Solid arrows point from a procedure to one which it calls. Dashed arrows point from an interface to procedures which implement that interface. This could include the module procedures in a generic interface or the implementation in a submodule of an interface in a parent module. Where possible, edges connecting nodes are given different colours to make them easier to distinguish in large graphs.
Nodes of different colours represent the following:
Solid arrows point from a procedure to one which it calls. Dashed arrows point from an interface to procedures which implement that interface. This could include the module procedures in a generic interface or the implementation in a submodule of an interface in a parent module. Where possible, edges connecting nodes are given different colours to make them easier to distinguish in large graphs.
SUBROUTINE GetWatertoAirHPInput
! SUBROUTINE INFORMATION:
! AUTHOR Hui Jin
! DATE WRITTEN Oct 2000
! MODIFIED Dan Fisher, Kenneth Tang (Jan 2004)
! RE-ENGINEERED na
! PURPOSE OF THIS SUBROUTINE:
! Obtains input data for HPs and stores it in HP data structures
! METHODOLOGY EMPLOYED:
! Uses "Get" routines to read in data.
! REFERENCES:
! na
! USE STATEMENTS:
USE InputProcessor
USE NodeInputManager
USE BranchNodeConnections, ONLY: TestCompSet
USE FluidProperties, ONLY : CheckFluidPropertyName, FindGlycol
USE GlobalNames, ONLY: VerifyUniqueCoilName
USE PlantUtilities, ONLY: RegisterPlantCompDesignFlow
USE OutputReportPredefined
IMPLICIT NONE ! Enforce explicit typing of all variables in this routine
! SUBROUTINE ARGUMENT DEFINITIONS:
! na
! SUBROUTINE PARAMETER DEFINITIONS:
CHARACTER (len=*), PARAMETER :: RoutineName='GetWatertoAirHPInput: ' ! include trailing blank space
! INTERFACE BLOCK SPECIFICATIONS
! na
! DERIVED TYPE DEFINITIONS
! na
! SUBROUTINE LOCAL VARIABLE DECLARATIONS:
INTEGER :: HPNum ! The Water to Air HP that you are currently loading input into
INTEGER :: NumCool
INTEGER :: NumHeat
INTEGER :: WatertoAirHPNum
INTEGER :: NumFluids
INTEGER :: NumAlphas
INTEGER :: NumParams
INTEGER :: NumNums
INTEGER :: MaxNums=0 ! Maximum number of numeric input fields
INTEGER :: MaxAlphas=0 ! Maximum number of alpha input fields
INTEGER :: IOSTAT
LOGICAL :: ErrorsFound = .false. ! If errors detected in input
LOGICAL :: IsNotOK ! Flag to verify name
LOGICAL :: IsBlank ! Flag for blank name
LOGICAL :: errflag
CHARACTER (len=MaxNameLength) :: CurrentModuleObject ! for ease in getting objects
CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: AlphArray ! Alpha input items for object
CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cAlphaFields ! Alpha field names
CHARACTER(len=MaxNameLength), ALLOCATABLE, DIMENSION(:) :: cNumericFields ! Numeric field names
REAL(r64), ALLOCATABLE, DIMENSION(:) :: NumArray ! Numeric input items for object
LOGICAL, ALLOCATABLE, DIMENSION(:) :: lAlphaBlanks ! Logical array, alpha field input BLANK = .true.
LOGICAL, ALLOCATABLE, DIMENSION(:) :: lNumericBlanks ! Logical array, numeric field input BLANK = .true.
! FLOW
NumCool = GetNumObjectsFound('Coil:Cooling:WaterToAirHeatPump:ParameterEstimation')
NumHeat = GetNumObjectsFound('Coil:Heating:WaterToAirHeatPump:ParameterEstimation')
NumWatertoAirHPs = NumCool+NumHeat
HPNum= 0
IF(NumWatertoAirHPs <= 0) THEN
CALL ShowSevereError('No Equipment found in SimWatertoAirHP')
ErrorsFound=.true.
END IF
! Allocate Arrays
IF (NumWatertoAirHPs.GT.0) THEN
ALLOCATE(WatertoAirHP(NumWatertoAirHPs))
ALLOCATE(CheckEquipName(NumWatertoAirHPs))
CheckEquipName=.true.
