Type | Intent | Optional | Attributes | Name | ||
---|---|---|---|---|---|---|
integer, | intent(in) | :: | WaterThermalTankNum |
Nodes of different colours represent the following:
Solid arrows point from a procedure to one which it calls. Dashed arrows point from an interface to procedures which implement that interface. This could include the module procedures in a generic interface or the implementation in a submodule of an interface in a parent module. Where possible, edges connecting nodes are given different colours to make them easier to distinguish in large graphs.
Nodes of different colours represent the following:
Solid arrows point from a procedure to one which it calls. Dashed arrows point from an interface to procedures which implement that interface. This could include the module procedures in a generic interface or the implementation in a submodule of an interface in a parent module. Where possible, edges connecting nodes are given different colours to make them easier to distinguish in large graphs.
SUBROUTINE SizeStandAloneWaterHeater(WaterThermalTankNum)
! SUBROUTINE INFORMATION:
! AUTHOR B. Griffith
! DATE WRITTEN October 2013
! MODIFIED na
! RE-ENGINEERED na
! PURPOSE OF THIS SUBROUTINE:
! allow autosizing of tank volume and heat capacity for stand alone tanks
! METHODOLOGY EMPLOYED:
! same as for plant connected water heaters, only draws are scheduled.
! REFERENCES:
! na
! USE STATEMENTS:
USE DataSizing, ONLY: AutoSize
USE FluidProperties, ONLY: GetDensityGlycol, GetSpecificHeatGlycol
USE ScheduleManager, ONLY: GetScheduleMaxValue
USE InputProcessor, ONLY: SameString
USE DataHeatBalance, ONLY: Zone
USE SolarCollectors, ONLY: Collector, NumOfCollectors
USE DataSurfaces, ONLY: Surface
IMPLICIT NONE ! Enforce explicit typing of all variables in this routine
! SUBROUTINE ARGUMENT DEFINITIONS:
INTEGER, INTENT(IN) :: WaterThermalTankNum
! SUBROUTINE PARAMETER DEFINITIONS:
Real(r64), PARAMETER :: GalTocubicMeters = 0.0037854D0
Real(r64), PARAMETER :: kBtuPerHrToWatts = 293.1D0
! INTERFACE BLOCK SPECIFICATIONS:
! na
! DERIVED TYPE DEFINITIONS:
! na
! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
REAL(r64) :: tmpTankVolume ! local temporary for tank volume m3
REAL(r64) :: tmpMaxCapacity ! local temporary for heating capacity W
REAL(r64) :: Tstart ! initial tank temp for sizing.
REAL(r64) :: Tfinish ! final target temp for sizing
Logical :: SizeVolume = .FALSE.
LOGICAL :: SizeMaxCapacity = .FALSE.
LOGICAL :: FuelTypeIsLikeGas = .FALSE.
INTEGER :: DummyWaterIndex = 1
REAL(r64) :: rho
REAL(r64) :: Cp
REAL(r64) :: DrawDesignVolFlowRate
REAL(r64) :: SumPeopleAllZones
REAL(r64) :: SumFloorAreaAllZones
INTEGER :: CollectorNum
! local inits
Tstart = 14.44d0
TFinish = 57.22d0
SizeVolume = .FALSE.
SizeMaxCapacity = .FALSE.
tmpTankVolume = WaterThermalTank(WaterThermalTankNum)%Volume
tmpMaxCapacity = WaterThermalTank(WaterThermalTankNum)%MaxCapacity
If (tmpTankVolume == Autosize) SizeVolume = .TRUE.
If (tmpMaxCapacity == Autosize) SizeMaxCapacity = .TRUE.
