,Node(InletNode)%HumRat)  &
                        - PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))

          ReqOutput = Node(InletNode)%MassFlowRate *  &
                       (PsyHFnTdbW(DXHeatPumpSystem(DXSystemNum)%DesiredOutletTemp,Node(InletNode)%HumRat) - &
                        PsyHFnTdbW(Node(InletNode)%Temp,Node(InletNode)%HumRat))
!         IF NoOutput is higher than (more heating than required) or very near the ReqOutput, do not run the compressor
          IF ((NoOutput-ReqOutput) > Acc) THEN
            PartLoadFrac = 0.0d0
            SpeedNum = 1
            SpeedRatio = 0.0d0
!         If the FullOutput is greater than (insufficient heating) or very near the ReqOutput,
!         run the compressor at PartLoadFrac = 1.
          ELSE IF ((FullOutput - ReqOutput) < Acc) THEN
            PartLoadFrac = 1.0d0
            SpeedNum = NumOfSpeeds
            SpeedRatio = 1.0d0
!         Else find the PLR to meet the load
          ELSE
!           OutletTempDXCoil is the full capacity outlet temperature at PartLoadFrac = 1 from the CALL above. If this temp is
!           greater than the desired outlet temp, then run the compressor at PartLoadFrac = 1, otherwise find the operating PLR.
            OutletTempDXCoil = VarSpeedCoil(VSCoilIndex)%OutletAirDBTemp
            IF (OutletTempDXCoil < DesOutTemp) THEN
              PartLoadFrac = 1.0d0
              SpeedNum = NumOfSpeeds
              SpeedRatio = 1.0d0
            ELSE
              PartLoadFrac = 1.0d0
              SpeedNum     = 1
              SpeedRatio = 1.0d0
              QZnReq = 0.001d0  !to indicate the coil is running
              Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
                 FanOpMode,MaxONOFFCyclesperHour, &
                 HPTimeConstant,FanDelayTime,&
                 On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

              TempSpeedOut =  VarSpeedCoil(VSCoilIndex)%OutletAirDBTemp

              IF((TempSpeedOut - DesOutTemp) .LT. Acc) THEN
                   ! Check to see which speed to meet the load
                PartLoadFrac = 1.0d0
                SpeedRatio = 1.0d0
                DO I=2,NumOfSpeeds
                  SpeedNum = I
                  Call SimVariableSpeedCoils(CompName,VSCoilIndex,&
                     FanOpMode,MaxONOFFCyclesperHour, &
                     HPTimeConstant,FanDelayTime,&
                     On, PartLoadFrac, OnOffAirFlowRatio,SpeedNum, SpeedRatio,QZnReq, QLatReq)

                 TempSpeedOut =  VarSpeedCoil(VSCoilIndex)%OutletAirDBTemp

                  IF ((TempSpeedOut - DesOutTemp) .GT. Acc) THEN
                    SpeedNum = I
                    Exit
                  END IF
                END DO
                Par(1) = REAL(VSCoilIndex,r64)
                Par(2) = DesOutTemp
                Par(5) = REAL(FanOpMode,r64)
                Par(3) = REAL(SpeedNum,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, SpeedRatio, VSCoilSpeedResidual, 1.0d-10, 1.0d0, Par)

                IF (SolFla == -1) THEN
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                        DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter = DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter+1
                        CALL ShowWarningError(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)// &
                                              ' - Iteration limit exceeded calculating DX unit sensible '// &
                                              'part-load ratio for unit = '//TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                        CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                        CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                        ' continues. Occurrence info: ')
                      ELSE
                        CALL ShowRecurringWarningErrorAtEnd(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' "'&
                          //TRIM(DXHeatPumpSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                          ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                          ,DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                      END IF
                    END IF
                  ELSE IF (SolFla == -2) THEN
                    PartLoadFrac = ReqOutput/FullOutput
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                        DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail = DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail+1
                        CALL ShowWarningError(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//  &
                           ' - DX unit sensible part-'// &
                          'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                          TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                        CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                        ' continues. Occurrence info: ')
                      ELSE
                        CALL ShowRecurringWarningErrorAtEnd(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' "'&
                          //TRIM(DXHeatPumpSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                          ' failed error continues. Sensible PLR statistics follow.' &
                          ,DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                      END IF
                    END IF