ENDIF
CALL GetObjectDefMaxArgs('Coil:Cooling:WaterToAirHeatPump:ParameterEstimation',NumParams,NumAlphas,NumNums)
MaxNums=MAX(MaxNums,NumNums)
MaxAlphas=MAX(MaxAlphas,NumAlphas)
CALL GetObjectDefMaxArgs('Coil:Heating:WaterToAirHeatPump:ParameterEstimation',NumParams,NumAlphas,NumNums)
MaxNums=MAX(MaxNums,NumNums)
MaxAlphas=MAX(MaxAlphas,NumAlphas)
ALLOCATE(AlphArray(MaxAlphas))
AlphArray=' '
ALLOCATE(cAlphaFields(MaxAlphas))
cAlphaFields=' '
ALLOCATE(lAlphaBlanks(MaxAlphas))
lAlphaBlanks=.TRUE.
ALLOCATE(cNumericFields(MaxNums))
cNumericFields=' '
ALLOCATE(lNumericBlanks(MaxNums))
lNumericBlanks=.TRUE.
ALLOCATE(NumArray(MaxNums))
NumArray=0.0d0
! Get the data for detailed cooling Heat Pump
CurrentModuleObject = 'Coil:Cooling:WaterToAirHeatPump:ParameterEstimation'
DO WatertoAirHPNum = 1, NumCool
HPNum= HPNum + 1
CALL GetObjectItem(CurrentModuleObject,HPNum,AlphArray,NumAlphas, &
NumArray,NumNums,IOSTAT,&
NumBlank=lNumericBlanks,AlphaBlank=lAlphaBlanks, &
AlphaFieldNames=cAlphaFields,NumericFieldNames=cNumericFields)
IsNotOK=.false.
IsBlank=.false.
CALL VerifyName(AlphArray(1),WatertoAirHP%Name,HPNum-1, ISNotOK,ISBlank,TRIM(CurrentModuleObject)//' Name')
IF (IsNotOK) THEN
ErrorsFound=.true.
IF (IsBlank) AlphArray(1)='xxxxx'
ENDIF
CALL VerifyUniqueCoilName(CurrentModuleObject,AlphArray(1),errflag,TRIM(CurrentModuleObject)//' Name')
IF (errflag) THEN
ErrorsFound=.true.
ENDIF
WatertoAirHP(HPNum)%Name = TRIM(AlphArray(1))
WatertoAirHP(HPNum)%WatertoAirHPType = 'COOLING'
WatertoAirHP(HPNum)%WAHPPlantTypeOfNum = TypeOf_CoilWAHPCoolingParamEst
WatertoAirHP(HPNum)%Refrigerant = TRIM(AlphArray(3))
WatertoAirHP(HPNum)%DesignWaterVolFlowRate = NumArray(1)
WatertoAirHP(HPNum)%CoolingCapacity = NumArray(2)
WatertoAirHP(HPNum)%Twet_Rated=NumArray(3)
WatertoAirHP(HPNum)%Gamma_Rated=NumArray(4)
WatertoAirHP(HPNum)%HighPressCutOff=NumArray(5)
WatertoAirHP(HPNum)%LowPressCutOff=NumArray(6)
WatertoAirHP(HPNum)%WaterInletNodeNum = &
GetOnlySingleNode(AlphArray(4),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Water,NodeConnectionType_Inlet,2,ObjectIsNotParent)
WatertoAirHP(HPNum)%WaterOutletNodeNum = &
GetOnlySingleNode(AlphArray(5),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Water,NodeConnectionType_Outlet,2,ObjectIsNotParent)
WatertoAirHP(HPNum)%AirInletNodeNum = &
GetOnlySingleNode(AlphArray(6),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)
WatertoAirHP(HPNum)%AirOutletNodeNum = &
GetOnlySingleNode(AlphArray(7),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)
!2010-01-13 ESL: Jason Glazer noted that these were out of order previously, but they are good now
WatertoAirHP(HPNum)%LoadSideTotalUACoeff=NumArray(7)
WatertoAirHP(HPNum)%LoadSideOutsideUACoeff=NumArray(8)
IF ((WatertoAirHP(HPNum)%LoadSideOutsideUACoeff .LT. rTinyValue) .OR. &
(WatertoAirHP(HPNum)%LoadSideTotalUACoeff .LT. rTinyValue)) THEN
CALL ShowSevereError('Input problem for '//TRIM(CurrentModuleObject)//'='//TRIM(WatertoAirHP(HPNum)%Name))
CALL ShowContinueError(' One or both load side UA values entered are below tolerance, likely zero or blank.')