IF (SizeVolume .OR. SizeMaxCapacity) THEN
SELECT CASE (WaterThermalTank(WaterThermalTankNum)%Sizing%DesignMode)
CASE (SizePeakDraw)
! get draw rate from maximum in schedule
rho = GetDensityGlycol('WATER', InitConvTemp, DummyWaterIndex, 'SizeStandAloneWaterHeater')
DrawDesignVolFlowRate = GetScheduleMaxValue(WaterThermalTank(WaterThermalTankNum)%FlowRateSchedule) &
* WaterThermalTank(WaterThermalTankNum)%MassFlowRateMax &
/ rho
If (SizeVolume) THEN
tmpTankVolume = &
WaterThermalTank(WaterThermalTankNum)%Sizing%TankDrawTime & ! hours
* DrawDesignVolFlowRate & ! m3/s
* SecInHour ! (3600 s/1 hour)
WaterThermalTank(WaterThermalTankNum)%Volume = tmpTankVolume
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Tank Volume [m3]', WaterThermalTank(WaterThermalTankNum)%Volume )
ENDIF
If (SizeMaxCapacity) THEN
IF (WaterThermalTank(WaterThermalTankNum)%Sizing%RecoveryTime > 0.0d0) THEN
rho = GetDensityGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
Cp = GetSpecificHeatGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
tmpMaxCapacity = ( WaterThermalTank(WaterThermalTankNum)%Volume & ! m3
* rho & ! kg/m3
* Cp & ! J/Kg/K
* (Tfinish - Tstart)) & ! K
/ (WaterThermalTank(WaterThermalTankNum)%Sizing%RecoveryTime * SecInHour) ! seconds
ELSE
CALL ShowFatalError('SizeStandAloneWaterHeater: Tank="'//TRIM(WaterThermalTank(WaterThermalTankNum)%Name)// &
'", requested sizing for max capacity but entered Recovery Time is zero.')
ENDIF
WaterThermalTank(WaterThermalTankNum)%MaxCapacity = tmpMaxCapacity
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Maximum Heater Capacity [W]', WaterThermalTank(WaterThermalTankNum)%MaxCapacity )
ENDIF
CASE (SizeResidentialMin)
! assume can propagate rules for gas to other fuels.
FuelTypeIsLikeGas = .FALSE.
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Gas')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Diesel')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Gasoline')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Coal')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'FuelOil#1')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'FuelOil#2')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Propane')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Steam')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'OtherFuel1')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'OtherFuel2')) THEN
FuelTypeIsLikeGas = .TRUE.
ELSEIF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'DistrictHeating')) THEN
FuelTypeIsLikeGas = .TRUE.
ENDIF
IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBedrooms == 1 ) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
IF (SizeVolume) tmpTankVolume = 20.0D0 * GalTocubicMeters
IF (SizeMaxCapacity) tmpMaxCapacity = 2.5D0 * 1000.0D0 !2.5 kW
ELSE IF (FuelTypeIsLikeGas) THEN
IF (SizeVolume) tmpTankVolume = 20.0D0 * GalTocubicMeters
IF (SizeMaxCapacity) tmpMaxCapacity = 27.0D0 * kBtuPerHrToWatts !27kBtu/hr
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBedrooms == 2 ) THEN
IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms <= 1.5D0) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
IF (SizeVolume) tmpTankVolume = 30.0D0 * GalTocubicMeters
IF (SizeMaxCapacity) tmpMaxCapacity = 3.5D0 * 1000.0D0 !3.5 kW
ELSE IF (FuelTypeIsLikeGas) THEN
IF (SizeVolume) tmpTankVolume = 30.0D0 * GalTocubicMeters
IF (SizeMaxCapacity) tmpMaxCapacity = 36.0D0 * kBtuPerHrToWatts !36 kBtu/hr
ENDIF
ELSE IF ((WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms > 1.5D0) &
.and. (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms < 3.0D0)) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 4.5D0 * 1000.0D0 !4.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 30.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 36.0D0 * kBtuPerHrToWatts !36 kBtu/hr