                  END IF
              ELSE
                Par(1) = REAL(VSCoilIndex,r64)
                Par(2) = DesOutTemp
                Par(5) = REAL(FanOpMode,r64)
                CALL SolveRegulaFalsi(Acc, MaxIte, SolFla, PartLoadFrac, VSCoilCyclingResidual, 1.0d-10,   &
                                            1.0d0, Par)
                IF (SolFla == -1) THEN
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter .LT. 1)THEN
                        DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter = DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIter+1
                        CALL ShowWarningError(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)// &
                                              ' - Iteration limit exceeded calculating DX unit sensible '// &
                                              'part-load ratio for unit = '//TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Estimated part-load ratio  = '//RoundSigDigits((ReqOutput/FullOutput),3))
                        CALL ShowContinueError('Calculated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                        CALL ShowContinueErrorTimeStamp('The calculated part-load ratio will be used and the simulation'// &
                                                        ' continues. Occurrence info: ')
                      ELSE
                        CALL ShowRecurringWarningErrorAtEnd(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' "'&
                          //TRIM(DXHeatPumpSystem(DXSystemNum)%Name)//'" - Iteration limit exceeded calculating'// &
                          ' sensible part-load ratio error continues. Sensible PLR statistics follow.' &
                          ,DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRIterIndex,PartLoadFrac,PartLoadFrac)
                      END IF
                    END IF
                  ELSE IF (SolFla == -2) THEN
                    PartLoadFrac = ReqOutput/FullOutput
                    IF(.NOT. WarmupFlag)THEN
                      IF(DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail .LT. 1)THEN
                        DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail = DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFail+1
                        CALL ShowWarningError(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//  &
                           ' - DX unit sensible part-'// &
                           'load ratio calculation failed: part-load ratio limits exceeded, for unit = '// &
                           TRIM(DXHeatPumpSystem(DXSystemNum)%Name))
                        CALL ShowContinueError('Estimated part-load ratio = '//RoundSigDigits(PartLoadFrac,3))
                        CALL ShowContinueErrorTimeStamp('The estimated part-load ratio will be used and the simulation'// &
                                                        ' continues. Occurrence info: ')
                      ELSE
                        CALL ShowRecurringWarningErrorAtEnd(TRIM(DXHeatPumpSystem(DXSystemNum)%DXHeatPumpSystemType)//' "'&
                          //TRIM(DXHeatPumpSystem(DXSystemNum)%Name)//'" - DX unit sensible part-load ratio calculation'// &
                          ' failed error continues. Sensible PLR statistics follow.' &
                          ,DXHeatPumpSystem(DXSystemNum)%DXCoilSensPLRFailIndex,PartLoadFrac,PartLoadFrac)
                      END IF
                    END IF

                  END IF
              END IF
            END IF
          END IF

          IF(PartLoadFrac.GT.1.0d0) THEN
            PartLoadFrac = 1.0d0
          ELSEIF(PartLoadFrac < 0.0d0) THEN
            PartLoadFrac = 0.0d0
          END IF

        CASE DEFAULT
          CALL ShowFatalError('ControlDXHeatingSystem: Invalid DXHeatPumpSystem coil type = '//  &
                              TRIM(DXHeatPumpSystem(DXSystemNum)%HeatPumpCoilType))