CALL ShowContinueError(' Verify inputs, as the parameter syntax for this object went through a change with')
CALL ShowContinueError(' the release of EnergyPlus version 5.')
ErrorsFound = .TRUE.
END IF
WatertoAirHP(HPNum)%SuperheatTemp=NumArray(9)
WatertoAirHP(HPNum)%PowerLosses=NumArray(10)
WatertoAirHP(HPNum)%LossFactor=NumArray(11)
SELECT CASE (AlphArray(2))
CASE ('RECIPROCATING')
WaterToAirHP(HPNum)%CompressorType=CompressorType_Reciprocating
WatertoAirHP(HPNum)%CompPistonDisp=NumArray(12)
WatertoAirHP(HPNum)%CompSucPressDrop=NumArray(13)
WatertoAirHP(HPNum)%CompClearanceFactor=NumArray(14)
CASE ('ROTARY')
WaterToAirHP(HPNum)%CompressorType=CompressorType_Rotary
WatertoAirHP(HPNum)%CompPistonDisp=NumArray(12)
WatertoAirHP(HPNum)%CompSucPressDrop=NumArray(13)
CASE ('SCROLL')
WaterToAirHP(HPNum)%CompressorType=CompressorType_Scroll
WatertoAirHP(HPNum)%RefVolFlowRate=NumArray(15)
WatertoAirHP(HPNum)%VolumeRatio=NumArray(16)
WatertoAirHP(HPNum)%LeakRateCoeff=NumArray(17)
CASE DEFAULT
CALL ShowSevereError(RoutineName//'Invalid '//TRIM(cAlphaFields(2))//' ('// &
TRIM(AlphArray(2))//') entered.'//TRIM(CurrentModuleObject)//'='//TRIM(WatertoAirHP(HPNum)%Name))
ErrorsFound=.true.
END SELECT
WatertoAirHP(HPNum)%SourceSideUACoeff=NumArray(18)
WatertoAirHP(HPNum)%SourceSideHTR1=NumArray(19)
WatertoAirHP(HPNum)%SourceSideHTR2=NumArray(20)
CALL TestCompSet(TRIM(CurrentModuleObject),AlphArray(1),AlphArray(4),AlphArray(5),'Water Nodes')
CALL TestCompSet(TRIM(CurrentModuleObject),AlphArray(1),AlphArray(6),AlphArray(7),'Air Nodes')
CALL SetupOutputVariable('Cooling Coil Electric Energy [J]', &
WatertoAirHP(HPNum)%Energy,'System','Summed',WatertoAirHP(HPNum)%Name, &
ResourceTypeKey='Electric',EndUseKey='Cooling',GroupKey='System')
CALL SetupOutputVariable('Cooling Coil Total Cooling Energy [J]', &
WatertoAirHP(HPNum)%EnergyLoadTotal,'System','Summed',WatertoAirHP(HPNum)%Name, &
ResourceTypeKey='ENERGYTRANSFER',EndUseKey='COOLINGCOILS',GroupKey='System')
CALL SetupOutputVariable('Cooling Coil Sensible Cooling Energy [J]', &
WatertoAirHP(HPNum)%EnergySensible,'System','Summed',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Latent Cooling Energy [J]', &
WatertoAirHP(HPNum)%EnergyLatent,'System','Summed',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Source Side Heat Transfer Energy [J]', &
WatertoAirHP(HPNum)%EnergySource,'System','Summed',WatertoAirHP(HPNum)%Name, &
ResourceTypeKey='PLANTLOOPCOOLINGDEMAND',EndUseKey='COOLINGCOILS',GroupKey='System')
! save the design source side flow rate for use by plant loop sizing algorithms
CALL RegisterPlantCompDesignFlow(WatertoAirHP(HPNum)%WaterInletNodeNum,0.5d0*WatertoAirHP(HPNum)%DesignWaterVolFlowRate)
!create predefined report entries
CALL PreDefTableEntry(pdchCoolCoilType,WatertoAirHP(HPNum)%Name,CurrentModuleObject)