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms >= 3.0D0) then
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 36.0D0 * kBtuPerHrToWatts !36 kBtu/hr
ENDIF
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBedrooms == 3 ) THEN
IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms <= 1.5D0) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 4.5D0 * 1000.0D0 !4.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 30.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 36.0D0 * kBtuPerHrToWatts !36 kBtu/hr
ENDIF
ELSE IF ((WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms > 1.5D0) &
.and. (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms < 3.0D0)) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
IF (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
IF (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 36.0D0 * kBtuPerHrToWatts !36 kBtu/hr
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms >= 3.0D0) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 38.0D0 * kBtuPerHrToWatts !38 kBtu/hr
ENDIF
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBedrooms == 4 ) THEN
IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms <= 1.5D0) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 36.0D0 * kBtuPerHrToWatts !36 kBtu/hr
ENDIF
ELSE IF ((WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms > 1.5D0) &
.and. (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms < 3.0D0)) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 40.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 38.0D0 * kBtuPerHrToWatts !38 kBtu/hr
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBathrooms >= 3.0D0) THEN
IF (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 66.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 38.0D0 * kBtuPerHrToWatts !38 kBtu/hr
ENDIF
ENDIF
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBedrooms == 5 ) THEN
If (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 66.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 47.0D0 * kBtuPerHrToWatts !47 kBtu/hr
endif
ELSE IF (WaterThermalTank(WaterThermalTankNum)%Sizing%NumberOfBedrooms >= 6 ) THEN
If (SameString(WaterThermalTank(WaterThermalTankNum)%FuelType , 'Electric') ) THEN
If (SizeVolume) tmpTankVolume = 66.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 5.5D0 * 1000.0D0 !5.5 kW
ELSE IF (FuelTypeIsLikeGas ) THEN
If (SizeVolume) tmpTankVolume = 50.0D0 * GalTocubicMeters
If (SizeMaxCapacity) tmpMaxCapacity = 50.0D0 * kBtuPerHrToWatts !50 kBtu/hr
ENDIF
ENDIF
IF (SizeVolume ) THEN
WaterThermalTank(WaterThermalTankNum)%Volume = tmpTankVolume
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Tank Volume [m3]', WaterThermalTank(WaterThermalTankNum)%Volume )
ENDIF
IF (SizeMaxCapacity ) THEN
WaterThermalTank(WaterThermalTankNum)%MaxCapacity = tmpMaxCapacity
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Maximum Heater Capacity [W]', WaterThermalTank(WaterThermalTankNum)%MaxCapacity )
ENDIF
CASE (SizePerPerson)
! how to get number of people?
SumPeopleAllZones = SUM(Zone%TotOccupants)
IF (SizeVolume) THEN
tmpTankVolume = &
WaterThermalTank(WaterThermalTankNum)%sizing%TankCapacityPerPerson &
* SumPeopleAllZones
ENDIF
IF (SizeMaxCapacity) THEN
rho = GetDensityGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
Cp = GetSpecificHeatGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
tmpMaxCapacity = SumPeopleAllZones &
* WaterThermalTank(WaterThermalTankNum)%sizing%RecoveryCapacityPerPerson & !m3/hr/person
* (Tfinish - Tstart) & ! delta T in K
* (1.0D0 / SecInHour) & ! 1 hr/ 3600 s
* rho & ! kg/m3
* Cp ! J/Kg/k
ENDIF
IF (SizeVolume ) THEN