      END SELECT
    END IF ! End of cooling load type (sensible or latent) if block
  END IF   ! End of If DXheatingSystem is scheduled on and there is flow
  !Set the final results
  DXHeatPumpSystem(DXSystemNum)%PartLoadFrac = PartLoadFrac
  DXHeatPumpSystem(DXSystemNum)%SpeedRatio = SpeedRatio
  DXHeatPumpSystem(DXSystemNum)%SpeedNum = SpeedNum

RETURN
END Subroutine ControlDXHeatingSystem


FUNCTION DXHeatingCoilResidual(PartLoadFrac, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Richard Raustad, FSEC
          !       DATE WRITTEN   June 2006
          !       MODIFIED
          !       RE-ENGINEERED

          ! PURPOSE OF THIS FUNCTION:
          ! Calculates residual function (desired outlet temp - actual outlet temp)
          ! DX Coil output depends on the part load ratio which is being varied to zero the residual.

          ! METHODOLOGY EMPLOYED:
          ! Calls CalcDoe2DXCoil to get outlet temperature at the given cycling ratio
          ! and calculates the residual as defined above

          ! REFERENCES:

          ! USE STATEMENTS:
  USE DXCoils, ONLY: DXCoilOutletTemp, CalcDXHeatingCoil

  IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadFrac               ! Compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! Par(1) = DX coil number
                                                    ! Par(2) = desired air outlet temperature [C]
    REAL(r64)         :: Residuum                   ! Residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER :: CoilIndex        ! Index of this coil
  REAL(r64)    :: OutletAirTemp    ! Outlet air temperature [C]
  REAL(r64)    :: OnOffAirFlowFrac ! Ratio of compressor ON to compressor OFF air mass flow rate

  CoilIndex        = INT(Par(1))
  OnOffAirFlowFrac = Par(3)

  CALL CalcDXHeatingCoil(CoilIndex,PartLoadFrac,ContFanCycCoil,OnOffAirFlowFrac)

  OutletAirTemp = DXCoilOutletTemp(CoilIndex)
  Residuum      = Par(2) - OutletAirTemp

  RETURN
END FUNCTION DXHeatingCoilResidual

!******************************************************************************

FUNCTION VSCoilCyclingResidual(PartLoadRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Bo Shen
          !       DATE WRITTEN   Feb, 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function, iterate part-load ratio
          !  compare the desired temperature value with exit temperature from a variable-speed heating coil

          ! REFERENCES:

          ! USE STATEMENTS:
          ! na
   USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

   IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: PartLoadRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER             :: SpeedNum = 1            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq = 0.001d0               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq = 0.0d0              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour = 4.0d0        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant = 0.0d0               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime = 0.0d0                ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio = 1.0d0 ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: SpeedRatio = 0.0d0        ! SpeedRatio varies between 1.0 (higher speed) and 0.0 (lower speed)

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))

  Call SimVariableSpeedCoils('  ', CoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadRatio, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

  OutletAirTemp = VarSpeedCoil(CoilIndex)%OutletAirDBTemp
  Residuum = Par(2) - OutletAirTemp

  RETURN

END FUNCTION VSCoilCyclingResidual


!******************************************************************************

FUNCTION VSCoilSpeedResidual(SpeedRatio, Par) RESULT (Residuum)
          ! FUNCTION INFORMATION:
          !       AUTHOR         Bo Shen
          !       DATE WRITTEN   Feb, 2013
          !       MODIFIED       na
          !       RE-ENGINEERED  na

          ! PURPOSE OF THIS FUNCTION:
          !  Calculates residual function, iterate speed ratio
          !  compare the desired temperature value with exit temperature from a variable-speed heating coil

          ! REFERENCES:

          ! USE STATEMENTS:
          ! na
   USE VariableSpeedCoils,   ONLY: SimVariableSpeedCoils, VarSpeedCoil