CALL PreDefTableEntry(pdchCoolCoilTotCap,WatertoAirHP(HPNum)%Name,WatertoAirHP(HPNum)%CoolingCapacity)
CALL PreDefTableEntry(pdchCoolCoilSensCap,WatertoAirHP(HPNum)%Name,'-')
CALL PreDefTableEntry(pdchCoolCoilLatCap,WatertoAirHP(HPNum)%Name,'-')
CALL PreDefTableEntry(pdchCoolCoilSHR,WatertoAirHP(HPNum)%Name,'-')
CALL PreDefTableEntry(pdchCoolCoilNomEff,WatertoAirHP(HPNum)%Name,'-')
END DO
CurrentModuleObject = 'Coil:Heating:WaterToAirHeatPump:ParameterEstimation'
DO WatertoAirHPNum = 1, NumHeat
HPNum= HPNum + 1
CALL GetObjectItem(CurrentModuleObject,WatertoAirHPNum,AlphArray,NumAlphas, &
NumArray,NumNums,IOSTAT,&
NumBlank=lNumericBlanks,AlphaBlank=lAlphaBlanks, &
AlphaFieldNames=cAlphaFields,NumericFieldNames=cNumericFields)
IsNotOK=.false.
IsBlank=.false.
CALL VerifyName(AlphArray(1),WatertoAirHP%Name,HPNum-1, ISNotOK,ISBlank,TRIM(CurrentModuleObject)//' Name')
IF (IsNotOK) THEN
ErrorsFound=.true.
IF (IsBlank) AlphArray(1)='xxxxx'
ENDIF
CALL VerifyUniqueCoilName(CurrentModuleObject,AlphArray(1),errflag,TRIM(CurrentModuleObject)//' Name')
IF (errflag) THEN
ErrorsFound=.true.
ENDIF
WatertoAirHP(HPNum)%Name = TRIM(AlphArray(1))
WatertoAirHP(HPNum)%WatertoAirHPType = 'HEATING'
WatertoAirHP(HPNum)%WAHPPlantTypeOfNum = TypeOf_CoilWAHPHeatingParamEst
WatertoAirHP(HPNum)%Refrigerant = TRIM(AlphArray(3))
WatertoAirHP(HPNum)%DesignWaterVolFlowRate = NumArray(1)
WatertoAirHP(HPNum)%HeatingCapacity = NumArray(2)
WatertoAirHP(HPNum)%HighPressCutOff=NumArray(3)
WatertoAirHP(HPNum)%LowPressCutOff=NumArray(4)
WatertoAirHP(HPNum)%WaterInletNodeNum = &
GetOnlySingleNode(AlphArray(4),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Water,NodeConnectionType_Inlet,2,ObjectIsNotParent)
WatertoAirHP(HPNum)%WaterOutletNodeNum = &
GetOnlySingleNode(AlphArray(5),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Water,NodeConnectionType_Outlet,2,ObjectIsNotParent)
WatertoAirHP(HPNum)%AirInletNodeNum = &
GetOnlySingleNode(AlphArray(6),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Air,NodeConnectionType_Inlet,1,ObjectIsNotParent)
WatertoAirHP(HPNum)%AirOutletNodeNum = &
GetOnlySingleNode(AlphArray(7),ErrorsFound,TRIM(CurrentModuleObject),AlphArray(1), &
NodeType_Air,NodeConnectionType_Outlet,1,ObjectIsNotParent)
WatertoAirHP(HPNum)%LoadSideTotalUACoeff=NumArray(5)
IF (WatertoAirHP(HPNum)%LoadSideTotalUACoeff .LT. rTinyValue) THEN
CALL ShowSevereError('Input problem for '//TRIM(CurrentModuleObject)//'='//TRIM(WatertoAirHP(HPNum)%Name))
CALL ShowContinueError(' Load side UA value is less than tolerance, likely zero or blank.')
CALL ShowContinueError(' Verify inputs, as the parameter syntax for this object went through a change with')
CALL ShowContinueError(' the release of EnergyPlus version 5.')