WaterThermalTank(WaterThermalTankNum)%Volume = tmpTankVolume
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Tank Volume [m3]', WaterThermalTank(WaterThermalTankNum)%Volume )
ENDIF
IF (SizeMaxCapacity ) THEN
WaterThermalTank(WaterThermalTankNum)%MaxCapacity = tmpMaxCapacity
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Maximum Heater Capacity [W]', WaterThermalTank(WaterThermalTankNum)%MaxCapacity )
ENDIF
CASE (SizePerFloorArea)
SumFloorAreaAllZones = SUM(Zone%FloorArea)
IF (SizeVolume) THEN
tmpTankVolume = &
WaterThermalTank(WaterThermalTankNum)%sizing%TankCapacityPerArea &
* SumFloorAreaAllZones
ENDIF
IF (SizeMaxCapacity) THEN
rho = GetDensityGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
Cp = GetSpecificHeatGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
tmpMaxCapacity = SumFloorAreaAllZones & ! m2
* WaterThermalTank(WaterThermalTankNum)%sizing%RecoveryCapacityPerArea & !m3/hr/m2
* (Tfinish - Tstart) & ! delta T in K
* (1.0D0 / SecInHour) & ! 1 hr/ 3600 s
* rho & ! kg/m3
* Cp ! J/Kg/k
ENDIF
IF (SizeVolume) THEN
WaterThermalTank(WaterThermalTankNum)%Volume = tmpTankVolume
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Tank Volume [m3]', WaterThermalTank(WaterThermalTankNum)%Volume )
ENDIF
IF (SizeMaxCapacity) THEN
WaterThermalTank(WaterThermalTankNum)%MaxCapacity = tmpMaxCapacity
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Maximum Heater Capacity [W]', WaterThermalTank(WaterThermalTankNum)%MaxCapacity )
ENDIF
CASE (SizePerUnit)
If (SizeVolume) tmpTankVolume = &
WaterThermalTank(WaterThermalTankNum)%sizing%TankCapacityPerUnit &
* WaterThermalTank(WaterThermalTankNum)%sizing%NumberOfUnits
If (SizeMaxCapacity) THEN
rho = GetDensityGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
Cp = GetSpecificHeatGlycol('WATER', ((Tfinish + Tstart)/2.0D0), DummyWaterIndex, 'SizeStandAloneWaterHeater')
tmpMaxCapacity = &
WaterThermalTank(WaterThermalTankNum)%sizing%NumberOfUnits &
* WaterThermalTank(WaterThermalTankNum)%sizing%RecoveryCapacityPerUnit & !m3/hr/ea
* (Tfinish - Tstart) & ! delta T in K
* (1.0D0 / SecInHour) & ! 1 hr/ 3600 s
* rho & ! kg/m3
* Cp ! J/Kg/k
ENDIF
IF ( SizeVolume ) THEN
WaterThermalTank(WaterThermalTankNum)%Volume = tmpTankVolume
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Tank Volume [m3]', WaterThermalTank(WaterThermalTankNum)%Volume )
ENDIF
IF ( SizeMaxCapacity ) THEN
WaterThermalTank(WaterThermalTankNum)%MaxCapacity = tmpMaxCapacity
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Maximum Heater Capacity [W]', WaterThermalTank(WaterThermalTankNum)%MaxCapacity )
ENDIF
CASE (SizePerSolarColArea)
WaterThermalTank(WaterThermalTankNum)%sizing%TotalSolarCollectorArea = 0.0D0
DO CollectorNum = 1, NumOfCollectors
WaterThermalTank(WaterThermalTankNum)%sizing%TotalSolarCollectorArea = &
WaterThermalTank(WaterThermalTankNum)%sizing%TotalSolarCollectorArea &
+ Surface( Collector(CollectorNum)%Surface )%Area !
ENDDO
IF (SizeVolume) tmpTankVolume = &
WaterThermalTank(WaterThermalTankNum)%sizing%TotalSolarCollectorArea &
* WaterThermalTank(WaterThermalTankNum)%sizing%TankCapacityPerCollectorArea
IF (SizeMaxCapacity) tmpMaxCapacity = 0.0D0
IF (SizeVolume ) THEN
WaterThermalTank(WaterThermalTankNum)%Volume = tmpTankVolume
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Tank Volume [m3]', WaterThermalTank(WaterThermalTankNum)%Volume )
ENDIF
IF (SizeMaxCapacity ) THEN
WaterThermalTank(WaterThermalTankNum)%MaxCapacity = tmpMaxCapacity
CALL ReportSizingOutput(WaterThermalTank(WaterThermalTankNum)%Type, &
WaterThermalTank(WaterThermalTankNum)%Name, &
'Maximum Heater Capacity [W]', WaterThermalTank(WaterThermalTankNum)%MaxCapacity )
ENDIF
END SELECT
ENDIF
RETURN
END SUBROUTINE SizeStandAloneWaterHeater