   IMPLICIT NONE    ! Enforce explicit typing of all variables in this routine

          ! SUBROUTINE ARGUMENT DEFINITIONS:
    REAL(r64), INTENT(IN)  :: SpeedRatio ! compressor cycling ratio (1.0 is continuous, 0.0 is off)
    REAL(r64), INTENT(IN), DIMENSION(:), OPTIONAL :: Par ! par(1) = DX coil number
                                                    ! par(2) = desired air outlet temperature [C]
                                                    ! par(5) = supply air fan operating mode (ContFanCycCoil)
    REAL(r64)         :: Residuum ! residual to be minimized to zero

          ! FUNCTION PARAMETER DEFINITIONS:
          ! na

          ! INTERFACE BLOCK SPECIFICATIONS
          ! na

          ! DERIVED TYPE DEFINITIONS
          ! na

          ! FUNCTION LOCAL VARIABLE DECLARATIONS:
  INTEGER   :: CoilIndex       ! index of this coil
  REAL(r64) :: OutletAirTemp   ! outlet air temperature [C]
  INTEGER   :: FanOpMode       ! Supply air fan operating mode
  INTEGER             :: SpeedNum = 1            !speed number of variable speed DX cooling coil
  REAL(r64)           :: QZnReq = 0.001d0               ! Zone load (W), input to variable-speed DX coil
  REAL(r64)           :: QLatReq = 0.0d0              ! Zone latent load, input to variable-speed DX coil
  REAL(r64)           :: MaxONOFFCyclesperHour = 4.0d0        ! Maximum cycling rate of heat pump [cycles/hr]
  REAL(r64)           :: HPTimeConstant = 0.0d0               ! Heat pump time constant [s]
  REAL(r64)           :: FanDelayTime = 0.0d0                ! Fan delay time, time delay for the HP's fan to
  REAL(r64)           :: OnOffAirFlowRatio = 1.0d0 ! ratio of compressor on flow to average flow over time step
  REAL(r64)           :: PartLoadRatio = 1.0d0        ! SpeedRatio varies between 1.0 (higher speed) and 0.0 (lower speed)

  CoilIndex = INT(Par(1))
  FanOpMode = INT(Par(5))
  SpeedNum  = INT(Par(3))

  Call SimVariableSpeedCoils('  ', CoilIndex,&
           FanOpMode,MaxONOFFCyclesperHour, &
           HPTimeConstant,FanDelayTime,&
           On, PartLoadRatio, OnOffAirFlowRatio,SpeedNum, SpeedRatio, QZnReq, QLatReq)

  OutletAirTemp = VarSpeedCoil(CoilIndex)%OutletAirDBTemp
  Residuum = Par(2) - OutletAirTemp

  RETURN

END FUNCTION VSCoilSpeedResidual


END MODULE HVACDXHeatPumpSystem

!        End of Calculation subroutines for the DXCoolingSystem Module
! *****************************************************************************


!     NOTICE
!
!     Copyright © 1996-2013 The Board of Trustees of the University of Illinois
!     and The Regents of the University of California through Ernest Orlando Lawrence
!     Berkeley National Laboratory.  All rights reserved.
!
!     Portions of the EnergyPlus software package have been developed and copyrighted
!     by other individuals, companies and institutions.  These portions have been
!     incorporated into the EnergyPlus software package under license.   For a complete
!     list of contributors, see "Notice" located in EnergyPlus.f90.
!
!     NOTICE: The U.S. Government is granted for itself and others acting on its
!     behalf a paid-up, nonexclusive, irrevocable, worldwide license in this data to
!     reproduce, prepare derivative works, and perform publicly and display publicly.
!     Beginning five (5) years after permission to assert copyright is granted,
!     subject to two possible five year renewals, the U.S. Government is granted for
!     itself and others acting on its behalf a paid-up, non-exclusive, irrevocable
!     worldwide license in this data to reproduce, prepare derivative works,
!     distribute copies to the public, perform publicly and display publicly, and to
!     permit others to do so.
!
!     TRADEMARKS: EnergyPlus is a trademark of the US Department of Energy.
!