ErrorsFound = .TRUE.
END IF
WatertoAirHP(HPNum)%SuperheatTemp=NumArray(6)
WatertoAirHP(HPNum)%PowerLosses=NumArray(7)
WatertoAirHP(HPNum)%LossFactor=NumArray(8)
SELECT CASE (AlphArray(2))
CASE ('RECIPROCATING')
WaterToAirHP(HPNum)%CompressorType=CompressorType_Reciprocating
WatertoAirHP(HPNum)%CompPistonDisp=NumArray(9)
WatertoAirHP(HPNum)%CompSucPressDrop=NumArray(10)
WatertoAirHP(HPNum)%CompClearanceFactor=NumArray(11)
CASE ('ROTARY')
WaterToAirHP(HPNum)%CompressorType=CompressorType_Rotary
WatertoAirHP(HPNum)%CompPistonDisp=NumArray(9)
WatertoAirHP(HPNum)%CompSucPressDrop=NumArray(10)
CASE ('SCROLL')
WaterToAirHP(HPNum)%CompressorType=CompressorType_Scroll
WatertoAirHP(HPNum)%RefVolFlowRate=NumArray(12)
WatertoAirHP(HPNum)%VolumeRatio=NumArray(13)
WatertoAirHP(HPNum)%LeakRateCoeff=NumArray(14)
CASE DEFAULT
CALL ShowSevereError(RoutineName//'Invalid '//TRIM(cAlphaFields(2))//' ('// &
TRIM(AlphArray(2))//') entered.'//TRIM(CurrentModuleObject)//'='//TRIM(WatertoAirHP(HPNum)%Name))
ErrorsFound=.true.
END SELECT
WatertoAirHP(HPNum)%SourceSideUACoeff = NumArray(15)
WatertoAirHP(HPNum)%SourceSideHTR1 = NumArray(16)
WatertoAirHP(HPNum)%SourceSideHTR2 = NumArray(17)
CALL TestCompSet(TRIM(CurrentModuleObject),AlphArray(1),AlphArray(4),AlphArray(5),'Water Nodes')
CALL TestCompSet(TRIM(CurrentModuleObject),AlphArray(1),AlphArray(6),AlphArray(7),'Air Nodes')
CALL SetupOutputVariable('Heating Coil Electric Energy [J]', &
WatertoAirHP(HPNum)%Energy,'System','Summed',WatertoAirHP(HPNum)%Name, &
ResourceTypeKey='Electric',EndUseKey='Heating',GroupKey='System')
CALL SetupOutputVariable('Heating Coil Heating Energy [J]', &
WatertoAirHP(HPNum)%EnergyLoadTotal,'System','Summed',WatertoAirHP(HPNum)%Name, &
ResourceTypeKey='ENERGYTRANSFER',EndUseKey='HEATINGCOILS',GroupKey='System')
CALL SetupOutputVariable('Heating Coil Source Side Heat Transfer Energy [J]', &
WatertoAirHP(HPNum)%EnergySource,'System','Summed',WatertoAirHP(HPNum)%Name, &
ResourceTypeKey='PLANTLOOPHEATINGDEMAND',EndUseKey='HEATINGCOILS',GroupKey='System')
! save the design source side flow rate for use by plant loop sizing algorithms
CALL RegisterPlantCompDesignFlow(WatertoAirHP(HPNum)%WaterInletNodeNum,0.5d0*WatertoAirHP(HPNum)%DesignWaterVolFlowRate)
!create predefined report entries
CALL PreDefTableEntry(pdchHeatCoilType,WatertoAirHP(HPNum)%Name,CurrentModuleObject)
CALL PreDefTableEntry(pdchHeatCoilNomCap,WatertoAirHP(HPNum)%Name,WatertoAirHP(HPNum)%HeatingCapacity)
CALL PreDefTableEntry(pdchHeatCoilNomEff,WatertoAirHP(HPNum)%Name,'-')
END DO
DEALLOCATE(AlphArray)
DEALLOCATE(cAlphaFields)
DEALLOCATE(lAlphaBlanks)
DEALLOCATE(cNumericFields)
DEALLOCATE(lNumericBlanks)
DEALLOCATE(NumArray)
IF (ErrorsFound) THEN
CALL ShowFatalError(RoutineName//'Errors found getting input. Program terminates.')
