Solid arrows point from a procedure to one which it calls. Dashed arrows point from an interface to procedures which implement that interface. This could include the module procedures in a generic interface or the implementation in a submodule of an interface in a parent module. Where possible, edges connecting nodes are given different colours to make them easier to distinguish in large graphs.
FUNCTION EstimateHEXSurfaceArea(CoilNum) RESULT(SurfaceArea)
! FUNCTION INFORMATION:
! AUTHOR Bereket A Nigusse, FSEC
! DATE WRITTEN July 2010
! MODIFIED
! RE-ENGINEERED
! PURPOSE OF THIS FUNCTION:
! Splits the UA value of a simple coil:cooling:water heat exchanger model into
! "A" and U" values.
! METHODOLOGY EMPLOYED:
! A typical design U overall heat transfer coefficient is used to split the "UA" into "A"
! and "U" values. Currently a constant U value calculated for a typical cooling coil is
! used. The assumptions used to calculate a typical U value are:
! (1) tube side water velocity of 2.0 [m/s]
! (2) inside to outside total surface area ratio (Ai/Ao) = 0.07 [-]
! (3) fins overall efficiency = 0.92 based on aluminum fin, 12 fins per inch, and
! fins area to total outside surafce area ratio of about 90%.
! (4) air side convection coefficient of 140.0 [W/m2C]. Assumes sensible convection
! of 58.0 [W/m2C] and 82.0 [W/m2C] sensible convection equivalent of the mass
! transfer coefficient converted using the approximate relation:
! hequivalent = hmasstransfer/Cpair.
! REFERENCES:
! USE STATEMENTS:
IMPLICIT NONE ! Enforce explicit typing of all variables in this routine
! SUBROUTINE ARGUMENT DEFINITIONS:
INTEGER, INTENT(IN) :: CoilNum ! coil number, [-]
REAL(r64) :: SurfaceArea ! Heat exchanger surface area, [m2]
! FUNCTION PARAMETER DEFINITIONS:
REAL(r64), PARAMETER :: OverallFinEfficiency = 0.92d0 ! Assumes aluminum fins, 12 fins per inch, fins
! area of about 90% of external surface area Ao.
REAL(r64), PARAMETER :: AreaRatio = 0.07d0 ! Heat exchanger Inside to Outside surface area ratio
! design values range from (Ai/Ao) = 0.06 to 0.08
! INTERFACE BLOCK SPECIFICATIONS
! na
! DERIVED TYPE DEFINITIONS
! na
! FUNCTION LOCAL VARIABLE DECLARATIONS:
REAL(r64) :: UOverallHeatTransferCoef ! over all heat transfer coefficient for coil [W/m2C]
REAL(r64) :: hAirTubeOutside ! Air side heat transfer coefficient [W/m2C]
REAL(r64) :: hWaterTubeInside ! water (tube) side heat transfer coefficient [W/m2C]
WaterCoil(CoilNum)%UACoilTotal = 1.d0/(1.d0/WaterCoil(CoilNum)%UACoilExternal &
+ 1.d0/WaterCoil(CoilNum)%UACoilInternal)
! Tube side water convection heat transfer coefficient of the cooling coil is calculated for
! inside tube diameter of 0.0122m (~0.5 inch nominal diameter) and water velocity 2.0 m/s:
hWaterTubeInside = 1429.d0*(2.d0**0.8d0)*(0.0122d0**(-0.2d0))
! Constant value air side heat transfer coefficient is assumed. This coefficient has sensible
! (58.d0 [W/m2C]) and latent (82.d0 [W/m2C]) heat transfer coefficient components.
hAirTubeOutside = 58.d0 + 82.d0
! Estimate the overall heat transfer coefficient, UOverallHeatTransferCoef in [W/(m2C)].
! Neglecting tube wall and fouling resistance, the overall U value can be estimated as:
! 1/UOverallHeatTransferCoef = 1/(hi*AreaRatio) + 1/(ho*OverallFinEfficiency)
UOverallHeatTransferCoef = 1.d0/(1.d0/(hWaterTubeInside*AreaRatio) &
+ 1.d0/(hAirTubeOutside*OverallFinEfficiency))
! the heat exchanger surface area is calculated as follows:
SurfaceArea=WaterCoil(CoilNum)%UACoilTotal/UOverallHeatTransferCoef
RETURN
END Function EstimateHEXSurfaceArea