AirflowNetworkBalanceManager.f90 AirflowNetworkSolver.f90 BaseboardRadiator.f90 BaseboardRadiatorElectric.f90 BaseboardRadiatorSteam.f90 BaseboardRadiatorWater.f90 BranchInputManager.f90 BranchNodeConnections.f90 ConductionTransferFunctionCalc.f90 CoolTower.f90 CostEstimateManager.f90 CurveManager.f90 CVFOnlyRoutines.f90 DataAirflowNetwork.f90 DataAirLoop.f90 DataAirSystems.f90 DataBranchAirLoopPlant.f90 DataBranchNodeConnections.f90 DataBSDFWindow.f90 DataComplexFenestration.f90 DataContaminantBalance.f90 DataConvergParams.f90 DataConversions.f90 DataCostEstimate.f90 DataDaylighting.f90 DataDaylightingDevices.f90 Datadefineequip.f90 DataDElight.f90 DataEnvironment.f90 DataEquivalentLayerWindow.f90 DataErrorTracking.f90 DataGenerators.f90 DataGlobalConstants.f90 DataGlobals.f90 DataHeatBalance.f90 DataHeatBalFanSys.f90 DataHeatBalSurface.f90 DataHVACControllers.f90 DataHVACGlobals.f90 DataInterfaces.f90 DataIPShortCuts.f90 DataLoopNode.f90 DataMoistureBalance.f90 DataMoistureBalanceEMPD.f90 DataOutputs.f90 DataPhotovoltaics.f90 DataPlant.f90 DataPlantPipingSystems.f90 DataPrecisionGlobals.f90 DataReportingFlags.f90 DataRoomAir.f90 DataRootFinder.f90 DataRuntimeLanguage.f90 DataShadowingCombinations.f90 DataSizing.f90 DataStringGlobals.f90 DataSurfaceColors.f90 DataSurfaceLists.f90 DataSurfaces.f90 DataSystemVariables.f90 DataTimings.f90 DataUCSDSharedData.f90 DataVectorTypes.f90 DataViewFactorInformation.f90 DataWater.f90 DataZoneControls.f90 DataZoneEnergyDemands.f90 DataZoneEquipment.f90 DaylightingDevices.f90 DaylightingManager.f90 DElightManagerF.f90 DElightManagerF_NO.f90 DemandManager.f90 DesiccantDehumidifiers.f90 DirectAir.f90 DisplayRoutines.f90 DXCoil.f90 EarthTube.f90 EconomicLifeCycleCost.f90 EconomicTariff.f90 EcoRoof.f90 ElectricPowerGenerators.f90 ElectricPowerManager.f90 EMSManager.f90 EnergyPlus.f90 ExteriorEnergyUseManager.f90 ExternalInterface_NO.f90 FanCoilUnits.f90 FaultsManager.f90 FluidProperties.f90 General.f90 GeneralRoutines.f90 GlobalNames.f90 HeatBalanceAirManager.f90 HeatBalanceConvectionCoeffs.f90 HeatBalanceHAMTManager.f90 HeatBalanceInternalHeatGains.f90 HeatBalanceIntRadExchange.f90 HeatBalanceManager.f90 HeatBalanceMovableInsulation.f90 HeatBalanceSurfaceManager.f90 HeatBalFiniteDifferenceManager.f90 HeatRecovery.f90 Humidifiers.f90 HVACControllers.f90 HVACCooledBeam.f90 HVACDualDuctSystem.f90 HVACDuct.f90 HVACDXSystem.f90 HVACEvapComponent.f90 HVACFanComponent.f90 HVACFurnace.f90 HVACHeatingCoils.f90 HVACHXAssistedCoolingCoil.f90 HVACInterfaceManager.f90 HVACManager.f90 HVACMixerComponent.f90 HVACMultiSpeedHeatPump.f90 HVACSingleDuctInduc.f90 HVACSingleDuctSystem.f90 HVACSplitterComponent.f90 