ENDIF
DO HPNum=1,NumWatertoAirHPs
IF ( WatertoAirHP(HPNum)%WAHPPlantTypeOfNum == TypeOf_CoilWAHPCoolingParamEst) THEN
! COOLING COIL: Setup Report variables for the Heat Pump
CALL SetupOutputVariable('Cooling Coil Electric Power [W]', &
WatertoAirHP(HPNum)%Power,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Total Cooling Rate [W]', &
WatertoAirHP(HPNum)%QLoadTotal,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Sensible Cooling Rate [W]', &
WatertoAirHP(HPNum)%QSensible,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Latent Cooling Rate [W]', &
WatertoAirHP(HPNum)%QLatent,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Source Side Heat Transfer Rate [W]', &
WatertoAirHP(HPNum)%QSource,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Part Load Ratio []', &
WatertoAirHP(HPNum)%PartLoadRatio,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Runtime Fraction []', &
WatertoAirHP(HPNum)%RunFrac,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Air Mass Flow Rate [kg/s]', &
WatertoAirHP(HPNum)%OutletAirMassFlowRate,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Air Inlet Temperature [C]', &
WatertoAirHP(HPNum)%InletAirDBTemp,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Air Inlet Humidity Ratio [kgWater/kgDryAir]', &
WatertoAirHP(HPNum)%InletAirHumRat,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Air Outlet Temperature [C]', &
WatertoAirHP(HPNum)%OutletAirDBTemp,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Air Outlet Humidity Ratio [kgWater/kgDryAir]', &
WatertoAirHP(HPNum)%OutletAirHumRat,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Source Side Mass Flow Rate [kg/s]', &
WatertoAirHP(HPNum)%OutletWaterMassFlowRate,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Source Side Inlet Temperature [C]', &
WatertoAirHP(HPNum)%InletWaterTemp,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Cooling Coil Source Side Outlet Temperature [C]', &
WatertoAirHP(HPNum)%OutletWaterTemp,'System','Average',WatertoAirHP(HPNum)%Name)
ELSEIF (WatertoAirHP(HPNum)%WAHPPlantTypeOfNum == TypeOf_CoilWAHPHeatingParamEst) THEN
! HEATING COIL Setup Report variables for the Heat Pump
CALL SetupOutputVariable('Heating Coil Electric Power [W]', &
WatertoAirHP(HPNum)%Power,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Heating Rate [W]', &
WatertoAirHP(HPNum)%QLoadTotal,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Sensible Heating Rate [W]', &
WatertoAirHP(HPNum)%QSensible,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Source Side Heat Transfer Rate [W]', &
WatertoAirHP(HPNum)%QSource,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Part Load Ratio []', &
WatertoAirHP(HPNum)%PartLoadRatio,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Runtime Fraction []', &
WatertoAirHP(HPNum)%RunFrac,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Air Mass Flow Rate [kg/s]', &
WatertoAirHP(HPNum)%OutletAirMassFlowRate,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Air Inlet Temperature [C]', &
WatertoAirHP(HPNum)%InletAirDBTemp,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Air Inlet Humidity Ratio [kgWater/kgDryAir]', &
WatertoAirHP(HPNum)%InletAirHumRat,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Air Outlet Temperature [C]', &
WatertoAirHP(HPNum)%OutletAirDBTemp,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Air Outlet Humidity Ratio [kgWater/kgDryAir]', &
WatertoAirHP(HPNum)%OutletAirHumRat,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Source Side Mass Flow Rate [kg/s]', &
WatertoAirHP(HPNum)%OutletWaterMassFlowRate,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Source Side Inlet Temperature [C]', &
WatertoAirHP(HPNum)%InletWaterTemp,'System','Average',WatertoAirHP(HPNum)%Name)
CALL SetupOutputVariable('Heating Coil Source Side Outlet Temperature [C]', &
WatertoAirHP(HPNum)%OutletWaterTemp,'System','Average',WatertoAirHP(HPNum)%Name)
ENDIF
END DO
RETURN
END SUBROUTINE GetWatertoAirHPInput