HVACStandAloneERV.f90 HVACSteamCoilComponent.f90 HVACTranspiredCollector.f90 HVACUnitaryBypassVAV.f90 HVACUnitarySystem.f90 HVACVariableRefrigerantFlow.f90 HVACWaterCoilComponent.f90 HVACWatertoAir.f90 HVACWatertoAirMultiSpeedHP.f90 InputProcessor.f90 MatrixDataManager.f90 MixedAir.f90 MoistureBalanceEMPDManager.f90 NodeInputManager.f90 NonZoneEquipmentManager.f90 OutAirNodeManager.f90 OutdoorAirUnit.f90 OutputProcessor.f90 OutputReportPredefined.f90 OutputReports.f90 OutputReportTabular.f90 PackagedTerminalHeatPump.f90 PackagedThermalStorageCoil.f90 Photovoltaics.f90 PhotovoltaicThermalCollectors.f90 PlantAbsorptionChillers.f90 PlantBoilers.f90 PlantBoilersSteam.f90 PlantCentralGSHP.f90 PlantChillers.f90 PlantCondLoopOperation.f90 PlantCondLoopTowers.f90 PlantEIRChillers.f90 PlantEvapFluidCoolers.f90 PlantExhaustAbsorptionChiller.f90 PlantFluidCoolers.f90 PlantGasAbsorptionChiller.f90 PlantGroundHeatExchangers.f90 PlantHeatExchanger.f90 PlantIceThermalStorage.f90 PlantLoadProfile.f90 PlantLoopEquipment.f90 PlantLoopSolver.f90 PlantManager.f90 PlantOutsideEnergySources.f90 PlantPipeHeatTransfer.f90 PlantPipes.f90 PlantPipingSystemManager.f90 PlantPondGroundHeatExchanger.f90 PlantPressureSystem.f90 PlantPumps.f90 PlantSolarCollectors.f90 PlantSurfaceGroundHeatExchanger.f90 PlantUtilities.f90 PlantValves.f90 PlantWaterSources.f90 PlantWaterThermalTank.f90 PlantWatertoWaterGSHP.f90 PlantWaterUse.f90 PollutionAnalysisModule.f90 PoweredInductionUnits.f90 PsychRoutines.f90 Purchasedairmanager.f90 RadiantSystemHighTemp.f90 RadiantSystemLowTemp.f90 RefrigeratedCase.f90 ReportSizingManager.f90 ReturnAirPath.f90 RoomAirManager.f90 RoomAirModelCrossVent.f90 RoomAirModelDisplacementVent.f90 RoomAirModelMundt.f90 RoomAirModelUFAD.f90 RoomAirModelUserTempPattern.f90 RootFinder.f90 RuntimeLanguageProcessor.f90 ScheduleManager.f90 SetPointManager.f90 SimAirServingZones.f90 SimulationManager.f90 SizingManager.f90 SolarReflectionManager.f90 SolarShading.f90 SortAndStringUtilities.f90 sqlite3.c SQLiteCRoutines.c SQLiteFortranRoutines.f90 SQLiteFortranRoutines_NO.f90 StandardRatings.f90 SurfaceGeometry.f90 SystemAvailabilityManager.f90 SystemReports.f90 TarcogComplexFenestration.f90 ThermalChimney.f90 ThermalComfort.f90 UnitHeater.f90 UnitVentilator.f90 UserDefinedComponents.f90 UtilityRoutines.f90 VectorUtilities.f90 VentilatedSlab.f90 WaterManager.f90 WeatherManager.f90 WindowAC.f90 WindowComplexManager.f90 WindowEquivalentLayer.f90 WindowManager.f90 WindTurbine.f90 Zoneairloopequipmentmanager.f90 ZoneContaminantPredictorCorrector.f90 ZoneDehumidifier.f90 Zoneequipmentmanager.f90 ZonePlenumComponent.f90 ZoneTempPredictorCorrector.f90